Subject: Compliance Evaluation Inspection
Stansted Subdivision Well # 2 WTP
NPDES Pen -nit No. NCO086690
Hollybrook WTP
NPDES Permit No. NCO082996
Wake County
` fV-1 I
M1�41.1111i
The subject inspections were conducted December 30, 2019 by Mitch Hayes of the Raleigh
Regional Office. The cooperation and assistance of Chris Weaver, certified PC -I Operator in
Responsible Charge, was greatly appreciated. Below are findings developed from permit review
and the inspection:
Stansted Subdivision Well #2 WTP
I. The current permit was rene%%-ed and became effective November I, 2018 and will expire
April 30, 2023.
2. The 0.065 MGD potable water plant consists of the following units: groundwater source
well; chlorine disinfection and dechlorination units; two (2) -settling tanks; Bennefloc
before and after filters; three (3) greensand filters with backwash flow meter; distribution
flow meter; wastewater backwash drain line to settling tank; sand -bed filter with discharge
to outfall.
3. All units were in operation at the time of inspection. Effluent appeared clear and free of
solids flowing from the discharge pipe.
4. Chris Weaver is field certified for pH and residual chlorine. Eneo Laboratories performs
all other permit parameters.
5. COC`s for October 2019 were on file. A check of lab bench sheets to data on the Discharge
Monitoring Report (DMR) revealed no transcription errors.
North Carolina Department of Env ronmental Quality Division of Water Resources Raleigh Regional Office
3800 Barrett Drive 1628 Lfad Service Center Raleigh. North Carol na 27699-1628
,, . ,,
.y�
6. A review of DMR data from April 2016 to November 2019 include the following:
monitoring violation for total nitrogen for 06.2016 and 12.2016; late DMR reporting for
01.201 S. There were no other violations for the review period.
Hollybrook Subdivision WTP
7. The current permit was renewed and became effective November 1, 2018 and will expire
April 30, 2023.
S. The 0.017 MGD WTP consists of the following units: groundwater well at 26 gpm; sodium
hypochlorite .' sodium hydroxide feed system; two (2) greensand filters; chlorination
dechlorination units; potable water storage tank; wastewater storage; filter backwash to
subsurface sandbed; sludge removal for landfill disposal; discharge line to outfall.
9. The WTP has been inactive since 10.08.2015. Well #3 has been capped off. There is no
discharge to the environment. Please inform this office if Aqua would like to keep or
rescind this permit.
I would like,to thank Chris Weaver for his time and assistance with this inspection. If you have
any questions about this letter or the inspection, please contact Mitch Hayes at 919.791.4261 or at
mitch.haves cuncdenr.l'ov .
cc: permit files, Laserfiche
Sincerely,
2
J4*
Scott Vinson, Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources NC DEQ
N";,
North Carolina Department of Environmental Quabt} Division of Water Resources
512 North Salisbury Street :1617 Mail Service Center Raleigh. North Carolina 27699.1617
01 a 7n7 0f1r1()
Unled States Environmental Protection Agency
Form Approved.
EPA Washington D C 2W1B0
OMB No, 2040-0957
Water Compliance Inspection Report
Approval expires8-31-98
Section A: National Data System Coding (i,e., PCS)
Transaction Code NPDES yrlmolday Inspection Type Inspector Fac Type
1 u 2 15 1 3 NC0086690 11 12 19112130 17 18 C; I I 19 I LS J I 20I
r — ' r�l
21 6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CIA Reserved
67 70 (, LJ f, 71 Lj 72 ti) 73 ( ) I74 75 80
LJ I I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 45AM 19/12/30
18/11101
Stansted Well 92 (WiP)
Exit Time/Date
Permit Expiration Date
Stansted Dr
Cary NC 27518
11 30AM 19112/30
23/04/30
Name(s) of Onsite Representative(s)1Tides(syPhone and Fax Number(s)
Other Facility Data
!!1
Christopher Lee Weaver!!!
Christopher Lee WeaverlORCI!
Name, Address of Responsible OffciallritlelPhone and Fax Number
Joseph R Pearce 202 Mackenan Crt Cary NC 27511lOireclor of Contacted
Operationsl919-653-6964/9194601788 No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 RecordslReports Self -Monitor ng Program 0 Facility Site Review
Effluent/Receiving Waters
Section D Summary of FindinglComments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signalure(s) of Inspector(s) AgencylOffice/Phone and Fax Numbers Date
Mitchell S Hayes DWRlRRO WC:919-791.42D0!
Signature of Management C A Reviewer Agency;Office:Phone and Fax Numbers Date
/R40
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Pagr.:
HPDES yrtmolday Inspection Type (Cont.)
31 NCO086690 I11 12 19112130 17 18 ICI
Section 0 Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current permit was renewed and became effective November 1, 2018 and will expire April 30,
2023.
The 0.065 MGD potable water plant consists of the following units: groundwater source well; chlorine
disinfection and dechlorination units; two (2) -settling tanks; Bennefloc before and after filters; three (3)
greensand filters with backwash flow meter; distribution flow meter; wastewater backwash drain line to
settling tank; sand -bed filter with discharge to outfall.
All units were in operation at the time of inspection. Effluent appeared clear and free of solids flowing
from the discharge pipe.
Chris Weaver is field certified for pH and residual chlorine. Enco Laboratories performs all other permit
parameters.
COC's for October 2019 were on file. A check of lab bench sheets to data on the Discharge Monitoring
Report (DMR) revealed no transcription errors.
A review of DMR data from April 2016 to November 2019 include the following, monitoring violation for
total nitrogen for 06.2016 and 12.2016; late DMR reporting for 01.201 B. There were no other violations
for the review period.
Permit: NCO086690 Owner • Facility: Stansted Well #2 (1+WiP)
Inspection Data: I V30l2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
❑
0
❑
❑
# Are there any special conditions for the permit?
❑0
❑
❑
Is access to the plant site restricted to the general public?
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Two settling tanks have been added to aid in Manganese and Iron removal with the addition
of benefloc.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
Cl
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
0
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete- do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator
❑
❑
M
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Facility has copy of previous years Annual Report on file for review?
❑
❑
❑
Comment: October 2019 data was reviewed. There were no errors.
Effluent Pipe Yes No NA NE
Is right of way to the outfall property maintained? 0 ❑ [l ❑
oagc# 2
Permit: NCODS669D
Inspection Date: 12/3012019
Owner -Facility: Stansted Well #2 (WTP)
Inspection Type: Compliance Evaluation
Effluent Pipe
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: Effluent appeared clear with no foam or solids.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: Samples are GRAB type. Flow is based on estimate.
Yes No NA NE
M ❑ ❑ ❑
❑ ❑ M ❑
Yes No NA NE
❑ ❑ M ❑
■ ❑ ❑ ❑
M ❑ ❑ ❑
❑ ❑ M ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Pages 4
United States Environmental Protection Agency
Form Approved.
EPA Washington D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr moeday Inspection Type Inspector Fac Type
1 u 2 15 1 3 I NC0082996 111 121 1902:30 I17 18 I C I 19 I fi LJ LJ I 201 I
LI
21 6
Inspection Work Days Facility Self-Momtonng Evaluat on Rating B1 QA Reserved
67 70 71 f 1 72 I ., I 73I I J174 751— _ _ II 1 I ' 4 I8O
I I I I I I r
Section B Facility Data
Name and Location of Facility Inspected:For Industrial Users discharging to POTW also include
Entry TimelDate
3-ermit EHe=tine Date
POTW name and NPDES Permit Number)
10 OOAM 19-12130
1sit 1101
Hollybrook WTP
Exit Time:Date
Permit Expiration Date
OH Kildare Farm Rd
Cary NC 27519
10 30AM 19-12 30
2Y04130
Name(s) of Onsite Representative(silTitlests)iPhone and Fax N„mber(s)
Cther Facility Data
ur
Christopher Lee Weaverl:'
Christopher Lee WeaverlORC;-
Name Address of Responsible OfficiaUTitWPhone and Fax N;,mber
Reid Andrew Campbe11,202 Mackenan Cl Cary NC 27511:�'919-476-8712r .L Ia. ted
No
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Facility Site Review
Section D Summary of Finding/Comments (Attach addil.onal sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspeclor(s) Agency:Off ce.-Phone a--d = ax N.-mbers Date
Mitchell S Hayes (- �L DWRIRRO WQ;919-791.42007
�� �G�i�,J r7
i TI �i I � • ? � • �G` �
Signature of Manage rpen1 O A Reviewer Agency:Off ce:Phone and Fax Numbers Date
/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
pagWr
NPOES yr-ma,day Inspection Type
31 NCoo82996 111 121 19/12130 117 18 I I
Section D. Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
WTP Plant ceased operation 10.08.201.5, There was no discharge. Subdivision is connected to the
Town of Cary public water supply. Permit can be rescinded if Aqua agrees to.
Page#
Permit: NCOOB2996
Inspection Date: 12/30/2019
Owner • Facility: Hollybrook WTP
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Yes No NA NE
❑ ❑ ■ ❑
❑ ❑ ❑
❑ M ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Comment: Plant ceased operation 10.08.2015. There was no discharge. Subdivision is connected to
the Town of Cary Public water supply. Permit can be rescinded if Aqua agrees to.