HomeMy WebLinkAboutNC0002305_Compliance Evaluation Inspection_20191231 (2)DocuSign Envelope ID: B155AF80-7FFD-4289-B909-CDOC8F42CBC5
ROY COOPER NORTH CAPOLINA
Gove7no? Environmental Quality
-W HAEL - RE AN
Secretary
L=- A CTJTPEPPER
Interim Direcmr
December 31, 2019
Mr. Keith Westbrook
Lear Corporation WWTP
1754 NC Highway 903 North
Kenansville, NC 28349
SUBJECT: Compliance Inspection Report
Lear Corporation WWTP
NPDES Permit No. NC0002305
Duplin County
A compliance inspection of the Lear Corporation WWTP was conducted on November 22, 2019 to verify that
the facility is operating in compliance with the conditions and limitations specified in Permit NC0002305. The
DWR would like to thank you and your staff for your time and assistance provided during the inspection. The
findings and comments noted during this inspection are provided in the enclosed copy of the "Compliance
Inspection Report". If you have any questions concerning this report, you may contact the inspector at (910)
796-7215 or via email at chad.coburn@ncdenr.gov .
Sincerely,
Signed by:
[ro-
,",',','1E73B6F3456—N44rin.�o&
...
Tom Tharrington, Assistant Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Cc: Wilmington Regional Office Files
Central Files, Water Quality Section
WE�
North Carolina Department of Environmental Quality I Division of Water Resources
127 Cardinal Drive Extension, Wilmington, North Carolina 28405
910-796-7215
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0002305 111 12 I 19/11/22 I17 18 I S i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80
u ty I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:50AM 19/11/22
18/10/01
Lear Corporation WWTP
1754 NC Hwy 903 N
Exit Time/Date
Permit Expiration Date
Kenansville NC 28349
01:00PM 19/11/22
23/04/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Edward Keith Westbrook/ORC/910-296-5200/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Edward K Westbrook,1754 NC Hwy 903 N Kenansville NC 28349/Wastewater
Manager/910-296-5201/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Chad Coburn DocuSigned by: DWR/WIRO WQ/910-796-7379/
E� r,D�wlt 1/2/2020
8237FC6EDFCC4A3...
Signature of Manageme�locCu g �e6yiewer Agency/Office/Phone and Fax Numbers Date
'1o,Y) 12/31/2019[Tom Tharringtn
7FE
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
NPDES yr/mo/day Inspection Type
NC0002305 I11 121 19/11/22 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The facility appeared to be compliant with the NPDES permit during the inspection. All records were
organized and available.
Page#
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
Permit: NC0002305 Owner - Facility: Lear Corporation WWTP
Inspection Date: 11/22/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The current permit doesn't expire until 2023.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
Permit: NC0002305 Owner - Facility: Lear Corporation WWTP
Inspection Date: 11/22/2019 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
❑
# Is basin size/volume adequate?
❑
❑
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Page# 4
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
Permit: NC0002305
Inspection Date: 11/22/2019
Aeration Basins
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Comment: The DO during this time of
warmer months.
Owner - Facility: Lear Corporation WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
❑ ❑ ❑ ■
is around 4 averaae but is between 1.5 to 2.5 durina the
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
Comment: The ORC uses a sludae iudae to base the rate of wastina. PumDS are set to maintain a 30
day sludge age approximately. Settleometer is used to get MLSS.
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment:
Anaerobic Digester
Yes No NA NE
Type of operation:
Is the capacity adequate?
❑
❑
❑
# Is gas stored on site?
❑
❑
❑
Is the digester(s) free of tilting covers?
❑
❑
❑
Is the gas burner operational?
❑
❑
❑
Is the digester heated?
❑
❑
❑
Is the temperature maintained constantly?
❑
❑
❑
Is tankage available for properly waste sludge?
❑
❑
❑
Page# 5
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
Permit: NC0002305 Owner - Facility: Lear Corporation WWTP
Inspection Date: 11/22/2019 Inspection Type: Compliance Evaluation
Anaerobic Digester Yes No NA NE
Comment:
Drying Beds
Yes No NA NE
Is there adequate drying bed space?
0
❑
❑
❑
Is the sludge distribution on drying beds appropriate?
0
❑
❑
❑
Are the drying beds free of vegetation?
0
❑
❑
❑
# Is the site free of dry sludge remaining in beds?
0
❑
❑
❑
Is the site free of stockpiled sludge?
0
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
0
❑
❑
❑
# Is the sludge disposed of through county landfill?
❑
0
❑
❑
# Is the sludge land applied?
0
❑
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
0
❑
Comment: EMA currently takes the solids and land applies.
Disinfection -Liquid
Yes No NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
❑ ❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Comment:
Are the tablets the proper size and type? ❑ ❑ 0 ❑
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Page# 6
DocuSign Envelope ID: B5A99F2C-AE90-4E10-847A-DD789DFDF592
Permit: NC0002305 Owner - Facility: Lear Corporation WWTP
Inspection Date: 11/22/2019 Inspection Type: Compliance Evaluation
De -chlorination
Comment:
Yes No NA NE
Page#