HomeMy WebLinkAboutNC0026611_Inspection_20191205DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 ROY COOPED 66weil r K41CHAEL S. R.EGAN Secretary LINDA CULPEPPER arwtor Daniel K Williams Town of Morehead City 706 Arendell Street Morehead City, NC 28557-4234 NORTH CAROLINA Environmental Qual" December 16, 2019 SUBJECT: Compliance Inspection Report Morehead City WWTP NPDES WW Permit No. NCO026611 Carteret County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Morehead City WWTP on 12/05/2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0026611. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at helen.perez@ncdenr.gov. Sincerely, E-T DocuSigned by: oµ 'TAU-M) �cOA, for 7F141E73B6F3456... Morelia Sanchez -King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Cc: Chad Sutton — electronic copy Uploaded to Laserfiche NorthC.aroSnaDepartrcantoftnvironmeata3Qaadrty I DWsion of Water Resou roes r, Wilniiagbon Reg •3ca-Off w 1 127 CA rd'inslD ivefxtension I VAIrnington, North Caro --ra23405 �'T._..... 910-796-7215 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IF I 3 I NCO026611 111 12 I 19/12/05 I17 18 I S i 19 i G i 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved ------------------- 671 70Id I 71 I I 72 I r, I 73I I I74 751 I I I I I I I80 I —I I� I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 10:15AM 19/12/05 13/04/01 Morehead City WWTP 1000 Treatment Plant Rd Exit Time/Date Permit Expiration Date Morehead City NC 28557 12:OOPM 19/12/05 17/07/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data William Chad Sutton//252-726-6237 / William Chad Sutton/ORC/252-726-6237/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Daniel K Williams,706 Arendell St Morehead City NC 285574234/Public Utilities Director/252-726-6848/2527262267 Yes Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date DOCO$1g"ea �'y- DWR/WIRO WQ/910-796-7387/ Helen I PerezE 12/16/2019 1 D645B4A39694BE... Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date DocuSigned by: 12/18/2019 Tom TharringtfWQ/ Toµ �1 oWR/WIRO "- 71`141 E731361`3456... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 NPDES yr/mo/day Inspection Type (Cont.) NCO026611 I11 121 19/12/05 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) A routine compliance inspection of the Morehead City WWTP was conducted on December 5, 2019. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit NC0026611. Chad Sutton, facility ORC, was present during the inspection. The facility is well maintained and records were organized and complete. A thorough check and maintenance of the entire plant to include oil, belts, grease and filters is scheduled twice a year, and the most recent schedule was completed in October. The grit and classifier system has not been in operation for approximately five months. The City is in the process of planning the replacement of the whole system. Also planned are repairs and part replacements to the two clarifers. A review of files for the last two years indicated one violation issued, a NOD in June 2018 for a weekly TSS limit violation. The Morehead City WWTP permit expired on July 31, 2017. The permit renewal is currently in draft form. The facility is compliant with NPDES permit NC0026611. Please review the comment sections of the inspection report for more details. Page# DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NCO026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ ❑ ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The Dermit exDired on July 31. 2017. and the new Dermit is currently in draft form. SDecial conditions include the requirement of notification of release of any partially treated or untreated wastewater to the Marine Fisheries, Shellfish Sanitation and Recreational Water Quality Section. Also, there is a requirement to notify the Wilmington Regional Office if the UV disinfection system fails. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Comment: Operation/maintenance log was detailed and complete. Page# 3 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NCO026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑ Comment: The majority of the reportable parameters are analyzed by the facility lab,certification #19. The remaining parameters are analyzed by the contract lab, Envirochem, certification # 94. Bench sheets and calibration sheets for the Hach DO meter and the Thermo Scientific Orion pH meter were complete. Standards for pH calibration were within expiration dates. Flow Measurement - Influent Yes No NA NE # Is flow meter used for reporting? ❑ 0 ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ❑ Comment: The flow meter was calibrated on 10-30-18 by Chadwick Instruments. This years calibration is scheduled for 12-16-19 and the ORC will send the records when it is completed. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ❑ Comment: The flow meter was calibrated on 10-30-18 by Chadwick Instruments. This vears calibration is scheduled for 12-16-19 and the ORC will send the records when it is completed. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The oxidation ditch system is monitored for DO, temp, PH, mixed liquor solids and a microscopic inspecton daily. Settleable solids are monitored twice a week. Bar Screens Type of bar screen Page# 4 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NCO026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Bar Screens Yes No NA NE a.Manual ❑ b.Mechanical Are the bars adequately screening debris? ❑ ❑ ❑ Is the screen free of excessive debris? ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? ❑ ❑ ❑ Comment: There are three barscreen units within the collection system at pump stations #9, #10 and #18A. Pump station #10 is located outside of the fenced WWTP. Screening debris is disposed of at the landfill. Grit Removal Type of grit removal Yes No NA NE a.Manual ❑ b.Mechanical Is the grit free of excessive organic matter? ❑ ❑ ❑ Is the grit free of excessive odor? ❑ ❑ ❑ # Is disposal of grit in compliance? ❑ ❑ ❑ Comment: The Lakeside Raptor grit removal and classifier system has not been in operation for approximately 5 months due to a broken pipe. Plans are in place to replace the whole unit in the near future. Influent Sampling Yes No NA NE # Is composite sampling flow proportional? 0 ❑ ❑ ❑ Is sample collected above side streams? 0 ❑ ❑ ❑ Is proper volume collected? ❑ ❑ ❑ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Is sampling performed according to the permit? 0 ❑ ❑ ❑ Comment: The composite sampler was 4°C and the tubing was clean. Staff changes the tubing two times a month in the winter and three times a month in the summer. Oxidation Ditches Yes No NA NE Are the aerators operational? 0 ❑ ❑ ❑ Are the aerators free of excessive solids build up? 0 ❑ ❑ ❑ Page# 5 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NCO026611 Owner - Facility: Inspection Date: 12/05/2019 Inspection Type: Morehead City WWTP Compliance Evaluation Oxidation Ditches Yes No NA NE # Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Are settleometer results acceptable (> 30 minutes)? ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) 0 ❑ ❑ ❑ Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes) ❑ ❑ ❑ Comment: Influent and RAS mix toaether as it enters the three anerobic reactors. There are two mixers in each reactor. Wastewater then flows to the first oxidation ditch which is in anoxic mode. It then flows to the second oxidation ditch in oxic mode. DO levels in ditch one was 0.06 mq/I and 1.68 mg/I in ditch two during the inspection. Nutrient Removal Yes No NA NE # Is total nitrogen removal required? 0 ❑ ❑ ❑ # Is total phosphorous removal required? 0 ❑ ❑ ❑ Type Biological # Is chemical feed required to sustain process? N ❑ ❑ ❑ Is nutrient removal process operating properly? 0 ❑ ❑ ❑ Comment: The permit has a Total Nitrogen limit of 41,856 Ibs/year and a Total Phosphorus limit of 7,610 Ibs/year. Staff keeps a <2 mq/I monthly average for Total Phosphorus and a <9 mq/1 monthly average for Total Nitrogen to stay within the yearly permit limit. Alum is fed in approximately late May through October to aid in phosphorus removal. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? 0 ❑ ❑ ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? 0 ❑ ❑ ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ❑ ❑ ❑ Page# 6 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NC0026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Comment: Weirs are cleaned two times a month. The sludge blanket is checked twice a day and level is kept around two feet. Plans are in place to repair and/or replace parts on the clarifiers in the near future due to age. Pumps-RAS-WAS Yes No NA NE Are pumps in place? 0 ❑ ❑ ❑ Are pumps operational? 0 ❑ ❑ ❑ Are there adequate spare parts and supplies on site? 0 ❑ ❑ ❑ Comment: No comment. Chemical Feed Yes No NA NE Is containment adequate? 0 ❑ ❑ ❑ Is storage adequate? 0 ❑ ❑ ❑ Are backup pumps available? ❑ ❑ ❑ Is the site free of excessive leaking? 0 ❑ ❑ ❑ Comment: No comment. Filtration (High Rate Tertiary) Yes No NA NE Type of operation: Down flow Is the filter media present? ❑ ❑ ❑ Is the filter surface free of clogging? ❑ ❑ ❑ Is the filter free of growth? ❑ ❑ ❑ Is the air scour operational? ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Is the clear well free of excessive solids and filter media? ❑ ❑ ❑ Comment: Tertiary filtration consists of dual traveling bridge sand filters. The filters are backwashed automatically every four hours or more often due to activation of a high float switch. Disinfection - UV Are extra UV bulbs available on site? Are UV bulbs clean? Is UV intensity adequate? Is transmittance at or above designed level? Is there a backup system on site? Is effluent clear and free of solids? Yes No NA NE ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ Page# 7 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NCO026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Disinfection - UV Yes No NA NE Comment: One UV bank of the three banks in series was in operation during the inspection. A post aeration tank is located before the UV system. The tank is covered to control algae growth and is also cleaned twice a year. Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: Tubinq was clean and sampler temperature was 4.5° C. Aerobic Digester Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: One of the two digesters was cleaned in 2017 to remove grit and debris and improve digester performance. The City plans to cleaned the second digester when the budget allows. Solids Handling Equipment Is the equipment operational? Is the chemical feed equipment operational? Is storage adequate? Is the site free of high level of solids in filtrate from filter presses or vacuum filters? Is the site free of sludge buildup on belts and/or rollers of filter press? Is the site free of excessive moisture in belt filter press sludge cake? The facility has an approved sludge management plan? Yes No NA NE ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Page# 8 DocuSign Envelope ID: E001B10C-C3E8-47A8-AE90-9671EB9E8545 Permit: NC0026611 Owner - Facility: Morehead City WWTP Inspection Date: 12/05/2019 Inspection Type: Compliance Evaluation Solids Handling Equipment Yes No NA NE Comment: The facility produces Class A residuals the majority of the time. The sludge press and dryer system is operated every 5-6 weeks. It takes 5-6 days to press all the material. When Class B residuals are made, they are removed and disposed of by Lewis Farms. Presses were not in operation at time of inspection. Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ■ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ Comment: The facility has two generators, one for the laboratory building and the other for the rest of the wastewater plant. The generators are tested weekly under load and maintained by Morehead City staff. Page# 9