HomeMy WebLinkAboutNC0038709_Compliance Evaluation Inspection_20200227ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
S. DANIEL SMITH
Director
Mr. Tommy Spicer
Wilkes County Schools
613 Cherry Street
Wilkesboro, NC 28659
NORTH CAROLINA
Environmental Quality
February 27, 2020
SUBJECT: Compliance Evaluation Inspection
Roaring River Elementary School WWTP
NPDES Permit No. NCO038709
Wilkes County
Dear Mr. Spicer,
On February 25, 2020, Kelli Park, of this office, met with you, the Operator in Responsible
Charge, and Daryl Winebarger, backup Operator in Responsible Charge, to perform a
Compliance Evaluation Inspection at the Roaring River Elementary School wastewater
treatment plant. This type of inspection consists of two basic parts: an in -office file review
and an on -site inspection of the treatment facility. The attached EPA inspection form
details the areas that were evaluated during this inspection.
The inspection of the facility was satisfactory. If you have any questions regarding the
inspection or this report, please contact Kelli Park or me at (336) 776-9800 or by email at
kelli.park(a-)_ncdenr.gov or Ion. snider(a_ncdenr.gov.
Sincerely,
ED''ocu SiTgnedl�by:
Li7�. l
145B49E225C94EA..
Lon Snider
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments: EPA Water Compliance Inspection Report
cc: WSRO
D � North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office i 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
NOh �HCARO UHA
^^ •^^ma^� u�•i` r 336.776.9800
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO038709 111 12 I 20/02/25 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80
u ty I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:30AM 20/02/25
19/01/01
Roaring River Elementary School
283 White Plains Rd
Exit Time/Date
Permit Expiration Date
Roaring River NC 28669
11:00AM 20/02/25
23/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bergie Speaks,613 Cherry St North Wilkesboro NC
28659//336-667-2021/3366679688 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Kelli A Park DocuSigned by: DWR/WSRO WQ/336-776-9689/
P" 2/27/2020
E
DCF74Q34PtQ
Signature of Management Q A Reviewer uSigned by: Agency/Office/Phone and Fax NumbersDate
Snider FLIumber
Lon Snider -r Snider 2/27/2020
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO038709 I11 121 20/02/25 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On February 25, 2020, Kelli Park, of this office, met with you, the Operator in Responsible Charge, and
Daryl Winebarger, backup Operator in Responsible Charge, to perform a Compliance Evaluation
Inspection at the Roaring River Elementary School wastewater treatment plant. This type of inspection
consists of two basic parts: an in -office file review and an on -site inspection of the treatment facility.
The attached EPA inspection form details the areas that were evaluated during this inspection.
The inspection of the facility was satisfactory. If you have any questions regarding the inspection or
this report, please contact Kelli Park or me at (336) 776-9800 or by email at kelli.park@ncdenr.gov or
Ion.snider@ncdenr.gov.
Page#
Permit: NCO038709 Owner - Facility: Roaring River Elementary School
Inspection Date: 02/25/2020 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: There is no fence around the septic tank
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Page# 3
Permit: NCO038709 Owner - Facility: Roaring River Elementary School
Inspection Date: 02/25/2020 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑
Comment: ORC is a grade 2, bORC is a Grade 1
Calibration and post calibration records were available. Some days there was not a post
calibration- please be sure to do post calibration checks EACH time the instrument is used.
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The school's drinking water meter is used for reporting flow.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment: There are no alarms on this septic tank
Pumped once a year at the minimum, pumped as needed between yearly visit.
Myers septic service is used for pumping, records are kept
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
MOM zFs►1cIIIIIIIIIIII►1=M
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ■ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: At the time of inspection it was apparent that the sand is uneven. This needs to be fixed to
prevent potential ponding.
Minimal vegetation.
There is no recirculation at this plant. The plant is raked weekly.
There are no alarms on the sand beds as thev are aravitv fed.
Pump Station - Effluent
Yes No NA NE
Page# 4
Permit: NCO038709
Inspection Date: 02/25/2020
Owner - Facility: Roaring River Elementary School
Inspection Type: Compliance Evaluation
Pump Station - Effluent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
0
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment:
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: Grab samples are taken out of the wet well and then put on ice.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
❑ ❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑ ❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑ ❑
❑
Comment: The effluent pipe is far from the plant, and not easily accessible by
vehicle or walking. The
ORC has provided a blueprint of the effluent pipe's location.
The effluent was clear at the time of ins
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Page# 5
Permit: NCO038709 Owner - Facility: Roaring River Elementary School
Inspection Date: 02/25/2020 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Comment: Calibration and Dost calibration records were available. Some days there was not a
calibration- please be sure to do post calibration checks EACH time the instrument is used.
The pH 10 standard expires this month. pH 4 expires in March 2020
Lab number 5406
Water Tech Labs is used for non -field parameters
Page#