HomeMy WebLinkAboutWQ0006984_Compliance Evaluation Inspection_20191218ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
NORTH CAROLINA
Environmental Quality
December 18, 2019
Mr. Everette Owens, Plant Manager (via email)
South Fork Industries, Inc.
100 W. Pine St.
Maiden, NC 28203
Subject: Non -Discharge Permit Compliance
Inspection South Fork Industries
Permit No.: WQ0006984
Land Application of Residuals
(503 Exempt)
Catawba County
Dear Mr. Owens:
On December 16, 2019, Edward Watson of the MRO performed a compliance inspection for
South Fork Industries Residuals Land Application Program (RLAP). We would like to thank
Mr. Don Burkey and his staff for their assistance during the inspection event.
Overall, the facility is compliant with permit specifications. There is, however, one item that
should be addressed to maintain compliance:
• Animal burrows, along with other erosion features were observed in multiple areas on the
north berm wall. These impairments of the berm wall may result in a bypass of the pond
contents.
In accordance with Section II Performance Standards and Section III Operation and Maintenance
Requirements of your permit, the program shall be properly operated and maintained at all times.
This would include maintenance to structures such as the lagoon berms.
Please provide information about how the berm damage will be addressed and a time -line to
make the repairs to the berm wall.
D Q North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NORTH CAROHNA �
o.namremor �w.c�giuuei� /`� 704.663.1699
The attached report should be self-explanatory. Should you have any questions regarding this
report, Ed Watson can be reached at (704) 663-1699 ext. 2198 or by email at
edward.watson@ncdenr.gov.
Sincerely,
DocuSigned by:
A N P4444
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Mooresville Regional Office
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: Inspection Report
CC: Mr. Don Burkey (via email)
Mr. Alex Fox, Synagro (via email)
Compliance Inspection Report
Permit: WQ0006984
SOC:
County: Catawba
Region: Mooresville
Contact Person: Fred Poovey
Directions to Facility:
System Classifications: LA,
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
24 hour contact name
Effective: 04/17/18 Expiration: 03/31/23 Owner : South Fork Industries Inc
Effective: Expiration: Facility: South Fork Industries RLAP
100 W Pine St
Maiden NC 28650
Title: President Phone: 704-732-6946
Certification: Phone:
Donald Burkey 828-428-9920
Related Permits:
NC0006190 South Fork Industries Inc - South Fork Industries - Maiden Plant
Inspection Date: 12/16/2019 Entry Time: 09:OOAM Exit Time: 02:30PM
Primary Inspector: Edward Watson Phone:
Secondary Inspector(s):
Reason for Inspection: Routine
Permit Inspection Type: Land Application of Residual Solids (503)
Facility Status: Compliant Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping
Pathogen and Vector Attraction Storage
(See attachment summary)
Inspection Type: Compliance Evaluation
Treatment
Page 1 of 4
Permit: WQ0006984 Owner - Facility: South Fork Industries Inc
Inspection Date: 12/16/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Mooresville Regional Office (MRO) staff performed a Compliance Inspection of the South Fork Industries for Non -Discharge
permit WQ0006984. This permit renewed in April 2018. The last inspection for this facility was September of 2017.
The freeboard is being maintained at 2 feet. However, as a result of high facility production rates, the freedboard is being run
right at the limit.
During the lagoon review, damage to the lagoon North berm wall was noted. There appears to be evidence of animal burrows
in two places in the North berm wall of the lagoon. However, it is difficult to determine if the burrows are actively being used.
Southfork Operations staff mentioned that burrowing animals had been noticed near the lagoon area.
Also, there are erosional features present on the lagoon North berm wall where large sections of soil have eroded from the
berm face. Please present information on how the berm damage will be repaired.
There is a storm drain box located on the far western side of the lagoon at the edge of the property. There is significant
erosion present around the storm drain. This issue will be addressed in the NPDES permit inspection report. However, the
flow direction from the drain box is to the east and has the potential to undermine the west berm wall if the erosion area is
not properly repaired.
Both Clarifiers are displaying significant rust. The clarifiers will be addressed in the NPDES inspection repoprt.
The facility is in compliance with the sampling requirement for annual TCLP based on Attachemnt A of the permit.
Page 2 of 4
Permit: WQ0006984 Owner - Facility: South Fork Industries Inc
Inspection Date: 12/16/2019 Inspection Type : Compliance Evaluation
Type
Distribution and Marketing
Land Application
Reason for Visit: Routine
Yes No NA NE
Record Keeping
Yes No NA NE
Is GW monitoring being conducted, if required?
❑
❑ ❑
Are GW samples from all MWs sampled for all required parameters?
❑
❑ ❑
Are there any GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is a copy of current permit on -site?
❑ ❑ ❑
Are current metals and nutrient analysis available?
❑ ❑ ❑
Are nutrient and metal loading calculating most limiting parameters?
❑
❑ ❑
a. TCLP analysis?
❑ ❑ ❑
b. SSFA (Standard Soil Fertility Analysis)?
❑
❑ ❑
Are PAN balances being maintained?
❑ ❑ ❑
Are PAN balances within permit limits?
❑ ❑ ❑
Has land application equipment been calibrated?
❑
❑ ❑
Are there pH records for alkaline stabilization?
❑
❑ ❑
Are there pH records for the land application site?
❑
❑ ❑
Are nutrient/crop removal practices in place?
❑ ❑ ❑
Do lab sheets support data reported on Residual Analysis Summary?
❑ ❑ ❑
Are hauling records available?
❑
❑ ❑
Are hauling records maintained and up-to-date?
❑
❑ ❑
# Has permittee been free of public complaints in last 12 months?
❑ ❑ ❑
Has application occurred during Seasonal Restriction window?
❑
0 ❑ ❑
Comment: A Land Application event was not observed during this inspection. Hauling records and
pH soil
amendement data for the October LA event will be presented in the 2019 AR.
Pathogen and Vector Attraction
Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
❑
❑ ❑
Class A, all test must be <1000 MPN/dry gram
❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
❑
Fecal coliform SM 9222 D (Class B only)
❑ ❑ ❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
❑
❑ ❑
c. pH records for alkaline stabilization (Class B)
❑
❑ ❑
Temperature corrected
❑
Page 3 of 4
Permit: WQ0006984 Owner - Facility: South Fork Industries Inc
Inspection Date: 12/16/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
d. Salmonella (Class A, all test must be < 3MPN/4 gram day) ❑ ❑ 0 ❑
e. Time/Temp on: ❑ ❑ 0 ❑
Digester (MCRT)
Compost ❑
Class A lime stabilization ❑
f. Volatile Solids Calculations ❑ ❑ 0 ❑
g. Bench -top Aerobic/Anaerobic digestion results ❑ ❑ 0 ❑
Comment: Fecal Densities are used to exhibit reduction as per 15A NCAC 02T .1106(b)(1) Fecal Coliform
Density Demostration. The sludge generated by a non -biological process. The waste is
completely industrial in nature. Domsetic WW from the facility is sent to the Maiden WWTP.
Scum continues to be present on the south pond. The scum laver seems to to focused at the
East end of the South pond at the area where the water enters the ponds. The scum appears to
be the result of surfactants used in the dying process.
There was also a fairly high presence of foam in both the clarifiers and aeration basins.
Treatment
Check all that apply
Yes No NA NE
Aerobic Digestion
Anaerobic Digestion ❑
Alkaline Pasteurization (Class A) ❑
Alkaline Stabilization (Class B) ❑
Compost ❑
Drying Beds ❑
Other ❑
Comment: Treatment is performed by aerobic digestion. The analytical results presented indicate that the
results meet the <2,000,000 MPN per gram of total solids and is in compliance with permit
conditions for pathogen reduction.
During the site visit there was and aerator that was not operating properly in Aeration Basin #1.
This issue will be addressed in the NPDES inspection report.
Page 4 of 4