HomeMy WebLinkAboutNC0082949_Compliance Evaluation Inspection_20191204ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
NORTH CAROLINA
Environmental Quality
Certified Mail # 70171450 0001 6450 1129
Return Receipt Requested
December 4, 2019
Mr. Kenneth Gamble, Town Manager
Town of Denton
PO Box 306
Denton, NC 27239
Subject: Compliance Evaluation Inspection Report
Notice of Violation & Intent to Issue Civil Penalty
Denton Water Treatment Plant Wastewater Discharge
NPDES Permit # NCO082949
Davidson County
Dear Mr. Gamble:
On November 6, 2019, Paul DiMatteo of the Division of Water Resources (Division), Winston-
Salem Regional Office met with Heather Hicks, Operator in Responsible Charge (ORC), Troy
Branch, Backup ORC, and you to conduct a Compliance Evaluation Inspection at the above
referenced wastewater discharge facility. The inspection was prompted by an in -office review of
submitted Discharge Monitoring Reports (DMRs) which appeared to be missing data. The primary
purpose of the inspection was to review DMR and self -monitoring data.
Summary of Non -Compliance
The facility inspection and subsequent file review revealed the following monitoring and reporting
violations from January 2016 through September 2019.
1. Effluent Limitations and Monitoring Requirements — Part I, Condition A.1 of the
Permit requires the discharged effluent to be limited and monitored as stated in that
Condition.
a. Total Aluminum and Total Manganese not reported in 20 of the reviewed months.
The Permit requires these parameters to be monitored monthly.
b. Total Fluoride, Total Zinc, Total Copper and Total Iron not reported in 2 of the
reviewed quarters. The Permit requires these parameters to be monitored quarterly.
c. The Permit defines the measurement frequency "2/month" as "Samples are
collected twice per month with at least ten calendar days between sampling events.
[... ]". Improper separation between twice monthly sampling events was identified
in 6 months of data.
D North Carolina Department of Environmental Quality I Division of Water Resources
EQ�p
Winston-Salem Regional Office 1 450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
NORTH CAROLINA �
o•o•°"•mme""°"^•"vin"•i� /� 336.776.9800
d. The Permit requires quarterly metals (Fluoride, Copper, Zinc, and Iron) to be
"collected concurrently with WET -test samples." Metals were not collected
concurrently with WET samples in at least 5 quarters.
2. Reporting Requirements — Part II, Condition E.5 of the Permit requires that "(a).
Monitoring results must be reported on a Discharge Monitoring Report (DMR)..." and that
"(b). If the Permittee monitors any pollutant more frequently than required by this permit
[... ], the results of such monitoring shall be included in the calculation and reporting of the
data submitted on the DMR."
a. Total Nitrogen (including Total Kjeldahl Nitrogen and NO2+NO3) and Total
Phosphorus samples were analyzed but not reported in 36 separate instances.
b. All quarterly metals were analyzed but not reported in 3 quarters
c. Aluminum and manganese were analyzed but not reported in 5 months.
d. Incorrect results were recorded in 7 instances. It was noted that in no case would
the correct result have resulted in a violation of effluent limitations.
3. Missing Lab Data — Data was reported on the DMR without the accompanying laboratory
data being provided during the review process for December 20, 2016 and November 9,
2017. Please note the following permit conditions:
a. Records Retention — Part II, Condition D.5 requires that all monitoring
information except sludge use and disposal be maintained for at least 3 years.
b. Duty to Provide Information — Part II, Condition B.8 requires that the Permittee
shall provide copies of records required by the Permit upon request.
c. Falsification of Reports — Part II, Condition E.I I provides significant penalties
for knowingly falsifying records or statements in relation to the Permit.
Requested Response
This Notice of Violation / Notice of Intent to Enforce (NOV/NOI) is being issued for the noted
violations. Pursuant to G.S. 143 215.6A, a civil penalty of not more than twenty-five thousand
dollars ($25,000.00) may be assessed against any person who violates or fails to act in accordance
with the terms, conditions, or requirements of any permit issued pursuant to G.S. 143 215.1.
This office requests that you respond to this Notice, in writing, within 10 business days of its
receipt. In your response, you should address the causes of non-compliance, remedial actions,
and all other actions taken to prevent the recurrence of similar situations. The response to this
correspondence will be considered in the enforcement process. If you have any questions
concerning this report, please contact Paul DiMatteo at (336) 776-9691 or me at (336) 776-9800.
Sincerely,
cuSigned by:
[�_"4
z SmJtr
9E22¢5 4EA...
Lon T. Smder, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Enclosures — Inspection Report
CC: WSRO Laserfiche Files
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO082949 111 12 I 19/11/06 I17
18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I
I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA
---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I
u I�
73 I I 174 751 I I I I I I I80
I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:30AM 19/11/06
14/05/01
Denton WTP
3049 Bringle Ferry Rd
Exit Time/Date
Permit Expiration Date
Denton NC 27239
12:30PM 19/11/06
19/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Heather Hicks/ORC/336-859-3139/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Angel Jenkins,201 W Salisbury St Denton NC 27239//336-859-4231/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Records/Reports
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
Paul DiMatteo DocuSigned by: DWR/WSRO WQ/336-776-9691/
4L
12/4/2019
F10C7C2E5BB34D4...
Signature of Management Q A Reviewe by: Agency/Office/Phone and Fax Numbers
Date
Lcued
S'ac,
12/4/2019
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO082949 I11 121 19/11/06 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO082949 Owner - Facility: Denton WTP
Inspection Date: 11/06/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
0
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Some DMR data was missing.
Page# 3