HomeMy WebLinkAboutNC0033111_NOV-2019-LV-0759 Response_20191022* W *N46 �tWi vam 22 October 2019 Carolina Water Service of North Carolina TM Robert Tankard, Asst. Regional Supervisor Water Quality Regional Operations Section Washington Regional Office 943 Washington Square Mall Washington NC 27889 Subject: Notice of Violation: NOV-2019-LV-0759 Fairfield Harbour W WTP NPDES Permit NC0033111 Dear Mr. Tankard: In reference to the Notice of Violation dated 16 October 2019, we offer the following response: The ultraviolet (UV) disinfection system bulbs were replaced the week prior to the Enterococci exceedances as a part of routine maintenance. Upon notification of the high results, an investigation revealed that the new bulbs had been stored in our warehouse when the building was flooded by Hurricane Florence. Though there was no evidence of damage to them, the working intensity measured at only 51 %. Operators immediately converted to the back-up chlorine disinfection system and ordered new bulbs. All subsequent samples were well within permit compliance. The UV system was brought back online on 25 June 2019. Respectfully, Dana Hill Director of Operations 4944 Parkway Plaza Boulevard, Suite 375 • Charlotte, North Carolina 28217 (800) 525-7990 • cwsnc@carolinawaterservicenc.com •www.carolinawaterservicenc.com