HomeMy WebLinkAboutNC0021326_Compliance Evaluation Inspection_20200213ROY COOPER Governor MICHAEL S. REGAN Secretary S. DANIEL SMITH Director Laura Neely, Town Manager Town of Dobson P.O. Box 351 Dobson, NC 27017 NORTH CAROLINA Environmental Quality February 13, 2020 Subject: Compliance Evaluation Inspection Town of Dobson WWTP NPDES Permit No. NCO021326 Surry County Dear Ms. Neely: A Compliance Evaluation Inspection was performed by North Carolina Division of Water Resources (DWR) staff person, Justin Henderson on February 12, 2020. Mr. Michael Frazier, Public Works Director & ORC was present during this inspection. This type of inspection consists of two basic parts: an in -office review of the facility files and self -monitoring data and an on -site inspection of the facility. While this inspection mostly reflects compliance with the subject permit, the following items of concern warrant your attention and action: 1) Collection of composite sampling for required influent parameters is currently being obtained via a constant time/constant volume method. Per Permit Condition Part II. Section A. Composite Sampling (4), use of this method requires prior Approval by the Director and may only be used in situations where effluent flow rates vary less than 15 percent. The following restrictions also apply: influent and effluent grab samples shall be of equal size and no less than 100 milliliters; influent samples shall not be collected more than once per hour. Future composite sample collection for required monitoring shall comply with collection methods (1), (2), or (3) described herein. 2) Permit Condition Part II. Section D. (6) and 40 CFR 503 require that records related to the Permittee's sewage sludge use and disposal activities be retained for a period of a least five years. While, Mr. Frazier indicated that documentation for the subject facility's disposal events did exist that it is not currently being maintained in an easily reviewable format. 3) Thermometers located in both the effluent and influent composite samplers indicated that temperatures in each were above six degrees Celsius at the time of this inspection. While, sample collection was not occurring during this inspection, samples must be refrigerated to less than or equal to six degrees Celsius during the entire composting period per CFR D � North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office [ 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105 NOh �HCARO UHA ^^ •^ �ku^m I u�•i` r 336.776.9800 part 136.3 Table II. Please ensure that the facility's automated composite samplers can comply with this regulation when sample collection is occurring. 4) The subject permit contains a facility description that includes back-up chlorine disinfection. While, this equipment may have been present at the time of permit issuance, it has since been removed and is no longer available as part of "back-up" operations. As such, the permitted facility description needs to be updated to accurately reflect the facility's treatment equipment available for operations. Please refer to the enclosed inspection report for additional observations and/or comments. If you have questions concerning this correspondence, 776-9800. Sincerely, DocuSiiggned by: L-4A, l l >mJtr on'SMURFlbegional Supervisor Water Quality Regional Operations Section Division of Water Resource, NCDEQ-WSRO enc: Inspection Report please contact Justin Henderson or me at (336) cc: Michael Frazier, Public Works Director- frazierm(kdobson-nc.com Laserfiche Files (electronic copies) United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 I 3 I NC0021326 111 12 I 20/02/12 I17 18 I S J 19 L G] 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 671 70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80 u ty I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 09:30AM 20/02/12 19/01/01 Dobson WWTP 500 Nature Center Rd Exit Time/Date Permit Expiration Date Dobson NC 27017 12:OOPM 20/02/12 23/12/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Michael Allen Frazier/ORC/336-356-9000/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Laura H Neely,PO Box 351 Dobson NC 27017/Town Manager/336-356-8962/3363564836 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Justin L Henderson DouSigned by: DWR/WSRO WQ/336-776-9701/ t,tsh t, qt,IWt,k,V 6V' 2 / 13 /2 0 2 0 D51F3525961`8113496.. Signature of Management Q A Revie uSigned by: Agency/Office/Phone and Fax Numbers Date '? Sti,Jcr 2/13/2020 L-L:RAC1P: EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type (Cont.) NCO021326 I11 121 20/02/12 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) A Compliance Evaluation Inspection was performed by North Carolina Division of Water Resources (DWR) staff person, Justin Henderson on February 12, 2020. Mr. Michael Frazier, Public Works Director & ORC was present during this inspection. This type of inspection consists of two basic parts: an in -office review of the facility files and self -monitoring data and an on -site inspection of the facility. While this inspection mostly reflects compliance with the subject permit, the following items of concern warrant your attention and action: 1) Collection of composite sampling for required influent parameters is currently being obtained via a constant time/constant volume method. Per Permit Condition Part II. Section A. Composite Sampling (4.), use of this method requires prior Approval by the Director and may only be used in situations where effluent flow rates vary less than 15 percent. The following restrictions also apply: influent and effluent grab samples shall be of equal size and no less than 100 milliliters; influent samples shall not be collected more than once per hour. Future composite sample collection for required monitoring shall comply with collection methods (1), (2), or (3) described herein. 2) Permit Condition Part II. Section D. (6) and 40 CFR 503 require that records related to the Permittee's sewage sludge use and disposal activities be retained for a period of a least five years. While, Mr. Frazier indicated that documentation for the subject facility's disposal events did exist that it is not currently being maintained in an easily reviewable format. 3) Thermometers located in both the effluent and influent composite samplers indicated that temperatures in each were above six degrees Celsius at the time of this inspection. While, sample collection was not occurring during this inspection, samples must be refrigerated to less than or equal to six degrees Celsius during the entire composting period per CFR part 136.3 Table II. Please ensure that the facility's automated composite samplers can comply with this regulation when sample collection is occurring. 4) The subject permit contains a facility description that includes back-up chlorine disinfection. While, this equipment may have been present at the time of permit issuance, it has since been removed and is no longer available as part of "back-up" operations. As such, the permitted facility description needs to be updated to accurately reflect the facility's treatment equipment available for operations. Please refer to the enclosed inspection report for additional observations and/or comments. If you have questions concerning this correspondence, please contact Justin Henderson or me at (336) Page# Permit: NCO021326 Inspection Date: 02/12/2020 Owner - Facility: Dobson WWTP Inspection Type: Compliance Evaluation Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: reportedly NH3 is only anlysis analyzed as process control. Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Yes No NA NE ❑ ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ ❑ ■ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: The back-up chlorine disinfection equipment is no longer present or available at the facility. Pump Station - Influent Yes No NA NE Is the pump wet well free of bypass lines or structures? 0 ❑ ❑ ❑ Is the wet well free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Is SCADA telemetry available and operational? ❑ ❑ 0 ❑ Is audible and visual alarm available and operational? ❑ ❑ ❑ Comment: Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical Are the bars adequately screening debris? ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Page# 3 Permit: NCO021326 Inspection Date: 02/12/2020 Owner - Facility: Dobson WWTP Inspection Type: Compliance Evaluation Bar Screens Yes No NA NE Comment: Mechanical barscreen is primarily used but facility has a back-up manual barscreen available for necessary maintenace or repairs related to the mechanical barscreen are needed. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: Sludge blanket is maintained at approximately 50-60 percent of clarifier depth per the ORC in each clarifier. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ ❑ Comment: Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? 0 ❑ ❑ ❑ Are UV bulbs clean? 0 ❑ ❑ ❑ Is UV intensity adequate? 0 ❑ ❑ ❑ Page# 4 Permit: NCO021326 Inspection Date: 02/12/2020 Disinfection - UV Is transmittance at or above designed level? Is there a backup system on site? Is effluent clear and free of solids? Owner - Facility: Dobson WWTP Inspection Type: Compliance Evaluation Yes No NA NE ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ Comment: Back-up generator is present should a power outage occur. Generate can operate entire plant if necessary including UV disinfection. Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Comment: Influent Sampling # Is composite sampling flow proportional? Is sample collected above side streams? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is sampling performed according to the permit? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Yes No NA NE ❑ ■ ❑ ❑ ■ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ Comment: Composite sampling is not collected in compliance with permit conditions. Composite sampler temperature was 10 degrees Celsius at time inspection was conducted. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? 0 ❑ ❑ ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ 0 ❑ ❑ Celsius)? Page# 5 Permit: NC0021326 Inspection Date: 02/12/2020 Effluent Sampling Owner - Facility: Dobson WWTP Inspection Type: Compliance Evaluation Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: Composite sampler temperature was 13 degrees Celsius during this inspection. Upstream / Downstream Sampling Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? Comment: Yes No NA NE ■ ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ Page# 6 Facility.. _ COMPLIANCE EVALUATION INSPECTION NPDES: Permit Effective Dates: to Inspection Date: 12:00 PM Inspection Time: am/pm PERMIT Complete copy of current NPDES permit DMRs (Dates: SELF -MONITORING PROGRAM to Yes LABORATORY Lab Data (per DMR dates) Available for review - matched DMR reporting Laboratories used for analysis Statesville Analytical Chain of Custody forms (per DMR dates) Available for review -- Effluent is collected flow proportionally Influent andlor effluent samplers Influent re uired fl w proportional ASAP Need to make influent collect flow proportionally d Field parameter certification # N/A - UV disinfection Nist calibrated 12/6/19 / Per event cal records present FLOW MEASUREMENT V Both monitored -reports highest (typicaly influent) Flow meter calibration records Calibrated all meters 2x/year - last done 5/1/19 Flow charts SLUDGE HANDLING DISPOSAL Sludge / Residuals hauling records ORC current certificatio Back Up certification- OPERATION & MAINTENANCE 0 Process control data (includes field parameters tested and equipment calibrations) NH3 is all Generator Inspection I under load checks Yes Serviced 4x/year and tested weekly RECORDS & REPORTS Wastewater Annual Report (fiscal or calendar year -- if appficable) Present and avaiable for review. Daily Operator's log / ORC visitation log Avaiable for review Maintenance log Available for review FACILITY SITE REVIEW Plant visual inspection of treatment units Made sure to mentioned this deadline mission Reportedely Mt. Airy is taking sluge at 4000 gallons of sludge or every I uuuuu gallons bt potable water Dobson supplies tb Airy. No SIUs users domestic flows only) Planning to LA this March/April 2020 EFFLUENT/RECEIVING WATERS Stream accessible for inspection (at effluent discharge pipe) Clear w/ no evidence of solids or foam Yes None on -site and no chlorine Back -back up onsite. No back-up chlorine disinfection anymore Must maintain residual/ sewage sluge Removal disposal records for 5 years Influent composite sampler temp was 10 at time of inspection Effluent composite temp was 13 at time of inspection