Loading...
HomeMy WebLinkAboutNC0050661_Compliance Evaluation Inspection_20200124ROY COOPER Governor MICHAEL S. REGAN Secretory LINDA CULPEPPER Director Eric Johnson Town of Macclesfield PO Box 185 Macclesfield, NC 27852-0185 NORTH CAROLINA Environmental Quality January 24.2020 Subject: Compliance Evaluation Inspection Town of Macclesfield WWTP NPDES Permit NCO050661 Edgecombe County Dear Mr. Johnson: On January 15, 2020, Vanessa Manuel of the Raleigh Regional Office conducted a compliance evaluation inspection of the treatment facilities located at the Town of Macclesfield Wastewater Treatment PIant (WWTP). The purpose of this inspection was to ensure compliance with the subject NPDES permit. During the inspection, the presence and cooperation of Sidney Bridgers, Operator in Responsible Charge (ORC), Brent Stilley and Jamie Linkous, were helpful and appreciated. The Town of Macclesfield WWTP is located at 77I South Fountain Road in Macclesfield, North Carolina. The facility is a Grade II Biological Water Pollution Control System with an as -built flow of 0.175 MGD that treats domestic wastewater. Through NPDES permit NCO050661, the Town of Macclesfield, hereinafter referred to as the Town, is authorized to discharge the treated wastewater through outfall 001 to receiving waters designated as an unnamed tributary to Briery Branch, a waterbody classified as C Nutrient Sensitive Waters within the Tar -Pamlico River Basin. This NPDES compliance evaluation inspection consisted of the following: • Review of the NPDES permit; • Review of the owner/facility information; • Review of November 2017 — October 2019 monitoring data and compliance history; • On -site inspection of the wastewater treatment units; and • On -site inspection of the discharge outfall. The current NPDES permit is effective from November 1, 2014 until September 30, 2019, and is subject to specific conditions, limits and monitoring requirements. On December 7, 2018, the Division received the Town's permit renewal application for the Town of Macclesfield WWTP. The Division is in the process of renewing this NPDES permit. The overall conditions of the records reviewed and the treatment components inspected were compliant with the NPDES D E Q 4 North Carolina Department of Environmental Quality ' Division of Water Resourcrs Raleigh Regional Officr i 3800 Barrett Drive I Raleigh, North Carolina 27609 919.791.4200 --qWW �•. Town of Macclesfield, NPDES Permit NCO050661 Pave 2 of 2 January 24, 2020 permit. We appreciate the Town's efforts to maintain a compliant wastewater treatment system. Please refer to the attached inspection report for full inspection details. If you have questions or comments about the inspection, this report or the requirements to take corrective action (if applicable), please contact Vanessa Manuel at 919-791-4255 or via email at Vanessa.Manuel ,ncdenr.Joy. Sincerely, Scott Vinson, Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of %Water Resources, NCDEQ Attachments. EPA Water Compliance Inspection Report Cc: RRO SWP Files Sidney T. Bridgers, ORC (via email) Laserfiche United States Enwronmental Protection Agency Form Approved. EPA Washington, D C 20460 OMB No, 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A. National Data System Coding (i.e., PCS) Transaction Code NPDES yrlmolday Inspection Type Inspector Fac Type 1 1ti l 2 1a 1 3 NCO050661 Ill 12 20101/15 17 18 Li r I 19 I g I 201 I t--I J L 21 6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 OA Reserved 67 70 LJ I j 71 Lj 72 L LN j 73 f t J74 75 J_U80 J l I I Section B. Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW also include Entry Time/Date Permit Effective Date POTVV name and NPDES permit Number) 10 05AM 20/01115 14111i01 Town of Macclesfield WWTP Exit Time/Date Permit Expiration Date 771 S Fountain Rd Macclesfield NC 27852 01 OOPM 20/01/15 19/09/30 Name(s) of Onsite Representative(s)1Tides(s)lPhone and Fax Number(s) Other Facility Data X Sidney T Bridgers10RC1252-827.44351 Name Address of Responsible OfficiaVTidelPhone and Fax Number Phillip T Wainwright. PO Box 185 Macclesfield NC Contacted 27852!Superintendent/252-236-1153; Yes Section C, Areas Evaluated During Inspection (Check only those areas evaluated) Permit E Flow Measurement Operations 8 Maintenance 0 Records/Reports Self -Monitoring Program 0 Sludge Handling Disposal � Facility Site Review E Effluent/Receiving Waters Laboratory Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspectar(s) Agency-Offceirhone and Fax N,.mbers Date Vanessa E Manuel DWR;RRO W0;919-79142130r Signature of Management 0 A Reviewer AgencyfOff!.ef'J^.ne and Fax Numbers Date j-2Z �f-- EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yrlmolday Inspection Type 31 NC0050661 I11 12 20101:15 17 18 ICI Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) See attached inspection letter. Page# Permit NCO050661 Owner - Facility: Town of klacdesfield MVTP Inspection Dale: 0111512020 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ application? Is the facility as described in the permit? 0❑ ❑ ❑ # Are there any special conditions for the permit? M ❑ ❑ ❑ Is access to the plant site restricted to the general public? M❑ ❑ ❑ Is the inspector granted access to all areas for inspection? M❑ ❑ ❑ Comment: The NPDES germit expired September 30 2019 and the permit renewal application was received December 7, 2018. The permit re uires the Permittee to submit its monitoring data electronically to the NC OWR. Record KeeDing Yes No NA NE Are records kept and maintained as required by the permit? ❑ ❑ ❑ Is all required information readily available, complete and current? ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ❑ ❑ ❑ Is the chain -of -custody complete? ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses ❑ Transported COCs Are DMRs complete do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWO? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ ■ Facility has copy of previous year's Annual Report on fife for review? ❑ ❑ 0 El Comment: Because the treatment Qlant has a Permitted discharge of 0.175 MGD the Permittee is not re aired to provide an annual performance report to the NC DWR and its users/customers. Page# 3 Permit NCO050661 Owner • Facility: Town of blacclesfie{d 11UWTP Inspection Date: 01r1512020 Inspection Type: Compliance Evaluation operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters. for ex MtSS, MCRT, Settleable ❑ ❑ ❑ 0 Solids, pH, DO Sludge Judge, and other that are applicable? Comment: Pump Station - Influent Yes No NA NE 1s the pump wet well free of bypass lines or structures? ❑ Is the wet well free of excessive grease? ® ❑ ❑ Are all pumps present? M ❑ ❑ ❑ Are all pumps operable? N ❑ ❑ ❑ Are float controls operable? 0 0 ❑ 0 Is SCADA telemetry available and operational? N ❑ 11 ❑ Is audible and visual alarm available and operational? ❑ ❑ ❑ M Comment Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? ■ ❑ Is the screen free of excessive debris? N C1 ❑ ❑ Is disposal of screening in compliance? 0 El El 0 Is the unit in good condition? M ❑ El 13 Comment: Grit Removal Yes No NA NE Type of grit removal a.Manual ❑ b.Mechanical Is the grit free of excessive organic matter? Is the grit free of excessive odor? 0 # Is disposal of grit in compliance? N ❑ ❑ ❑ Comment: Page# 4 Permit NG0050651 Owner - Facility: Town of Macclesfield wtNTP Inspection Date: 01115:2C20 Inspection Type; Cairpliance Evaluation Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well cf orvular clarifier-, Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-c rcuit,ng? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately Y4 of the sidewall depth) ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ M ■ ❑ ❑ ❑ 110 ❑ ❑ Comment; The ORC stated the clarifier is 12.5 feet deer), the operator measured the sludge depth at 4 feet which is greater than 1 /4 of the sidewall depth, The permittee should take measures to reduce the amount of solids in the clarifier, Oxidation Ditches Are the aerators operational? Are the aerators free of excessive solids build up? * Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Are settleometer results acceptable (> 30 minutes)? Is the DO level acceptable?(1.0 to 3.0 mg/1) Are settelometer results acceptable?(400 to 800 mllf in 30 minutes) Yes No NA NE ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑❑❑■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: One of the 2 rotors was down and not in operation at the time of the inspection. The operators stated Pearson Pum s has been contracted to repair the rotor which has been out of operation since January $ 2020. The repair is exiciected around January 16 2020. Filtration (High Rate Tertiary) Yes No NA NE Type of operation. Down flow Is the filter media present? 0 11 ❑ ❑ Is the filter surface free of clogging? 0❑ ❑ El Is the filter free of growth? . ❑ ❑ ❑ Is the air scour operational? ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Page# 5 Permit: NCO050681 owner -Facility: Town of Macclesfield WWiP Inspection Date' 011517o20 Inspection Type: Compliance Evaluation Filtration (High Rate Tertiand Yes No NA NE 1s the clear well free of excessive solids and filter media? 0 ❑ ❑ ❑ Comment: Pumps-RAS-WAS Yes No NA NE Are pumps in place? a ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? ❑ ❑ ❑ 0 Comment: Disinfection -Liquid Yes No NA NE Is there adequate reserve supply of disinfectant? 0 ❑ ❑ ❑ {Sodium Hypochlorite) Is pump feed system operational? 0 ❑ ❑ ❑ 1s bulk storage tank containment area adequate? (free of leakslopen drains) ❑ ❑ ❑ Is the level of chlor ne residual acceptable? ❑ ❑ ❑ Is the contact chamber free of growth. or sludge buildup? ❑ ❑ ❑ Is there chlorine residual pnor to de -chlorination? 0 ❑ ❑ ❑ Comment: De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount 0 to 1)? ❑ ❑ ❑ Is storage appropriate for cylinders? E ❑ ❑ ❑ # Is de -chlorination substance stored away from chlorine containers? N ❑ ❑ ❑ Comment. Are the tablets the proper size and type? ❑ ❑ E El Are tablet de -chlorinators operational? ❑ ❑ Number of tubes in use? Comment: Standby Power Yes No NA NE Is automatically activated standby power available? N ❑ Is the generator tested by interrupting primary power source? 0 ❑ ❑ ❑ Is the generator tested under load? E ❑ ❑ ❑ Page# 6 Permit: NCOOS0661 Owner - Facility: Town of Macclesfield WWrP Inspection Date: 01115/2020 Inspection Type: Compliance Evaluation Standby Power Yes No NA NE Was generator tested & operational during the inspection? ❑ ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site? N 0 ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power? ❑ ❑ ❑ Is the generator fuel level monitored? ❑ ❑ ❑ Comment: Aerobic Digester Yes No NA NE Is the capacity adequate? 0❑ ❑ ❑ Is the mixing adequate? N❑ ❑ ❑ Is the site free of excessive foaming in the tank? 0 ❑ ❑ ❑ # Is the odor acceptable? 0 ❑ ❑ ❑ # Is tankage available for properly waste sludge? 0 ❑ ❑ ❑ Comment: Drying Beds Yes No NA NE Is there adequate drying bed space? N❑ ❑ ❑ Is the sludge distribution on drying beds appropriate? 0 ❑ ❑ ❑ Are the drying beds free of vegetation? 0❑ ❑ ❑ # Is the site free of dry sludge remaining in beds? ■ ❑ ❑ ri Is the site free of stockpiled sludge? E ❑ ❑ ❑ Is the filtrate from sludge drying beds returned to the front of the plant? ❑ ❑ ❑ # Is the sludge disposed of through county landfill? ❑ ❑ ❑ # Is the sludge land applied? ❑ ❑ ❑ (Vacuum filters) Is polymer mixing adequate? ❑ ❑ ❑ Comment: Upon removal from the drying beds. the solids are hauled to the Bertie Countv Landfill b Jeffe 's Construction company. Theo erators stated the sludge is hauled approximately once per year. Influent Sampling Yes No NA NE # Is composite sampling flow proportional? ❑N ❑ ❑ Is sample collected above side streams? ❑ ❑ ❑ Is proper volume collected? ❑ ❑ Is the tubing clean? Cl❑ ri Page# 7 permit: N00050661 Owner - Facility: Town of Macclesfield VVWTP Inspection Date: 011151202o Inspection Type: Compliance Evaluation Influent Sampling Yes No NA NE # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees E ❑ ❑ ❑ Celsius)? Is sampling performed according to the permit? ❑ ❑ ❑ Comment: There is no flow meter on the influent waste stream to the treatment plant. The temperature of the influent composite refrigerator was 4.5 deg. Celcius. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 130 Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? ❑ ❑ ❑ 0 Is the tubing clean? N ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees S ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency sampling type 0 ❑ ❑ ❑ representative)? Comment: The temperature in the effluent composite sample refrigerator was observed at 4.5 deg. Celcius. Upstream ! Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type. and 0 ❑ ❑ ❑ sampling location)? Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? N ❑ ❑ ❑ Is flow meter calibrated annually? E ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ❑ Comment: The flow meter was calibrated on January 23 2018 and January 16 2019 by Carolina Technical Services, Inc. CTS is scheduled to calibrate the flow meter on January 20, 2020. The permittee should ensure the flow meter is calibrated at least annually as required by the NPDES permit. Effluent Pik Yes No NA NE Is right of way to the outfall properly mainta--ned? E ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? E ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ E ❑ Page# 8 Permit NCOOMW Inspection Data: 01115/2020 Effluent Pipe Comment: Owner • Facility: Town of Macclesfield WWTP Inspection Type: Compliance Evaluation Yes No NA NE Pale*