HomeMy WebLinkAboutNC0000108_Compliance Evaluation Inspection_20191021DocuSign Envelope ID: 76828798-744B-4FB8-BCEB-47CF49D8C68A
ROY COOPER_
CiO.ernOr a
K41CHAEL S. RECAN p. ;
Seererary
LINDA CULPEPPER NORTH CAROLINA
cuwtor Environmental Quality
October 21, 2019
Craig Hillyer, Plant Manager
New Excelsior Inc
1379 Old Rosman Hwy
Brevard, NC 28712
SUBJECT: Compliance Inspection Report
New Excelsior WWTP
NPDES WW Permit No. NC0000108
Transylvania County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the New Excelsior WWTP on
10/11/2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0000108. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
The following item of significance was noted at the time of the inspection:
It is recommended that the facility consider connecting to the adjacent Town of Rosman sewer lift station,
decommissioning their wastewater treatment facility and rescinding their NPDES permit. This will eliminate
the operation and maintenance costs associated with an aging facility and the environmental liability
associated with an NPDES permit and discharge.
If you should have any questions, please do not hesitate to contact me with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
Sincerely,
DocuSigned by:
082B1105A3CA418_..
Tim Heim, P.E., Environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Ec:
WQS-ARO Server
LF
G:\WR\WQ\Transylvania\Wastewater\Minors\Excelsior 00108\Inspections\2019 CEI\20191021_NC0000108_CEI.Rtf
North CaroiibsDepart rnentofEovironmerttalQuality I DiNsionofWater Resourres
Ashevil ie Regional Office 1 2090 U.S_ 70 Htg3nray I Swan nanos. North Carolina 23773
'� 328 2M-4500
DocuSign Envelope ID: 76828798-744B-4FB8-BCEB-47CF49D8C68A
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO000108 111 12 I 19/10/1, I17
18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I
I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA
---------------------- Reserved -------------------
671
70 I I 71 I I 72 I r I
u ty
73 I I 174 751 I I I I I I I80
I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
01:OOPM 19/10/11
16/05/01
New Excelsior WWTP
1379 Old Rosman Hwy
Exit Time/Date
Permit Expiration Date
Rosman NC 28772
02:OOPM 19/10/11
20/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Davis Allen James/ORC/828-697-0063/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Craig Hillyrd,1379 Old Rosman Hwy Brevard NC 28712//828-885-2929/8288846121
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenance 0 Facility Site Review 0 Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
10/21/2019
F.Sii ea by:
MON" 6'im
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers
Date
ooasig-d by:
1
10/ 2 1/ 2 019
p�� )I' —
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 76828798-744B-4FB8-BCEB-47CF49D8C68A
NPDES yr/mo/day Inspection Type (Cont.)
NC0000108 I11 121 19/10/11 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a routine Compliance Evaluation Inspection of the
facility on October 11, 2019. Craig Hillyer (Plant Manager) and plant maintenance staff assisted with
the inspection.
The plant appeared to be operating adequately during the inspection, but many components have
reached the end of their design life and are potentially in need of repair/replacement.
It is recommended that the facility consider connecting to the adjacent Town of Rosman sewer lift
station, decommissioning their wastewater treatment facility and rescinding their NPDES permit. This
will eliminate the operation and maintenance costs associated with an aging facility and the
environmental liability associated with an NPDES permit and discharge.
Page#
DocuSign Envelope ID: 76828798-744B-4FB8-BCEB-47CF49D8C68A
Permit: NC0000108 Owner - Facility: New Excelsior WWTP
Inspection Date: 10/11/2019 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The plant appeared to be operating adequately during the inspection, but many components
have reached the end of their design life and are potentially in need of repair/replacement.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
❑
❑
0
❑
Are the diffusers operational?
0
❑
❑
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑
❑
❑
Comment: Visible steel comDonents of the aeration basin are showina sianificant deterioration. rust and
holes.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? 0 ❑ ❑ ❑
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment: The chlorinator chamber and lid appeared in poor condition and tablets were being
inserted
adjacent to the tablet sleeves to achieve contact treatment.
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Page# 3
DocuSign Envelope ID: 76828798-744B-4FB8-BCEB-47CF49D8C68A
Permit: NC0000108 Owner - Facility: New Excelsior WWTP
Inspection Date: 10/11/2019 Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment:
Are the tablets the proper size and type? ❑ ❑ ❑
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use? 2
Comment: The de-chlor chamber and lid appeared in poor condition and tablets were being inserted
adjacent to the tablet sleeves to achieve contact treatment.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
❑
❑
■
❑
Page# 4