Subject: Application No. WQ0005233
Additional Information Request
Enlisted Men's Barracks — Atlantic
Airfield WWTF
Wastewater Irrigation System
Carteret County
Dear Mr. Schulz:
Division of Water Resources' Central and Regional staff has reviewed the application package
received September 3, 2019. However, additional information is required before the review may be
completed. Please address the items on the attached pages no later than the close of business on December
9, 2019
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant's responsibility. In addition, any omissions made in responding to the outstanding items
in Sections A and B, or failure to provide the additional information on or before the above requested date
may result in your application being returned as incomplete.
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with two paper
copies and one electronic copy submitted to my attention at the address below.
If you have any questions regarding this request, please do not hesitate to contact me at (919) 707-
3659 or erickson.saunders@ncdenr.gov. Thank you for your cooperation.
Since ely
Erick Saunders, Vggli4eer
Division of Water Resources
cc: Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
J, Kevin Avolis, PE — Avolis Engineering, PA (Electronic Copy)
Permit Application File WQ0005233
�� North Carolina Department of Environmental Quality I Division of Water Resources
c���—Dff512 North Salisbury Street 1 1617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTH CPR OL KA
w;; -1 %� 919.707.9000
Mr. Charles E. Schulz
November 8, 2019
Page 2 of 2
A. Application:
1. In application item IV.6 of the WWIS 06-16 form, you list the wastewater flow as 10,000 gallons
per day (GPD), but the previous permit issued April 15, 2019 had a permitted flow of 5,000 GPD.
The flow listed in this field should be the permitted flow. Please explain this discrepancy, and
indicate whether or not you are requesting that the permitted flow of this permit be increased.
B. Power Reliability Plan:
In application item V.5. of the WWIS 06-16 form, you did not indicate how power reliability will
be provided. According to 15A NCAC 02T .0305(h)(1)(B), a standby power source or pump shall
be required at all pump stations except for simplex pump stations, and controls shall be provided
to automatically activate the standby source and signal an alarm condition. The Power Riser
Diagram on page E-501 of the engineering plans indicates that there is an existing generator with
an existing automatic transfer switch, but the location of this generator is not given and the
generator was not listed in any previous facility description for this permit. Please answer the
following:
a. Provide the technical specifications of the existing generator.
b. Provide the locations of the existing generator and automatic transfer switch.
c. Describe the operation of the generator and automatic transfer switch. This explanation should
provide the controller settings in the case of power failure, and provide a list of all the
connections that use the generator as an auxiliary power source. Please note that the operation
of this generator should meet the requirements of 15A NCAC 02T .0305(h)(1)(B) listed above.
2. According to 15A NCAC 02T .0305(h)(1)(E)-(F), all pump stations designed for two pumps or
more shall have a telemetry system to provide remote notification of a problem condition, including
power failure and high water alarm. Alarms on site should be both audio and visual. Please verify
that these conditions are met for the specified pump station.