January 24.2020
Subject: Compliance Evaluation Inspection
Town of Macclesfield WWTP
NPDES Permit NCO050661
Edgecombe County
Dear Mr. Johnson:
On January 15, 2020, Vanessa Manuel of the Raleigh Regional Office conducted a compliance
evaluation inspection of the treatment facilities located at the Town of Macclesfield Wastewater
Treatment PIant (WWTP). The purpose of this inspection was to ensure compliance with the
subject NPDES permit. During the inspection, the presence and cooperation of Sidney Bridgers,
Operator in Responsible Charge (ORC), Brent Stilley and Jamie Linkous, were helpful and
appreciated.
The Town of Macclesfield WWTP is located at 77I South Fountain Road in Macclesfield, North
Carolina. The facility is a Grade II Biological Water Pollution Control System with an as -built
flow of 0.175 MGD that treats domestic wastewater. Through NPDES permit NCO050661, the
Town of Macclesfield, hereinafter referred to as the Town, is authorized to discharge the treated
wastewater through outfall 001 to receiving waters designated as an unnamed tributary to Briery
Branch, a waterbody classified as C Nutrient Sensitive Waters within the Tar -Pamlico River
Basin.
This NPDES compliance evaluation inspection consisted of the following:
• Review of the NPDES permit;
• Review of the owner/facility information;
• Review of November 2017 — October 2019 monitoring data and compliance history;
• On -site inspection of the wastewater treatment units; and
• On -site inspection of the discharge outfall.
The current NPDES permit is effective from November 1, 2014 until September 30, 2019, and is
subject to specific conditions, limits and monitoring requirements. On December 7, 2018, the
Division received the Town's permit renewal application for the Town of Macclesfield WWTP.
The Division is in the process of renewing this NPDES permit. The overall conditions of the
records reviewed and the treatment components inspected were compliant with the NPDES
D E Q 4 North Carolina Department of Environmental Quality ' Division of Water Resourcrs
Raleigh Regional Officr i 3800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
--qWW �•.
Town of Macclesfield, NPDES Permit NCO050661 Pave 2 of 2
January 24, 2020
permit. We appreciate the Town's efforts to maintain a compliant wastewater treatment system.
Please refer to the attached inspection report for full inspection details.
If you have questions or comments about the inspection, this report or the requirements to take
corrective action (if applicable), please contact Vanessa Manuel at 919-791-4255 or via email at
Vanessa.Manuel ,ncdenr.Joy.
Sincerely,
Scott Vinson, Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of %Water Resources, NCDEQ
Attachments. EPA Water Compliance Inspection Report
Cc: RRO SWP Files
Sidney T. Bridgers, ORC (via email)
Laserfiche
United States Enwronmental Protection Agency
Form Approved.
EPA Washington, D C 20460
OMB No, 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A. National Data System Coding (i.e., PCS)
Transaction Code NPDES yrlmolday Inspection Type Inspector Fac Type
1 1ti l 2 1a 1 3 NCO050661 Ill 12 20101/15 17 18 Li r I 19 I g I 201 I
t--I J L
21 6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 OA Reserved
67 70 LJ I j 71 Lj 72 L LN j 73 f t J74 75 J_U80
J l I I
Section B. Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW also include
Entry Time/Date
Permit Effective Date
POTVV name and NPDES permit Number)
10 05AM 20/01115
14111i01
Town of Macclesfield WWTP
Exit Time/Date
Permit Expiration Date
771 S Fountain Rd
Macclesfield NC 27852
01 OOPM 20/01/15
19/09/30
Name(s) of Onsite Representative(s)1Tides(s)lPhone and Fax Number(s)
Other Facility Data
X
Sidney T Bridgers10RC1252-827.44351
Name Address of Responsible OfficiaVTidelPhone and Fax Number
Phillip T Wainwright. PO Box 185 Macclesfield NC Contacted
27852!Superintendent/252-236-1153; Yes
Section C, Areas Evaluated During Inspection (Check only those areas evaluated)
Permit E Flow Measurement Operations 8 Maintenance 0 Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal � Facility Site Review E Effluent/Receiving Waters
Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspectar(s) Agency-Offceirhone and Fax N,.mbers Date
Vanessa E Manuel DWR;RRO W0;919-79142130r
Signature of Management 0 A Reviewer AgencyfOff!.ef'J^.ne and Fax Numbers Date
j-2Z
�f--
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yrlmolday Inspection Type
31 NC0050661 I11 12 20101:15 17 18 ICI
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
See attached inspection letter.
Page#
Permit NCO050661 Owner - Facility: Town of klacdesfield MVTP
Inspection Dale: 0111512020 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑
application?
Is the facility as described in the permit?
0❑
❑
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
M❑
❑
❑
Is the inspector granted access to all areas for inspection?
M❑
❑
❑
Comment: The NPDES germit expired September 30 2019 and the permit renewal application
was
received December 7, 2018.
The permit re uires the Permittee to submit its monitoring data electronically to the NC
OWR.
Record KeeDing
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
❑
Transported COCs
Are DMRs complete do they include all permit parameters? ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWO? ❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator ❑ ❑ 0 ❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
■
Facility has copy of previous year's Annual Report on fife for review?
❑
❑
0
El
Comment: Because the treatment Qlant has a Permitted discharge of 0.175 MGD the
Permittee is
not
re aired to provide an annual performance report to the NC DWR and its users/customers.
Page# 3
Permit NCO050661 Owner • Facility: Town of blacclesfie{d 11UWTP
Inspection Date: 01r1512020 Inspection Type: Compliance Evaluation
operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters. for ex MtSS, MCRT, Settleable ❑ ❑ ❑ 0
Solids, pH, DO Sludge Judge, and other that are applicable?
Comment:
Pump Station - Influent Yes No NA NE
1s the pump wet well free of bypass lines or structures? ❑
Is the wet well free of excessive grease? ® ❑ ❑
Are all pumps present? M ❑ ❑ ❑
Are all pumps operable? N ❑ ❑ ❑
Are float controls operable? 0 0 ❑ 0
Is SCADA telemetry available and operational? N ❑ 11 ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ M
Comment
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
■
❑
Is the screen free of excessive debris?
N
C1
❑
❑
Is disposal of screening in compliance?
0
El
El
0
Is the unit in good condition?
M
❑
El
13
Comment:
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
0
# Is disposal of grit in compliance?
N ❑ ❑ ❑
Comment:
Page# 4
Permit NG0050651 Owner - Facility: Town of Macclesfield wtNTP
Inspection Date: 01115:2C20 Inspection Type; Cairpliance Evaluation
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well cf orvular clarifier-,
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-c rcuit,ng?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately Y4 of the sidewall depth)
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
■ ❑ ❑ ❑
M ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ M
■ ❑ ❑ ❑
110 ❑ ❑
Comment; The ORC stated the clarifier is 12.5 feet deer), the operator measured the sludge depth at 4
feet which is greater than 1 /4 of the sidewall depth, The permittee should take measures to
reduce the amount of solids in the clarifier,
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
* Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Are settelometer results acceptable?(400 to 800 mllf in 30 minutes)
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑❑❑■
❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑
Comment: One of the 2 rotors was down and not in operation at the time of the inspection. The
operators stated Pearson Pum s has been contracted to repair the rotor which has been
out of operation since January $ 2020. The repair is exiciected around January 16 2020.
Filtration (High Rate Tertiary)
Yes No NA NE
Type of operation.
Down flow
Is the filter media present?
0 11
❑
❑
Is the filter surface free of clogging?
0❑
❑
El
Is the filter free of growth?
. ❑
❑
❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑
❑
❑
Page# 5
Permit: NCO050681 owner -Facility: Town of Macclesfield WWiP
Inspection Date' 011517o20 Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiand Yes No NA NE
1s the clear well free of excessive solids and filter media? 0 ❑ ❑ ❑
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? a ❑ ❑ ❑
Are pumps operational? 0 ❑ ❑ ❑
Are there adequate spare parts and supplies on site? ❑ ❑ ❑ 0
Comment:
Disinfection -Liquid
Yes No NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
{Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
1s bulk storage tank containment area adequate? (free of leakslopen drains)
❑
❑
❑
Is the level of chlor ne residual acceptable?
❑
❑
❑
Is the contact chamber free of growth. or sludge buildup?
❑
❑
❑
Is there chlorine residual pnor to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount 0 to 1)? ❑ ❑ ❑
Is storage appropriate for cylinders? E ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? N ❑ ❑ ❑
Comment.
Are the tablets the proper size and type? ❑ ❑ E
El
Are tablet de -chlorinators operational? ❑ ❑
Number of tubes in use?
Comment:
Standby Power
Yes No NA NE
Is automatically activated standby power available?
N
❑
Is the generator tested by interrupting primary power source?
0
❑ ❑
❑
Is the generator tested under load?
E
❑ ❑
❑
Page#
6
Permit: NCOOS0661 Owner - Facility: Town of Macclesfield WWrP
Inspection Date: 01115/2020 Inspection Type: Compliance Evaluation
Standby Power
Yes No NA NE
Was generator tested & operational during the inspection?
❑
❑
Do the generator(s) have adequate capacity to operate the entire wastewater site?
N
0
❑
❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
❑
❑
❑
Is the generator fuel level monitored?
❑
❑
❑
Comment:
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0❑
❑
❑
Is the mixing adequate?
N❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment:
Drying Beds
Yes No NA NE
Is there adequate drying bed space?
N❑
❑
❑
Is the sludge distribution on drying beds appropriate?
0
❑
❑
❑
Are the drying beds free of vegetation?
0❑
❑
❑
# Is the site free of dry sludge remaining in beds?
■
❑
❑
ri
Is the site free of stockpiled sludge?
E
❑
❑
❑
Is the filtrate from sludge drying beds returned to the front of the plant?
❑
❑
❑
# Is the sludge disposed of through county landfill?
❑
❑
❑
# Is the sludge land applied?
❑
❑
❑
(Vacuum filters) Is polymer mixing adequate?
❑
❑
❑
Comment: Upon removal from the drying beds. the solids are hauled to the Bertie Countv Landfill b
Jeffe 's Construction company. Theo erators stated the sludge is hauled approximately
once per year.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
❑N
❑
❑
Is sample collected above side streams?
❑
❑
❑
Is proper volume collected?
❑
❑
Is the tubing clean?
Cl❑
ri
Page# 7
permit: N00050661 Owner - Facility: Town of Macclesfield VVWTP
Inspection Date: 011151202o Inspection Type: Compliance Evaluation
Influent Sampling Yes No NA NE
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees E ❑ ❑ ❑
Celsius)?
Is sampling performed according to the permit?
❑ ❑ ❑
Comment: There is no flow meter on the influent waste stream to the treatment plant. The temperature
of the influent composite refrigerator was 4.5 deg. Celcius.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
130
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
❑
❑
❑
0
Is the tubing clean?
N
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
S
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency sampling type
0
❑
❑
❑
representative)?
Comment: The temperature in the effluent composite sample refrigerator was observed at 4.5 deg.
Celcius.
Upstream ! Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type. and 0 ❑ ❑ ❑
sampling location)?
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
N
❑
❑
❑
Is flow meter calibrated annually?
E
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
❑
Comment: The flow meter was calibrated on January 23 2018 and January 16 2019 by Carolina
Technical Services, Inc. CTS is scheduled to calibrate the flow meter on January
20, 2020.
The permittee should ensure the flow meter is calibrated at least annually as required by
the
NPDES permit.
Effluent Pik
Yes No NA NE
Is right of way to the outfall properly mainta--ned?
E
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
E
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
E
❑
Page# 8
Permit NCOOMW
Inspection Data: 01115/2020
Effluent Pipe
Comment:
Owner • Facility: Town of Macclesfield WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Pale*