October 10, 2019
Mark Jones
Director of Maintenance, Engineering & Energy Management
Charlotte -Mecklenburg BOE
3301 Stafford Drive
Charlotte, North Carolina 28202
Subject: Compliance Evaluation Inspection
Berryhill Elementary School WWTP
NPDES Permit No. NCO028711
Mecklenburg County
Dear Mr. Jones:
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on
September 27, 2019, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of
our findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell(cr�,ncdenr.gov.
Sincerely,
DocuSigned by:
A44" H P4z
for
F161F669A2D84A3...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure:
Inspection Report
D Q
� North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NORTH CAROLINA
Da"MoM a enWmn�bl mwnq 704,663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NCO028711 111 12 I 19/09/27 I17 18 I S i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [„ I 72 n 73 � i 74 75I I I I I I I I80
u u I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:OOAM 19/09/27
15/08/01
Berryhill Elementary School WWTP
10501 Walkers Ferry Rd
Exit Time/Date
Permit Expiration Date
Charlotte NC 28208
10:25AM 19/09/27
20/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Gregory Alexander Trombello/ORC/704-989-0165/
Jeffery G Mitchell//980-215-3291 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
George M Jones,3301 Stafford Dr Charlotte NC 28208/Director of Maintenance,
Engineering & Energy Management/704-343-6050/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell Signedd by: DWR/MRO WQ/704-663-1699 Ext.2192/ 10/10/2019
19E�D`
2 re
1696D90=437...
Fs —Signed by: Date
Signature of Management Q A Reviewer Agency/Office/Phone and Fax N CXt" H M4-t4
Andrew Pitner DWR/MRO WQ/704-663-1699 Ext.2180/ 10.10.19
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO028711 I11 121 19/09/27 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO028711 Owner - Facility: Berryhill Elementary School WWTP
Inspection Date: 09/27/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The last compliance evaluation inspection by DWR staff was performed on 3/3/17.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Page# 3
Permit: NCO028711
Inspection Date: 09/27/2019
Record Keeping
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period August 2018 through July 2019.
An effluent total residual chlorine (TRC) daily maximum violation was reported in September
2018. The Division has previously addressed this limit violation through the issuance of a
Notice of Deficiency (NOD).
Effluent TRC values were being reported below the lowest standard verified on the total
residual chlorine (TRC) meter (including negative results) in August, September and
October 2018. In addition, the effluent temperature values were not properly transcribed
(sample times were listed) for the entire week of 5/20/19 and a "0" flow was reported for the
week of 4/15/19. Revised edmrs (including the mailing in of two signed processed copies)
should be performed on all above -noted months.
The ORC must ensure to monitor and report the flows during future effluent sampling
events.
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
M
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: On -site field analvses (dissolved oxvaen. oH. temDerature. TRC) are Derformed under
Metwater, Inc.'s laboratory certification #5615. The CMBOE/Berryhill Elementary also
maintains a field laboratory certification (#5512) to perform dissolved oxygen, pH,
temperature and TRC on -site. Water Tech Labs (all permit parameters except field) has
also been contracted to provide analytical support.
The ORC must ensure that the pH check standard (must be within +/- 0.1 SU) is
performed/documented following the initial pH meter calibration.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires effluent grab samples.
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Page# 4
Permit: NCO028711 Owner - Facility: Berryhill Elementary School WWTP
Inspection Date: 09/27/2019 Inspection Type: Compliance Evaluation
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑
sampling location)?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well maintained.
Process control measurements were being documented and maintained on -site.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Screenings are disposed at a permitted landfill by a contracted company.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Comment: The facility's telemetry -type alarm system functioned properly during the on -site test.
Aeration Basins
Mode of operation
Type of aeration system
Yes No NA NE
Ext. Air
Diffused
Page# 5
Permit: NCO028711
Inspection Date: 09/27/2019
Aeration Basins
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/1)
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Soda ash is added on an as -needed basis to maintain appropriate
alkalinity/pH levels.
The settleability test (one hour settling time) performed during
the inspection was 300 ml/L
with a clear supernate.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Comment:
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
1
Is the level of chlorine residual acceptable?
0❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
Page# 6
Permit: NCO028711 Owner - Facility:
Inspection Date: 09/27/2019 Inspection Type:
Berryhill Elementary School WWTP
Compliance Evaluation
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is calibrated annually and was last calibrated on 10/10/18 by Clearwater.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
Tablet
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
2
Yes No NA NE
❑
❑
■
❑
❑
❑
❑
■
❑
❑
■
❑
Comment: The effluent appeared clear with no floatable solids or foam. The effluent is discharged into
the receiving stream via submerged outfall.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
M
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: Wastewater solids are removed on an as -needed basis by a contracted company (curre
L&L Environmental).
Page# 7