HomeMy WebLinkAbout6301_Moore_CDLF_MSWLF_LFG_FID1261716_20181127I pENR USE ONLY ❑Paper Report ❑Electronic Data - Email CD (data loaded: Yes / No Doe/Event #:
NC DENR I IEnvironmental Monitoring
Division of Waste Management - Solid Waste Reporting Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are
available for inspection and examination by any person upon request (NC General Statute 132-6).
Instructions:
Prepare one form for each individually monitored unit.
Please type or print legibly.
Attach a notification table with values that attain or exceed NC 2L groundwater standards or NC 2B surface water standards. The notification
must include a preliminary analysis of the cause and significance of each value. (e.g. naturally occurring, off -site source, pre-existing
condition, etc.).
Attach a notification table of any groundwater or surface water values that equal or exceed the reporting limits.
Attach a notification table of any methane gas values that attain or exceed explosive gas levels. This includes any structures on or nearby the
facility (NCAC 13B .1629 (4)(a)(i).
Send the original signed and sealed form, any tables, and Electronic Data Deliverable to: Compliance Unit, NCDENR-DWM, Solid Waste
Section, 1646 Mail Service Center, Raleigh, NC 27699-1646.
Solid Waste Monitoring Data Submittal Information
Name of entity submitting data (laboratory, consultant, facility owner):
Golder Associates NC, Inc. (on behalf of Moore County)
Contact for questions about data formatting. Include data preparer's name, telephone number and E-mail address:
Name: David "Dusty" Y. Reedy, PG Phone: 336-852-4903
E-mail: dreedy@golder.com
NC Landfill Rule: Actual sampling dates (e.g.,
Facility name: Facility Address: Facility Permit # (.0500 or .1600) October 20-24, 2006)
456 Turning Leaf Way November 27-28, 2018
Moore County Landfill Aberdeen, NC 28315 63-01 .0500 December 7, 2018
Environmental Status: (Check all that apply)
❑ Initial/Background Monitoring ❑ Detection Monitoring Assessment Monitoring ❑X Corrective Action
of data submitted: (Check all that apply)
Groundwater monitoring data from monitoring wells XQ Methane gas monitoring data
Groundwater monitoring data from private water supply wells Corrective action data (specify)
Leachate monitoring data ❑
itoring data Other(specify)
Surface water mon
Notification attached?
8 No. No groundwater or surface water standards were exceeded.
Yes, a notification of values exceeding a groundwater or surface water standard is attached. It includes a list of groundwater and surface water
monitoring points, dates, analytical values, NC 2L groundwater standard, NC 2B surface water standard or NC Solid Waste GWPS and
preliminary analysis of the cause and significance of any concentration.
�X Yes, a notification of values exceeding an explosive methane gas limit is attached. It includes the methane monitoring points. dates, sample
values and explosive methane gas limits.
Certification
To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct.
Furthermore, I have attached complete notification of any sampling values meeting or exceeding groundwater standards or explosive gas
levels, and a preliminary analysis of the cause and significance of concentrations exceeding groundwater standards. I am aware that there
are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
David "Dusty" Y. Reedy, PG Senior Hydrogeologist 336-852-4903
Facili esentativ/am � Title (Area Code) Telephone Number
Affix NC Licensed/ Professional Geologist Seal
Signature
Golder Associates NC, Inc., 5B Oak Branch Drive, Greensboro, NC 27407
Facility Representative Address
PE C-2862; PG C-399
NC PE Firm License Number (if applicable effective May 1, 2009)
Revised 612009
2- N-/
Date
,�€066
November 2018
0739615018.200
kil GOLDER
Project Name: Moore County Landfill
Site Contact: JW Baucom
Day 1: 11/27/2018
High Temperature: 47°F
Starting Barometric Pressure: 29.3 in Ha
Monitoring Equipment: GEM 2000+
Day 2: 1112812018
High Temperature: 44°F
Starting Barometric Pressure: 29.4 in Ha
Monitoring Equipment: GEM 2000+
Day 2: 1210712018
High Temperature: 50°F
Starting Barometric Pressure: 29.4 in Ha
Monitoring Equipment: GEM 2000+
BOUNDARY PROBE MONITORING LOG
Project Number: 0739-615018.200
Technician(s): Erik Vasko & Travis Martinez
Low Temperature: 46° F
End Barometric Pressure: 29.2 in Ho
Low Temperature: 40° F
End Barometric Pressure: 29.4 in Ha
Low Temperature: 50° F
End Barometric Pressure: 29.4 in Ho
DATE: 11/27-28 & 12/07/2018
Monitoring
Point
Date
Time
Methane
(CHa)
%Carbon
Dioxide
CO
%Oxygen
(%)
H2S
(ppm)
Comments
GP-9
11/28/18
13:59
0.0
0.0
21.5
0
1 inch well
GP-10
11/28/18
13:42
0.3
0.3
20.5
0
1 inch well
GP-11
11/28/18
14:35
0.0
1.2
20.1
0
1 inch well
GP-12
11/28/18
14:19
0.0
0.3
20.8
0
1 inch well
GP-13
11/28/18
12:55
0S
20A
0.0
0
1 inch well
GP-13R
11/28/18
12:51
0.0
0.6
20.7
0
1 inch well
GP-14
11/28/18
13:07
0.0
8A
12.5
0
1 inch well
GP-14R
11/28/18
12:45
0.0
1.1
20.1
0
1 inch well
GP-15
11/28/18
12:31
0.1
0.3
20.7
0
1 inch well
GP-15R
11/28/18
12:39
0.0
1.2
20.5
0
1 inch well
GP-16
11/28/18
15:13
0.0
2A
18.5
0
1 inch well
GP-17
11/28/18
13:16
0.0
1.9
17.0
0
1 inch well
MW-6
11/28/18
13:26
7.1
4.8
15.5
0
2inch groundwater well
MW-15
11/28/18
13:32
8.1
9.9
9.2
0
2inch groundwater well
GV-1
11/27/18
14:31
0.0
0.1
21.7
0
Gas vent
GV-2
11/27/18
14:29
0.0
0.0
21.8
0
Gas vent
GV-3
11/27/18
14:27
0.0
0.0
211
0
Gas vent
GV-4
11/27/18
14:25
0.0
0.0
21.7
0
Gas vent
GV-5
11/27/18
14:23
0.0
0.0
211
0
Gas vent
GV-6
11/27/18
14:21
0.0
0.0
21.6
0
Gas vent
GV-7
11/27/18
14:20
0.0
0.0
21.6
0
Gas vent
GV-8
11/27/18
14:18
0.0
0.0
21.6
0
Gas vent
GV-9
11/27/18
13:03
0.0
0.0
21.3
0
Gas vent
GV-10
11/27/18
13:00
0.0
0.0
21.4
0
Gas vent
GV-11
11/27/18
12:57
0.1
0.0
21.3
0
Gas vent
GV-12
11/27/18
12:55
0.0
0.0
21.2
0
Gas vent
GV-13
11/27/18
13:29
19.1
13.3
13.7
0
Gas vent
GV-14
11/27/18
Gas vent
GV-15
11/27/18
13:34
5.9
4.6
18.8
0
Gas vent
GV-16
11/27/18
Gas vent
GV-17
11/27/18
13:52
0.1
0.0
21.7
0
Gas vent
GV-18
11/27/18
13:54
0.0
0.1
21.6
0
Gas vent
GV-19
11/27/18
13:56
4.0
2.8
19.7
0
Gas vent
GV-20
11/27/18
13:59
2.1
1.5
21.4
0
Gas vent
GV-21
11/27/18
14:01
5.8
4.0
19.0
0
Gas vent
GV-22
11/27/18
14:03
0.0
0.1
21.6
0
Gas vent
GV-23
11/27/18
14:16
0.0
0.0
21.6
0
Gas vent
GV-24
11/27/18
14:06
0.0
0.0
21.8
0
Gas vent
GV-25
11/27/18
13:06
57.5
40.1
1.0
222
Gas vent
GV-26
11/27/18
13:10
0.0
0.0
21.6
0
Gas vent
GV-27
11/27/18
13:12
48.6
33.9
4.9
58
Gas vent
GV-28
11/27/18
13:13
2.4
2.0
20.6
1
Gas vent
GV-29
11/27/18
13:17
6.9
6.7
14.7
0
Gas vent
GV-30
11/27/18
14:50
57.2
42.0
0.7
58
Passive LFG Gas vent well
GV-31
11/27/18
14:41
56.5
36.7
2.4
164
Passive LFG Gas vent well
GV-32
11/27/18
14:44
58.3
41.6
0.0
63
Passive LFG Gas vent well
GV-33 Eastern Trench Vent
11/27/18
12:42
46.5
37.4
0.2
0
New LFG Trench Gas vent
GV-34 Western Trench Vent
11/27/18
1242
1.4
1.4
20.2
0
New LFG Trench Gas vent
Scalehouse
11/27/18
12:17
0.0
0.1
21.2
0
1 Building
Maintenace Shop
12/07/18
13:41
0.0
0.2
21.4
0
Building
Transfer Station
12/07/1
13:46
0.0
0.1
21.6
0
Buildin
Blake Residence Crawl space)
1112711:
15:19
0.0
0.0
21.2
0
Building
Completed by: Erik Vasko & Travis Martinez
G:\PROJECTS\Moore County\0739615018 - Moore - Env Services\P200 - CH4 Mon & Reporting\200 DELIVERABLES\200 Draft Issued\202 Q4 November 2018\Aftachment A - Landfill Gas Probe Log.dsx
LEGEND
rn
0
0
0
rn
co
0
O
45
E
co
z
iL
r
C
a
aD
C7
0
N
PdROUND OBSCURED `
SEE ACCURACY NOTE
11 I.tss�
PERENNIAL STREAM
i
—
—
INTERMITTENT STREAM
— — — —
— — — — —
EPHEMERALSTREAM
—
POND AND WETLAND LIMITS
EXISTING 10 FT GROUND SURFACE CONTOUR
EXISTING 2 FT GROUND SURFACE CONTOUR
PROPERTY LINE
\
APPROXIMATE LIMITS OF WASTE
EXISTING ROAD
385
POTENTIOMETRIC GROUNDWATER CONTOURS (5 FT. INTERVAL)
GROUNDWATER FLOW SEGMENTS
'388.96
MW-1
MONITORING
D GROUNDWATER ELEVATION
GP-10
METHANE PROBE AND IDENTIFICATION
C
❑
SW-1
SURFACE WATER MONITORING POINT AND IDENTIFICATION
0 0
0 o `
LANDFILL GAS TRENCH VENTS AND IDENTIFICATION
o 0
e9
PASSIVE LANDFILL GAS VENTS
\
O PW-1
PRIVATE WELL LOCATION AND IDENTIFICATION
O
\� :.��
4
WETLAND AREA
N M NOT MEASURED
SB-2 SOIL SAMPLE LOCATIONS
PZ-1 EXISTING MONITORING WELLS
365.43
NOTES
1. TOPOGRAPHIC CONTOUR INTERVAL = 2 FEET
2. GROUNDWATER SURFACE CONTOUR INTERVAL = 5 FEET
3. GROUNDWATER ELEVATIONS MEASURED ON JUNE 20, 2018.
4. GROUNDWATER CONTOURS BASED ON LINEAR INTERPOLATION BETWEEN AND
EXTRAPOLATION FROM KNOWN DATA, TOPOGRAPHIC CONTOURS, AND KNOWN FIELD
CONDITIONS. THEREFORE, GROUNDWATER CONTOURS MAY NOT REFLECT ACTUAL
CONDITIONS.
5. GROUNDWATER CONTOUR LINES SHOW THE WATER TABLE SHAPE AND ELEVATION. THESE
CONTOURS ARE INFERRED LINES FOLLOWING THE GROUNDWATER SURFACE AT A
CONSTANT ELEVATION ABOVE SEA LEVEL. THE GROUNDWATER FLOW DIRECTION IS
GENERALLY PERPENDICULAR TO THE GROUNDWATER SURFACE CONTOURS, SIMILAR TO THE
RELATIONSHIP BETWEEN SURFACE WATER FLOW AND TOPOGRAPHIC CONTOURS.
6. PROPERTY BOUNDARY SURVEY BY JAMES L. WRIGHT DATED NOVEMBER 1984. ITS LOCATION
IS RELATIVE TO TOPOGRAPHY APPROXIMATE BY HDR ENGINEERING, INC.
7. EXISTING TOPOGRAPHY WITHIN ACTIVE AND PROPOSED LANDFILL PROVIDED BY MATTHEWS
LAND SURVEYING & MAPPING, PLLC DATED APRIL 17, 2015.
8. MONITORING WELLS MW-1 THROUGH MW-5 SURVEYED JUNE 1987 BY S&ME, INC. MONITORING
WELLS MW-6 THROUGH MW-16 SURVEYED APRIL 1995, SEPTEMBER 1996, AND APRIL 2003 BY
HDR ENGINEERING INC./ ED BUCKNER RLS APRIL 17, 2015. MONITORING WELLS MW-11SR, MW-
11DR,MW- 15R, MW-17S, MW- 17P, MW- 18 AND PIEZOMETERS PZ-1, PZ-2 AND PZ-3 WERE
SURVEYED BY FLEMING ENGINEERING, INC. ON JULY 3, 2018.
9. THE LOCATIONS OF LANDFILL GAS TRENCH VENTS ARE APPROXIMATE.
10. GROUNDWATER WELLS MW-11 D, MW-13D, AND MW-16D ARE NOT SCREENED IN THE SHALLOW
AQUIFER AND ELEVATION DATA WERE NOT USED IN THE CONSTRUCTION OF GROUNDWATER
CONTOURS.
11. A STREAM DETERMINATION WAS CONDUCTED ON APRIL 17, 2013 BY A GOLDER ASSOCIATES
NC, INC. REPRESENTATIVE. THE STREAM DETERMINATION WAS CONDUCTED USING NCDWQ'S
"METHODOLOGY FOR IDENTIFICATION OF INTERMITTENT AND PERENNIAL STREAMS AND
THEIR ORIGINGS, VERSION 4.11".
12. THE WATER LEVEL FROM MW- 18 WAS NOT USED IN THE CONSTRUCTION OF GROUNDWATER
CONTOURS AS IT WAS NOT YET STABILIZED.
0 200 400
SCALE FEET
/ CLIENT PROJECT
j - MOORE COUNTY MOORE COUNTY LANDFILL
-01
PERMIT NO. 63
ABERDEEN NORTH CAROLINA
,. •� O o \ r - �) !` jf1t�, CONSULTANT TITLE
YYYY-MM-DD 2018-09-13
• / j'�'/� L..T� �n •'r ' if `J�f(f / \ PG C-399 GROUNDWATER SURFACE CONTOUR MAP
I). j(' �7--'�.1i/;�c" � ,� : i ,'L _ A '� �� >, ���� r' �'•:.6�' '��rid' PREPARED KL
JUNE 209 2018
DESIGN WBB
GOLDER
SITE LOCATION MAP REVIEW RPK PROJECT No. PHASE DRAWING
NOT TO SCALE GOLDER ASSOCIATES NC, INC. APPROVED RPK 0739615018 100 0
INSTRUMENT CALIBRATION REPORT
Pine Environmental Services LLC
8411 Garvey Drive, Suite 113
Raleigh, NC 27614
Toll -free: (866) 646-PINE (7463)
Pine Environmental Services, Inc.
Instrument ID 8665
Description Landtec GEM-2000 +
Calibrated 11/26/2018 8:44:55AM
Test Instruments Used During the Calibration
Test Standard ID Description Manufacturer
NC 4 GAS 20.9 NC 4 GAS 20.9 Gasco
FBH-412-6 EX FBH-412-6 EX 5/19
5/ 19
NC 50/35 NC 50 CH4/35 CO2 Gasco
MAP-399-5 1 /20
Notes about this calibration
Calibration Result Calibration Successful
Who Calibrated Ryan Williamson
Serial Number /
Model Number Lot Number
32211 FBH-412-6
GP 12126 - 31803 MAP-399-5
As Of Cal Entry Date
Next Cal Date /
Last Cal Date/ Expiration Date
Opened Date
5/19/2019
1/20/2020
All instruments are calibrated by Pine Environmental Services LLC according to the manufacturer's
specifications, but it is the customer's responsibility to calibrate and maintain this unit in accordance with the
manufacturer's specifications and/or the customer's own specific needs.
Notify Pine Environmental Services LLC of any defect within 24 hours of receipt of equipment
Please call 800-301-9663 for Technical Assistance
Pine Environmental Services LLC Windsor Industrial Park, 92 North Main Street, Bldg 20, Windsor, NJ 08561, 800-301-9663
www.pine-enviromnental.com
INSTRUMENT CALIBRATION REPORT
Pine Environmental Services LLC
8411 Garvey Drive, Suite 113
Raleigh, NC 27614
Toll -free: (866) 646-PINE (7463)
Pine Environmental Services, Inc.
Instrument 1D 8665
Description Landtec GEM-2000 +
Calibrated 11/26/2018 8:44:55AM
Manufacturer
CES Landtec
State Certified
Model Number
GEM2000+
Status Pass
Serial Number/ Lot
GM08581
Temp °C 21
Number
Location
North Carolina
Humidity % 39
Department
Calibration Specifications
Group # 1
Range Ace %
0.0000
Group Name Methane
Reading Ace %
3.0000
Stated Accy Pet of Reading
Plus/Minus
0.00
Nom In Val / In Val In Type Out Val
Out Type
Fnd As
Lft As
Dev%
Pass/Fail
50.00 / 50.00 %Volume 50.00
%Volume
49.00
50.00
0.00%
Pass
Group # 2
Range Ace %
0.0000
Group Name Carbon Dioxide
Reading Ace %
3.0000
Stated Accy Pet of Reading
Plus/Minus
0.00
Nom In Val / In Val In Type Out Val
Out Type
Fnd As
Lft As
Dev%
Pass/Fail
35.00 / 35.00 %Volume 35.00
%Volume
34.70
35.00
0.00%
Pass
Group # 3
Range Ace %
0.0000
Group Name Oxygen
Reading Ace %
3.0000
Stated Accy Pet of Reading
Plus/Minus
0.00
Nom In Val / In Val In Type Out Val
Out Type
Fnd As
Lft As
Dev%
Pass/Fail
20.90 / 20.90 %Volume 20.90
%Volune
20.70
20.90
0.00%
Pass
Group # 4
Range Ace %
0.0000
Group Name Hydrogen Sulfide
Reading Ace %
3.0000
Stated Accy Pet of Reading
Plus/Minus
0.00
Nom In Val / In Val In Type Out Val
Out Type
Fnd As
Lft As
Dev%
Pass/Fail
25.00 / 25.00 PPM 25.00
PPM
28.00
25.00
0.00%
Pass
Group # 5
Range Ace %
0.0000
Group Name Carbon Monoxide
Reading Ace %
3.0000
Stated Accy Pet of Reading
Plus/Minus
0.00
Nom In Val / In Val In Type Out Val
Out Tvve
Fnd As
Lft As
Dev%
Pass/Fail
50.00 / 50.00 PPM 50.00
PPM
48.00
50.00
0.00%
Pass
Pine Environmental Services LLC Windsor Industrial Park, 92 North Main Street, Bldg 20, Windsor, NJ 08561, 800-301-9663