HomeMy WebLinkAbout0601_AveryCountyMSWLF_LFG_DIN28178_20161104 December 13, 2016 Ms. Jaclynne Drummond NCDENR DWM Solid Waste Section 2090 U.S. 70 Highway Swannanoa, North Carolina 28778-8211 RE: Operations, Monitoring, and Maintenance Report –Nov 2016 Avery County Closed MSW Landfill Spruce Pine, North Carolina Dear Ms. Drummond: Smith Gardner, Inc. (S+G) is pleased to present this report concerning the operation and maintenance (O&M) of the Avery County Closed MSW Landfill (Permit No. 06-01) Landfill Gas Collection and Control System (LFGCCS). Monitoring of the on- and off-site landfill gas probes was also performed. Mr. Frank Terry with B.E.L. performed the site visit on November 4th, 2016. Site visit details are provided below. LFG EXTRACTION WELL MONITORING PROGRAM Monthly monitoring of the LFGCCS will continue and shall include the following items:  CH4, O2, CO2, and pressure monitoring at each extraction well head;  CH4, O2, CO2, and pressure monitoring at the flare station; and  Adjustment of the LFGCCS to balance recovery and ensure safe system operation. The County will maintain this LFGCCS and will continue to evaluate the effectiveness of increased LFG recovery from the waste mass in alleviating off-site LFG migration. Results from monthly monitoring events will be reported in accordance with the approved LFG Monitoring Plan. LFG EXTRACTION WELL MONITORING ACTIVITIES Mr. Terry performed the flare station and well field monitoring on November 4th, 2016. Initial measurements indicated there was approximately 28 inches of available vacuum average throughout the well field, ranging from approximately 31 to 37 inches of available vacuum at each of the LFG wells across the well field. The results from this event are summarized below. Recommended actions are underlined. Well field data and flare station data are provided in the attached Table 1. Ms. Drummond December 13, 2016 Page 2 of 3 LFG Extraction Well Field  W-1 through W-10: S+G performed methane (CH4), oxygen (O2), carbon dioxide (CO2), and pressure monitoring. Valves on extraction Wells W3 and W5 were opened slightly (Approx. 1 turn).  Orifice Plates: S+G continues to evaluate orifice plate sizes at wells W5, W7, W9, and W10 during each site visit. As LFG flow potential at these locations remains stable, the correct orifice plate sizes are currently installed. Flare Station  Condensate Tank: The condensate tank was observed during this site visit; the liquid was at an acceptable level. S+G will continue to monitor the liquid level of the condensate tank.  Filter Tank: The filter tank was observed during the November 2016 site visit and the liquid level was found to be at an acceptable level. S+G will continue to monitor the liquid level of the filter tank.  Flare operation: Due to low concentrations of methane measured at the flare combustion was not observed. The spark generator was operational; however, the flare was not able to be ignited prior to S+G leaving the site. S+G will continue to adjust the system to optimize gas flow and quality. LFG MONITORING WELL (PERIMETER) MONITORING PROGRAM Mr. Terry performed monitoring of the perimeter LFG monitoring network during this event. Monitoring wells exceeding the LEL include P-2, and P-7 which exhibited methane concentrations of 18.1% and 7.1% respectively. Monitoring Well P-1 and P-3 exhibited 1.8% and 4.2% respectively but did not exceed the LEL of 5%. The other wells, monitored during this event, had no detectable concentrations of CH4. Results of this monitoring event are included in Attachment 1. Attachment 2 provides a CH4 concentration graph over time for monitoring wells that have historically had methane present. The current well network will continue to be monitored and data will be reported to NCDEQ and the County. CONCLUSIONS The site has been generally characterized by a trend of consistently decreasing LFG concentrations. Elevated methane concentrations have been observed in a few wells during the past few monitoring events. These detections may be attributable to the extremely dry conditions currently present. We will continue to monitor the CH4 concentrations at the site monthly. Ms. Drummond December 13, 2016 Page 3 of 3 The next routine monitoring event is scheduled for early December 2016. If you have any questions, or require additional information, please contact us at your earliest convenience at 919-828-0577 or by e-mail (address below). Sincerely, SMITH GARDNER, INC. Britt Ransom Madeline German, P.G. Project Manager, ext. 301 Project Geologist ext. 222 britt@smithgardnerinc.com madeline@smithgardnerinc.com Attachments cc: Eric Foster – Avery County Deb Aja – NCDEQ file H:\Projects\Avery County (NC)\Avery-15-1 (LFG Sys Ops)\2016 LFG Monitoring\11 November 2016\Avery Co MSW LFG Monitoring Rpt Nov 2016.docx This page intentionally left blank. FIGURE This page intentionally left blank. 0 2 0 0 ' 4 0 0 ' 123 456 4 G:\CAD\Avery County\Avery 13-6\sheets\AVERY-B0216.dwg - 12/3/2013 11:03 AM           Th i s P a g e I n t e n t i o n a l l y L e f t B l a n k TABLE This page intentionally left blank. DATE:BY:BPR Da t e / T i m e C H 4 C O 2 O 2 B a l a n c e I n i t . T e m p e r a t u r e In i t . S t a t i c Pr e s s u r e Ad j . S t a t i c Pr e s s u r e Ad j . D i f f . Pr e s s u r e * Init. Flow A d j . F l o w System Pressure mm / d d / y y y y % % % % d e g F i n H 2 O i n H 2 O i n H 2 O S c f m S c f m i n H 2 O AV E R Y - W 1 1 1 / 4 / 2 0 1 6 9 : 5 7 7 1 . 9 2 8 . 1 0 . 0 0. 0 7 4 - 2 8 . 2 - 2 8 . 2 0 . 0 N R N R - 2 7 . 8 AV E R Y - W 2 1 1 / 4 / 2 0 1 6 9 : 4 8 5 0 . 1 2 6 . 5 0 . 5 2 2 . 9 7 1 - 2 8 . 4 - 2 8 . 3 0 . 0 6 . 4 7 . 5 - 2 8 . 2 AV E R Y - W 3 1 1 / 4 / 2 0 1 6 9 : 4 4 6 7 . 6 2 9 . 9 0 . 4 2 . 1 7 1 - 2 8 . 4 - 2 8 . 3 0 . 0 7 . 9 0 . 0 - 2 8 . 2 AV E R Y - W 4 1 1 / 4 / 2 0 1 6 9 : 5 1 1 9 . 6 2 3 . 2 2 . 0 5 5 . 2 7 3 - 2 7 . 0 - 2 7 . 0 0 . 0 9 . 4 6 . 1 - 2 8 . 6 AV E R Y - W 5 1 1 / 4 / 2 0 1 6 1 0 : 1 4 2 8 . 5 2 5 . 0 0 . 3 46 . 2 7 2 - 2 7 . 0 - 2 7 . 0 0 . 8 3 . 1 2 . 8 - 2 8 . 3 AV E R Y - W 6 1 1 / 4 / 2 0 1 6 1 0 : 0 7 9 . 4 2 0 . 6 1 . 2 68 . 8 7 5 - 0 . 6 N R N R 0 . 8 N R - 2 8 . 0 AV E R Y - W 7 1 1 / 4 / 2 0 1 6 1 0 : 1 1 7 . 6 1 9 . 6 2 . 4 7 0 . 4 7 8 - 7 . 3 - 7 . 6 0 . 0 4 . 3 4 . 3 - 2 7 . 9 AV E R Y - W 8 1 1 / 4 / 2 0 1 6 1 0 : 1 8 1 4 . 9 2 2 . 1 2 . 6 60 . 4 7 4 - 1 4 . 0 - 1 4 . 0 0 . 0 0 . 0 0 . 0 - 2 7 . 9 AV E R Y - W 9 1 1 / 4 / 2 0 1 6 9 : 5 5 1 0 . 0 1 9 . 2 5 . 0 6 5 . 8 7 3 - 2 8 . 4 - 2 8 . 2 0 . 1 0 . 3 0 . 3 - 2 7 . 5 AV E R Y - W 1 0 1 1 / 4 / 2 0 1 6 9 : 4 1 2 6 . 9 1 3 . 1 1 3 . 1 4 6 . 9 6 7 - 2 8 . 4 - 2 8 . 3 0 . 4 0 . 3 0 . 5 - 2 8 .2 Av - F l a r e 1 1 / 4 / 2 0 1 6 1 1 : 0 1 1 5 . 5 1 2 . 0 1 0 . 6 6 1 . 9 N R N R N R N R N R N R N R NR = n o t r e c o r d e d La n d f i l l G a s C o l l e c t i o n a n d C o n t r o l S y s t e m M o n i t o r i n g No v e m b e r 2 0 1 6 *T h e d i f f e r e n t i a l p r e s s u r e m e a s u r e m e n t s h o u l d b e p o s i t i v e . A n e g a t i v e d i f f e r e n t i a l p r e s s u r e m a y i n d i c a t e n o g a s f l o w .    N e g a t i v e d i f f e r e n t i a l pr e s s u r e c a n b e t h e r e s u l t o f d i r t o r w a te r o b s t r u c t i n g t h e p i t o t t u b e p e r f o r a t i o n s .   O v e r p u l l i n g b y a d j a c e n t e x t r a c t i o n w e l l s m a y a l s o r e s u l t in n e g a t i v e p r e s s u r e b e i n g d i s p l a y e d . November 4, 2016 Av e r y C o u n t y C l o s e d M S W L a n d f i l l TA B L E 1 De v i c e I D Attachment 1 This page intentionally left blank. NC Division of Waste Management - Solid Waste Section Landfill Gas Monitoring Data Form Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and examination by any person upon request (NC General Statute 132-6). Facility Name: ______________________________________________ Permit Number: ____________________________ Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________ Name and Position of Sample Collector: _________________________________________ Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________ Date and Time of Field Calibration: _____________________ Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________ Pump Rate of Gas Meter: _____________ Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________ Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane by volume = % LEL/20 If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same information as contained on this form. Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment. __________________________________ ________________________ SIGNATURE TITLE .0500 Avery County Closed Landfill 06-01 11/4/16 .0500 Frank Terry, BEL ENVISION 1510204 2/18/16 11/4/16 9:00AM 35/50 12/2018 0.5 L/min 57 30.21 Sunny P-1 >60s 1225 >60s 36.0 36.0 1.8 19.6 1.2 P-2 >60s 1118 >60s 362.0 362.0 18.1 0.1 25.7 P-3 >60s 1000 >60s 84.0 84.0 4.2 16.9 4.2 P-4 >60s 1126 >60s 0.0 0.0 0.0 11.8 9.6 P-5 >60s 1130 >60s 0.0 0.0 0.0 19.2 3.0 P-6 >60s 1055 >60s 0.0 0.0 0.0 18.4 3.0 P-7 >60s 1045 >60s 142.0 142.0 7.1 3.9 1.3 P-8 >60s 1109 >60s 0.0 0.0 0.0 17.4 5.0 P-9 >60s 1142 >60s 0.0 0.0 0.0 20.5 0.2 P-10 >60s 1138 >60s 0.0 0.0 0.0 20.8 0.0 P-11 >60s 1149 >60s 0.0 0.0 0.0 17.4 2.4 P-12 >60s 1049 >60s 0.0 0.0 0.0 20.8 1.8 P-13 >60s 1159 >60s 0.0 0.0 0.0 20.9 0.0 Britton Ransom Digitally signed by Britton Ransom DN: cn=Britton Ransom, o=S+G, ou=Columbia Office, email=britt@smithgardnerinc.com, c=US Date: 2016.11.29 13:01:35 -05'00'Project Manager, S+G NC Division of Waste Management - Solid Waste Section Landfill Gas Monitoring Data Form Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and examination by any person upon request (NC General Statute 132-6). Facility Name: ______________________________________________ Permit Number: ____________________________ Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________ Name and Position of Sample Collector: _________________________________________ Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________ Date and Time of Field Calibration: _____________________ Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________ Pump Rate of Gas Meter: _____________ Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________ Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane by volume = % LEL/20 If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same information as contained on this form. Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment. __________________________________ ________________________ SIGNATURE TITLE .0500 Avery County Closed Landfill 06-01 11/4/16 .0500 F.Terry, BEL Environmental ENVISION 2/18/16 11/4/16 9:00 AM 15/15 12/2018 0.5 L/min 57 30.21 Sunny Avery County Airport Structure #1 NE Corner >60s 1230 >60s 0 0 0 20.9 0 NW Corner >60s 1233 >60s 0 0 0 21.0 0 SE Corner >60s 1236 >60s 0 0 0 20.9 0 SW Corner >60s 1239 >60s 0 0 0 20.9 0 Avery County Airport Structure #2 NE Corner >60s 1245 >60s 0 0 0 20.9 0 NW Corner >60s 1248 >60s 0 0 0 20.9 0 SE Corner >60s 1251 >60s 0 0 0 20.9 0 SW Corner >60s 1254 >60s 0 0 0 20.9 0 Avery County Airport Structure #3 NE Corner >60s 1300 >60s 0 0 0 20.9 0 NW Corner >60s 1303 >60s 0 0 0 20.9 0 SE Corner >60s 1306 >60s 0 0 0 20.9 0 SW Corner >60s 1309 >60s 0 0 0 20.9 0 Avery County Airport Structure #4 NE Corner >60s 1312 >60s 0 0 0 20.9 0 NW Corner >60s 1315 >60s 0 0 0 20.9 0 SE Corner >60s 1318 >60s 0 0 0 20.9 0 SW Corner >60s 1321 >60s 0 0 0 20.9 0 Avery County Airport Structure #5 NE Corner >60s 1324 >60s 0 0 0 20.9 0 NW Corner >60s 1327 >60s 0 0 0 20.9 0 SE Corner >60s 1331 >60s 0 0 0 21.0 0 SW Corner >60s 1335 >60s 0 0 0 20.9 0 Britton Ransom Digitally signed by Britton Ransom DN: cn=Britton Ransom, o=S+G, ou=Columbia Office, email=britt@smithgardnerinc.com, c=US Date: 2016.11.29 12:39:49 -05'00'Field Service Mgr, S+G NC Division of Waste Management - Solid Waste Section Landfill Gas Monitoring Data Form Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and examination by any person upon request (NC General Statute 132-6). Facility Name: ______________________________________________ Permit Number: ____________________________ Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________ Name and Position of Sample Collector: _________________________________________ Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________ Date and Time of Field Calibration: _____________________ Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________ Pump Rate of Gas Meter: _____________ Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________ Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane by volume = % LEL/20 If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same information as contained on this form. Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment. __________________________________ ________________________ SIGNATURE TITLE .0500 Avery County Closed Landfill 06-01 11/4/16 .0500 F.Terry, BEL Environmental ENVISION 2/18/16 11/4/16 9:00 AM 15/15 12/2018 0.5 L/min 57 30.21 Sunny Field Service Mgr, S+G Avery County Airport Structure #6 NE Corner >60s 1338 >60s 0 0 0 20.9 0 NW Corner >60s 1341 >60s 0 0 0 20.9 0 SE Corner >60s 1344 >60s 0 0 0 20.9 0 SW Corner >60s 1347 >60s 0 0 0 20.9 0 Attachment 2 This page intentionally left blank. By:DMM Updated by:BPR Date:11/29/2016 Methane Concetrations Between May 2011 and October 2016 Landfill Gas Monitoring Well Network Avery County MSW Landfill 0 10 20 30 40 50 60 70 80 Ma y - 1 1 Ju n - 1 1 Ju l - 1 1 Au g - 1 1 Se p - 1 1 Oc t - 1 1 No v - 1 1 De c - 1 1 Ja n - 1 2 Fe b - 1 2 Ma r - 1 2 Ap r - 1 2 Ma y - 1 2 Ju n - 1 2 Ju l - 1 2 Au g - 1 2 Se p - 1 2 Oc t - 1 2 No v - 1 2 De c - 1 2 Ja n - 1 3 Fe b - 1 3 Ma r - 1 3 Ap r - 1 3 Ma y - 1 3 Ju n - 1 3 Ju l - 1 3 Au g - 1 3 Se p - 1 3 Oc t - 1 3 No v - 1 3 De c - 1 3 Ja n - 1 4 Fe b - 1 4 Ma r - 1 4 Ap r - 1 4 Ma y - 1 4 Ju n - 1 4 Ju l - 1 4 Au g - 1 4 Se p - 1 4 Oc t - 1 4 No v - 1 4 De c - 1 4 Ja n - 1 5 Fe b - 1 5 Ma r - 1 5 Ap r - 1 5 Ma y - 1 5 Ju n - 1 5 Ju l - 1 5 Au g - 1 5 Se p - 1 5 Oc t - 1 5 No v - 1 5 De c - 1 5 Ja n - 1 6 Fe b - 1 6 Ma r - 1 6 Ap r - 1 6 Ma y - 1 6 Ju n - 1 6 Ju l - 1 6 Au g - 1 6 Se p - 1 6 Oc t - 1 6 No v - 1 6 P1 P3 P7 P11 P12 P13 P2 Well % CH4 by Installation of W9 and W10 (April 30, 2013) Installation of W9/P3 Connection (September 11, 2014 Installation of P7/W8 and P1/W10 Connection (September 3, 2015)