HomeMy WebLinkAboutNC0085812_Short Term Monitoring Plan_20191218 Public Works
4600 Goldmine Rd
Monroe NC 28110
Union County
T. 704-289-1434
II I
www.unioncountync.gov
EST. 1842
December 18, 2019 ','E VED
Monti Hassan JAN 0 3 2020
PERCS Unit
Pretreatment Coordinator NCDEC/DWR/NPDES
1617 Mail Service Center
Raleigh, NC 27699-1617
Subject: Approval of LTMP's & STMP; Union County
Dear Mr. Hassan,
In the interest in obtaining necessary data prior to requesting the full approval of Union County's
Pretreatment Program; Union County would like to request approval of the attached LTMP's for
Twelve Mile WRF & Crooked Creek LTMP along with the STMP for Grassy Branch WRF. The
additional data required within these plans will allow for a clearer evaluation of our
uncontrollable pollutant levels throughout our Collection System & Industrial
baselines/contributions. The data collected will allow for more accurate calculations of our
Headworks Analysis, and allocation tables.
Please contact Katie Fleming 980-425-0735; kate.fleminq(u�unioncountync.gov , Union County
Industrial Pretreatment Program Manager with any questions, concerns, or corrections. Thank
you.
Sincerely,
&Aieet-
Andrew Neff, PE
Union County Public Works
Water/Wastewater Division Director, Union County Public Works
CC:
Hyong Yi, UCPW Administrator
Bart Farmer, WRF Superintendent
Kate Fleming, Industrial Pretreatment Program Manager
E�Gj'Lj`
yaLv ''�H QG
°9Ty,..CpPo)
Short Term Monitoring Plan
Union County Public Works
Grassy Branch Wastewater Treatment Plant
NC0085812
December 2019
Revision 1:
Revision 2:
Revision 3:
Union County Public Works
Short Term Monitoring Plan—Grassy Branch WWTP
A. Sampling Points(See Figure 1)
1. Influent(sample point 1): prior to mixing with recycle streams
a. Regular composite sample collected for NPDES monitoring.
2. Effluent(sample point 2): after all treatment including chlorination
a. Regular composite sample collected for NPDES monitoring
3. Activated Sludge Basin(sample point 3):
a. Collect grab samples from mixed liquor influent and effluent distribution boxes
4. Sludge to Disposal(sample point 4): sample sludge going to final disposal
a. Collect grab sample
5. Uncontrollable: locations in collection system that serve residential and commercial development
a. Collect grab samples at GrassyBranch(MH-2723)
P
6. Note: The Grassy Branch WWTP consists of solely domestic contribution;therefore, SIU sampling
is not included in this monitoring plan.
B. Pollutants of Concern(POCs)
1. NPDES permit requirements—biochemical oxygen demand(BOD),total suspended solids(TSS),
ammonia(NH3-N),total Kjeldahl nitrogen(TKN),nitrite(NO2),nitrate(NO3),total phosphorus
(TP).
2. Headworks analysis required—BOD, TSS,NH3-N,TKN,NO2,NO3,TP,nickel(Ni),copper(Cu),
zinc(Zn),cadmium(Cd), chromium(Cr),cyanide(CN), lead(Pb),mercury(Hg), silver(Ag),and
arsenic(As).
3. For land application 40 CFR 503 pollutants—As,Cd,Cr,Cu,Pb,Hg,molybdenum(Mo),Ni, Se,Zn,
%solids,and sludge to disposal flow.
4. EPA required—Cd,Cr,Cu,Ni, Pb and Zn.
5. Additional monitored pollutants of concern—total oil and grease(HEM)and total petroleum
hydrocarbon(SGT-HEM).
C. Detention Times
Detention time is not considered in this program. The influent and effluent samples are taken on the same
day and time for unpaired data for use in the headworks analysis.
D. Flow
Flow monitoring points are indicated on the attached map. Flow will be monitored during sampling
events or calculated.
Grassy Branch STMP Page 2
Union County Public Works
Short Term Monitoring Plan—Grassy Branch WWTP
E. Sample Frequency and Plan
Aeration Basin Sludge to Uncontrollable
Pollutant of Influent(1)and Effluent(2) (3) Disposal (4) i (5)
Concern Year 1 Year 2,3,4 Year 5 Years 1-5 Years 1-5 Years 1-5
QuarterlyQuarterly
Arsenic(As) Quarterly1/year Per 503 1/6 months
Q Y Y
Cadmium(Cd) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Chromium(Cr) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Copper(Cu) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Lead(Pb) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Mercury(Hg) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Molybdenum(Mo) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Nickel (Ni) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Selenium(Se) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Silver(Ag) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Zinc(Zn) Quarterly Quarterly Quarterly 1/year Per 503 1/6 months
Cyanide (Cn) 1/month 1/month 1/month 1/year ---- 1/6 months
Flow Continuous i Continuous Continuous Continuous ---- ---
BOD * Daily Daily Daily ---- ---- 1/6 months
TSS * Daily Daily Daily Daily MLSS Weekly 1/6 months
(/o solids)
NH3-N * I/month 1/month 1/month 1/6 months ---- 1/6 months
Nitrate and nitrite Quarterly Quarterly Quarterly 1/6 months ---- ----
Nitrogen,total Quarterly Quarterly Quarterly 1/6 months ---- ----
Phosphorus,total 1/month 1/month 1/month 1/6 months ---- ----
Grassy Branch STMP Page 3
Union County Public Works
Short Term Monitoring Plan—Grassy Branch WWTP
Aeration Basin Sludge to Uncontrollable
Pollutant of Influent(1)and Effluent(2) (3) Disposal(4) (5)
Concern Year 1 Year 2,3,4 Year 5 Years 1-5 Years 1-5 Years 1-5
Total oil and grease 1/year 1/year 1/year
(HEM) ---- ---- ----
Total petroleum
hydrocarbon 1/year 1/year 1/year ---- ---- ----
(SGT-HEM)
* Daily sampling excludes weekends and holidays
Grassy Branch STMP Page 4
Union County Public Works
Short Term Monitoring Plan—Grassy Branch WWTP
F. Detection Level and Sample Method
Practical Quantitation Limits
Pollutant of Concern (PQLs),mg/L Sample Method
Arsenic(As) 0.01 24 hr Composite
Cadmium(Cd) 0.002 24 hr Composite
Chromium(Cr) 0.005 24 hr Composite
Copper(Cu) 0.005 24 hr Composite
Lead(Pb) 0.01 24 hr Composite
Mercury(Hg) 1.0 ng/L* (Method 1631) Grab*
Molybdenum(Mo) 0.01 24 hr Composite
Nickel(Ni) 0.01 24 hr Composite
Selenium(Se) 0.01 24 hr Composite
Zinc(Zn) 0.01 24 hr Composite
Silver(Ag) 0.001 24 hr Composite
Cyanide(Cn) 0.01 Grab
BOD 2.0 24 hr Composite
TSS 2.5 24 hr Composite
NH3-N 0.1 24 hr Composite
TKN 0.50 24 hr Composite
Nitrate and nitrite 0.10 24 hr Composite
Phosphorus,total 0.10 24 hr Composite
Total oil and grease(HEM) 5 mg/L Grab
Total petroleum hydrocarbon 5 mg/L Grab
(SGT-HEM)
Sampling, preservation, and analytical method must be from 40 CFR 136.
* Graphite Furnace Determinations are required to attain the desired detection level for the metals.
However,analysis of aeration basin and sludge to disposal samples often cannot meet these detection
levels. In this case, analysis of these samples must obtain a detection level at least as stringent as the
applicable inhibition criteria or sludge ceiling standard.
** All aeration basin and sludge to disposal samples will be grab.
Grassy Branch STMP Page 5
Union County Public Works
Short Term Monitoring Plan—Grassy Branch WWTP
G. WWTP Diagram
Legend:
FBW =Filter Backwash
RAS =Return Activated Sludge
WAS =Waste Activated Sludge
It =Sampling Point
0 0
Influent Coarse Influent Equalization Flow
PumpStation Aeration Basins
Screens Splitter Box Splitter Box
T
Influent %� 4 j4 ►
RAS
Crooked O Tertiary
Creek Filters
` , Secondary t
UV Disinfection
FBW
RAS
Pumping
Pump Station •
O WAS
Pumping
A 0104- • MO
Aerated
To Land Solids Holding
Tank
Application
Figure 1
► WWTP Process Flow Diagram
Union County,NC
Grassy Branch WWTP
NC0085812
30831-052-001 Figure 01 Greasy Elreneltedr
Grassy Branch STMP Page 6
UNION COUNTY PERSONNEL REPORT
REPORT OF NEW HIRES
July 2019
Name Hire Date Position
911 COMMUNICATIONS
ROBERT V DALE 7/22/19 SYSTEMS SUPPORT
BUDGET
MARY B NAMALA 7/22/19 SENIOR BUDGET ANALYST
COMMUNITY SUPPORT&OUTREACH
KENNETH S PRUSIENSKY 7/8/19 SITE MANAGER RPT
HEALTH
KELLY E GATES 7/22/19 ASSOC PUBLIC HEALTH NURSE PT
INFORMATION TECHNOLOGY
IRYNA N BYCHAK 7/8/19 ADMIN SUPP SPECIALIST I PT
JENNIFERANN T YU 7/8/19 ADMIN SUPP SPECIALIST I PT
PUBLIC LIBRARY
ZOEY E KNOX 7/8/19 LIBRARY ASSOCIATE PT
STEPHANIE S WILEY 7/8/19 TRAINING &TECHNOLOGY COOR
PUBLIC WORKS OPERATIONS
NOAH D ASHBURNER 7/8/19 UTILITY TECHNICIAN I
MARK D HARRINGTON 7/8/19 UTILITY TECHNICIAN I
SHERIFF/JAIL/FACILITIES
MICHAEL L AYTES 7/11/19 PT DEPUTY SHERIFF
SOCIAL SERVICES
RANAYDA D DRAYTON 7/22/19 SCHOOL SOCIAL WORKER
JANIE M LAKEMAN 7/22/19 SENIOR SOCIAL WORKER
LASHANDA M NOBLES 7/22/19 SENIOR SOCIAL WORKER
MELISSA A PONTIUS 7/22/19 ELIGIBILITY SPECIALIST
SOLID WASTE
CALVIN W MULLIS 7/13/19 UTILITY SITE ATTENDANT PT
TRANSPORTATION
AIMEE C CHANEY 7/8/19 DRIVER PT
DONALD WHITTINGTON 7/22/19 DRIVER PT