Subject: Notice of Deficiency
Compliance Evaluation Inspection
NOD-2020-PC-0025
Berkley Oaks WWTP
NPDES Permit No. NCO062278
Gaston County
Enclosed is a copy of the Compliance Evaluation Inspection report for the inspection
conducted at the subject facility on November 28, 2018, by Ori Tuvia and Michael Meilinger.
The cooperation of Gregory Trombello during the site visit was much appreciated. Please advise
the staff involved with this NPDES Permit by forwarding a copy of the enclosed report.
Overall the site condition appears to have improved from the previous inspection. The
main areas of concern observed during this inspection were as follows:
1. Floor grating was broken at the entrance to the plant. Floor grating should be repaired to
ensure the safety of the ORC/operators and DWR staff.
2. At the time of inspection, the required records/reports could not be reviewed due to the
fact they are not maintained on site. Per permit condition Part II, Section D.6 the
Permittee shall retain records of all monitoring information, including:
D all calibration and maintenance records
D all original strip chart recordings for continuous monitoring instrumentation
➢ copies of all reports required by this permit
➢ copies of all data used to complete the application for this permit
The records were eventually sent for review in the mail three weeks after the inspection.
If copies (electronic or hard copies) of these records/reports were maintained on site, it
would greatly assist the inspector to conduct a thorough inspection. These records/reports
should include: a copy of the permit, DMR's and any associated lab data/documentation
(lab results, chain of custody, calibration data, solids removal records).
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
You are requested to respond to this Notice by march 10, 2020, with your plan of action to
resolve the broken floor grating.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
EDocuSigned by:
AwN P:z>v.yfor
F161 F669A2D84A3...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
cc: NPDES, MRO files (Laserfiche)
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO062278 111 12 I 20/01/15 I17 18 I S i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I r, I 73 I I I74 751 I I I I I I I80
1.0 70 I z I 71 tyI I
I —I � I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
01:00PM 20/01/15
15/09/01
Berkley Oaks WWTP
602 Ramsey Cir
Exit Time/Date
Permit Expiration Date
Gastonia NC 28052
03:OOPM 20/01/15
20/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Gregory Alexander Trombello/ORC/704-989-0165/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Sam Misuraca,821 W Eleven Mile Rd Royal Oak MI 48067//248-399-7722/2483999975
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori A Tuvia DWR/MRO WQ/704-663-1699/ 2/6/2020
Michael J MellingerJDWR/MRO WQ/910-796-7336/
IBB057A2DE017498...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Nu DocuSigned by: Date
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ A�•�nt1v H pa*." 2 .6.2020Aqnsgai
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO062278 I11 121 20/01/15 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO062278 Owner - Facility: Berkley Oaks WWTP
Inspection Date: 01/15/2020 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 8/31/2020. The last compliance evaluation inspection was
performed on November 28 , 2018 and resulted in a Notice of Violation (NOV-2018-PC-0460.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
❑
0
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: DMRs, COC's, ORC lops and calibration lops were reviewed for the moths of October 2019
through December 2019 (sent by mail on later date).
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Page# 3
Permit: NCO062278 Owner - Facility: Berkley Oaks WWTP
Inspection Date: 01/15/2020 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑
# Is the facility using a contract lab? 0 ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑
Comment: On -site field analyses (PH, temperature, total residual chlorine) are performed under
Metwater, Inc.'s field laboratory certification #5615. Water Tech Labs, Inc. (Certification #50)
has also been contracted to provide analytical support for all remaining permit -required
parameters (BOD, TSS, ammonia, fecal coliform).
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires effluent grab and composite samples.
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type, and
sampling location)?
Comment:
Operations & Maintenance
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Is the plant generally clean with acceptable housekeeping? ❑ 0 ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Floor grating was broken at the entrance to the plant. Floor grating should be repaired to
ensure the safety of the ORC/operators and DWR staff.
Bar Screens
Type of bar screen
Yes No NA NE
Page# 4
Permit: NCO062278
Inspection Date: 01/15/2020
Owner - Facility: Berkley Oaks WWTP
Inspection Type: Compliance Evaluation
Bar Screens
Yes No NA NE
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The facilitv is eauiooed with a coarse bar screen located in the aeration basin. A new biaaer
bar screen was installed at the facillity in 2018. At the time of the inspection it appeared that
the upgraded bar screen greatly reduced the screening debris in downstream treatment
units that was observed in the previous inspections.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
S
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
0
❑
Comment: Since the previous inspection the facility has developed and implemented a maintenance
program for the blower/motor units.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Page# 5
Permit: NC0062278 Owner - Facility: Berkley Oaks WWTP
Inspection Date: 01/15/2020 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) 0 ❑ ❑ ❑
Comment:
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
0 ❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Comment:
Are the tablets the proper size and type? ❑ ❑ ❑
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment: Flow meter has been annually calibrated.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? M ❑ ❑ ❑
Page# 6
Permit: NC0062278
Inspection Date: 01/15/2020
Effluent Pipe
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Owner - Facility: Berkley Oaks WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
❑ ❑ ■ ❑
Page#