USE THE TAB KEY TO MOVE FROM FIELD TO FIELD! Application Number. �� O /�
(to be completed by dWQ) 0 3
1. OwnerlPermittee:
la. Grifols Therapeutics LLC Ul C '7
Full Legal Name (company, municipality, HOA, utility, etc.) I ,f�
1 b. Chuck Blatchley, Director of Facility Engineering _ r 14
Signing Official Name and Title (Please review 15A NCAC 2T .0106 (b) for authorized signing officials!)
1 c. The legal entity who will own this system is;
❑ Individual ❑ Federal ® Municipality ❑ StatelCounty ❑ Private Partnership ® Corporation ❑ Other (specify):
1 d. 8368 US 70 Bus Hwy W ;
le, Clayion
Mailing Address City i
1f. NC 1g. 27520
Stale Zip Code
11h. 919-3594269 1 i. 919-359-5450 1 j. Chuck.
Telephone Facsimile E-mail
2. Proect(Facility) information:
2a. Grifols Plasma Warehouse 2b
Brief Project Name (permit will refer to this name)
3. Contact Person:
Johnston _
County Where Project is Located
3a. David L. Dunn, PE — Bass. Nixon and Kennedy, Inc.
Name and Affiliation of Someone Who Can Answer Questions About this Application
3b. 919-851-4422 3c. david.dunn bnkinc.com
Phone Number E-mail
1. Project is ❑ New ® Modification (of an existing permit) If Modification, Permit No.: W00036438
R
C
U
Z
2. Owner is ❑ Public (skip to Item B(3)) ® Private (go to Item 2(a))
2a. If private, applicant will be: 2b. If sold, facilities owned by a (must choose one)
® Retaining Ownership (i.e. store, church, single office, etc.) or f] Public Utility (Instruction C)
❑ Leasing units (lots, townhomes, etc. - skip to item B(3)) ❑ Homeowner Assoc./Developer (Instruction D)
❑ Selling units (lots, townhomes, etc. - go to Item B(2b))
3. Town of Clayton
Owner of Wastewater Treatment Facility (WWTF) Treating Wastewater From This Project
4a. Little Creek WWTP 4b. NCO0025453
Name of WWTF WWTF Permit No.
5a. Town of Cla on b. 6" r❑ Gravity Sc. NIA
Owner of Downstream Sewer Receiving Sewer Size !® Force Main Permit # of Downstream Sewer (Instruction E)
6. The origin of this wastewater is (check all that apply): ,
❑ Residential Subdivision
❑ Apartments/Condominiums
❑ Mobile Home Park
❑ School
❑ Restaurant
❑ Office
❑ Retail (Stores, shopping centers)
❑ Insfitution
❑ Hospital
❑ Church
❑ Nursing Home
® Other
(specify):Warehouse
7. Volume of wastewater to be allocated or Permitted for this particular project: 2,850
'Do not include future flows or previously permitted allocations
8. If the permitted flow is zero, indicate why: NIA
100 % Domestic/Commercial
% industrial (attach
description.)
(RO: contact your Regional Office
Pretreatment staff)
Other (specify):
gallons per day
❑ Pump Station, Outfall or Interceptor Line where flow will be permitted in subsequent permits that connect to this line
❑ Flow has already been allocated in Permit No.
❑ Rehabilitation or replacement of existing sewer with no new flow expected (see 15A NCAC 02T .0303 to determine if a
permit is required)
FfAl2r07
W
Z
Z
0
0
%..
Z
O
H
a
O
U.
Z
F-
W
0.
ri
9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2T .0114 fo
the value in Item 13(7) AND/OR the design flow for line or pump station sizing if a reduced or zero flow Is being requested in
Item 13(7). Values other than that in 15A NCAC 2T .0114 (b) and (c) must be supported with actual water or wastewater us(
data in accordance with 15A NCAC 2T ,0114 (f),
I` Shift 38 Employees x 25 gallonslemployeelshlft = 950 gpd
2 nd Shift 38 Employees x 25 gallons/employee/shift = 950 gpd
3rd Shift 38 Employees x 25 gallons/employee/shift = 950 gpd
Total = 2,850 gpd
10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary)
Size (inches)
6"
2.5"
Length (feet) New Gravity or Additional
Force Main
165 New Gravity
1,171 Force Main
11. Summary of Pump Stations wl associated Force Mains to be Permitted (attach additional sheets as necessary)
Pump Station Location ID NIA (self chosen - as shown on plans/map for
Design Flow Power Reliability Option
Operational Point 1 - permanent generator Force Main
{MGD} GPM @TDH w1ATS; 2 - portable generator Force Main Size Length
w/MTS
0.007 60
2.5"
1.171
Pump Station Location ID NIA (self chosen - as shown on
Design Flow Operational Point Power Reliability Option
(MGD) GPM @TDH 1 - permanent generator w1ATS; Force Main Size Force Main Length
2 - portable generator wIMTS
Pump Station Location 1D NIA (self chosen - as shown on
Design Flow Power ReliabilityOption
Operational Point p
{MGD} GPM @TDH 1 - permanent generator w1ATS; Force Main Size Force Main Length
2 - portable generator wIMTS
12. Will the wastewater flow in the proposed sewer lines or pump stations be able to be directed to another treatment facility?
® Yes ❑ No If Yes, permit number of 2nd treatment facility WWPS (WO 0006419)
(RO if "yes" to 13,12 please contact the Central Office PERCS Unit)
13. Does the sewer system comply with the Minimum Design Criteria for the Fast Track Permitting of Pump Stations and Force
Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC Chapter 2T as
applicable?
® Yes ❑ No If No, please reference the pertinent minimum design criteria or regulation and Indicate why a
variance is requested. SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS
PERTINENT TO THE VARIANCE WITH YOUR APPLICATION
FTA12107
Z
O
F-
a
U
F-
1W
0
14. Have the following permits/certifications been submitted for approval for the system or project to be served?
Wetland/Stream Crossings - General Permit or 401 Certification? ❑ Yes ❑ No ® NIA
Sedimentation and Erosion Control Plan? ® Yes ❑ No ❑ NIA
Stormwater? ® Yes ❑ No ❑ NIA
15. Does this project include any high priority lines, [see 15A NCAC 02T .0402 (2)] Involve aerial lines, siphons, or interference
manholes)? These lines will be considered high Priority and must be checked once every six months
Check if Yes: ❑ and provide details
1. OwnerlPermittee's Certification: (Signature of Signing Official and Project Name)
1, Chuck Blatchlev, attest that this application for Grifols Plasma warehouse has been reviewed by me and is
accurate and complete to the best of my knowledge. 1 understand that if all required parts of this application are not
completed and that if all required supporting documentation and attachments are not Included, this application package
is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143-215 6A and
143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application
shall be guilty of a Class 2 misdemeanor, which may include a rrne not to exceed $10,000 as wel as civil penalties up to
$25,000 per violation.
1 a.
Signing Official Signature
Date
ENGINEERING DESIGN DOCUMENTS MUST BE COMPLETED PRIOR TO SUBMITTAL OF THIS
APPLICATION. THESE DOCUMENTS MUST INCLUDE PLAN AND PROFILE OF SEWERS, THEIR PROXIM
TO OTHER UTILITIES, DESIGN CALCULATIONS. ETC. REFER TO 15A NCAC 02T .0305
2, Professional Engineer's Certification: (Signature of Design Engineer and Project Name)
1, David L. Dunn , attest that this application for Grifols Plasma Warehouse has been reviewed by
me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other
supporting documentation to the best of my knowledge. l further attest that to the best of my knowledge the proposed
design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for
Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump
Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance.
Although other professionals may have developed certain portions of this submittal package, inclusion of these materials
under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the
proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who knowingly
makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor
which may include a line not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
2a. David L. Dunn, PE
Professional Engineer Name
2b. Bass, Nixon and Kennedy, Inc.
Engineering Firm -
2c. 6310 Chapel Hill Rd., Ste. 250
Mailing Address
2d. Ralei h 2e. NC 21. 27607
City State Zip
2g. 919-851-4422 2h. 919-851-8962 2i. david.dunn bnkinc.com
Telephone Facsimile E-mail
�„�NrllHlglh�
ti
2t 4¢ SEAL 9
k 15395
2
L.
—-!.)$)'�
NC PE Seal, SI nature & Date
FTA 12107
BASS, NIXON & KENNEDY, INC., CONSULTING ENGINEERS
6310 CHAPEL HILL ROAD, SUITE 250, RALEIGH, NC 27607
919/851-4422 0 FAX 919/851-8968
NC Dept of Environmental Quality
GRIFOLS PLASMA WAREHOUSE
CLAYTON, NORTH CAROLINA
PUMP STATION SUMMARY
AND FINAL DESIGN CALCULATIONS
FOR NCDEQ AS -BUILT SUBMITTAL
October 29, 2019
OCT 2 9 2019
Raleigh Regional Office
The Grifols Plasma Warehouse is located on the Grifols site on US 70 Business in
Clayton, North Carolina. The site improvements included the construction of the
Plasma Warehouse facility with parking. The facility includes a total of 114 employees
(38 employees per shift with three shifts per day). Based on Section 15A NCAC 02T
.0114, the daily flow for design is 25 gallons/employee/shift. The following summarizes
the design wastewater flow for the pumping station:
Average Daily Flowrate
Peak Daily Flowrate
Original Permitted Design
_ (114 employees)(25 gal/employee/shift)
= 2,850 gpd
2.0 gpm
(2.5)(2,850 gpd)
= 7,125 gpd
5.0 gpm +/-
The original design included a duplex grinder package pump station designed for 38
gpm at 47 feet TDH. The original design also included approximately 1,171 LF of 2"
force main. The original design was submitted to NCDEQ and a permit was issued
on May 2, 2013 as permit No. WQ0036438. The following provides a summary of
permitted improvements:
• Permitted flowrate = 2,850 gpd
• A duplex pump station designed for 38 gpm at 47' TDH
• Approximately 335 LF of 6" gravity sewer
• Approximately 1,171 LF of 2" force main
Revisions to Permitted Design
After issuance of the permit, it was anticipated the condenser units for the Plasma
Warehouse facility would need to discharge to the lift station; consequently, alternate
pumps were proposed and the force main size was increased to 2-1/2". The
alternate pumps were installed along with the larger diameter force main. During
construction, the drainage from the building condenser units was directed to the roof
drains; consequently, the flow to the lift station did not increase. The following
provides a summary of the revisions to the permitted design:
Grifols — Pump Station Design (As -Built) 1 10/2919
• Permitted Fowrate = 2,850 gpd (No Change)
• A duplex pump station designed for 60 gpm at 47' TDH (Revised Flowrate)
• Approximately 165 LF of 6" gravity sewer (Revised Length)
• Approximately 1,171 LF of 2.5" force main (Revised Size)
Pump Station/Force Main Summary (Based on As -Built Conditions)
The following summarizes the revised pump station/force main design and as -
built conditions:
• Pump Design - Weil Model 2516 Duplex Grinder Pumps
o 60 gpm at 47' TDH
o 3 Phase, 5 FIR 3450 RPM pumps
o Average Daily Flowrateto PS = 2.0 gpm
o Peak Daily Flowrate to PS = 5.0 gpm
o Top of Lift Station (As -Built) = 293.10 feet
o Invert of Lift Station (As -Built) = 284.32 feet
• Level Control Settings
o OfflStop Setting =
285.35 feet (93" from top)
o Lead Pump Setting =
288.35 feet (57" from top)
o Lag Pump Setting -
289.35 feet (45" from top)
o High Water Alarm Setting =
290.10 feet (36" from top)
• Pump Cycle Time (Lead Pump)
o Storage Depth (Lead) =
36"
o Storage Volume (Lead) =
37.7 CF (282 gallons)
o Average Flow Cycle Time =
0.4 Starts per Hour *
o Average Flow Run Time =
4.9 minutes
o Peak Flow Cycle Time =
1.0 Starts per Hour *
o Peak Flow Run Time =
5.1 minutes
*Although the pump cycle times are less than 2-8 starts per hour, the Owner
has indicated the pump station has been in operation approximately 5 years
and they have never experienced odor issues.
• Wetwell
o Wetwell Size -
48" Diameter Wetwell
o Top of Wetwell =
293.10 feet (As -Built)
o Invert of Wetwell =
284.32 feet (As -Built)
o Storage at Pump Off Setting =
12.9 CF (97 gallons)
o Storage at Lead Pump Setting =
50.6 CF (379 gallons)
o Storage at HW Alarm =
72.6 CF (543 gallons)
o Flow Detention Time =
141 minutes
o Buoyancy - The pump station is not located in a floodplain or area with
high water table; consequently, ballast concrete was not needed to
prevent flotation. The pump station
has been in operation
approximately 5 years with no floatation issues.
• Force Main
o Force Main Size =
2-112" PVC force main
o Force Main Length =
1,171 LF
Grifols - Pump Station Design (As -Built) 2
10129119
o Velocity (at 60 gpm) = 3.9 fps
o Minimum Velocity Req'd = 2.0 fps c 3.9 fps Okay
*The velocity in the force main provides sufficient flushing velocity for the low
points in the force main.
Back -Up Power/Alarms
o The Grifols Plasma Warehouse and pump station are both connected
to a back-up generator for standby power in the event of electrical
power outages. Due to the critical nature of the contents of the Plasma
Warehouse, electrical power for the warehouse and pump station are
monitored closely by Grifols. The pumping station is equipped with
both audible and visual high water alarms as well as telemetry which is
connected to the permanent emergency generator. A sign is also
posted near the pumping station with an emergency number to call in
the event the alarms are triggered. The pumping station has been
operational for approximately 5 years without issues.
The Grifols Plasma Warehouse Pump Station discharges to the Grifols North
Fractionation Facility Pump Station located to the east of the Plasma Warehouse
site. The original permit application provided documentation confirming the
downstream facilities were adequately sized for the additional pump station.
Since the proposed flowrate did not change from the original permit application,
additional information in not needed for the downstream facilities.
Pumping Station TDH Calculations (Based on As -Built Conditions)
The following calculations are for determining the pumping head for the pumping
station based on the as -built conditions:
• Static Head Conditions
The pumping station for the Grifols Plasma Warehouse will pump to the existing
pumping station located at the Grifols North Fractionation Facility site located
east of the Plasma Warehouse site. The following summarizes the static head
conditions:
o Minimum Waterlevel Condition - Plasma Warehouse Pumping Station
■ Top of Pumping Station
■ Invert of Pumping Station
■ Off/Stop Setting
■ Lead Pump Setting
■ Lag Pump Setting
■ Use for Design
293.10 feet
284.32 feet
285.35 feet
= 288.35 feet
= 289.35 feet
(285.35 + 288.35)12
286.85 feet
Use 286.8 feet
Grifols - Pump Station Design (As -Built) 3 10/29/19
o Maximum Waterlevel Condition - Existing North Fractionation Facility
Pumping Station or high point in force main alignment
■ Top of Pumping Station = 304.17 feet
■ Invert of 2.5" Force Main
at Lift Station = 301.00 feet +1-
■ Max. Force Main Elev. = 300.00 feet +1-
• Use for Design = 301.00 feet +1-
Approximate Static Head = 301.0 - 286.8
14.2 feet
• Hydraulic (Friction) Loss Conditions
The pump station includes two 2" submersible grinder pumps with 2" discharge
piping and a 2-112" force main. The following summarizes the hydraulic (friction)
loss calculations:
o Total Length of 2.5" Force Main = 1,171 LF (based on CAD)
o Use for Design = 1,180 LF
o Summary of fittings and hydraulic losses:
Fitting K-Value* Total K-Value*
(1) 2.0"
Entrance
0.5
0.5
(3) 2.0"
- 9010 Bends
0.57
1.71
(1) 2.0"
Check Valve
1.9
1.9
(1) 2.0"
Plug Valve
0.34
0.34
(1) 2.0"
Tee
1.14
1.14
(1) 2"x2.5" Increaser
0.03
0.03
(3) 2.5"
- 450 Bends
0.29
0.87
(1) 2.5"
Exit
1.0
1.0
Total K2 -
Total K2. s°
= 5.62
1.87
"K-Value = Resistance Coefficient (from Cameron Hydraulic Data, pages 3-111 to 3-120).
o Develop System Head Curve for Various Flowrates (Dynamic Losses
only)
Flowrate Velocity (fps) Hydraulic Losses (feet)
(gpm) 2" Pipe 2.5" Pipe Friction * Fitting ** Total Losses,
10 1.02 0.65 1.1 0.1 1.2
20 2.04 1.31 3.9 0.4 4.3
Grifols - Pump Station Design (As -Built) 4 10/29/19
30
3.07
1.96
8.3
0.9
9.2
40
4.09
2.62
14.2
1.7
15.9
50
5.11
3.27
21.4
2.6
24.0
60
6.13
3.92
30.0
3.7
33.7
70
7.15
4.58
39.9
5.1
45.0
80
8.17
5.23
51.1
6.6
57.7
90
9.20
5.89
63.5
8.4
71.9
100
10.22
6.54
77.2
10.4
87.6
" Velocity and Friction Losses calculated using Engineering Toolbox with PVC pipe C-
value of 140.
Fitting Losses calculated using hr= K(V2)12g
o Determine Total Pumping Head for Various Flowrates (included Static and
Dynamic Losses)
Flowrate Dynamic Head Static Head Total Pumping
m feet feet Head feet
10
1.2
14.2
15.4
20
4.3
14.2
18.5
30
9.2
14.2
23.4
40
15.9
14.2
30.1
50
24.0
14.2
38.2
60
33.7
14.2
47.9
70
45.0
14.2
59.2
80
57.7
14.2
71.9
90
71.9
14.2
86.1
100
87.6
14.2
101.8
The modified pump station design included two submersible pumps designed for
60 gpm at 47.0 feet TDH. Based on the above revised calculations to reflect the
pump station and force main as -built conditions, the pumps are operating at 60
gpm at approximately 47.9 feet TDH. The as -built calculations do not differ
significantly from the pump design conditions; consequently, the pump station
as -built conditions appear acceptable and it is anticipated the pump station will
operate within the approximate flow and head conditions included in the design
and reflected in the modified permit application. The pumping station has been in
operation for approximately 5 years and it is our understanding it has been
operating as designed without issues. %%'A ,
O O ESSIp� /y
C-712
z ¢ SEAL
15395
ill zg���i
Grifols - Pump Station Design (As -Built) 5 10/29/19
BASS, NIXON & KENNEDY, INC., CONSULTING ENGINEERS
6310 CHAPEL HILL ROAD, SUITE 250, RALEIGH, NC 27607
919/8 4g22 ■F�9191851-� NK@BNKinc.com
�C l?ept o nvironmental u:q i
OCT 2 9 71119
October 29, 2019
Raleigh Regional Office
NCDEQ — Division of Water Resources
Water Quality Regional Operations
Raleigh Regional Office
3800 Barrett Drive
Raleigh, NC 27609
Attention: Mr. Ted Cashion
Re: Grifols Therapeutics, Inc.
Grifols Plasma Warehouse
Wastewater Collection System Extension
Permit No. WQ0036438
Clayton, North Carolina
Record Drawing Submittal for Pump Station and Force Main
Dear Mr. Cashion,
The Grifols Plasma Warehouse pump station and force main were originally permitted
on May 2, 2013 as permit No. W00036438. The following provides a summary of
permitted improvements:
• Permitted flowrate = 2,850 gpd
• A duplex pump station designed for 38 gpm at 47' TDH
• Approximately 335 LF of 6" gravity sewer
• Approximately 1,171 LF of 2" force main
After issuance of the permit, it was anticipated the condenser units for the Plasma
Warehouse facility would need to discharge to the lift station; consequently, alternate
pumps were proposed and the force main size was increased to 2-1/2". The alternate
pumps were installed along with the larger diameter force main. During construction,
the drainage from the building condenser units was directed to the roof drains instead of
the pump station; consequently, the flow to the pump station did not increase. The
following provides a summary of the revisions to the permitted design:
• Permitted flowrate = 2,850 gpd (No Change)
• A duplex pump station designed for 60 gpm at 47' TDH (Revised Flowrate)
• Approximately 165 LF of 6" gravity sewer (Revised Length)
• Approximately 1,171 LF of 2.5" force main (Revised Size)
We are requesting a modification to the original permit to account for the increased
pump station flow, reduced length of 6" gravity sewer and increased force main
diameter. The following information is included with this transmittal as requested in your
e-mail dated August 28, 2019:
Grifols Record Drawing Submittal
Page 2
October 29, 2019
• Fast track application for the proposed permit modifications (original copy
submitted). Per our discussion, a revised FTSE is not required since the flowrate
did not change.
• Check in the amount of $480.00 for processing fee.
• One copy of the project construction record drawings including plan/profile and
field survey for sewer force main and pump station.
• One copy of the supporting applicable design calculations modified to reflect the
as -built conditions.
Please let us know if the attached will be acceptable or if you have any
questions/comments concerning the submittal package. Thanks for your help.
Very truly yours,
ss, Nixon & Kennedy, Inc.
David L. Dunn, PE
Principal Engineer
Cashion, Ted
From: David Dunn <David.Dunn@bnkinc.com>
Sent: Tuesday, October 29, 2019 10:30 AM
To: Cashion, Ted
Cc: Marty Bizzell; Robinson, Jason
Subject: RE: [External] RE: final engineering certification for Grifols Plasma Warehouse, W00036438
Attachments: Attachments. html
■ee..yy�J ExternaylyemalL D-o no && Finks .or open attuhnientsuntessyou verify. Send altsuspidous emaitais an:atfachmentto
Ted,
Please find attached pdf's of the record drawing submittal package that will be delivered to your attention this
afternoon per your below request. The package will include the original signed permit application along with a check in
the amount of $480.00 for the permit modification request. I apologize for the delay in getting this information to
you. Please let us know if you have any questions or need anything else. Thanks for your help.
Citrix Attachments Expires April 26, 2020
01- Grifols - Record Drawing Transmittal Le ... 19).pdf 606.4 KB
02 - Grifols - Sewer Permit Application (Per...19).pdf 2.9 MB
03 - Grifols - Record Drawing Calculations a ... 19).pdf 1.9 N1B
Grifols - NCDEQ Record Drawing Submittal (... 19).pdf 8.3 MB
David Dunn uses Citrix Files to share documents securely.
David L. Dunn, PE
Principal Civil Engineer david.dunn bnkinc.com
BASS, NIXON $ KENNEDY, Inc.
6310 Chapel Hill Road, Suite 250
Raleigh, NC 27607 www.bnkinc.com
i9" not (p) 919-851-4422 (f) 919-851-8968
4Woo"Serving the Triangle and surrounding areas since 1969"
From: Cashion, Ted <ted.cashion@ncdenr.gov>
Sent: Monday, October 21, 201910:58 AM
To: David Dunn <David.Dunn@bnkinc.com>
Cc: Marty Bizzell <Marty.BizzelI@bnkinc.com>; Robinson, Jason <jason.t.robinson@ncdenr.gov>
Subject: RE: [External] RE: final engineering certification for Grifols Plasma Warehouse, WQ0036438
Ok thanks David
Ted Cashion
Water Quality Regional Operations
Division of Water Resources
NC Department of Environmental Quality
Raleigh Regional Office
919-791-4254
ted.cashion@ncdenr.eov
1628 Mail Service Center
Raleigh, NC 27699-1628
3800 Barrett Drive
Raleigh, NC 27609
Subscribe to Collection System & Sewer Permitting Updates
Email correspondence to and from this address may be subject to the North Carolina Public Records Law and may be
disclosed to third parties unless the content is exempt by statute or other regulation.
From: David Dunn <David.DunnPbnkinc.com>
Sent: Monday, October 21, 2019 9:54 AM
To: Cashion, Ted <ted.cashion@ncdenr.eov>
Cc: Marty Bizzell <Marty.Bizzell@bnkinc.com>
Subject: (External] RE: final engineering certification for Grifols Plasma Warehouse, WQ0036438
�r`�f�q?�ii:�7p �l�rrlb: t i���r��eT a acFir�ients�r�lessy�o� fiver-rfy. erkt3 allstii5�3 does err�ail as an attaehmeri�YO�
�epdrt.�par �ne�aau .
Ted,
Just wanted to let you know we are working on the below and hope to get to you by end of this week or early next
week. We had to get survey crew out to site to pick-up a few more things. Sorry for the delay.
David L. Dunn, PE
Principal Civil Engineer david.dunn@bnkinc.com
BASS, NIXON & KENNEDY, Inc.
e 6310 Chapel Hill Road, Suite 250
Raleigh, NC 27607 www,bnkinc.com
(p) 919-851-4422 (f) 919-851-8968
"Serving the Triangle and surrounding areas since 1969"
From: Cashion, Ted <ted.cashion@ncdenr.eov>
Sent: Wednesday, August 28, 2019 2:16 PM
To: Marty Bizzell <Marty.Bizzell@bnkinc.com>; David Dunn <David.Dunn@bnkinc.com>
Cc: Robinson, Jason <iason.t.robinson@ncdenr.eov>
Subject: RE: final engineering certification for Grifols Plasma Warehouse, WQ0036438
Marty and David,
After discussing with Jason, we determined that a permit modification is required due to the following condition in Part
11.7 of the permit:
Prior to Certification (Final or Partial): Permit modifications are required far any changes resulting in non-compliance
with this permit (including but not limited to pipe length changes of 10% or greater, increased flow, pump station
design opacity desi n increases of 5% or areater...
Please submit a fast track application to modify the original permit, along with the $480 processing fee. The modified
permit will void the original permit; in the permit mod application please include all items in the original permit (335 If of
6-inch gravity, 1171 If of 2-inch FM; however, the drawing showed a 2.5-inch FM) along with the 60 gpm PS. Also, the
approximate volume of the chiller condensate discharge must be included in the application. A revised FTSE from the
Town of Clayton must be submitted with the permit mod application showing the increased flow.
Also, the submitted drawing was stamped by the land surveyor and not the PE; ensure the permit mod certification
properly includes a PE stamp.
When submitting the engineering certification for the permit mod, please include the following items required in Part
11.7 of the permit:
a. One copy of the project construction record drawings (Alan & profile views of sewer lines & force mains l of the
wastewater collection system extension. Final record drawings should be clear on the plans or on digital media
(CD or DVD disk) and are defined as the design drawings that are marked up or annotated with after construction
information and show required buffers, separation distances, material changes, etc.
One copy of the supporting applicable design calculations including pipe and pump sizing, velocity, pump cycle
times, and level control settings, pump station buoyancy, wet well storage, surge protection, detention time in the
wet well, and force main, ability to flush low points in force mains with a pump cycle, and downstream sewer
capacity analysis. !f a portable power source or pump is dedicated to multiple stations, an evaluation of all the
pump stations' storage capacities and the rotation schedule of the portable power source or pump, include travel
timeframes, shall be provided.
c. Changes to the project that do not result in non-compliance with this permit, regulations, or the Minimum Design
Criteria should be clearly identified on the record drawings, on the certification in the space provided, or in written
summary form.
We are 6-8 weeks out from receipt of applications to issuing permits. Since this is a mod to a permit, we'll try to
expedite the permit issuance.
Thanks, please call if you have questions.
ted
Ted Cashion
Water Quality Regional Operations
Division of Water Resources
NC Department of Environmental Quality
Raleigh Regional Office
919-791-4254
ted.cashion ncdenr. ov
1628 Mail Service Center
Raleigh, NC 27699-1628
3800 Barrett Drive
Raleigh, NC 27609
Subscribe to Collection System & Sewer Permitting Updates
Email correspondence to and from this address may be subject to the North Carolina Public Records Law and may be
disclosed to third parties unless the content is exempt by statute or other regulation.
From: Cashion, Ted
Sent: Wednesday, August 28, 2019 11:05 AM
To: Marty Bizzell <Mart .Bizzell bnkinc.com>
Cc: Robinson, Jason <iason.t.robinson ncdenr. ov>
Subject: final engineering certification for Grifols Plasma Warehouse, WQ0036438
Marty,
We are reviewing the subject certification. Profiles of the gravity and FM sewers were not included as required. Please
submit these items.
Also the PS design flow rate was noted as 60 gpm. The permit allowed for a 38 gpm PS. Pis confirm the capacity of the
PS.
Since this is a relative small project, you may email the profile and PS info to us.
Thx
ted
Ted Cashion
Water Quality Regional Operations
Division of Water Resources
NC Department of Environmental Quality
Raleigh Regional Office
919-791-4254
ted.cashion ncdenr.eov
1628 Mail Service Center
Raleigh, NC 27699-1629
3800 Barrett Drive
Raleigh, NC 27609
Qg;l
Dspaelrtt\ !' J
Subscribe to Collection System & Sewer Permitting Updates
Email correspondence to and from this address may be subject to the North Carolina Public Records Law and may be
disclosed to third parties unless the content is exempt by statute or other regulation.
cc) ~~�*'
Cashion, Ted
From: David Dunn <David.Dunn@bnkinc.com>
Sent: Monday, October 21, 2019 9-54 AM
To: Cashion, Ted
Cc: Marty Bizzell
Subject: [External] RE; final engineering certification for Grifois Plasma Warehouse, WQ0036438
• xternal email. Do not. click -links or open attarhments unless you verfV. Send all suspicious erriAll as an atiactj' ent to
a
Ted,
Just wanted to let you know we are working on the below and hope to get to you by end of this week or early next
week. We had to get survey crew out to site to pick-up a few more things. Sorry for the delay.
David L. Dunn, PE
Principal Civil Engineer david.dunn o&bnkinc.com
BASS, NIXON & KENNEDY, Inc.
6310 Chapel Hill Road, Suite 250
Raleigh, NC 27607 www.bnkinc.com
2"t (p) 919-851-4422 (f) 919-851-8968
"Serving the Triangle and surrounding areas since 1969"
From: Cashion, Ted <ted.cashion@ncdenr.gov>
Sent: Wednesday, August 28, 2019 2:16 PM
To: Marty Bizzeli <Marty.Bizzell@bnkinc.com>; David Dunn <David.Dunn@bnkinc.com>
Cc: Robinson, Jason <jason.t.robinson@ncdenr.gov>
Subject: RE: final engineering certification for Grifols Plasma Warehouse, WQ0036438
Marty and David,
After discussing with Jason, we determined that a permit modification is required due to the following condition in Part
11.7 of the permit:
Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting in non-compliance
with this permit (including but not limited to pipe length changes of 10% or greater, increased flow, pump station
design caoacity design increases of S% or greater...
Please submit a fast track application to modify the original permit, along with the $480 processing fee. The modified
permit will void the original permit; in the permit mod application please include all items in the original permit (335 If of
6-inch gravity,1171 If of 2-inch FM; however, the drawing showed a 2.5-inch FM) along with the 60 gpm PS. Also, the
approximate volume of the chiller condensate discharge must be included in the application. A revised USE from the
Town of Clayton must be submitted with the permit mod application showing the increased flow.
Also, the submitted drawing was stamped by the land surveyor and not the PE; ensure the permit mod certification
properly includes a PE stamp.
When submitting the engineering certification for the permit mod, please include the following items required in Part
111.7 of the permit:
a. One copy of the project construction record drawings (plan & profile views of sewer lines & force mains} of the
wastewater collection system extension. Final record drawings should be clear on the plans or on digital media
(CO or DVD disk) and are defined as the design drawings that are marked up or annotated with after construction
information and show required buffers, separation distances, material changes, etc.
b. One copy of the supporting applicable design calculations including pipe and pump sizing, velocity, pump cycle
times, and level control settings, pump station buoyancy, wet well storage, surge protection, detention time in the
wet well, and force main, ability to flush low points in force mains with a pump cycle, and downstream sewer
capacity analysis. !f a portable power source or pump is dedicated to multiple stations, an evaluation of all the
pump stotions'storage capacities and the rotation schedule of the portable power source or pump, include travel
timeframes, shall be provided.
c. Changes to the project that do not result in non-compliance with this permit, regulations, or the Minimum Design
Criteria should be clearly identified on the record drawings, on the certification in the space provided, or in written
summary form.
We are 6-8 weeks out from receipt of applications to issuing permits. Since this is a mod to a permit, we'll try to
expedite the permit issuance.
Thanks, please call if you have questions.
ted
Ted Cashion
Water Quality Regional Operations
Division of Water Resources
NC Department of Environmental Quality
Raleigh Regional Office
919-791-4254
ted.cashion@ncdenr.sov
1628 Mail Service Center
Raleigh, NC 27699-1628
3800 Barrett Drive
Raleigh, NC 27609
Subscribe to Collection System & Sewer Permitting Updates
Email correspondence to and from this address may be subject to the North Carolina Public Records Law and may be
disclosed to third parties unless the content is exempt by statute or other regulation.
From: Cashion, Ted
Sent: Wednesday, August 28, 201911:05 AM
To: Marty Bizzell <Marty.Bizzell@bnkinc.com>
Cc: Robinson, Jason <iason.t.robinson@ncdenr.eoV>
Subject: final engineering certification for Grifols Plasma Warehouse, WQ0036438
Marty,
We are reviewing the subject certification. Profiles of the gravity and FM sewers were not included as required. Please
submit these items.
Also the PS design flow rate was noted as 60 gpm. The permit allowed for a 38 gpm PS. Pls confirm the capacity of the
PS.
Since this is a relative small project, you may email the profile and PS info to us.
Thx
ted
Ted Cashion
Water Quality Regional Operations
Division of Water Resources
NC Department of Environmental Quality
Raleigh Regional Office
919-791-4254
ted.cashion@ncdenr.gov
1628 Mail Service Center
Raleigh, NC 27699-1628
3800 Barrett Drive
Raleigh, NC 27609
Depu^avnc et 1 mrarrnal qwL�
Subscribe to Collection System & Sewer Permitting Updates
Email correspondence to and from this address may be subject to the !North Carolina Public Records Low and may be
disclosed to third parties unless the content is exempt by statute or other regulation.