HomeMy WebLinkAboutNC0060461_Compliance Evaluation Inspection_20191021ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Martin Lashua
Carolina Water Services Inc. of NC
P.O. Box 240908
Charlotte, NC 28224-0908
NORTH CAROLINA
Environmental Quality
October 21, 2019
SUBJECT: Compliance Evaluation Inspection
Abington WWTP
NPDES Permit No. NCO060461
Forsyth County
Dear Mr. Miller,
On October 15, 2019, Gary Hudson, of this office, met with Richard Philips, Operator in
Responsible Charge (ORC), and Jack Burner, Back-up Operator in Responsible Charge
(BORC) to perform a Compliance Evaluation Inspection at the Abington wastewater
treatment plant. This type of inspection consists of two basic parts: an in -office file review
and an on -site inspection of the treatment facility. The attached EPA inspection form
details the areas that were evaluated during this inspection.
The inspection of the facility was satisfactory. If you have any questions regarding the
inspection or this report, please contact Gary Hudson or me at (336) 776-9800 or by email
at gary.hudson(c�ncdenr.gov or Ion. snider(a)_ncdenr.gov.
Sincerely,
EDocuSigned<by:
LJn. -T :5,,Jtr
145B49B225C94BA...
Lon Snider
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments: EPA Water Compliance Inspection Report
cc: WSRO
D North Carolina Department of Environmental Quality I Division of Water Resources
EQ�p
Winston-Salem Regional Office 1 450 Hanes Mill Road, Suite 300 1 Winston-Salem, North Carolina 27105
NORTH C�30LINA �
o•o•°^•mme""°""•"viu"•i� /� 336.776.9800
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NC0060461 111 12 I 19/10/15 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I 73 I I 174 751 I I I I I I I80
u I� I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 19/10/15
17/03/01
Abington WWTP
6890 Bainburg Ct
Exit Time/Date
Permit Expiration Date
Kernersville NC 27284
12:OOPM 19/10/15
22/02/28
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Andrew Richard Phillips/ORC/336-240-5866/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Dana Hill,PO Box 240908 Charlotte NC 28224/Director of Operations/704-319-0503/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Gary Hudson DWR/Division of Water Quality/336-776-9694/
Signature of Management Q A Reviewe usigned by: Agency/Office/Phone and Fax Numbers Date
E�-5'1349E225C94EA—
EPA
Page#
NPDES yr/mo/day Inspection Type
NC0060461 I11 121 19/10/15 117 18 ICI
(Cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
*The permit for this facility was renewed on 1 MAR17 and expires on 28FEB22. A copy of the permit
was presented for inspection. There are no special conditions related to this permit.
*Richard Philips is the ORC and holds a Biological WW Grade 2 license, and Jack Burner is the
BUORC and holds a Grade 1 Biological WW license.
*The effluent composite sampling is flow proportional. Influent sampling is not a requirement.
*The influent goes through 2 seperate bar screens before entering the flow equalization basin.
*The flow equalization basin appeared to be well operated and maintained.
*The aeration basin appeared to be well operated and maintained. The blowers are on a timer and are
set to turn off for 2 hours every morning.
*At the time of this inspection both clarifiers were clean and free of floating sludge.
*Sodium Bisulfite is being used for de-chorination.
*A new flow meter was installed and calibrated on 9SEP19.
*The effluent was clear on the day of this inspection.
*During this inspection the entire WWTP appeared to be very well operated and maintained.
Page# 2
Permit: NCO060461 Owner - Facility: Abington WWTP
Inspection Date: 10/15/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The permit for this facility was renewed on 1 MAR17 and expires on 28FEB22. A copy of the
permit was presented for inspection. There are no special conditions related to this permit.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: Richard Philips is the ORC and holds a Biological WW Grade 2 license, and Jack Burner is
the BUORC and holds a Grade 1 Biological WW license.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? 0 ❑ ❑ ❑
Page# 3
Permit: NCO060461 Owner - Facility: Abington WWTP
Inspection Date: 10/15/2019 Inspection Type: Compliance Evaluation
Effluent Sampling
Yes No NA NE
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
M
❑
❑
❑
representative)?
Comment: The effluent composite sampling is flow proportional. Influent sampling is not a requirement.
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
0
❑
❑
❑
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
0
❑
❑
❑
Comment: None.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The influent goes through 2 seperate bar screens before entering the flow equalization
basin.
Equalization Basins
Yes No NA NE
Is the basin aerated?
0
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Page# 4
Permit: NCO060461
Inspection Date: 10/15/2019
Owner - Facility: Abington WWTP
Inspection Type: Compliance Evaluation
Equalization Basins
Yes No NA NE
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Are audible and visual alarms operable?
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: The flow equalization basin appeared to be well operated and maintained.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
0 ❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0 ❑
❑
❑
Comment: The aeration basin appeared to be well operated and maintained. The blowers are on a
timer and are set to turn off for 2 hours every morning.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
Comment: At the time of this inspection both clarifiers were clean and free of floating sludge.
Yes No NA NE
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Page# 5
Permit: NC0060461
Inspection Date: 10/15/2019
Owner - Facility: Abington WWTP
Inspection Type: Compliance Evaluation
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment: None.
Disinfection -Liquid
Yes No NA NE
Is there adequate reserve supply of disinfectant?
0
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment: None.
De -chlorination
Yes No NA NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
0
❑
Comment: Sodium Bisulfite is being used for de-chorination.
Are tablet de -chlorinators operational? ❑ ❑ 0 ❑
Number of tubes in use?
Comment: None.
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: Anew flow meter was installed and calibrated on 9SEP19.
Effluent Pipe Yes No NA NE
Page# 6
Permit: NCO060461 Owner - Facility:
Inspection Date: 10/15/2019 Inspection Type:
Abington WWTP
Compliance Evaluation
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent was clear on the day of this inspection.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: None.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: During this inspection the entire WWTP appeared to be very well operated and maintained.
Page# 7