HomeMy WebLinkAboutNC0073539_Inspection_20191015ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Director Mr. Shannon V. Becker, President Aqua North Carolina, Inc. 202 Mackenan Court Cary, North Carolina 27511 Dear Mr. Becker: NORTH CAROLINA Environmental Quality October 15, 2019 Subject: Compliance Evaluation Inspection Willowbrook Subdivision WWTP NPDES Permit No. NCO073539 Mecklenburg County Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on September 25, 2019, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding a copy of the enclosed report. It is requested that a written response be submitted to this Office by November 6, 2019, addressing the concerns regarding the old bar screen and V-notch weir angle, as discussed further in the Bar Screen and Flow Measurement — Effluent Sections in the attached report. The response must include a copy of the third parry evaluation of the V-notch weir and any corrective actions. Please address your response to the attention of Mr. Bell. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell(cr�,ncdenr.gov. Sincerely, Docu Signed by: F161FB69A2D84A3... for W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ Enclosure: Inspection Report D Q � North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115 NORTH CAROLINA Da"MoM a enWmn�bl mwnq 704,663.1699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IF I 3 I NCO073539 111 12 I 19/09/25 I17 18 I S i 19 i G i 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved ------------------- 67 2.0 70 Id I 71 [.. I 72 73 L_LJ74 751 I I I I I I I80 I —I u Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 01:00PM 19/09/25 19/02/01 Willowbrook Subdivision WWTP 12309 Ramah Creek Ct Exit Time/Date Permit Expiration Date Huntersville NC 28078 03:15PM 19/09/25 23/11/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Daniel G Wimpey/ORC/704-572-6472/ Keith Alan Shattuck//704-489-9404 / Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Shannon V Becker,202 Mackenan Ct Cary NC 27511/President/919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date by: DWR/MRO WQ/704-663-1699 Ext.2192/ 10/14/2019 2 Ge,a Wes Bell E�:O,,�6')96ID90=437- entsignedd Signature of Manage ��`Au}.�view i Agency/Office/Phone and Fax Numbers Date 10.14.19 Andrew PitnerLt1`1369A21D84A3.�H /MRO WQ/704-663-1699 Ext.2180/ 161 .. EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type (Cont.) NCO073539 I11 121 19/09/25 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) FLOW MEASUREMENT — EFFLUENT SECTION cont'd: The V-notch weir angle was measured at approximately 83 degrees during the inspection; however, the flow meter was programmed to measure flows for a 90 degree V-notch weir. The Permittee must contract a third party experienced in flow meter calibrations to verify the V-notch weir angle and the calibration procedures. Please be advised that the NPDES Permit requires the flow measurement device be installed, calibrated, and maintained to ensure that the accuracy of the measurements is consistent with the accepted capability of the type of device and shall be capable of measuring flows with a maximum deviation of less than 10% from the true discharge rates throughout the range of expected discharge volumes (Permit Condition Reference: Part II, Section D.3 Flow Measurements). Page# Permit: NCO073539 Owner - Facility: Willowbrook Subdivision WWTP Inspection Date: 09/25/2019 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ 0 ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The last compliance evaluation inspection by DWR staff was performed on 7/21/16. Overall, the facility is adequately described in the Permit; however, the facility's aerated equalization tank (surge tank) was not included. The facility description will need to be updated during the next Permit renewal process. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Page# 3 Permit: NCO073539 Inspection Date: 09/25/2019 Record Keeping Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Yes No NA NE Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae Monitoring Reports (eDMRs) were reviewed for the period August 2018 through July 2019. No effluent limit violations were reported and all monitoring frequencies were correct. The ORC and staff must ensure not to report (on edmrs) effluent total residual chlorine (TRC) values below the lowest standard verified on the TRC meter (annual curve verification). Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? M ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On -site field analvses (dissolved oxvaen. DH. temperature. total residual chlorine) are performed under Aqua NC's laboratory certification #5035. Water Tech Labs (all permit parameters except field) has also been contracted to provide analytical support. The ORC and staff must ensure that the pH check standard is performed/documented following the initial pH meter calibration. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? 0 ❑ ❑ ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type ❑ ❑ ❑ representative)? Comment: The subiect Dermit requires composite and arab effluent samples. The sampler temperature was less than one degree Celsius and collecting 120 ml. aliquots at the time of the inspection. The ORC and staff must ensure that all effluent fecal coliform samples are collected directly into a sterilized container. Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑ sampling location)? Page# 4 Permit: NCO073539 Owner - Facility: Willowbrook Subdivision WWTP Inspection Date: 09/25/2019 Inspection Type: Compliance Evaluation Upstream / Downstream Sampling Yes No NA NE Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater treatment facility appeared to be properly operated and well maintained. Process control measurements were being documented and maintained on -site. The facility's telemetry -type alarm system functioned properly during the on -site test. Equalization Basins Yes No NA NE Is the basin aerated? N ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? 0 ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Are audible and visual alarms operable? 0 ❑ ❑ ❑ # Is basin size/volume adequate? 0 ❑ ❑ ❑ Comment: Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical ❑ Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: The old coarse bar screen had oartiallv separated from the WWTP structure and was bein held in place with a rope (in aeration basin). The old bar screen should be removed as soon as possible to prevent this structure from breaking off into the aeration basin and potentially damaging the aeration system (diffusers, air headers, etc.). Aeration Basins Yes No NA NE Mode of operation Ext. Air Page# 5 Permit: NCO073539 Inspection Date: 09/25/2019 Aeration Basins Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/1) Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Yes No NA NE Diffused ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Comment: Soda ash and lime are added on an as -needed basis to maintain appropriate alkalinity/pH levels. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ 0 ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) 0 ❑ ❑ ❑ Comment: Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 4 Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Page# 6 Permit: NC0073539 Inspection Date: 09/25/2019 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Disinfection -Tablet Yes No NA NE Comment: The tablet chlorinator was properly secured following the previous inspection; however, the metal supports did appear to be severely corroded and deteriorated. The Permittee should investigate the installation of an improved support structure within the near future. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: The flow meter was last calibrated/verified by Aqua NC staff on 2/12/19. See "Summary" Section for additional comments. De -chlorination Type of system ? Is the feed ratio proportional to chlorine amount (1 to 1)? Is storage appropriate for cylinders? # Is de -chlorination substance stored away from chlorine containers? Comment: Are the tablets the proper size and type? Are tablet de -chlorinators operational? Number of tubes in use? Comment: Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Yes No NA NE Tablet ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ 4 Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did not appear to be negatively impacted. Aerobic Digester Yes No NA NE Is the capacity adequate? 0 ❑ ❑ ❑ Is the mixing adequate? 0 ❑ ❑ ❑ Is the site free of excessive foaming in the tank? 0 ❑ ❑ ❑ # Is the odor acceptable? 0 ❑ ❑ ❑ Page# 7 Permit: NC0073539 Inspection Date: 09/25/2019 Aerobic Digester # Is tankage available for properly waste sludge? Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Yes No NA NE ■ ❑ ❑ ❑ Comment: Wastewater solids are removed on an as -needed basis by a contracted company (currently L&L Environmental). Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Comment: A new backup generator had been recently installed prior to the insr switch had to be ordered and will be installed within the near future. Yes No NA NE ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ A new transfer Page# 8