HomeMy WebLinkAboutWQ0002571_Compliance Evaluation Inspection_20200124DocuSign Envelope ID: E6CB04BC-E5B7-44A8-BB90-DDF67DFOBOAF
ROY COOPER
Governor
MICHAEL S. REGAN
secretary
LINDA CULPEPPER
DVrector
Certified Mail # 7018 2290 0001 8295 9748
Return Receipt Requested
Bobby F Williams
164 Harris Creek Rd
Jacksonville, NC 28540
NORTH CAROLINA
environmental Qual ty
February 3, 2020
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2020-PC-0056
Permit No. WQ0002571
Village Oaks Mobile Home Park WWTF
Onslow County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Village Oaks Mobile Home Park
WWTF on January 24, 2020. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in Non -discharge Permit No. WQ0002571. A summary of the findings
and comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Wilmington
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation
Record Keeping Failure to document maintenance activities. (section IV.9)
End Use -Irrigation Failure to perform inspections and maintenance of the irrigation facility to ensure proper
operations. (section V.1-2)
End Use -Irrigation Failure to take measures to prevent effluent ponding in or runoff from the irrigation site.
(section III.5)
Noah Caroon a Departmentof Env:+onments Quasfty I Divs,on of Water Resources
Wrm.ngton Reg on Off oe 1127 Catoona:Dnve Enenson I W.rtn n ilon. North Caroaaa28405
2•"""'°zi�""� 910-796-7215
DocuSign Envelope ID. E6CB04BC-E5B7-44A8-BB90-DDF67DFOBOAF
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility's Non -discharge Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten (10) business days after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality
Regional Operations Section in the Wilmington Regional Office at 910-796-7215.
Sincerely,
DocuSignetl by:
70. 'Cha,r1_
7F141E73B6F3456. for
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Allen Rhue — electronic copy
Uploaded to Laser fiche
North Caroene Deponm ritof Envvwrne WQual4y I Divsonof Water Resources
Wdmngton Reg~0fFoe 1127 Cardinal Dnve EAt on I WSfmngtm, North Crosne 2f3405
af. 910-796-7215
Compliance Inspection Report
Permit: WO0002571 Effective: 08/23/19 Expiration: 09/30/24 Owner: Bobby F Williams
SOC: Effective: Expiration: Facility: Village Oaks Mobile Home Park WWTF
County: Onslow 2980 Burgaw Hwy
Region: Wilmington
Jacksonville NC 28540
Contact Person: Bobby F Williams Title: Phone: 910-346-9912
Directions to Facility:
Southwest of Jacksonville. On the North side of NC Highway 53 approximately 0 4 mile West of SR 1109.
System Classifications: SI,
Primary ORC: Allen Wayne Rhue Certification: 987930 Phone: 910-358-3254
Secondary ORC(s):
On -Site Representative(s):
On -site representative Allen Wayne Rhue 910-358-3254
Related Permits:
Inspection Date: 01/24/2020 EnttryTime: 10.00AM Exit Time: 12:40PM
Primary Inspector: Helen I Perez �/a - /0 Phone: 910-796-7387
Secondary fnspector(s): W�
Tyler G Benson
Reason for Inspection: Routine
Permit Inspection Type: Wastewater Irrigation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Inspection Type: Compliance Evaluation
Treatment Flow Measurement -Effluent Treatment Flow Measurement-Innuent
Treatment Flow Measurement -Water Treatment
Use Records
End Use -Irrigation ■ Treatment Flow Measurement
(See attachment summary)
Miscellaneous Questions
Record Keeping
Page 1 of 5
Permit: W00002571 Owner- Facility: Bobby F Williams
Inspection Dale: 01/24/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary
A routine compliance inspection of the Village Oaks Mobile Home Park WWTF was conducted on January 24, 2020. The
purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified
in Permit WQ0002571. Allen Rhue, ORC, was present during the inspection.
This facultative lagoon system was originally issued in 1985 and is still covered under rules which contained no setback
requirements. It is permitted for 13,200 gpd but only averages a little less than half that flow. Influent flow is calculated by
water meter readings for the mobile home park.
The BORC is still listed as David Antinon for this facility. The ORC indicated that the BORC is Brandon Williams. An
Operator Designation Form will need to be submitted to the Raleigh address indicated on the form as well as a copy to the
Wilmington Regional Office as soon as possible.
Recently, the disposal site was cleared of trees that were damaged by hurricanes. This removal activity has caused uneven,
bare spots throughout the field. A vegetative cover will need to be maintained on the irrigation site to allow even effluent
distribution (Permit section 111.4)
Acreage of the disposal site is not fully utilized because of insufficient pressure to the spray heads. This issue has caused
ponding in some areas and was noted in a Notice of Deficiency issued for the last inspection on 7-25-2018. Please note that
the permit requires the irrigation equipment be tested and calibrated once per permit cycle (Permit section 111.7).
Runoff was observed from spray heads to a drainage ditch, cut over time, on the north side of the disposal site and
continues on a downward slope off the property. Irrigation pipes are exposed in the ditch. There is a drainage ditch between
the west edge of the disposal site and the lagoons, that also has pipe exposure and possible runoff. Samples were taken by
the inspectors during the inspection at each ditch for fecal coliform and nutrients. The north back three rows and the west
outer row of spray heads were shut off during the inspection so no more runoff would occur until the issue can be addressed.
Freeboard in the lagoons was at approximately 2 feet which is a concern since the above mentioned spray heads have been
shut off. There was no documentation found for maintenance of the irrigation equipment or disposal site.
A Notice of Violation and Intent to Issue Civil Penalty will be issued for the following non-compliance of Permit W00002571:
1. Failure to perform inspections and maintenance of the Irrigation facility to ensure proper operations. (section V.1-2)
2. Failure to document maintenance activities. (section IV.9)
3. Failure to take measures to prevent effluent ponding in or runoff from the irrigation site. (section 111.5)
Page 2 of 5
Permit: W00002571 Owner- Facility: Bobby F Williams
Inspection Date: 01/24/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Type
Yes No NA NE
Infiltration System
Activated Sludge Spray, HR
El
Single Family Spray, LR
Reuse (Quality)
Activated Sludge Drip, LR
Activated Sludge Spray, LR
Single Family Drip
Recycle/Reuse
Lagoon Spray, LR
Treatment
Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.) M El El n
Comment- No comment.
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
❑
❑ 0 ❑
Comment
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? 0 El ❑ ❑
Are the daily average values properly calculated? ❑ ❑ ❑
Comment: Influent flow is estimated using water meter readings for the mobile home park.
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑ ❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ 0 ❑
Does flowmeter record flow?
0
❑ ❑ ❑
Does flowmeter appear to monitor accurately?
0
110 ❑
Comment The flow meter was calibrated on 7-14-2019 by Neptune
Record Keeping Yes No NA NE
Is a copy of current permit available? ❑ ❑ ❑
Page 3 of 5
permit: WQ0002571 Owner- Facility: Bobby F Williams
Inspection Date: 01/24/2020 Inspection Type : Compliance Evaluation Reason for Visit:
Routine
Are monitoring reports present. NDMR?
0
❑ ❑ ❑
NDAR?
0
❑ ❑ ❑
Are Flow rates less than of permitted flow?
0
❑ ❑ ❑
Are Flow rates less than of permitted flow?
N
❑ ❑ ❑
Are application rates adhered to?
0
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑ ❑ ❑
Are all samples analyzed for all required parameters?
0
❑ ❑ ❑
Are there any 2L GW quality violations?
❑
N ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
0 ❑ ❑
Are annual soil reports available?
0
❑ ❑ ❑
# Are PAN records required?
❑
0 ❑ ❑
# Did last soil report indicate a need for lime?
❑
E ❑ ❑
If so, has it been applied?
❑
❑ 0 ❑
Are operational logs present?
E
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-590
❑
❑ ❑
Are Operational and Maintenance records present?
❑
E ❑ ❑
Were Operational and Maintenance records complete?
❑
❑ 0 ❑
Has permittee been free of public complaints in last 12 months?
❑
❑ ❑
Is a copy of the SOC readily available?
❑
❑ 0 ❑
No treatment units bypassed since last inspection?
0
❑ ❑ ❑
Comment. The operational log was present but there was no maintenance documentation found for the
irrigation equipment or disposal site.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
❑
❑ 0 ❑
Is the cover crop type specified in permit?
❑
0 ❑ ❑
Is the crop cover acceptable?
❑
N ❑ ❑
Is the site condition adequate?
❑
0 ❑ ❑
Is the site free of runoff / pondmg?
❑
0 ❑ ❑
Is the acreage specified in the permit being utilized?
❑
0 ❑ ❑
Is the application equipment present?
0
❑ ❑ ❑
Is the application equipment operational?
0
❑ ❑ ❑
Is the disposal field free of limiting slopes?
❑
0 ❑ ❑
Page 4 of 5
Permit: WQ0002571 Owner- Facility: Bobby F Williams
Inspection Date: 01/24/2020 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# into only. Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
Comment Acreage of the disposal site is not fully utilized because of insufficient pressure to the spray
heads. Ponding and runoff was observed. An acceptable crop cover needs to be maintained
since the removal of hurricane damaged trees from disposal site
❑ ❑ ❑
❑❑❑■
■❑❑❑
■❑❑❑
❑❑❑■
❑ ❑ ❑