February 20, 2020
Subject: Compliance Evaluation Inspection
Kinder Morgan Southeast Terminals
Charlotte Terminal 2
NPDES Permit No. NC0004839
Mecklenburg County
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject
facility on February 13, 2020, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible
Charge (ORC) of our findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bellgncdenr.gov.
Sincerely,
Docu Signed by:
A4114 v H ;P44r" for
F161 FB69A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
�� Office
Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NOR7H ORROLINA i
kmrlaam m EnNromi Wuwi\ /`� 704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0004839 111 12 I 20/02/13 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [„ I 72 n 73 � 74 751 I I I I I I I80
u u I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:10AM 20/02/13
16/03/01
Charlotte Terminal 2
6801 Freedom Dr
Exit Time/Date
Permit Expiration Date
Paw Creek NC 28130
11:47AM 20/02/13
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Carlos Augusto Arteaga/ORC/704-399-5696/
Johnny M Tapia//704-249-9936 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Robert E Gray,1000 Windward Concourse Sutie 450 Alpharetta GA 30005/Operations
Manager/770-751-4244/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell ocuSigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 2/20/2020
Be&
E�D:,,
96D90CC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numb DocuSigned by: Date
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ "� 2.20.2020
F1611`969A21D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NC0004839 I11 12, 20/02/13 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
OPERATION & MAINTENANCE SECTION cont'd:
Shamrock has been contracted to remove and dispose of the separated petroleum in the oil/water
separator on an as -needed basis (approximately three to four times per year). The carbon in the
filtration unit is replaced annually and Republic Services disposes of the spent carbon into a permitted
landfill.
Outfall 001 discharge is combined with the stormwater runoff from the driveways, etc. (via separate
piping system) prior to entering the receiving stream. This final outfall is equipped with a hydrocarbon
detection system that can shut down the discharge if a positive reading is detected.
Page#
Permit: NC0004839 Owner - Facility: Charlotte Terminal 2
Inspection Date: 02/13/2020 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division had received the facility's permit renewal application package on 11/21/19.
The last compliance evaluation inspection at the facility was performed by
Charlotte-Mecklenbura Stormwater Services/Water Qualitv Proaram staff on 7/20/17.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: The records reviewed during the inspection were organized and well maintained. Discharge
Monitoring Reports (eDMRs) were reviewed for the period January 2019 through
December
2019. No effluent limit violations were reported and monitoring frequencies were correct.
Page# 3
Permit: NC0004839 Owner - Facility: Charlotte Terminal 2
Inspection Date: 02/13/2020 Inspection Type: Compliance Evaluation
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: ESC Lab Sciences (a subsidiary of Pace Analytical, LLC.) has been contracted to perform
effluent analyses. The facility has also contracted SWE to collect all effluent samples.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: The subject permit requires effluent grab samples.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Site arounds includina secondary containment structures (berms) were well maintained
Facility staff perform both daily site inspections (including NPDES facilities) and monthly
tests on the high water alarms for the oil/water separator. The stormwater runoff from the
loading rack areas is conveyed through an oil/water separator, holding tank and carbon
filtration. The accumulated stormwater in the secondary containment structure is visually
inspected prior to being manually discharged (via pump system). The discharges from both
the treatment system and secondary containment structure are combined prior to Outfall
001. See 'Summary" Section for additional comments.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
Yes No NA NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Page# 4
Permit: NC0004839
Inspection Date: 02/13/2020
Flow Measurement - Effluent
Owner - Facility: Charlotte Terminal 2
Inspection Type: Compliance Evaluation
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
❑ ❑ ■ ❑
Comment: The treatment system and secondary containment discharaes are indeoendently measured
by in -line flow meters. The flows from both meters are added together to determine the total
flow for Outfall 001. The flow meters are calibrated annually
and new flow meters were
installed for each discharge in May 2019 (2" flow meter) and October 2019 (Y flow meter).
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0 ❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑ ❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑ ❑
0
❑
Comment: The effluent discharge from Outfall 001 appeared clear with no petroleum sheens or odors.