HomeMy WebLinkAboutWQ0005173_Compliance Evaluation Inspection_20200129DocuSign Envelope ID: 191BDA87-5667-4ED4-8A6D-E33EDE6A4291
ROY COOPER
Governor
MICHAEL S. REGAN
secretary
S. DANIEL SMITH
Dlreernr
NORTH CAROLINA
En vrraninga tal Quality
February 11, 2020
Doris Speicher
Cape Royall Dolphin Association Incorporated
9708 Lord Berkeley Dr
Emerald Isle, NC 28594-1812
SUBJECT: Compliance Inspection Report
Cape Royall Dolphin WWTP
Non -discharge Permit No. WQ0005173
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Cape Royall Dolphin
WWTP on 1/29/2020. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0005173. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Geoff Kegley with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
geoff.kegley@ncdenr.gov.
Sincerely bocuSigned by
Toµ 'N,.rr, OA, for
7F141 73B6F 4 6 .
Morella Sanc ez- Ing, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Cc: Fortin Contract Service
DWR-Laserfiche
North Cs{obna Department of Environmeatsd Quaiitp I Division of Water Resources
WflmngtonRego naaOffice 1127 CarMaaiDFive Extensen I Wilwngton, North Caroina2S405
°'-\ 910-796-7215
Permit: WQ0005173
SOC:
County: Carteret
Region: Wilmington
Compliance Inspection Report
Effective: 03/01/19 Expiration: 02/29/24 Owner: Cape Royall Dolphin Association
Incorporated
Effective: Expiration: Facility: Cape Royall Dolphin WWTP
304 Cape Fear Loop
Contact Person: Doris Speicher
Directions to Facility:
System Classifications: WW2,
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Title: Registered Agent
Certification:
Emerald Isle NC 28594
Phone: 252-354-4656
Phone:
Related Permits:
WQ0004985 Cape Royall Dolphin Association Incorporated - Cape Royall Dolphin Sewer
System
WQ0018525 Barnes Environmental Waste and Hauling Inc - Barnes Environmental RLAP
Inspection Date: 01/29/2020 Entry Time: 09:30AM Exit Time: 11:OOAM
Primary Inspector: Geoff Kegley Phone:
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Treatment Barscreen
Use Records
Treatment Filters Record Keeping Treatment Activated Sludge
Treatment Sludge Storage/Treatment Treatment Clarifiers Treatment Disinfection
End Use -Infiltration Treatment Flow Measurement Treatment Return pumps
Standby Power Wells
(See attachment summary)
Page 1 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection was performed with the assistance of Dan Fortin and company. Since the last inspection
the facility has been sandblasted and recoated and a new generator installed. The system has generally been in
compliance with effluent and groundwater monitoring limits except for some erratic TDS and coliform exceedances in
monitoring wells. The Division will continue to monitor and evaluate these results. The area's water supply is from an RO
system therefore the ORC is adding soda ash routinely to maintain alkalinity. See attached for further notes and
comments.
Page 2 of 7
Permit: WQ0005173
Inspection Date: 01/29/2020
Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Recycle/Reuse
❑
Single Family Drip
❑
Lagoon Spray, LR
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: Facility has been sandblasted and recoated since last inspection.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑ ❑ ❑
Is flowmeter operating properly?
❑ ❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
0
❑ ❑ ❑
Comment: Calibration sticker not present but ORC provided documentation after inspection.
Standby Power
Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Page 3 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? 0 ❑ ❑ ❑
Comment: New generator recently installed. Auto transfer tested and is operational.
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris?
0
❑ ❑ ❑
Is disposal of screenings in compliance?
0
❑ ❑ ❑
Are the bars spaced properly?
0
❑ ❑ ❑
Is the unit in good condition?
0
❑ ❑ ❑
Comment: Grinder pumps
Treatment Activated Sludge
Yes No NA NE
Is the aeration mechanism operable?
0
❑ ❑ ❑
Is the aeration basin thoroughly mixed?
❑ ❑ ❑
Is the aeration equipment easily accessed?
❑ ❑ ❑
Is Dissolved Oxygen adequate?
❑ ❑ ❑
Are Settleometer results acceptable?
❑ ❑ ❑
Is activated sludge an acceptable color?
0
❑ ❑ ❑
Comment: Regional water supply is from an RO system therefore the ORC is adding
soda ash routinely to
maintain alkalinity.
Treatment Clarifiers
Yes No NA NE
Are the weirs level?
❑ ❑ ❑
Are the weirs free of solids and algae?
❑ ❑ ❑
Is the scum removal system operational?
❑ ❑ ❑
Is the scum removal system accessible?
❑ ❑ ❑
Is the sludge blanket at an acceptable level?
❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids?
❑ ❑ ❑
Comment
Treatment Return pumps Yes No NA NE
Are they in place? ❑ ❑ ❑
Are they operational? ❑ ❑ ❑
Comment:
Treatment Filters Yes No NA NE
Is the filter media present? 0 ❑ ❑ ❑
Is the filter media the correct size and type? ❑ ❑ ❑
Is the air scour operational? 0 ❑ ❑ ❑
Page 4 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the scouring acceptable? ❑ ❑ ❑
Is the clear well free of excessive solids? ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? 0 ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: Filters do not have auto backwash, therefore it is performed manually on a daily basis.
Treatment Sludge Storage/Treatment Yes No NA NE
Is the aeration operational? ❑ ❑ ❑
Is the aeration pattern even? ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑
Comment:
Treatment Disinfection
Yes No NA NE
Is the system working?
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑ ❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑ ❑ ❑
If tablets, are tablets present?
0
❑ ❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑
❑ ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑ ❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available? ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑
NDAR? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Are flow rates less than of permitted flow? ❑ ❑ ❑
Page 5 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit:
Routine
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
❑
❑ ❑
Comment: Groundwater monitoring indicates some erratic TDS and coliform exceedances. Discussed
with the ORC during the inspection.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
Is municipal water available in the area?
❑ ❑ ❑
Are GW monitoring wells required?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RIB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑ ❑ ❑
Is a usable green area maintained?
❑
❑ ❑
Is the disposal site acceptable?
❑ ❑ ❑
Is the distribution equipment acceptable?
❑ ❑ ❑
Is the disposal site free of ponding?
❑ ❑ ❑
Is the disposal site free of breakout?
❑ ❑ ❑
Page 6 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Are the disposal sites free of solids, algae, etc.?
Do the records show that the fields are properly maintained?
Are the disposal sites free of vegetation?
Do any surface water features appear to be adversely impacted by GW discharge?
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
Comment:
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑❑■❑
❑❑❑■
Page 7 of 7