United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0060461 19/10/15 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Abington WWTP
6890 Bainburg Ct
Kernersville NC 27284
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 19/10/15 17/03/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Andrew Richard Phillips/ORC/336-240-5866/
Other Facility Data
12:00PM 19/10/15 22/02/28
Name, Address of Responsible Official/Title/Phone and Fax Number
Dana Hill,PO Box 240908 Charlotte NC 28224/Director of Operations/704-319-0503/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Gary Hudson DWR/Division of Water Quality/336-776-9694/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
10/21/2019
NPDES yr/mo/day
19/10/15
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
*The permit for this facility was renewed on 1MAR17 and expires on 28FEB22. A copy of the permit
was presented for inspection. There are no special conditions related to this permit.
*Richard Philips is the ORC and holds a Biological WW Grade 2 license, and Jack Burner is the
BUORC and holds a Grade 1 Biological WW license.
*The effluent composite sampling is flow proportional. Influent sampling is not a requirement.
*The influent goes through 2 seperate bar screens before entering the flow equalization basin.
*The flow equalization basin appeared to be well operated and maintained.
*The aeration basin appeared to be well operated and maintained. The blowers are on a timer and are
set to turn off for 2 hours every morning.
*At the time of this inspection both clarifiers were clean and free of floating sludge.
*Sodium Bisulfite is being used for de-chorination.
*A new flow meter was installed and calibrated on 9SEP19.
*The effluent was clear on the day of this inspection.
*During this inspection the entire WWTP appeared to be very well operated and maintained.
NC0060461 17 (Cont.)
Page#2
Permit:NC0060461
Inspection Date:10/15/2019
Owner - Facility:
Inspection Type:
Abington WWTP
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
The permit for this facility was renewed on 1MAR17 and expires on 28FEB22. A copy of the
permit was presented for inspection. There are no special conditions related to this permit.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Richard Philips is the ORC and holds a Biological WW Grade 2 license, and Jack Burner is
the BUORC and holds a Grade 1 Biological WW license.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Page#3
Permit:NC0060461
Inspection Date:10/15/2019
Owner - Facility:
Inspection Type:
Abington WWTP
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The effluent composite sampling is flow proportional. Influent sampling is not a requirement.Comment:
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
None.Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
The influent goes through 2 seperate bar screens before entering the flow equalization
basin.
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Page#4
Permit:NC0060461
Inspection Date:10/15/2019
Owner - Facility:
Inspection Type:
Abington WWTP
Compliance Evaluation
Equalization Basins Yes No NA NE
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
The flow equalization basin appeared to be well operated and maintained.Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
The aeration basin appeared to be well operated and maintained. The blowers are on a
timer and are set to turn off for 2 hours every morning.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
At the time of this inspection both clarifiers were clean and free of floating sludge.Comment:
Page#5
Permit:NC0060461
Inspection Date:10/15/2019
Owner - Facility:
Inspection Type:
Abington WWTP
Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
None.Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
None.Comment:
De-chlorination Yes No NA NE
Type of system ?Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Sodium Bisulfite is being used for de-chorination.Comment:
Are tablet de-chlorinators operational?
Number of tubes in use?
None.Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
A new flow meter was installed and calibrated on 9SEP19.Comment:
Effluent Pipe Yes No NA NE
Page#6
Permit:NC0060461
Inspection Date:10/15/2019
Owner - Facility:
Inspection Type:
Abington WWTP
Compliance Evaluation
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
The effluent was clear on the day of this inspection.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
None.Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
During this inspection the entire WWTP appeared to be very well operated and maintained.Comment: