February 11, 2020
SUBJECT: Compliance Inspection Report
Peppertree Resort WWTP
Non -discharge Permit No. WQ0011313
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Peppertree Resort
WWTP on 1/29/2020. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0011313. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 days of your receipt of this letter regarding your plans
or measures to be taken to address the following issue(s):
• Facility is showing signs of age and is heavily corroded. The wastewater treatment plant is in need
of sandblasting, structural repairs and recoating along with any necessary repair or replacement of
treatment components.
North Cs{obna Department of Environmeatsd Quaiitp I Division of Water Resources
,�D,F.0-,i WdfmngwnRego naaOffice 1127 CarMaaiDrive Extensen I Wilwngton, North Caroina2S405
°'-\ 910-796-7215
DocuSign Envelope ID: 191BDA87-5667-4ED4-8A6D-E33EDE6A4291
If you should have any questions, please do not hesitate to contact Geoff Kegley with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
geoff.kegley@ncdenr.gov.
Sincerely,
E-T
DocuSigned by:
oµ�cOA, for
7F141 E73B6F3456_
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Cc: Fortin Contract Service
DWR-Laserfiche
Q�North Cafobns Department of Environmeatsd Qua;ity I Division of Water Resources
WdfningtonR ionmOfhce 1 127 CarMin:!Diive Extensen 11i91m,ngton, North Caroina2S405
i 8 " 910-796-7215
Compliance Inspection Report
Permit: WQ0011313 Effective: 11/15/18 Expiration: 09/30/23 owner: Festiva Real Estate Holdings LLC
SOC: Effective: Expiration: Facility: Peppertree Resort WWTP
County: Carteret 715 W Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person: H Catherine Claussen Title: President Phone: 828-348-2505
Directions to Facility:
From Wilmington, follow US 17N to NC 24 E to US 70E. Turn right on Atlantic Beach Causeway, Turn right on NC 58W, facility is on
the left.
System Classifications: WW2,
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 01/29/2020 Entry Time: 11:OOAM
Primary Inspector: Geoff Kegley
Secondary Inspector(s):
Reason for Inspection: Routine
Permit Inspection Type: High Rate Infiltration
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent
Treatment Flow Measurement -Water Treatment
Use Records
Treatment Filters Record Keeping
Treatment Sludge Storage/Treatment End Use -Irrigation
Treatment Disinfection Treatment Flow Measurement
Standby Power Wells
(See attachment summary)
Exit Time: 12:30PM
Phone:
Inspection Type: Compliance Evaluation
Miscellaneous Questions
Treatment Barscreen
Treatment Activated Sludge
Treatment Clarifiers
Treatment Return pumps
Page 1 of 7
Permit: WQ0011313 Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection was performed with the assistance of Dan Fortin and company. Facility is showing signs of
age and is heavily corroded. Operators have been working diligently to maintain functionality of the system, however
sandblasting, structural repairs and recoating of the wastewater treatment plant is needed. See below for further notes and
comments. A plan of action for repair is requested within 30 days.
Page 2 of 7
Permit: WQ0011313
Inspection Date: 01/29/2020
Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Activated Sludge Spray, HR
❑
Infiltration System
❑
Recycle/Reuse
❑
Single Family Spray, LR
❑
Lagoon Spray, LR
❑
Reuse (Quality)
❑
Single Family Drip
❑
Activated Sludge Spray, LR
❑
Activated Sludge Drip, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) ❑ 0 ❑ ❑
Comment: Anoxic basin is not in use but being used as additional flow EQ. The original trains "1 and 2"
have been taken offline as they are severely corroded and are reportedly scheduled for
demolition.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
1:10 ❑
Is flowmeter operating properly?
❑
1:10 ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑ ❑ ❑
Is flowmeter operating properly?
❑ ❑ ❑
Does flowmeter monitor continuously?
❑ ❑ ❑
Does flowmeter record flow?
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
0
❑ ❑ ❑
Comment: Calibration sticker not present but ORC provided documentation after inspection.
Page 3 of 7
Permit: WQ0011313 Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Standby Power
Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑
Is generator operable? ❑ ❑ ❑
Does generator have adequate fuel? 0 ❑ ❑ ❑
Comment: Auto transfer tested and is operational.
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris?
❑ ❑ ❑
Is disposal of screenings in compliance?
❑ ❑ ❑
Are the bars spaced properly?
❑ ❑ ❑
Is the unit in good condition?
❑ ❑ ❑
Comment:
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? 0 ❑ ❑ ❑
Is the aeration basin thoroughly mixed? ❑ ❑ ❑
Is the aeration equipment easily accessed? ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑
Are Settleometer results acceptable? ❑ ❑ ❑
Is activated sludge an acceptable color? 0 ❑ ❑ ❑
Comment: Heavy corrosion is present on the aeration basins. Operators have worked hard to make repairs
in the air header to bypass the worst corrosion and maintain some functionality. Aeration basins
are in need of sandblasting, welding, repair and recoating. Currently transferring from one train
to the other in preparation of this expected repair work.
Treatment Clarifiers Yes No NA NE
Are the weirs level? ❑ ❑ ❑
Are the weirs free of solids and algae? ❑ ❑ ❑
Is the scum removal system operational? ❑ ❑ ❑
Is the scum removal system accessible? ❑ ❑ ❑
Is the sludge blanket at an acceptable level? ❑ ❑ ❑
Is the effluent from the clarifier free of excessive solids? 0 ❑ ❑ ❑
Comment: Clarifiers are somewhat cloudy. Clarifiers are in need of sandblasting, welding, repair and
recoating.
Treatment Return pumps Yes No NA NE
Are they in place? 0 ❑ ❑ ❑
Are they operational? 0 ❑ ❑ ❑
Comment:
Page 4 of 7
Permit: WQ0011313 Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Treatment Filters Yes No NA NE
Is the filter media present? 0 ❑ ❑ ❑
Is the filter media the correct size and type? 0 ❑ ❑ ❑
Is the air scour operational? 0 ❑ ❑ ❑
Is the scouring acceptable? 0 ❑ ❑ ❑
Is the clear well free of excessive solids? 0 ❑ ❑ ❑
Is the mud well free of excessive solids and filter media? 0 ❑ ❑ ❑
Does backwashing frequency appear adequate? 0 ❑ ❑ ❑
Comment: Clear well effluent prior to filters is cloudy. Effluent from sample port after the disc filters looked
clear. Filters have auto backwash capability, but operators perform daily.
Treatment Sludge Storage/Treatment Yes No NA NE
Is the aeration operational? 0 ❑ ❑ ❑
Is the aeration pattern even? ❑ ❑ ❑
If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑
Comment:
Treatment Disinfection
Yes No NA NE
Is the system working?
❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection?
❑ ❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑ ❑
Is the system properly maintained?
❑
❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑ ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑ ❑
Is the chlorinator accessible?
❑ ❑ ❑
If tablets, are tablets present?
❑ ❑ ❑
Are the tablets the proper size and type?
❑
❑ ❑
Is contact chamber free of sludge, solids, and growth?
❑ ❑ ❑
If UV, are extra UV bulbs available?
❑
❑ 0 ❑
If UV, is the UV intensity adequate?
❑
❑ ❑
# Is it a dual feed system?
❑
❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑ ❑
If yes, then is there a Risk Management Plan on site?
❑
❑ ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: UV system is inoperable. Effluent monitorina mostly indicates proper disinfection from usin
chlorine disinfection in the old train's contact chamber. Severe corrosion is present in this
structure and this should be considered a temporary solution. Repair or replacement with a
proper disinfection contact chamber or new UV system needs to be installed.
Page 5 of 7
Permit: WQ0011313 Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit:
Routine
Record Keeping
Yes No NA NE
Is a copy of current permit available?
❑
❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑ ❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Is a copy of the SOC readily available?
❑
❑ ❑
No treatment units bypassed since last inspection?
❑
❑ 0 ❑
Comment: Groundwater monitoring indicates some erratic ammonia and coliform exceedances. The
Division will continue to monitor and evaluate these results. If future monitoring indicates
increasing trends in constituents in downgradient monitoring wells, corrective action may be
required.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
❑ ❑ ❑
Is the cover crop type specified in permit?
❑ ❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Page 6 of 7
Permit: WQ0011313 Owner - Facility: Festiva Real Estate Holdings LLC
Inspection Date: 01/29/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑
❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
0
❑ ❑ ❑
# Info only: Does the permit call for monitoring wells?
0
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑
0 ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
0
❑ ❑ ❑
Are monitoring wells damaged?
❑
❑ 0 ❑
Comment: A new map was received during the 2018 permit renewal. This map
indicates that several wells
are improperly located outside of the compliance boundary.
Page 7 of 7