HomeMy WebLinkAbout19084_ West Stonewall Street_OAR_201512031
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Phone +1 704 529 3200
Fax +1 704 529 3272
www.cardno.com
December 3, 2015
Ms. Linda Kaiser GSLH Charlotte Realty Holdings, LLC
6011 Connection Drive
Irving, Texas 75039
Re: Asbestos-Containing Building Materials Survey Report
The Charlotte Observer Facility
600 South Tryon Street
Charlotte, North Carolina
Dear Ms. Kaiser:
Cardno is pleased to submit a report for a survey of asbestos containing materials (ACM) for the Charlotte Observer
Facility, which includes an office building, a full basement with a tunnel, a warehouse, and parking lots. The Charlotte
Observer Building, located at 600 South Tryon Street, is a five-story office building with a basement and a basement
tunnel that extends northwest below South Church Street to the Charlotte Observer Warehouse. The warehouse is a
one-story building located at 621 South Poplar Street. The roof of the warehouse was in use as a parking deck.
Suspect building materials were collected from the buildings, which are slated for demolition. The site survey area
comprised approximately 394,800 square feet. The asbestos survey was performed by Diana Lanier, North Carolina
Asbestos Inspector (License No. 12694) and Kevin Headd, North Carolina Asbestos Inspector (License No. 11002),
on June 17-20, 2015, June 29, July 1, and July 9, 2015.
The Charlotte Observer Building and warehouse were built in 1971, with the exception of the northeastern part of
the building located in the basement that was constructed prior to 1929 and the press room in the basement that
was constructed in 1969. Numerous upgrades and renovations have occurred since the initial development.
The ACM survey included interior areas and exterior areas in preparation for demolition estimates and activities.
Because a demolition date has not been determined, the survey did not include assessment of suspect ACM on the
roof, and no roof core sampling was conducted. The suspect ACM roofing materials will need to be assessed and
any identified ACM will need to be abated prior to demolition.
BACKGROUND
During the ACM survey, Cardno was provided limited assessment and abatement information related to thermal
system insulation (TSI) in the survey area. Based on this review, minor TSI abatement as part of prior system
maintenance has occurred. Documents provided by maintenance staff indicated the presence and removal of
localized ACM as TSI. The prior information was used to further evaluate TSI existing at the site.
ASBESTOS-CONTAINING MATERIAL SURVEY
The site buildings were visually surveyed for the presence of building materials that are suspected to contain
asbestos. The asbestos survey consisted of three basic procedures: 1) conduct a visual observation of the
buildings; 2) identify homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and
miscellaneous materials; and 3) sample accessible, suspect materials.
The Charlotte Observer Facility
Asbestos Survey
December 3, 2015
2
Homogeneous Areas
Prior to sample collection, functional spaces and HAs were identified and listed to develop a sampling strategy. An
HA can be described as a material of similar appearance and texture with the same installation date and function. A
functional space is an area that may contain one or more HAs. Based on the age of the on-site buildings and the
potential for significant previous renovations, each floor of the Charlotte Observer Building, Basement Tunnel, and
Warehouse were considered separate functional spaces. The actual number of samples collected from each HA
within a functional space may vary, based on the type of material and the professional judgment of the inspector.
The table below presents the functional spaces, with estimated areas in square feet, for the site survey area.
TABLE 1: DESCRIPTIONS AND SQUARE FOOTAGES FOR SITE SURVEYED AREA
THE CHARLOTTE OBSERVER
CHARLOTTE, NORTH CAROLINA
Functional Space Estimated Square Footage (sf)
Basement 62,500 sf
Floor 1 62,500 sf
Floor 2 (includes Loading Dock) 62,500 sf
Floor 3 62,500 sf
Floor 4 62,500 sf
Floor 5/Mechanical Penthouse (includes Rooftop Elevator Equipment Rooms 18,700 sf
Basement Tunnel 1,600 sf
Warehouse 62,000 sf
Exterior (includes Charlotte Observer Building Park Lots and Loading Dock, and
Warehouse Parking Deck) Not Applicable
TOTAL ESTIMATED COMBINED BUILDING AREA: 394,800 sf
In some instances, the same HA was observed in more than one functional space (e.g. Black Window Caulk
observed on second and third floor, and Black Mastic seen on air ducts in vertical shaft extending from the
second floor to fifth floor), which were considered as overlapping HAs for this survey.
Hazard Assessment Factors
From the list of suspect homogeneous materials, a physical assessment was performed for each material on the list.
A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining
the friability of each material. Friability is a term used to describe the ease in which a building material inherently
lends itself to disturbance. By regulatory definition, friable materials are those that can be crumbled or reduced to
powder by hand pressure when dry. Each material on the list was further classified into one of three categories,
which have specific sampling requirements for each category.
Surfacing Materials: Refers to spray-applied or trowelled surfaces such as plaster ceilings and
walls, fireproofing, textured paints, textured plasters, and spray-applied
acoustical surfaces.
Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers,
tanks, ducts, and various other building components.
Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in
any of the above two categories such as resilient floor covering,
baseboards, mastics, adhesives, roofing material, caulking, glazing, and
siding. This category also contains wallboard and ceiling tile.
Materials were then assessed by their condition as good (intact), fair (damaged), or poor (significantly damaged) per
Title 40 Code of Federal Regulations Part 763. Material with localized significant damage was identified as poor if
and when observed.
The Charlotte Observer
Asbestos Survey
December 3, 2015
Sampling Strategy
The asbestos survey was conducted in general accordance with the EPA Asbestos Hazard Emergency Response
Act (AHERA) protocols using a minimum number of samples collected from each HA, to meet the sampling
requirement found in 29 CFR 1926.1101. Sample collection depended on the applicable category for the HA and
the amount of material present, as follows:
TABLE 2: AHERA GUIDELINES FOR DETERMINING THE NUMBER OF SAMPLES TO TAKE
HA CATEGORY HA SIZE SAMPLES REQUIRED
Surfacing Materials <1,000 SF 3
1,000-5,000 SF 5
>5,000 SF 7 or more
Thermal System Insulation No Stipulation 3+ (Must also sample all repair patches)
Miscellaneous Materials No Stipulation
Per AHERA, these materials must be sampled "in a manner
sufficient to determine whether or not they contain asbestos"
typically 1-3 samples based upon inspector judgment.
If the analytical results indicated that all the samples collected per HA did not contain asbestos, the material would be
considered a non-ACM. However, if the analytical results indicate one or more of the samples collected per HA
contains asbestos in quantities of greater than 1 percent asbestos (as defined by EPA), the entire material will be
designated and should be managed as an ACM. Materials which can visually be determined to be non-asbestos (i.e.,
fiberglass insulation, baseboard glue, wood, etc.) by the accredited inspector are not required to be sampled.
Miscellaneous materials require representative sampling which is typically done by collecting at least one (1) sample
per material. Inspectors typically rely on other survey observations such as the condition, friability, and quantity of
material to determine what would be a sufficient amount of samples to accurately evaluate the presence or absence
of asbestos materials.
For the Charlotte Observer the following functional spaces were utilized for the survey: Basement, First Floor,
Second Floor, Third Floor, Fourth Floor, Fifth Floor (Penthouse), Exterior, Basement Tunnel, and Warehouse. As
deemed appropriate by the asbestos survey field personnel, some materials such as the thermal system piping
insulations and elbows were treated as an overlapping HAs for the site survey area.
Sample Collection
During the sampling event, bulk samples of identified suspect ACM were generally collected and placed into
individual containers for transport to a National Voluntary Lab Accreditation Program (NVLAP) and an American
Industrial Hygiene Association (AIHA)-accredited laboratory for analysis. Some materials have multiple layers and
were analyzed separately, as determined by the laboratory. A total of 360 bulk samples were collected from the
survey area, and a total of 474 layers were analyzed by Polarized Light Microscopy (PLM). Bulk samples were
analyzed by the EMSL Analytical, Inc. laboratory located in Charlotte, North Carolina, using PLM according to EPA
Method 600/M4-82-020. The bulk samples were analyzed using PLM and were analyzed based on the number of
distinct layers of materials associated with each bulk sample. For example, vinyl floor tile and the associated mastics
are collected as one sample, but are analyzed as distinct layers by the laboratory.
A description of the bulk sampled materials is presented in Tables 1 through 9 in Tables in Attachment 1. Positively
identified ACM and assumed ACM are presented in Table 10 in the Tables in Attachment 1. Locations of the
surveyed units are provided in the Site Plans in the Figures in the Attachment 2. Attachment 3 contains the
analytical results for the survey area.
Any material containing greater than one percent (>1%) of asbestos by PLM analysis is considered an ACM.
Based on the laboratory analytical results, the following homogenous materials were identified as ACM:
The Charlotte Observer
Asbestos Survey
December 3, 2015
Basement Area – Off white 12”x12” vinyl floor tile with tan and brown smears, (2% Chrysotile), and mastic
(5% Chrysotile)
Drywall joint compound (2% Chrysotile) – Reanalyzed as composite sample via PLM
and found to be Non-ACM
6” pipe run insulation (10% Amosite and 3% Chrysotile)
6” pipe elbow (2% Amosite)
9” x 9” floor tile mastic (5% Chrysotile)
White, 12”x12” vinyl floor tile with gray smears (4% Chrysotile) and mastic (8%
Chrysotile)
Carpet mastic (2% Chrysotile)
Brown linoleum (10% Chrysotile)
Slate-like flooring (2% Chrysotile)
First Floor – Surfacing ceiling texture (5% Chrysotile)
Second Floor - Surfacing ceiling texture (3% Chrysotile)
Black window caulk (3% Chrysotile)
12” x 12” floor tile mastic (3% Chrysotile)
HVAC caulk, black (4% Chrysotile)
Third Floor - Floor Coating (2% Chrysotile)
Slate-like flooring (2% Chrysotile)
Carpet mastic (2% Chrysotile)
PATCH Caulk where wall meets stone pebble column (2% Chrysotile)
Black window caulk (5% Chrysotile)
Brown linoleum (2% Chrysotile)
White 12”x12” vinyl floor tile (3% Chrysotile)
Surfacing ceiling texture (3% Chrysotile)
Fourth Floor - Surfacing ceiling texture (3% Chrysotile)
Under sink spray (4% Chrysotile)
Fifth/Penthouse - HWR black 12” pipe run insulation (5% Amosite and 3% Chrysotile)- Hot Water Return
HWS-2 black 6” pipe run insulation (4% Amosite and 3% Chrysotile)-Hot Water Supply
HWR-2 black 12” pipe run insulation (4% Amosite and 3% Chrysotile)- Hot Water Return
HWR-2 black 6” elbow (gray - 50% Chrysotile and white - 10% Amosite and 2%
Chrysotile)-Hot Water Return
Asphaltic mastic (2% Chrysotile)
Chiller wall and door caulk (3% Chrysotile)
CHWS 4” elbow (25% Chrysotile)-Chilled Water Supply
Basement Tunnel - Wall caulk (3% Chrysotile)
30” pipe elbow (2% Chrysotile)
8” pipe run (10% Amosite and 4% Chrysotile)
Warehouse – No ACM identified
Exterior - Covers of paper chutes (2% Chrysotile)
Italicized HAs in the list above indicate overlapping HAs observed in the survey area. If an overlapping HA is
observed in other areas than those observed during the survey, the material should be assumed to be ACM.
Based on assessment and PLM analysis of collected samples, the Surfacing Ceiling Texture observed in the
parking deck of the Charlotte Observer Building, which was identified as Surfacing Ceiling Texture-2 in tables
and laboratory data, is a non-ACM and is not the same HA as the ACM Surfacing Ceiling Texture that is
The Charlotte Observer
Asbestos Survey
December 3, 2015
identified as Surfacing Ceiling Texture-1 in tables and laboratory data. The Surfacing Ceiling Texture within the
building has been positively identified as ACM.
Please note the drywall joint compound collected in the basement, was composited as a drywall system and
found by PLM point count analysis to contain <1% Chrysotile and is therefore not considered an ACM. Other
materials identified as <1% Chrysotile include stone wall caulk (first floor- lobby), CHWS (Chilled Water Supply)
Blue 3” pipe elbow insulation layer (fifth floor-mechanical penthouse), 1-inch pipe insulation (basement tunnel-air
handler room), and exterior window caulk (parking area). OSHA asbestos dust exposure regulations shall apply
when these materials are disturbed by employees or contractors.
Copies of the laboratory analytical report and corresponding chain-of-custody documents are provided as
Attachment 3. Inspector and laboratory accreditations are provided as Attachment 4. Photographic
documentation is provided in Attachment 5. Assumptions and Limitations are included as Attachment 6.
Recommendations
Prior to the anticipated demolition, Cardno ATC recommends abatement by removal of identified ACM. The
abatement will require state and local permitting before removal is conducted. The management of the ACM,
including abatement, air monitoring, and disposal should be conducted by qualified and properly licensed,
certified, and permitted contractors prior to demolition.
Because a demolition date has not been determined, the survey did not include assessment of suspect ACM on the
roof, and no roof core sampling was conducted. The suspect ACM roofing materials will need to be assessed, or
presumed to be ACM, and any identified or presumed ACM will need to be abated prior to demolition.
During the assessment, multiple materials were observed as TSI pipe runs, elbows, T’s, which included gray and
white powdery ACM, and non-ACM which included fiberglass, insulated foam glass (IFG), and woven fibers.
Tested TSI materials as covers (wraps) for pipes were found to be non-ACM. Wrapped pipes with IFG insulation
compared to those with ACM insulation were both found to be firm when touched by hand; however, the interior
pipe insulation was observed by making a small cut into the material to determine if the insulation was IFG or the
powdery ACM. Therefore, Cardno recommends that a NC Licensed Asbestos Inspector be present during the
abatement of the TSI to verify ACM from non-ACM based on observation.
Depending on the planned demolition methods and procedures, the presence of the non-ACM, non-friable
exterior window caulk, with <1% asbestos, found on the exterior of the Charlotte Observer Building could present
an exposure condition to demolition workers.
For the interior materials that contain <1% asbestos, which includes the joint compound in the basement, the
stone wall caulk in the first floor-lobby, the CHWS Blue 3” pipe elbow insulation layer that was seen in the fifth
floor-mechanical penthouse, and the 1-inch pipe insulation that was seen in the basement tunnel-air handler
room, which are considered non ACM, worker exposure regulations apply and considerations should be made to
leave the materials in place undisturbed prior to demolition, or another option is to abate the materials prior to
demolition.
An Asbestos Permit Application and Notification for Demolition/Renovation should be submitted to the Health
Hazards Control Branch of the NCDHHS-Division of Public Health in Raleigh, North Carolina. Please note that
the application must be submitted at least 10 working days prior to abatement, demolition, or renovation
activities. Because the demolition will occur in Mecklenburg County, submittal of a Mecklenburg County form (Air
Quality, Land Use and Environmental Services Agency (LUESA) National Emissions Standards for Hazardous
Air Pollutants (NESHAP) Notification of Demolition and/or Renovation Form) is also required at least 10 working
days prior to abatement, demolition or renovation activities. Due to the quantities and types of ACM present a
project design, supervisory air monitoring, and abatement oversight will be necessary as part of the abatement
process. The abated ACM will need to be placed in 6 mil plastic bags, be properly labeled, and be disposed at a
properly licensed landfill that can accept asbestos waste materials. The landfill should provide a disposal receipt
or certificate.
The Charlotte Observer
Asbestos Survey
December 3, 2015
Contractors and employees working in the area planned for demolition/renovations should be made aware of the
possibility that concealed ACM may also be found during demolition/renovation. The personnel should be
advised not to disturb known or suspect ACM. Because a demolition date has not been determined, the survey did
not include assessment of suspect ACM on the roof, and no roof core sampling was conducted. Due to large
quantities of carpeting that exists at the site, there is the potential for the discovery of additional flooring material
below the carpeting which will require assessment of suspect ACM and abatement of identified ACM prior to
demolition activities. Concealed building materials discovered during maintenance or demolition activities, which
are suspected to contain asbestos, should be sampled and analyzed to confirm the presence of asbestos prior to
disturbing. Until then, such suspect materials should be treated as presumed ACM in accordance with 29 CFR
1926.1101 and 1910.1001.
Cardno appreciates the opportunity to perform these services for GSLH Charlotte Realty Holdings, LLC, and we
look forward to working with you in the future. If you have questions or comments regarding the information in
this report, please contact the Cardno Charlotte, North Carolina, office at (704) 529-3200.
Sincerely,
Cardno
_____________________________ ____________________________
Diana Lanier Kevin Head, MS, MBA, CIH, PG, PMP, SAM
North Carolina Asbestos Inspector #126942 North Carolina Asbestos Inspector #11002
Senior Reviewer
David A. Hunter, P.G., Principal Scientist Senior Reviewer
Attachments
Attachment 1 Tables
Attachment 2 Figures
Attachment 3 Analytical Documentation
Attachment 4 Inspector and Laboratory Accreditations
Attachment 5 Photographic Documentation
Attachment 6 Assumptions and Limitations
ATTACHMENT 1
TABLES
Table 1 - Basement: Sampled Materials for Limited Asbestos Survey on June 17, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
B-001, B-002 Cove Base Basement Building Services ND
B-001, B-002 Cove Base - Mastic Basement Building Services ND
B-003, B-004 1'x1' Ceiling Tile Basement Building Services ND
B-005, B-006, B-007 Plaster Basement Building Services and Hall ND
B-008, B-009 12" x 12" Off White Floor Tile Basement Building Services 2% Chrysotile and Stop Positive
B-008, B-009 12" x 12" Off White Floor Tile (Mastic) Basement Building Services 5% Chrysotile and Stop Positive
B-010, B-11, B-12 Drywall Basement Building Services ND
*B-010, B-11, B-12 Drywall (Joint Compound) Basement Building Services *2% Chrysotile and Stop Positive (B-11 and B-12)
B-010 Drywall (Composite Sample) Basement Building Services <1% Chrysotile
B-013, B-014 Valve Insulation - Air Handler (Mastic) Basement Air Handler Room ND
B-013, B-014 Valve Insulation - Air Handler (Wrap) Basement Air Handler Room ND
B-013, B-014 Valve Insulation - Air Handler (Insulation) Basement Air Handler Room ND
B-015, B-016, B-017, B-018, B-019, B-020 6" Pipe Run - Cover Basement Hall Ceiling ND
B-021 4" Pipe Run - Cover Basement Hall Ceiling ND
B-022 2" Pipe Run - Cover Basement Air Handler Room ND
B-023, B-024, B-025 2" Pipe Elbows Basement Air Handler Room ND
B-026, B-027, B-028 6" Pipe Run (Wrap) Basement Air Handler Room ND
B-026, B-027, B-028 6" Pipe Run (Insulation) Basement Air Handler Room 10% Amosite, 3% Chrysotile,and Stop Positive
B-029, B-030, B-031 6" Pipe Elbow Basement Air Handler Room 2% Amosite, and Stop Positive
B-032, B-033 12"x12" Off White Floor Tile (Clear Mastic) Basement Copy Center ND, (assumed positive by contact with ACM layer
for abatement purposes)
B-032, B-033 12"x12" Off White Floor Tile (Tile) Basement Copy Center 2% Chrysotile and Stop Positive
B-032, B-033 12"x12" Off White Floor Tile (Black Mastic) Basement Copy Center 5% Chrysotile and Stop Positive
B-034 Drywall Basement Power Room ND
B-034 Drywall (Joint Compound) Basement Power Room ND
B-035, B-036 2'x2' Ceiling Tile Basement Power/UPS room ND
B-037, B-038 Caulk Patch (Gray) Basement Cage Room ND
B-037, B-038 Caulk Patch (White) Basement Cage Room ND
B-037, B-038 Caulk Patch (Black) Basement Cage Room ND
B-039, B-040 2'x4' Ceiling Tile Basement Machine Room Office ND
B-041, B-042 1'x1' Ceiling Tile Basement Machine Room Office ND
B-043, B-044 Carpet Mastic Basement Machine Room Office ND
B-045, B-046 HVAC Caulk, Gray Basement Dead Files Storage ND
B-047, B-048 Black Sealant Basement Dead Files Storage ND
B-049, B-050 9"x9" Floor Tile Basement Telephone Room ND, (assumed positive by contact with ACM layer
for abatement purposes)
B-049, B-050 9"x9" Floor Tile (Mastic) Basement Telephone Room 5% Chrysotile and Stop Positive
B-051, B-052 12"x12" White Floor Tile Basement Telephone Room 4% Chrysotile and Stop Positive
B-051, B-052 12"x 12" White Floor Tile (Mastic) Basement Telephone Room 8% Chrysotile and Stop Positive
B-053, B-054 1'x1' Ceiling Tile Basement Telephone Room ND
B-055, B-056 1'x1' Ceiling Tile (Wavy) Basement Telephone Room ND
B-057, B-058 HVAC Damper Basement Stairwell C HVAC Room ND
B-059, B-060 Carpet Mastic, Tan/Black Basement Facilities Maintenance 2% Chrysotile and Stop Positive
B-061, B-062, B-063 12" Metal Cover Pipe Insulation Basement Reel Room ND
B-064, B-065 HVAC Caulk, Tan Basement Reel Room ND
B-066, B-067 Plaster (Rough Coat) Basement Reel Room ND
B-066, B-067 Plaster (Skim Coat) Basement Reel Room ND
B-068, B-069 Brown Linoleum Basement Reel Room, Mez Level Bathrooms 10% Chrysotile and Stop Positive
B-068, B-069 Brown Linoleum (Mastic) Basement Reel Room, Mez Level Bathrooms ND
B-070, B-071 2'x4' Ceiling Tile Basement Reel Room, Mez. Level, Office ND
B-072, B-073 Blue Linoleum with Stone Design Basement Reel Room, Mez Level, First Aid ND
B-072, B-073 Blue Linoleum with Stone Design (Mastic) Basement Reel Room, Mez Level, First Aid ND
B-074, B-075 Floor Coating, Black # Basement Reel Room, Mez Level, First Aid, Closet <1% Chrysotile and <1% Chrysotile
B-076, B-077 Slate-Like Flooring Basement Reel Room, Mez Level, First Aid, Closet 2% Chrysotile and Stop Positive
Notes: Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
# Overlapping HA that was analyzed by PLM and found to be ACM in a separate functional space and is therefore considered ACM
Bulk Sample Homogeneous Material ResultLocation ObservedArea
*Recomposited (Sample B-010, Drywall and Joint Compound) as a Drywall System and was found by PLM analysis to be Non-ACM; however, OSHA regulations shall apply.
Table 2 - First Floor: Sampled Materials for Limited Asbestos Survey on June 17, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
F1-001, F1-002 Stone Wall Caulk First Floor Lobby <1% Chrysotile and <1% Chrysotile
F1-003, F1-004 Stone-Pebble Column Caulk First Floor Lobby ND
F1-005, F1-006, F1-007, F1-008, F1-009, F1-010, F1-011 Surfacing Ceiling Texture - 1 First Floor Lobby 5% Chrysotile and Stop Positive
F1-012, F1-013, F1-014 Drywall First Floor Hall ND
F1-012, F1-013, F1-014 Drywall (Joint Compound)First Floor Hall ND
F1-015, F1-016 Cove Base First Floor Hall ND
F1-015, F1-016 Cove Base (Mastic)First Floor Hall ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
F1-017, F1- 018, and F1- 019: Surfacing Ceiling Texture - 2, from parking area, provided in Table 9 (Exterior)
Bulk Sample Homogeneous Material Area Location Obsevered Result
Table 3 - Second Floor: Sampled Materials for Limited Asbestos Survey on June 17-18, 2015, and July 9, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
F2-001, F2-002 Cove Base Second Floor Human Resources ND
F2-001, F2-002 Cove Base (Mastic)Second Floor Human Resources ND
F2-003, F2-004, F2-005, F2-006, F2-007 Drywall Second Floor Human Resources ND
F2-003, F2-004, F2-005, F2-006, F2-007 Drywall (Joint Compound)Second Floor Human Resources ND
F2-008, F2-009, F2-010, F2-011, F2-012 Plaster (Rough Coat)Second Floor Hall ND
F2-008, F2-009, F2-010, F2-011, F2-012 Plaster (Skim Coat)Second Floor Hall ND
F2-013, F2-014 Carpet Mastic Second Floor Human Resources ND
F2-015, F2-016 Corner Wall Caulk, Clear Second Floor Human Resources ND
F2-017, F2-018 2'x2' Ceiling Tile Second Floor Training Room ND
F2-019, F2-020 Brown Linoleum w/ Stone Design - Flooring Second Floor Human Resources and Hall ND
F2-019, F2-020 Brown Linoleum w/ Stone Design (Tan Mastic)Second Floor Human Resources and Hall ND
F2-019, F2-20 Leveler Second Floor Human Resources and Hall ND
F2-019 Brown Linoleum w/ Stone Design (Black Mastic)Second Floor Human Resources and Hall ND
F2-021, F2-022 Window Caulk, Gray Second Floor Training Room (Inner Window)ND
F2-023 Stone-Pebble Column Caulk, Gray Second Floor Training Room ND
F2-024, F2-025, F2-026 Vent with Spray On Second Floor Training Room ND
F2-027, F2-028, F2-029, F2-030, F2-031 Surfacing Ceiling Texture Second Floor Hall 3% Chrysotile and Stop Positive
F2-032, F2-033 Black Window Caulk Second Floor Audience Development 3% Chrysotile and Stop Positive
F2-034, F2-035 Carpet Mastic Second Floor Audience Development ND
F2-034 Leveler Second Floor Audience Development ND
F2-036, F2-037 12"x12" Tan w/ White Flecks Floor Tile Second Floor Audience Development (Vaults)ND
F2-036, F2-037 12"x12" Tan w/ White Flecks Floor Tile (Mastic)Second Floor Audience Development (Vaults)3% Chrysotile and Stop Positive
F2-038, F2-039 1'x1' Ceiling Tile Second Floor Audience Development ND
F2-040, F2-041 Portable Wall Insulation Second Floor Data Processing ND
F2-042, F2-043 HVAC Caulk, Black Second Floor Mechanical Room 4% Chrysotile and Stop Positive
* 2-A1, 2-B1 Caulk Between Wall and Stone - Pebble Column,
White-Tan
Second Floor Hall ND
* 2-A2, 2-B2 Caulk between Window Frame and Stone - Pebble
Column, White
Second Floor Hall ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
* Sampled on July 9, 2015
Bulk Sample Homogeneous Material Area Location Observed Result
Table 4 - Third Floor: Sampled Materials for Limited Asbestos Survey on June 18, 2015, July 1, 2015, and July 9, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
F3-001, F3-002, F3-003 Floor Coating, Black Third Floor Mail Room 2% Chrysotile and Stop Positive
F3-004, F3-005 Slate-like Flooring Third Floor Mail Room 2% Chrysotile and Stop Positive
F3-006, F3-007, F3-008 Drywall Third Floor Mail Room ND
F3-006, F3-007, F3-008 Drywall (Joint Compound)Third Floor Mail Room ND
F3-009, F3-010 1'x1' Ceiling Tile Third Floor Mail Room ND
F3-011, F3-012 2'x2' Ceiling Tile Third Floor Mail Room ND
F3-013, F3-014 Cove Base Third Floor Mail Room ND
F3-013, F3-014 Cove Base (Mastic)Third Floor Mail Room ND
F3-015, F3-016 Carpet Mastic (Yellow Layer)Third Floor Mail Room ND, (Assumed positive by contact with ACM layer for
abatement purposes)
F3-015, F3-016 Carpet Mastic (Black Layer)Third Floor Mail Room, Offices 2% Chrysotile and Stop Positive
F3-017 Caulk Between Wall and Stone-Pebble Column,
White (PATCH)
Third Floor Locker Room 3% Chrysotile
F3-018, F3-019 Black Window Caulk Third Floor Locker Room 5% Chrysotile and Stop Positive
F3-020, F3-021 Brown Linoleum Third Floor Locker Room 2% Chrysotile and Stop Positive
F3-020, F3-021 Brown Linoleum (Brown Mastic)Third Floor Locker Room ND
F3-022, F3-023, F3-024, F3-025, F3-026, F3-027 Plaster (Rough Coat)Third Floor Hall ND
F3-022 Plaster (Beige Layer)Third Floor Hall ND
F3-022, F3-023, F3-024, F3-025, F3-026, F3-027 Plaster (Skim Coat)Third Floor Hall ND
F3-028, F-029 Drywall Third Floor Operations ND
F3-028, F-029 Drywall (Joint Compound)Third Floor Operations ND
F3-028 Drywall (Tape)Third Floor Operations ND
F3-030 Corner Wall Caulk Third Floor Operations ND
F3-031, F2-032 12"x12" Tan w/ White Flecks Floor Tile Third Floor Operations and A/P ND
F3-031, F2-032 12"x12" Tan w/ White Flecks Floor Tile (Top Mastic)Third Floor A/P ND
F3-031, F2-032 12"x12" Tan w/ White Flecks Floor Tile (Bottom Mastic)Third Floor A/P ND
F3-033, F3-034 Light Gray w/ Stone Design Linoleum Third Floor Storage Room ND
F3-033, F3-034 Light Gray w/ Stone Design Linoleum (Mastic)Third Floor Storage Room ND
F3-035, F3-036 Light Brown w/ Stone Design Linoleum Third Floor Hall ND
F3-035, F3-036 Light Brown w/ Stone Design Linoleum (Mastic)Third Floor Hall ND
F3-037, F3-038 Dark Brown w/ Stone Design Linoleum Third Floor Hall 25% Chrysotile and Stop Positive
F3-037, F3-038 Dark Brown w/ Stone Design Linoleum (Mastic)Third Floor Hall ND
F3-039, F3-040 Black Sealant Third Floor Kitchen ND
F3-041, F3-042 2'x2' Ceiling Tile Third Floor Cafeteria ND
F3-043, F3-044 Dark Blue Gray Linoleum Third Floor Auditorium Hall ND
F3-043, F3-044 Dark Blue Gray Linoleum (Mastic)Third Floor Auditorium Hall ND
F3-045, F3-046 12"x12" White w/ Brown Flecks Floor Tile Third Floor Advertising and
Auditorium
3% Chrysotile and Stop Positive
F3-045, F2-046 12"x12" White w/ Brown Flecks Floor Tile (Mastic)Third Floor Advertising and AuditoriumND
F3-047, F3-048, F3-049, F3-050, F3-051 Surfacing Ceiling Texture Third Floor Hall 4% Chrysotile and Stop Positive
*CO3-200, CO3-201 Belts on Equipment Third Floor Mail Room ND
** 3-A1, 3-B1 Caulk between Window Frame and Stone - Pebble
Column, White
Third Floor Bathroom ND
** 3-A2, 3-B2 Caulk Between Wall and Stone-Pebble Column,
White (PATCH)
Third Floor Locker Room 4% Chrysotile and 3% Chrysotile
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
* - Sampled on July 1, 2015
** Sampled on July 9, 2015
ResultLocation ObservedAreaHomogeneous MaterialBulk Sample
Table 5 - Fourth Floor: Sampled Materials for Limited Asbestos Survey on June 18, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
F4-001, F4-002 Cove Base Fourth Floor Office ND
F4-001, F4-002 Cove Base (Mastic)Fourth Floor Office ND
F4-003, F4-004 Carpet Mastic Fourth Floor Office ND
F4-005, F4-006 Light Brown Linoleum Fourth Floor Office ND
F4-005, F4-006 Light Brown Linoleum (Mastic)Fourth Floor Office ND
F4-007, F4-008, F4-009, F4-010, F4-011 Drywall Fourth Floor Office ND
F4-007, F4-008, F4-009, F4-010, F4-011 Drywall (Joint Compound)Fourth Floor Office ND
F4-008 Drywall (Tape)Fourth Floor Office ND
F4-012, F4-013, F4-014, F4-015, F4-016 Surfacing Ceiling Texture Fourth Floor Hall 3% Chrysotile and Stop Positive
F4-017, F4-018, F4-019, F4-020, F4-021 Plaster (Rough Coat)Fourth Floor Hall ND
F4-017, F4-018, F4-019, F4-020, F4-021 Plaster (Skim Coat)Fourth Floor Hall ND
F4-022, F4-023 12"x12" Gray Floor Tile with Gray
Smears
Fourth Floor News Room ND
F4-022, F4-023 12"x12"Gray Floor Tile with Gray
Smears (Mastic)
Fourth Floor News Room ND
F4-022, F4-023 Leveler Fourth Floor News Room ND
F4-024, F4-025 Mauve Linoleum with Stone Design Fourth Floor News Room ND
F4-024, F4-025 Mauve Linoleum with Stone Design
(Top Mastic)
Fourth Floor News Room ND
F4-024, F4-025 Mauve Linoleum with Stone Design
(Bottom Mastic)
Fourth Floor News Room ND
F4-026, F4-027 2'x2' Ceiling Tile Fourth Floor News Room ND
F4-028, F4-029 Light Gray Linoleum Fourth Floor Photo Room ND
F4-028, F4-029 Light Gray Linoleum (Mastic)Fourth Floor Photo Room ND
F4-030, F4-031 Corner Wall Caulk Fourth Floor Old Data Process ND
F4-032, F4-033 Paper Flooring (Mastic)Fourth Floor Old Data Process ND
F4-032, F4-033 Paper Flooring (Tan Layer)Fourth Floor Old Data Process ND
F4-032, F4-033 Paper Flooring (Gray layer)Fourth Floor Old Data Process ND
F4-034, F4-035 Window Seal Caulk Fourth Floor Imaging ND
F4-036, F4-037 Under Sink Spray Fourth Floor Imaging 4% Chrysotile and Stop Positive
F4-038, F4-039 Interior Window Caulk Fourth Floor Imaging ND
F4-040, F4-041 Plaster/Concrete Wall Caulk Fourth Floor Imaging ND
F4-042, F4-043 1'x1' Ceiling Tile, Rough Fourth Floor Hall ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
ResultLocation ObseveredAreaHomogeneous MaterialBulk Sample
Table 6 - Fifth Floor/Penthouse (Mechanical) and Elevator Equipment Rooms: Sampled Materials for Limited Asbestos Survey on June 19, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
F5-001, F5-002 Gray-Tan Caulk Fifth Floor/Penthouse Freight Elevator Equip Room <1% Chrysotile and 3% Chrysotile
F5-003, F5-004 Tan-White-Black Caulk Fifth Floor/Penthouse Main Elevator Equip Room ND
F5-005, F5-006 Exhaust Port Insulation, Gray Fifth Floor/Penthouse Main Elevator Equip Room ND
F5-R001, F5-R002, F5-R003 Silver Water Barrier Layer-Roof Surface Fifth Floor/Penthouse Main Building Roof ND
F5-007 CHWS Blue 3" Pipe Run Fifth Floor/Penthouse South Church Street Side ND
F5-008 CHWR Blue 3" Pipe Run Fifth Floor/Penthouse South Church Street Side ND
F5-009 CHWS Blue 4" Pipe Run Fifth Floor/Penthouse South Church Street Side ND
F5-010 HWS Black 4" Pipe Run Fifth Floor/Penthouse South Church Street Side ND
F5-011 HWR Black 12" Pipe Run (Wrap)Fifth Floor/Penthouse South Church Street Side ND
F5-011 HWR Black 12" Pipe Run (Insulation)Fifth Floor/Penthouse South Church Street Side 5% Amosite and 3% Chrysotile
F5-012 HWS-2 Black 6" Pipe Run (Wrap)Fifth Floor/Penthouse South Church Street Side ND
F5-012 HWS-2 Black 6" Pipe Run (Insulation)Fifth Floor/Penthouse South Church Street Side 4% Amosite and 3% Chrysotile
F5-013 HWS-2 Black 6" Pipe Run (Wrap)Fifth Floor/Penthouse South Church Street Side ND
F5-013 HWS-2 Black 6" Pipe Run (Insulation)Fifth Floor/Penthouse South Church Street Side 5% Amosite and 3% Chrysotile
F5-014 CHWR Blue 18" Pipe Run (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-015 CHWR Blue 18" Pipe Run (Insulation)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-016 CHWS Blue 12" Pipe Run (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-016 CHWS Blue 12" Pipe Run (Felt)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-017 CHWR Blue 12" Pipe Run (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-017 CHWR Blue 12" Pipe Run (Felt)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-018 HWR-2 Black 12" Pipe Run (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-018 HWR-2 Black 12" Pipe Run (Insulation)Fifth Floor/Penthouse West Stonewall Street Side 4% Amosite and 3% Chrysotile
F5-019 CHWS Blue 3" Pipe Elbow (Wrap)Fifth Floor/Penthouse South Church Street Side ND
F5-019 CHWS Blue 3" Pipe Elbow (Insulation)Fifth Floor/Penthouse South Church Street Side <1% Amosite
F5-020 HWR-2 Black 6" Pipe Elbow (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-020 HWR-2 Black 6" Pipe Elbow (Gray Insulation)Fifth Floor/Penthouse West Stonewall Street Side 50% Chrysotile
F5-020 HWR-2 Black 6" Pipe Elbow (White Insulation)Fifth Floor/Penthouse West Stonewall Street Side 10% Amosite and 3% Chrysotile
F5-021 HWS Black 6" Pipe Elbow (Gray Insulation)Fifth Floor/Penthouse West Stonewall Street Side 60% Chrysotile
F5-021 HWS Black 6" Pipe Elbow (White Insulation) Fifth Floor/Penthouse West Stonewall Street Side 8% Amosite and 3% Chrysotile
F5-022 HWR Blue 8" Pipe Elbow (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-022 HWR Blue 8" Pipe Elbow (Insulation)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-023 CHWS Blue 8" Pipe Elbow (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-023 CHWS Blue 8" Pipe Elbow (Insulation)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-024, F-027 12" Pipe Elbow (Wrap)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-024, F-027 12" Pipe Elbow (Insulation)Fifth Floor/Penthouse West Stonewall Street Side ND
F5-025, F5-026 Asphaltic Mastic Fifth Floor/Penthouse South Church Street Side 2% Chrysotile, and ND (Assumed Positive)
F5-028, F-029 2" DOM Pipe Elbow (Wrap)Fifth Floor/Penthouse Southwest Side ND
F5-028, F-029 2" DOM Pipe Elbow (Insulation)Fifth Floor/Penthouse Southwest Side ND
F5-030, F5-031 Chiller Wall and Door Caulk Fifth Floor/Penthouse Central Part 3% Chrysotile and Stop Positive
F5-032, F5-033 Mechanical Equipment Canvas Cover Fifth Floor/Penthouse Central Part ND
F5-034, F5-035 2" DOM Pipe Run (Wrap)Fifth Floor/Penthouse Southwest Side ND
F5-034, F5-035 2" DOM Pipe Run (Insulation)Fifth Floor/Penthouse Southwest Side ND
F5-036 CHWS Blue 4" Elbow (Wrap)Fifth Floor/Penthouse South Tryon Street Side ND
F5-036 CHWS Blue 4" Elbow (Insulation)Fifth Floor/Penthouse South Tryon Street Side 25% Chrysotile
F5-037 CHWR Blue 4" Elbow (Wrap)Fifth Floor/Penthouse South Tryon Street Side ND
F5-037 CHWR Blue 4" Elbow (Light Gray Insulation) Fifth Floor/Penthouse South Tryon Street Side 20% Chrysotile
F5-037 CHWR Blue 4" Elbow (Dark Gray Insulation) Fifth Floor/Penthouse South Tryon Street Side ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ResultLocation ObservedAreaHomogeneous MaterialBulk Sample
Table 7 - Basement Tunnel: Sampled Materials for Limited Asbestos Survey on June 19, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
T-001, T-002 Door Caulk Basement Tunnel Air Handler Room ND
T-003, T-004 Wall Caulk Basement Tunnel Air Handler Room 3% Chrysotile and Stop Positive
T-005, T-006 36" Pipe Run (Wrap)Basement Tunnel Air Handler Room ND
T-005, T-006 36" Pipe Run (Insulation/Felt/Black Layer)Basement Tunnel Air Handler Room ND
T-007, T008 1" Pipe Elbow (Wrap)Basement Tunnel Air Handler Room ND
T-007, T008 1" Pipe Elbow (Insulation)Basement Tunnel Air Handler Room <1% Amosite and <1% Amosite
T-009, T-010 30" Pipe Elbow (Wrap)Basement Tunnel Air Handler Room ND
T-009, T-010 30" Pipe Elbow (Insulation)Basement Tunnel Air Handler Room 2% Amosite and 50% Chrysotile
T-011, T-012 Cove Base Basement Tunnel Air Handler Room ND
T-011, T-012 Cove Base (Mastic)Basement Tunnel Air Handler Room ND
T-013, T-014 Drywall Basement Tunnel Air Handler Room ND
T-013, T-014 Drywall (Joint Compound)Basement Tunnel Air Handler Room ND
T-015, T-016 8" Pipe Run (Wrap)Basement Tunnel Air Handler Room ND
T-015, T-016 8" Pipe Run (Insulation)Basement Tunnel Air Handler Room 10% Amosite and 3-4% Chrysotile
T-017, T-018 Coating on Dryer Beads Basement Tunnel Air Handler Room ND
T-019, T-020 2'x2' Ceiling Tiles - Office Basement Tunnel Air Handler Room ND
T-021, T-022 2'x4' Ceiling Tiles - Tunnel Basement Tunnel Basement Tunnel ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ResultLocation ObservedAreaHomogeneous MaterialsBulk Samples
Table 8 - Warehouse: Sampled Materials for Limited Asbestos Survey on June 19, 2015, June 29, 2015, and July 1, 2015.
The Charlotte Observer
621 South Poplar Street (Charlotte Observer Warehouse)
Charlotte, North Carolina
WH-001, WH-002 Drywall Warehouse Warehouse ND
WH-001, WH-002 Drywall (Joint Compound)Warehouse Warehouse ND
WH-003, WH-004 Wall Caulk Warehouse Warehouse ND
WH-005, WH-006 12"x12" Black Floor Tile Warehouse East Office/Breakroom ND
WH-005, WH-006 12"x12" Black Floor Tile (Mastic)Warehouse East Office/Breakroom ND
WH-007, WH-008 12"x12" White Floor Tile Warehouse East Office/Breakroom ND
WH-007, WH-008 12"x12" White Floor Tile (Mastic)Warehouse East Office/Breakroom ND
WH-008 Leveler Warehouse East Office/Breakroom ND
WH-009, WH-010 Undersink Coating Warehouse East Office/Breakroom ND
WH-011, WH-012 2'x2' Ceiling Tiles - Office Warehouse East Office/Breakroom ND
WH-013 Drywall Warehouse West Breakroom ND
WH-013 Drywall (Joint Compound)Warehouse West Breakroom ND
WH-014, WH-015 Floor Caulk, Gray Warehouse Floor Joints ND
*WH-200, WH-201 HVAC Caulk, Gray Warehouse HVAC ND
**SH-001, SH-002 Shed - Roof Shingle Guard Shed Roof ND
**SH-003, SH-004 Shed - Window Caulk Guard Shed Window ND
**WHE-001, WHE-002 Exterior Window/Wall Caulk Warehouse (Exterior)Window/Wall ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
* Sampled on June 29, 2015
** Sampled on July 1, 2015
ResultLocation ObservedAreaHomogeneous MaterialBulk Sample
Table 9 - Exterior (Parking Area and Loading Dock): Sampled Materials for Limited Asbestos Survey on June 18, 19, and 29, 2015.
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
E-001, E-002 Side Building Caulk Exterior Parking Area ND
E-003, E-004 Exterior Window Caulk Exterior Parking Area <1% Chrysotile and <1% Chrysotile
E-005, E-006 Caulk Near Pebble Side Walk Exterior Parking Area ND
E-007, E-008 Caulk on Stone-Pebble Column Exterior Parking Area ND
E-009, E-010 Curb Caulk Exterior Parking Area ND
E-011, E-012 Wall Caulk, Main Building Exterior Parking Area ND
E-013, E-014 Access Road/Parking Lot Caulk Exterior Parking Area ND
E-015, E-016 Exterior Cover of Paper Chutes Exterior Loading Dock 2% Chrysotile and Stop Positive
* F1-017, F-018, F-019, and **D-1, 2, 3, 4 ,5 Surfacing Ceiling Texture - 2 Exterior Parking Area ND
E-017, E-018 Loading Dock Caulk Exterior Loading Dock ND
Notes:Bold = Asbestos Containing Material (ACM)
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
* Samples collected on June 18, 2015, collected with first floor samples on COC.
** Samples collected on June 29, 2015
ResultLocation ObseveredAreaBulk Sample Homogeneous Material
Table 10 - Identified ACM and Estimated Quantities
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
B-008, B-009 12" x 12" Off White Floor Tile Basement Office and Facilities Area 2% Chrysotile and Stop Positive NF
640 sf
B-008 12" x 12" Off White Floor Tile (Mastic) Basement Office and Facilities Area 5% Chrysotile and Stop Positive NF
640 sf
B-026, B-027, B-028 6" Pipe Run (Insulation) Through Out Building Air Handler 10% Amosite 3% Chrysotile and Stop Positive F
6000 lf
B-029, B-030, B-031 6" Pipe Elbow Through Out Building Air Handler 2% Amosite and Stop Positive F
60
B-032, B-033 12"x12" Off White Floor Tile (Black Mastic) Basement Copy Center 5% Chrysotile and Stop Positive NF
400 sf
B-032, B-033 12"x12" Off White Floor Tile (Tile) Basement Copy Center 2% Chrysotile and Stop Positive NF
400 sf
B-032, B-033 12"x12" Off White Floor Tile (Clear Mastic) Basement Copy Center ND (For abatement purposes, assumed positive by
contact with ACM layer)
NF
400 sf
B-049, B-050 9"x9" Floor Tile (Mastic) Basement Telephone Room 5% Chrysotile and Stop Positive NF
500 sf
B-049, B-050 9"x9" Floor Tile Basement Telephone Room ND (For abatement purposes, assumed positive by
contact with ACM layer)
NF
500 sf
B-051, B-052 12"x12" White Floor Tile Basement Telephone Room 4% Chrysotile and Stop Positive NF
500 sf
B-051, B-052 12"x 12" White Floor Tile (Mastic) Basement Telephone Room 8% Chrysotile and Stop Positive NF
500 sf
B-059, B-060 Carpet Mastic Tan/Black Basement Facilities Maitenance 2% Chrysotile and Stop Positive NF
300 sf
B-068, B-069 Brown Linoleum Basement Reel Room, Mezzanine Bathrooms 10% Chrysotile and Stop Positive NF
250 sf
B-074, B-075 # Floor Coating, Black Basement, Second,Third
Floor
Flooring <1% Chrysotile (See #, Therefore considered ACM) NF
7000 sf
B-076, B-077 Slate-Like Flooring Basement, Second,Third
Floor
Flooring 2% Chrysotile and Stop Positive NF
7000 sf
F1-005, F1-006, F1-007, F1-008, F1-
009, F1-010, F-011
Surfacing Ceiling Texture -1 First, Second, Third, and
Forth Floor
Lobby 5% Chrysotile and Stop Positive F
12400 sf
F2-027, F2-028, F2-029, F2-030, F2-031 Surfacing Ceiling Texture First, Second, Third, and
Forth Floor
Hall 3% Chrysotile and Stop Positive F
12400 sf
F2-032, F2-033 Black Window Caulk First, Second, and Third
Floor
Audience Development 3% Chrysotile and Stop Positive NF
30,000 lf
F2-036, F2-037 12"x12" Tan w/ White Flecks Floor Tile
(Mastic)
Second Floor Audience Development, Vaults 3% Chrysotile and Stop Positive NF
80 sf
F2-036, F2-037 12"x12" Tan w/ White Flecks Floor Tile Second Floor Audience Development, Vaults ND (For abatement purposes, assumed positive by
contact with ACM layer)
NF
80 sf
F2-042, F2-043 HVAC Caulk, Black Throughout Building Mechanical Room 4% Chrysotile and Stop Positive NF
100 lf
F3-001, F3-002, F3-003 Floor Coating, Black Basement, Second, Third
Floor
Mail Room 2% Chrysotile and Stop Positive NF
7000 sf
F3-004, F3-005 Slate-like Flooring Basement, Second,Third
Floor
Mail Room 2% Chrysotile and Stop Positive NF
7000 sf
F3-015, F3-016 Carpet Mastic (Black Layer) Third Floor Mail Room, Offices 2% Chrysotile and Stop Positive NF
600 sf
F3-017, 3-A2, 3-B2 Caulk Between Wall and Stone - Pebble
Column (Patch)
Third Floor Mail Room Locker Room 3%-4% Chrysotile NF
10 lf
F3-018, F3-019 Black Window Caulk First, Second, and Third
Floor
Mail Room Locker Room 5% Chrysotile and Stop Positive NF
30,000 lf
F3-020, F3-021 Brown Linoleum Third Floor Mail Room Locker Room 2% Chrysotile and Stop Positive NF
800 sf
F3-037, F3-038 Dark Brown w/ Stone Design Linoleum Third Floor Hall 25% Chrysotile and Stop Positive NF
4200 sf
F3-045, F3-046 12"x12" White w/ Brown Flecks Floor Tile Third Floor A/P 3% Chrysotile and Stop Positive NF
800 sf
F3-047, F3-048, F3-049, F3-050, F3-051 Surfacing Ceiling Texture First, Second, Third, and
Forth Floor
Hall 4% Chrysotile and Stop Positive F
12400 sf
F4-012, F4-013, F4-014, F4-015, F4-016 Surfacing Ceiling Texture First, Second, Third, and
Forth Floor
Hall 3% Chrysotile and Stop Positive F
12400 sf
F4-036, F4-037 Under Sink Spray Fourth Floor Imaging 4% Chrysotile and Stop Positive NF
5 sf
F5-001, F5-002 Gray/Tan Caulk Fifth Floor/Penthouse Elevator Equipment <1% Chrysotile and 3% Chrysotile NF
100 lf
F5-011 HWR Black 12" Pipe Run (Insulation) Fifth Floor/Penthouse South Church Street Side of Penthouse5% Amosite and 3% Chrysotile F
6000 lf
F5-012 HWS-2 Black 6" Pipe Run (Insulation) Through Out Building South Church Street Side of Penthouse4% Amosite and 3% Chrysotile F
6000 lf
F5-013 HWS-2 Black 6" Pipe Run (Insulation) Through Out Building West Stonewall Street Side of Penthous5% Amosite and 3% Chrysotile F
6000 lf
F5-018 HWR-2 Black 12" Pipe Run (Insulation) Through Out Building West Stonewall Street Side of Penthous4% Amosite and 3% Chrysotile F
6000 lf
F5-020 HWR-2 Black 6" Pipe Elbow (Gray) Through Out Building West Stonewall Street Side of Penthous50% Chrysotile F
60
F5-020 HWR-2 Black 6" Pipe Elbow (White) Through Out Building West Stonewall Street Side of Penthous10% Amosite and 3% Chrysotile F
60
F5-021 HWS Black 6" Elbow (Gray) Through Out Building West Stonewall Street Side of Penthous60% Chrysotile F
60
F5-021 HWS Black 6" Pipe Elbow (White) Through Out Building West Stonewall Street Side of Penthous8% Amosite and 3% Chrysotile F
60
F5-025, F5-026 Asphaltic Mastic Fifth Floor/Penthouse South Church Street Side of Penthouse 2% Chrysotile, and ND (Assumed Positive)NF
500 lf
F5-030, F5-031 Chiller Wall and Door Caulk Fifth Floor/Penthouse Central Part of Penthouse 3% Chrysotile and Stop Positive NF
2,500 lf
F5-036 CHWS Blue 4" Pipe Elbow (Insulation) Through Out Building South Church Street Side of Penthouse25% Chrysotile F
60
F5-037 CHWR Blue 4" Pipe Elbow (Light Gray
Insulation)
Through Out Building South Tryon Street Side of Penthouse 20% Chrysotile F
60
T-003, T-004 Wall Caulk Tunnel Air Handler Room 3% Chrysotile and Stop Positive NF
500 lf
T-009, T-010 30" Pipe Elbow (Insulation) Tunnel Air Handler Room 2% Amosite and 50% Chrysotile F
60
T-015, T-016 8" Pipe Run (Insulation) Tunnel Air Handler Room 10% Amosite and 3%-4% Chrysotile F
4000
E-015, E-016 Covers of Paper Chutes Exterior Loading Dock 2% Chrysotile and Stop Positive F
600 sf
Notes: Bold = Asbestos Containing Material (ACM) and assumed ACM
Samples analyzed for asbestos by Polarized Light Microscopy (PLM)
ND = No Asbestos Detected
Abatement Contractors are responsible for verifying ands/or providing the actual quanties present.
# Material observed in another location as ACM, therefore considered ACM
Bulk Sample Estimated
Quantity
Friable
or Non-ResultLocation ObservedAreaHomogeneous Material
ATTACHMENT 2
FIGURES
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 1A
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Basement
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
034
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
ACM and Non-ACM TSI
Large diameter (fiberglass-insulated (non-
ACM) metal pipe, installed after 1971
Pre-1971
Construction Section
Air Handler Room Building Services
Reel Room
Print Area
Old Print
Area
Machine
Shop
Electric
Shop
Facilities
Maintenance
Dead File Room
Copy
Center
002 Bulk Asbestos Sample Number
035, 036
037, 038
048
047
045
046 059
060
057, 058
053 054
055, 056
049
050 052 051
044
039,040
043
041, 042
032
033
005
015, 016, 017, 018,
019, 020
(6” Pipe Run Cover)
022 (2” Pipe Run Cover)
021 (4’ Pipe Run Cover)
029, 030, 031
(6” Pipe Elbow)
026, 027, 028
023, 024, 025
(2” Pipe Elbows)
013
014
012**
002
011** 010**
004
001
007
009
003
008
006
Sample 010, of Bulk samples
010, 011, 012, recomposited
as Drywall System and was
found by PLM analysis to be
Non-ACM; however, OSHA
regulations shall apply
010**
All Sample IDs begin with “B”
Main run of
ACM and Non-
ACM TSI
(multiple pipes
of multiple
diameters)
Review Tables for Overlapping HAs that may not be
identified in collected samples from this functional
space as ACM.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 1B
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Basement Level of Reel Room
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
N
066, 067
002 Bulk Sample Number
Sample Location
002 Bulk Asbestos Sample Number
ACM Sample Location
All Sample IDs begin with “B”
S
o
u
t
h
C
h
u
r
c
h
S
t
r
e
e
t
REEL ROOM
061
062
063
064, 065
Main run of ACM and non
ACM TSI (multiple pipes
of multiple diameters) ACM and Non ACM TSI
Review Tables for Overlapping HAs that may
not be identified in collected samples from this
functional space as ACM.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 2
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – First Floor, includes Parking Deck
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
045
Mezzanine
Mezzanine-
Bathrooms
B-068, 069
B-071
B-070
B-072, 073
Mezzanine-First Aid Room
All Interior Lobby/Hall Sample IDs begin with
“F1”
All Exterior Sample IDs from Parking Area
begin with “E”, except Surface Ceiling Texture
samples from Parking Area, which are F1-017,
-018, and -019, and D-1 through 5.
002 Bulk Asbestos Sample Number
All Interior Reel Room Mezzanine Level
Sample IDs begin with “B”
F1-012, 015
F1-014
F1-013, 016
Freight Elevator Elevators
E-001, 002
E-006 E-005
E-008
E-003, 004
E-007
D-001
D-002
D-003
D-004
D-005
F1-17
F1-18
F1-19
E-009, 010
E-011,
012
E-013,
014
F1-006, 009, 011
F1-005, 007, 008
F1-010
076, 077 Review Tables for Overlapping HAs that may
not be identified in collected samples from
this functional space as ACM.
F1-*003, * 004
F1-*001, *002
* B-074
* B-075
* Contains <%1 ACM, by PLM analysis and is
therefore non-ACM; however, OSHA regulations
shall apply.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 3
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Second Floor, Includes Loading Dock
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
All Sample IDs begin with “F2”, except bulk
samples collected from the exterior loading
dock area, which are E-015, 016
002 Bulk Asbestos Sample Number
040, 041
Freight Elevator
Elevators
Escalators
Audio Development Finance
Training
Room
E-015 E-016
042
043
024, 025, 026
023
021 022
031
030
027 028
029
017
005
018
034
036, 037
035
033 032
Vault
004
002, 013
006
011, 019
010, 012
008,
009
007
001, 003,
014, 015,
016, 020
038, 039
2-A1, 2-B1
2-A2, 2-B2
Vault
Review Tables for Overlapping HAs that may
not be identified in collected samples from
this functional space as ACM.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 4
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Third Floor
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
All Sample IDs begin with “F3”, except
bulk samples from conveyor belt (CO3-
200 and CO2-201), and caulk samples (3-
A1, 3-A2, 3-B1, 3-B2).
002 Bulk Asbestos Sample Number
001
A/P
Auditorium
Storage Room
Locker Room
Operations
Freight Elevator
Elevators
002 003
018, 019 006
007
014
008
011, 012
013 005
009
020, 021
017
022, 025 023, 026 024, 035
036
029
027, 031
028, 030
032
033,
034
039, 040
042 041
037 038
049
048
047
051
050
043, 044
045
046
004
010
015
016
CO3-200 CO3-201
3-A2, 3-B2 3-A1, 3-B1
Review Tables for Overlapping HAs that
may not be identified in collected samples
from this functional space as ACM.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 5
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Fourth Floor
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
All Sample IDs begin with “F4
002 Bulk Asbestos Sample Number
Library
Imaging
001, 003, 007
014
013
012 015
016
005, 006
028, 029
002, 004,
008, 024
025
026
027
009, 032, 033
042
043
010
011, 030, 031
017, 018, 019
020, 021
022
023
Breakroom
036, 037
034
035 038
039
040, 041
Freight Elevator
Elevators
Review Tables for Overlapping HAs that
may not be identified in collected samples
from this functional space as ACM.
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 6
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Fifth Floor, includes Rooftop Elevator Rooms and
Mechanical Penthouse
600 South Tryon Street
Charlotte, North Carolina
S
o
u
t
h
T
r
y
o
n
S
t
r
e
e
t
West Stonewall Street
N
002 Bulk Sample Number
Sample Location
ACM Sample Location
All Sample IDs begin with “F5”, except
Bulk samples of Roof Silver Water Barrier-
Surface Layer, as R-001, 002, 003
002 Bulk Asbestos Sample Number
Main Elevator Equipment
Room above Mechanical
Penthouse
Freight Elevator
Equipment Room
Elevators
Freight
Elevator
025, 026
007, 008,
009, 010,
012, *019,
025, 026
R-001
R-002
R-003
001 002
033
032 031
030
036, 037
014, 015,
016, 017,
022, 023,
024, 027
028, 029,
034, 035
006
005
004
003
018, 020,
021,
011, 013
Review Tables for Overlapping HAs that
may not be identified in collected samples
from this functional space as ACM.
* Contains <%1 ACM, by PLM analysis and is
therefore non-ACM; however, OSHA regulations
shall apply.
7606 Whitehall Executive Center Dr.
Suite 800
Charlotte, NC 28273
(704) 529-3200
ASBESTOS SURVEY
SAMPLE LOCATION MAP – FIG 7
Map based on site plans provided by the Charlotte Observer
Charlotte Observer – Basement Tunnel
601 South Tryon Street- 621 South Poplar Street
Charlotte, North Carolina
W
e
s
t
S
t
o
n
e
w
a
l
l
S
t
r
e
e
t
N
South Church Street
002 Bulk Sample Number
002 Bulk Asbestos Sample Number
ACM Sample Location
All Sample IDs begin with “T”
South Church Street (above)
Sample Location
002
004 001 011, 013
012, 014
006 005
017, 018
015, 016 019 020
021, 022
009, 010
003
ACM and non-ACM TSI
Main run of ACM and
Non-ACM TSI
(multiple pipes of
multiple diameters)
* Contains <%1 ACM, by PLM analysis
and is therefore non-ACM; however,
OSHA regulations shall apply.
Review Tables for Overlapping HAs that
may not be identified in collected samples
from this functional space as ACM.
*007, *008
ASBESTOS SURVEY SAMPLE LOCATION MAP – FIG 8
Map based on site plans provided by the Charlotte Observer
Charlotte Observer - Warehouse
621 South Poplar Street
Charlotte, North Carolina
South Church Street
W
e
s
t
S
t
o
n
e
w
a
l
l
S
t
r
e
e
t
South Poplar Street
N
009, 010
005, 007, 011
006, 008, 012
Sampled as part
of “Basement
Tunnel” area.
See Figure 7.
001, 004 002, 003
014
013
015
200, 201 WHE-001, 002
SH-001, 002 SH-003, 004
Guard shed, above in
parking deck
002 Bulk Sample Number
Sample Location
002 Bulk Asbestos Sample Number
ACM Sample Location
All Sample IDs begin with WH, except WHE
001 and 002, and SH-001 through 004
Review Tables for Overlapping HAs that may
not be identified in collected samples from
this functional space as ACM.
ATTACHMENT 3
ANALYTICAL DOCUMENTATION
OrderID: 411504177
Page 1 Of 3
OrderID: 411504177
Page 2 Of 3
OrderID: 411504177
Page 3 Of 3
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-001-Cove Base
411504177-0001
Cove Base &
Mastic - Building
Service
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-001-Mastic
411504177-0001A
Cove Base &
Mastic - Building
Service
Brown/Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-002-Cove Base
411504177-0002
Cove Base &
Mastic - Building
Service
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-002-Mastic
411504177-0002A
Cove Base &
Mastic - Building
Service
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-003
411504177-0003
1'x1' CT, Rough -
Building Service
Gray/White None Detected
Fibrous
Heterogeneous
Min. Wool80%
Cellulose3%
Non-fibrous (other)17%
B-004
411504177-0004
1'x1' CT, Rough -
Building Service
Gray None Detected
Fibrous
Homogeneous
Min. Wool45%
Cellulose30%
Non-fibrous (other)25%
B-005
411504177-0005
Plaster - Building
Service/ Hall
Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
B-006
411504177-0006
Plaster - Building
Service/ Hall
Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
1Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-007
411504177-0007
Plaster - Building
Service/ Hall
Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
B-008-Floor Tile
411504177-0008
12"x12" Off-White
w/ Tan/ Brown
Smears VFT -
Building Service
White
Non-Fibrous
Homogeneous
Chrysotile2%Ca Carbonate30%
Non-fibrous (other)68%
B-008-Mastic
411504177-0008A
12"x12" Off-White
w/ Tan/ Brown
Smears VFT -
Building Service
Black
Non-Fibrous
Homogeneous
Chrysotile5%Ca Carbonate30%
Non-fibrous (other)65%
B-009-Floor Tile
411504177-0009
12"x12" Off-White
w/ Tan/ Brown
Smears VFT -
Building Service
Stop Positive (Not Analyzed)
B-009-Mastic
411504177-0009A
12"x12" Off-White
w/ Tan/ Brown
Smears VFT -
Building Service
Stop Positive (Not Analyzed)
B-010-Drywall
411504177-0010
Drywall & Joint
Compound -
Building Service
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose10%Non-fibrous (other)90%
B-010-Joint
Compound
411504177-0010A
Drywall & Joint
Compound -
Building Service
White
Non-Fibrous
Homogeneous
Chrysotile2%Ca Carbonate30%
Non-fibrous (other)68%
2Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-010-Composite
411504177-0010B
Drywall & Joint
Compound -
Building Service
Gray/Tan
Composite analysis.
Fibrous
Homogeneous
Chrysotile<1%Cellulose5%Ca Carbonate25%
Non-fibrous (other)70%
B-011-Drywall
411504177-0011
Drywall & Joint
Compound -
Building Service
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose10%Non-fibrous (other)90%
B-011-Joint
Compound
411504177-0011A
Drywall & Joint
Compound -
Building Service
Stop Positive (Not Analyzed)
B-012-Drywall
411504177-0012
Drywall & Joint
Compound -
Building Service
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose8%Non-fibrous (other)92%
B-012-Joint
Compound
411504177-0012A
Drywall & Joint
Compound -
Building Service
Stop Positive (Not Analyzed)
B-013-Mastic
411504177-0013
Valve Insulation -
Air Handler
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate20%
Non-fibrous (other)80%
B-013-Wrap
411504177-0013A
Valve Insulation -
Air Handler
White/Silver None Detected
Fibrous
Homogeneous
Cellulose70%Non-fibrous (other)30%
B-013-Insulation
411504177-0013B
Valve Insulation -
Air Handler
Yellow None Detected
Fibrous
Homogeneous
Cellulose99%Non-fibrous (other)1%
3Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-014-Mastic
411504177-0014
Valve Insulation -
Air Handler
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate25%
Non-fibrous (other)75%
B-014-Wrap
411504177-0014A
Valve Insulation -
Air Handler
Tan None Detected
Fibrous
Homogeneous
Cellulose75%Non-fibrous (other)25%
B-014-Insulation
411504177-0014B
Valve Insulation -
Air Handler
Yellow None Detected
Fibrous
Homogeneous
Glass98%Non-fibrous (other)2%
B-015
411504177-0015
6" Pipe Run
Covers - Hall
Gray/Tan/Silver None Detected
Fibrous
Heterogeneous
Cellulose40%
Glass5%
Non-fibrous (other)55%
B-016
411504177-0016
6" Pipe Run
Covers - Hall
Tan/White None Detected
Fibrous
Heterogeneous
Cellulose60%Non-fibrous (other)40%
B-017
411504177-0017
6" Pipe Run
Covers - Hall
Tan/White/Silver None Detected
Fibrous
Heterogeneous
Cellulose70%
Glass5%
Non-fibrous (other)25%
B-018
411504177-0018
6" Pipe Run
Covers - Hall
Tan/White/Silver None Detected
Fibrous
Heterogeneous
Cellulose70%
Glass5%
Non-fibrous (other)25%
B-019
411504177-0019
6" Pipe Run
Covers - Hall
Tan/White None Detected
Fibrous
Homogeneous
Cellulose75%
Glass4%
Non-fibrous (other)21%
4Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-020
411504177-0020
6" Pipe Run
Covers - Hall
Tan/White None Detected
Fibrous
Homogeneous
Cellulose75%
Glass3%
Non-fibrous (other)22%
B-021
411504177-0021
4" Pipe Run Cover Tan/White/Silver None Detected
Fibrous
Heterogeneous
Cellulose60%
Glass5%
Non-fibrous (other)35%
B-022
411504177-0022
2" Pipe Run
Cover - Basement
Hall
Tan/White None Detected
Fibrous
Homogeneous
Cellulose70%
Glass3%
Non-fibrous (other)27%
B-023
411504177-0023
2" Elbows - Air
Handler
Gray None Detected
Non-Fibrous
Homogeneous
Min. Wool20%
Cellulose2%
Ca Carbonate20%
Non-fibrous (other)58%
B-024
411504177-0024
2" Elbows - Air
Handler
Gray None Detected
Non-Fibrous
Homogeneous
Min. Wool20%
Cellulose2%
Ca Carbonate10%
Non-fibrous (other)68%
B-025
411504177-0025
2" Elbows - Air
Handler
Gray None Detected
Fibrous
Homogeneous
Min. Wool20%
Cellulose5%
Ca Carbonate5%
Non-fibrous (other)70%
B-026-Wrap
411504177-0026
6" Pipe Runs - Air
Handler
White None Detected
Non-Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
B-026-Insulation
411504177-0026A
6" Pipe Runs - Air
Handler
Gray
Non-Fibrous
Homogeneous
Amosite10%
Chrysotile3%
Non-fibrous (other)87%
5Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-027-Wrap
411504177-0027
6" Pipe Runs - Air
Handler
White None Detected
Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
B-027-Insulation
411504177-0027A
6" Pipe Runs - Air
Handler
Stop Positive (Not Analyzed)
B-028-Wrap
411504177-0028
6" Pipe Runs - Air
Handler
Tan None Detected
Fibrous
Homogeneous
Cellulose98%Non-fibrous (other)2%
B-028-Insulation
411504177-0028A
6" Pipe Runs - Air
Handler
Stop Positive (Not Analyzed)
B-029
411504177-0029
6" Pipe Elbows -
Air Handler
Gray
Non-Fibrous
Homogeneous
Amosite2%Min. Wool30%
Cellulose2%
Ca Carbonate15%
Non-fibrous (other)51%
B-030
411504177-0030
6" Pipe Elbows -
Air Handler
Stop Positive (Not Analyzed)
B-031
411504177-0031
6" Pipe Elbows -
Air Handler
Stop Positive (Not Analyzed)
B-032-Clear Mastic
411504177-0032
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Clear None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
6Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-032-Floor Tile
411504177-0032A
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Tan
Non-Fibrous
Homogeneous
Chrysotile2%Ca Carbonate30%
Non-fibrous (other)68%
B-032-Black Mastic
411504177-0032B
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Black
Non-Fibrous
Homogeneous
Chrysotile5%Non-fibrous (other)95%
B-033-Clear Mastic
411504177-0033
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Tan/Clear None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
B-033-Floor Tile
411504177-0033A
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Stop Positive (Not Analyzed)
B-033-Black Mastic
411504177-0033B
Carpet Mastic -
VFT below -
12"x12" Off-White
w/ Brown Smears
Stop Positive (Not Analyzed)
B-034-Drywall
411504177-0034
Drywall/ JC - UPS
Room
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose10%Non-fibrous (other)90%
B-034-Joint
Compound
411504177-0034A
Drywall/ JC - UPS
Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate40%
Non-fibrous (other)60%
7Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-035
411504177-0035
2'x2' CT - UPS
Room
Gray/White None Detected
Non-Fibrous
Homogeneous
Cellulose60%
Min. Wool8%
Perlite10%
Non-fibrous (other)22%
B-036
411504177-0036
2'x2' CT - UPS
Room
Gray/White None Detected
Fibrous
Homogeneous
Cellulose55%
Min. Wool5%
Perlite10%
Non-fibrous (other)30%
B-037-Black Layer
411504177-0037
Caulk Patch -
Electrica
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-037-Gray Layer
411504177-0037A
Caulk Patch -
Electrica
Gray None Detected
Non-Fibrous
Homogeneous
Fibrous (other)3%Ca Carbonate20%
Non-fibrous (other)77%
B-037-White Layer
411504177-0037B
Caulk Patch -
Electrica
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
B-038-Black Layer
411504177-0038
Caulk Patch -
Electrica
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-038-Gray Layer
411504177-0038A
Caulk Patch -
Electrica
Gray None Detected
Non-Fibrous
Homogeneous
Fibrous (other)3%Ca Carbonate10%
Non-fibrous (other)87%
B-038-White Layer
411504177-0038B
Caulk Patch -
Electrica
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate8%
Non-fibrous (other)92%
8Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-039
411504177-0039
2'x4' CT -
Mechanic Room
Office
Gray/White None Detected
Fibrous
Heterogeneous
Cellulose60%
Min. Wool8%
Perlite15%
Non-fibrous (other)17%
B-040
411504177-0040
2'x4' CT -
Mechanic Room
Office
Gray/White None Detected
Fibrous
Homogeneous
Cellulose55%
Min. Wool8%
Perlite10%
Non-fibrous (other)27%
B-041
411504177-0041
1'x1' CT, Smooth -
Mechanic Room
Office
Tan/White None Detected
Fibrous
Heterogeneous
Cellulose99%Non-fibrous (other)1%
B-042
411504177-0042
1'x1' CT, Smooth -
Mechanic Room
Office
Tan None Detected
Fibrous
Homogeneous
Cellulose99%Non-fibrous (other)1%
B-043
411504177-0043
Carpet Mastic -
Mechanical Room
Office
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose2%Ca Carbonate10%
Non-fibrous (other)88%
B-044
411504177-0044
Carpet Mastic -
Mechanical Room
Office
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-045
411504177-0045
HVAC Caulk,
Gray - Dead Files
Storage
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose2%Ca Carbonate10%
Non-fibrous (other)88%
B-046
411504177-0046
HVAC Caulk,
Gray - Dead Files
Storage
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
9Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-047
411504177-0047
Black Sealant -
Dead Files Storage
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
B-048
411504177-0048
Black Sealant -
Dead Files Storage
Black None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-049-Floor Tile
411504177-0049
9x9 White w/ Gray
Smear -
Telephone Room
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
B-049-Mastic
411504177-0049A
9x9 White w/ Gray
Smear -
Telephone Room
Black
Non-Fibrous
Homogeneous
Chrysotile5%Non-fibrous (other)95%
B-050-Floor Tile
411504177-0050
9x9 White w/ Gray
Smear -
Telephone Room
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
B-050-Mastic
411504177-0050A
9x9 White w/ Gray
Smear -
Telephone Room
Stop Positive (Not Analyzed)
B-051-Floor Tile
411504177-0051
12x12 VFT Off-
White - Telephone
Room
White
Non-Fibrous
Homogeneous
Chrysotile4%Non-fibrous (other)96%
B-051-Mastic
411504177-0051A
12x12 VFT Off-
White - Telephone
Room
Black
Non-Fibrous
Homogeneous
Chrysotile8%Non-fibrous (other)92%
B-052-Floor Tile
411504177-0052
12x12 VFT Off-
White - Telephone
Room
Stop Positive (Not Analyzed)
10Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-052-Mastic
411504177-0052A
12x12 VFT Off-
White - Telephone
Room
Stop Positive (Not Analyzed)
B-053
411504177-0053
1'x1' CT, White,
Pin-Holed -
Telephone Room
Gray/White None Detected
Fibrous
Heterogeneous
Cellulose2%
Min. Wool80%
Non-fibrous (other)18%
B-054
411504177-0054
1'x1' CT, White,
Pin-Holed -
Telephone Room
Gray None Detected
Fibrous
Homogeneous
Min. Wool75%
Cellulose5%
Non-fibrous (other)20%
B-055
411504177-0055
1'x1' White,
Wavy - Telephone
Room
Tan/White None Detected
Fibrous
Heterogeneous
Glass99%Non-fibrous (other)1%
B-056
411504177-0056
1'x1' White,
Wavy - Telephone
Room
Yellow None Detected
Fibrous
Homogeneous
Glass99%Non-fibrous (other)1%
B-057
411504177-0057
HVAC Damper -
Air Handler
Room - C Stairwell
Gray None Detected
Fibrous
Heterogeneous
Glass15%Ca Carbonate5%
Non-fibrous (other)80%
B-058
411504177-0058
HVAC Damper -
Air Handler
Room - C Stairwell
Black None Detected
Fibrous
Homogeneous
Glass15%Non-fibrous (other)85%
B-059
411504177-0059
Carpet Mastic -
Facilities Building
Tan/Black
Non-Fibrous
Homogeneous
Chrysotile2%Ca Carbonate5%
Non-fibrous (other)93%
B-060
411504177-0060
Carpet Mastic -
Facilities Building
Stop Positive (Not Analyzed)
11Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-061
411504177-0061
12" Metal Cover
Pipe Insulation -
Reel Room
White None Detected
Non-Fibrous
Homogeneous
Cellulose5%
Glass2%
Non-fibrous (other)93%
B-062
411504177-0062
12" Metal Cover
Pipe Insulation -
Reel Room
White None Detected
Non-Fibrous
Homogeneous
Cellulose3%
Glass2%
Non-fibrous (other)95%
B-063
411504177-0063
12" Metal Cover
Pipe Insulation -
Reel Room
White None Detected
Fibrous
Homogeneous
Cellulose3%Ca Carbonate5%
Non-fibrous (other)92%
B-064
411504177-0064
HVAC Caulk,
Tan - Reel Room
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
B-065
411504177-0065
HVAC Caulk,
Tan - Reel Room
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-066-Skim Coat
411504177-0066
Plaster on Air
Duct - Reel Room
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
B-066-Rough Coat
411504177-0066A
Plaster on Air
Duct - Reel Room
Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
B-067-Skim Coat
411504177-0067
Plaster on Air
Duct - Reel Room
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
12Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-067-Rough Coat
411504177-0067A
Plaster on Air
Duct - Reel Room
Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
B-068-Flooring
411504177-0068
Brown Linoleum -
Reel Room Mez -
Bathrooms
Gray/Tan
Fibrous
Heterogeneous
Chrysotile10%Cellulose5%Non-fibrous (other)85%
B-068-Mastic
411504177-0068A
Brown Linoleum -
Reel Room Mez -
Bathrooms
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-069-Flooring
411504177-0069
Brown Linoleum -
Reel Room Mez -
Bathrooms
Stop Positive (Not Analyzed)
B-069-Mastic
411504177-0069A
Brown Linoleum -
Reel Room Mez -
Bathrooms
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
B-070
411504177-0070
2'x4' CT, White,
Grooved, Pin-
Holed - Mez Office
Gray/White None Detected
Fibrous
Heterogeneous
Cellulose60%
Min. Wool5%
Perlite10%
Non-fibrous (other)25%
B-071
411504177-0071
2'x4' CT, White,
Grooved, Pin-
Holed - Mez Office
Gray None Detected
Fibrous
Homogeneous
Cellulose50%
Min. Wool5%
Perlite15%
Non-fibrous (other)30%
B-072-Flooring
411504177-0072
Blue Linoleum w/
Stone Design -
First Aid
Gray None Detected
Fibrous
Heterogeneous
Cellulose10%
Glass1%
Non-fibrous (other)89%
13Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504177
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Basement
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/1/2015Analysis Date:
6/17/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
B-072-Mastic
411504177-0072A
Blue Linoleum w/
Stone Design -
First Aid
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-073-Flooring
411504177-0073
Blue Linoleum w/
Stone Design -
First Aid
Gray None Detected
Fibrous
Homogeneous
Cellulose10%
Glass1%
Non-fibrous (other)89%
B-073-Mastic
411504177-0073A
Blue Linoleum w/
Stone Design -
First Aid
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
B-074
411504177-0074
Floor Coating,
Black
Black
Fibrous
Homogeneous
Chrysotile<1%Cellulose10%Quartz5%
Non-fibrous (other)85%
B-075
411504177-0075
Floor Coating,
Black
Black
Fibrous
Homogeneous
Chrysotile<1%Cellulose8%Non-fibrous (other)92%
B-076
411504177-0076
Slate-Like Flooring Black
Non-Fibrous
Homogeneous
Chrysotile2%Cellulose10%Quartz5%
Non-fibrous (other)83%
B-077
411504177-0077
Slate-Like Flooring Stop Positive (Not Analyzed)
14THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 7/2/2015 8:02:26 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Report Amended: 07/02/2015 08:02:26 Replaces the Inital Report 06/23/2015 18:08:23. Reason Code: Client-Samples Added
Erin Guzowski (20)
Eric Loomis (58)
Maria Cao (17)
OrderID: 411504232
Page 1 Of 2
OrderID: 411504232
Page 2 Of 2
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504232
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Basement Tunnel #1
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
T-001
411504232-0001
Door Caulk/ Air
Handler Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-002
411504232-0002
Door Caulk/ Air
Handler Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-003
411504232-0003
Wall Caulk/ Air
Handler Room
White
Non-Fibrous
Homogeneous
Chrysotile3%Ca Carbonate10%
Non-fibrous (other)87%
T-004
411504232-0004
Wall Caulk/ Air
Handler Room
Stop Positive (Not Analyzed)
T-005-Wrap
411504232-0005
36" Pipe Run/ Air
Handler Room
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-005-Insulation
411504232-0005A
36" Pipe Run/ Air
Handler Room
Gray None Detected
Fibrous
Homogeneous
Cellulose2%
Min. Wool30%
Ca Carbonate5%
Non-fibrous (other)63%
T-006-Wrap
411504232-0006
36" Pipe Run/ Air
Handler Room
Beige None Detected
Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
T-006-Felt
411504232-0006A
36" Pipe Run/ Air
Handler Room
Black None Detected
Fibrous
Homogeneous
Cellulose60%Non-fibrous (other)40%
1Test Report PLM-7.28.9 Printed: 6/25/2015 8:08:17 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/25/2015 08:08:17
Eric Loomis (17)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504232
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Basement Tunnel #1
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
T-006-Black Layer
411504232-0006B
36" Pipe Run/ Air
Handler Room
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
T-007-Wrap
411504232-0007
1" Pipe Elbow/ Air
Handler Room
None Detected
Non-Fibrous
Homogeneous
Cellulose40%Non-fibrous (other)60%
T-007-Insulation
411504232-0007A
1" Pipe Elbow/ Air
Handler Room
Gray
Non-Fibrous
Homogeneous
Amosite<1%Cellulose2%
Min. Wool40%
Non-fibrous (other)58%
T-008-Wrap
411504232-0008
1" Pipe Elbow/ Air
Handler Room
Beige None Detected
Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
T-008-Insulation
411504232-0008A
1" Pipe Elbow/ Air
Handler Room
Gray
Fibrous
Homogeneous
Amosite<1%Min. Wool35%Ca Carbonate5%
Non-fibrous (other)60%
T-009-Wrap
411504232-0009
30" Pipe Elbow White None Detected
Non-Fibrous
Homogeneous
Cellulose60%Non-fibrous (other)40%
T-009-Insulation
411504232-0009A
30" Pipe Elbow Gray
Non-Fibrous
Homogeneous
Amosite2%Min. Wool30%
Cellulose2%
Non-fibrous (other)66%
T-010-Wrap
411504232-0010
30" Pipe Elbow Beige None Detected
Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
2Test Report PLM-7.28.9 Printed: 6/25/2015 8:08:17 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/25/2015 08:08:17
Eric Loomis (17)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504232
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Basement Tunnel #1
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
T-010-Insulation
411504232-0010A
30" Pipe Elbow Gray
Fibrous
Homogeneous
Chrysotile50%Ca Carbonate5%
Non-fibrous (other)45%
T-011-Cove Base
411504232-0011
Cove Base &
Mastic
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-011-Mastic
411504232-0011A
Cove Base &
Mastic
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-012-Cove Base
411504232-0012
Cove Base &
Mastic
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-012-Mastic
411504232-0012A
Cove Base &
Mastic
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
T-013-Drywall
411504232-0013
Drywall & Joint
Compound
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose5%
Glass1%
Non-fibrous (other)94%
T-013-Joint
Compound
411504232-0013A
Drywall & Joint
Compound
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate40%
Non-fibrous (other)60%
T-014-Drywall
411504232-0014
Drywall & Joint
Compound
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose15%Non-fibrous (other)85%
3Test Report PLM-7.28.9 Printed: 6/25/2015 8:08:17 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/25/2015 08:08:17
Eric Loomis (17)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504232
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Basement Tunnel #1
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
T-014-Joint
Compound
411504232-0014A
Drywall & Joint
Compound
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
T-015-Wrap
411504232-0015
8" Pipe Run Gray/Tan/White None Detected
Fibrous
Heterogeneous
Cellulose60%Non-fibrous (other)40%
T-015-Insulation
411504232-0015A
8" Pipe Run White
Fibrous
Homogeneous
Amosite10%
Chrysotile3%
Ca Carbonate5%
Non-fibrous (other)82%
T-016-Wrap
411504232-0016
8" Pipe Run Beige None Detected
Fibrous
Homogeneous
Cellulose90%Non-fibrous (other)10%
T-016-Insulation
411504232-0016A
8" Pipe Run Gray
Fibrous
Homogeneous
Amosite10%
Chrysotile4%
Min. Wool5%Ca Carbonate5%
Non-fibrous (other)76%
T-017
411504232-0017
Coating on Dryer
Beads Equip. Air
Handle
Tan None Detected
Fibrous
Homogeneous
Min. Wool99%Non-fibrous (other)1%
T-018
411504232-0018
Coating on Dryer
Beads Equip. Air
Handle
Yellow None Detected
Fibrous
Homogeneous
Min. Wool95%Non-fibrous (other)5%
T-019
411504232-0019
2'x2' CT/ Air
Handler Office
Gray/White None Detected
Fibrous
Heterogeneous
Cellulose60%
Min. Wool8%
Perlite10%
Non-fibrous (other)22%
4Test Report PLM-7.28.9 Printed: 6/25/2015 8:08:17 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/25/2015 08:08:17
Eric Loomis (17)
Maria Cao (17)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504232
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Basement Tunnel #1
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
T-020
411504232-0020
2'x2' CT/ Air
Handler Office
Gray None Detected
Fibrous
Homogeneous
Cellulose60%
Min. Wool5%
Perlite10%
Non-fibrous (other)25%
T-021
411504232-0021
2'x4' CT Tunnel/
Tunnel Ceiling
Gray/White None Detected
Fibrous
Heterogeneous
Cellulose50%
Min. Wool5%
Perlite10%
Non-fibrous (other)35%
T-022
411504232-0022
2'x4' CT Tunnel/
Tunnel Ceiling
Gray None Detected
Fibrous
Homogeneous
Cellulose55%
Min. Wool5%
Perlite10%
Non-fibrous (other)30%
5THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/25/2015 8:08:17 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/25/2015 08:08:17
Eric Loomis (17)
Maria Cao (17)
OrderID: 411504233
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504233
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Building - Exterior
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
E-001
411504233-0001
Side Building
Caulk, Black/
Parking Area
Black None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
E-002
411504233-0002
Side Building
Caulk, Black/
Parking Area
Black None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
E-003
411504233-0003
Exterior Window
Caulk, White &
Gray/ Parking Area
Gray
Non-Fibrous
Homogeneous
Chrysotile<1%Ca Carbonate5%
Non-fibrous (other)95%
E-004
411504233-0004
Exterior Window
Caulk, White &
Gray/ Parking Area
Gray
Non-Fibrous
Homogeneous
Chrysotile<1%Ca Carbonate5%
Non-fibrous (other)95%
E-005
411504233-0005
Caulk near
Pebbles/
Expansion
Caulking/ Parking
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
E-006
411504233-0006
Caulk near
Pebbles/
Expansion
Caulking/ Parking
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate8%
Non-fibrous (other)92%
E-007
411504233-0007
Stone-Pebble
Column Caulk,
Metallic White/
Parking
Gray/Black None Detected
Fibrous
Homogeneous
Cellulose1%Non-fibrous (other)99%
E-008
411504233-0008
Stone-Pebble
Column Caulk,
Metallic White/
Parking
Gray/Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
1Test Report PLM-7.28.9 Printed: 6/24/2015 3:08:29 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 15:08:29
Erin Guzowski (8)
Maria Cao (9)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504233
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Building - Exterior
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
E-009
411504233-0009
Curb/ Expansion
Caulk, White-
Gray/ Parking Area
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
E-010
411504233-0010
Curb/ Expansion
Caulk, White-
Gray/ Parking Area
Gray None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
E-011
411504233-0011
Wall Caulk, White/
Parking Area
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
E-012
411504233-0012
Wall Caulk, White/
Parking Area
White None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate5%
Non-fibrous (other)95%
E-013
411504233-0013
Access Road/
Parking Lot Caulk,
Lt. Gray-White
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate5%
Non-fibrous (other)95%
E-014
411504233-0014
Access Road/
Parking Lot Caulk,
Lt. Gray-White
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
E-015
411504233-0015
Exterior Cover of
Paper Chute,
Silver-White
Gray
Fibrous
Homogeneous
Chrysotile2%Cellulose<1%Non-fibrous (other)98%
E-016
411504233-0016
Exterior Cover of
Paper Chute,
Silver-White
Stop Positive (Not Analyzed)
2Test Report PLM-7.28.9 Printed: 6/24/2015 3:08:29 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 15:08:29
Erin Guzowski (8)
Maria Cao (9)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504233
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Building - Exterior
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
E-017
411504233-0017
Loading Dock
Caulk, Black/
Loading Dock
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
E-018
411504233-0018
Loading Dock
Caulk, Black/
Loading Dock
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
3THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/24/2015 3:08:29 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 15:08:29
Erin Guzowski (8)
Maria Cao (9)
OrderID: 411504178
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504178
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - First Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F1-001
411504178-0001
Stone Wall Caulk -
Lobby
Gray
Fibrous
Homogeneous
Chrysotile<1%Ca Carbonate5%
Non-fibrous (other)95%
F1-002
411504178-0002
Stone Wall Caulk -
Lobby
Gray
Non-Fibrous
Homogeneous
Chrysotile<1%Non-fibrous (other)100%
F1-003
411504178-0003
Stone-Peddle
Column Caulk -
Lobby
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F1-004
411504178-0004
Stone-Peddle
Column Caulk -
Lobby
White None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F1-005
411504178-0005
Surfacing Ceiling
Texture-1 - Lobby
White
Fibrous
Homogeneous
Chrysotile5%Cellulose3%Ca Carbonate5%
Non-fibrous (other)87%
F1-006
411504178-0006
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
F1-007
411504178-0007
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
F1-008
411504178-0008
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
F1-009
411504178-0009
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
1Test Report PLM-7.28.9 Printed: 6/23/2015 4:00:24 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:00:24
Kristie Elliott (7)
Maria Cao (11)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504178
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - First Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F1-010
411504178-0010
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
F1-011
411504178-0011
Surfacing Ceiling
Texture-1 - Lobby
Stop Positive (Not Analyzed)
F1-012-Drywall
411504178-0012
Drywall & Joint
Compound - Hall
to Lobby
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose20%Non-fibrous (other)80%
F1-012-Joint
Compound
411504178-0012A
Drywall & Joint
Compound - Hall
to Lobby
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate20%
Non-fibrous (other)80%
F1-013-Drywall
411504178-0013
Drywall & Joint
Compound - Hall
to Lobby
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose20%Non-fibrous (other)80%
F1-013-Joint
Compound
411504178-0013A
Drywall & Joint
Compound - Hall
to Lobby
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F1-014-Drywall
411504178-0014
Drywall & Joint
Compound - Hall
to Lobby
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose10%Non-fibrous (other)90%
F1-014-Joint
Compound
411504178-0014A
Drywall & Joint
Compound - Hall
to Lobby
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
2Test Report PLM-7.28.9 Printed: 6/23/2015 4:00:24 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:00:24
Kristie Elliott (7)
Maria Cao (11)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504178
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - First Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F1-015-Cove Base
411504178-0015
Cove Base &
Mastic - Hall to
Lobby
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F1-015-Mastic
411504178-0015A
Cove Base &
Mastic - Hall to
Lobby
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
F1-016-Cove Base
411504178-0016
Cove Base &
Mastic - Hall to
Lobby
Black None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F1-016-Mastic
411504178-0016A
Cove Base &
Mastic - Hall to
Lobby
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F1-017
411504178-0017
Surfacing Ceiling
Texture-2 - Deck
Tan/White None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate5%
Non-fibrous (other)95%
F1-018
411504178-0018
Surfacing Ceiling
Texture-2 - Deck
Tan/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F1-019
411504178-0019
Surfacing Ceiling
Texture-2 - Deck
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
3THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/23/2015 4:00:24 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:00:24
Kristie Elliott (7)
Maria Cao (11)
OrderID: 411504192
Page 1 Of 2
OrderID: 411504192
Page 2 Of 2
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-001-Cove Base
411504192-0001
Cove Base &
Mastic - Human
Resources
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-001-Mastic
411504192-0001A
Cove Base &
Mastic - Human
Resources
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-002-Cove Base
411504192-0002
Cove Base &
Mastic - Human
Resources
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-002-Mastic
411504192-0002A
Cove Base &
Mastic - Human
Resources
Beige None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F2-003-Drywall
411504192-0003
Drywall & Joint
Compound -
Human Resources
& Hall
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose30%Non-fibrous (other)70%
F2-003-Joint
Compound
411504192-0003A
Drywall & Joint
Compound -
Human Resources
& Hall
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F2-004-Drywall
411504192-0004
Drywall & Joint
Compound -
Human Resources
& Hall
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose50%Non-fibrous (other)50%
F2-004-Joint
Compound
411504192-0004A
Drywall & Joint
Compound -
Human Resources
& Hall
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
1Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-005-Drywall
411504192-0005
Drywall & Joint
Compound -
Human Resources
& Hall
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose50%Non-fibrous (other)50%
F2-005-Joint
Compound
411504192-0005A
Drywall & Joint
Compound -
Human Resources
& Hall
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F2-006-Drywall
411504192-0006
Drywall & Joint
Compound -
Human Resources
& Hall
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose50%Non-fibrous (other)50%
F2-006-Joint
Compound
411504192-0006A
Drywall & Joint
Compound -
Human Resources
& Hall
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F2-007-Drywall
411504192-0007
Drywall & Joint
Compound -
Human Resources
& Hall
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose10%
Glass1%
Non-fibrous (other)89%
F2-007-Joint
Compound
411504192-0007A
Drywall & Joint
Compound -
Human Resources
& Hall
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F2-008-Skim Coat
411504192-0008
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
2Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-008-Rough Coat
411504192-0008A
Plaster - Hall Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
F2-009-Skim Coat
411504192-0009
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-009-Rough Coat
411504192-0009A
Plaster - Hall Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
F2-010-Skim Coat
411504192-0010
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-010-Rough Coat
411504192-0010A
Plaster - Hall Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
F2-011-Skim Coat
411504192-0011
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-011-Rough Coat
411504192-0011A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
3Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-012-Skim Coat
411504192-0012
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-012-Rough Coat
411504192-0012A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
F2-013
411504192-0013
Carpet Mastic -
Human Resources
Gray/Tan None Detected
Fibrous
Homogeneous
Synthetic1%
Cellulose<1%
Ca Carbonate5%
Non-fibrous (other)94%
F2-014
411504192-0014
Carpet Mastic -
Human Resources
Yellow None Detected
Non-Fibrous
Homogeneous
Synthetic1%Non-fibrous (other)99%
F2-015
411504192-0015
Corner Wall
Caulk - Human
Resources
Clear None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F2-016
411504192-0016
Corner Wall
Caulk - Human
Resources
Clear None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F2-017
411504192-0017
2x2 CT, Rough,
Dotted - Training
Room
Gray None Detected
Fibrous
Homogeneous
Min. Wool5%
Cellulose55%
Perlite10%
Non-fibrous (other)30%
F2-018
411504192-0018
2x2 CT, Rough,
Dotted - Training
Room
Tan/White None Detected
Fibrous
Homogeneous
Cellulose55%
Min. Wool10%
Perlite10%
Non-fibrous (other)25%
4Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-019-Flooring
411504192-0019
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Brown/Tan None Detected
Fibrous
Homogeneous
Synthetic5%Non-fibrous (other)95%
F2-019-Tan Mastic
411504192-0019A
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F2-019-Leveler
411504192-0019B
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-019-Black/Tan
Mastic
411504192-0019C
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Tan/Black None Detected
Fibrous
Homogeneous
Cellulose2%Non-fibrous (other)98%
F2-020-Flooring
411504192-0020
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Gray/Tan None Detected
Fibrous
Homogeneous
Cellulose15%
Synthetic5%
Non-fibrous (other)80%
F2-020-Mastic
411504192-0020A
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Beige None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F2-020-Leveler
411504192-0020B
Linoleum, Brown,
Stone-Design -
Human Resources
& Hall
Gray None Detected
Non-Fibrous
Homogeneous
Quartz5%
Ca Carbonate5%
Non-fibrous (other)90%
5Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-021
411504192-0021
Window Caulk -
Training Room
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-022
411504192-0022
Window Caulk -
Training Room
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-023
411504192-0023
Stone Pebble
Column Caulk -
Training Room
Gray None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F2-024
411504192-0024
Spray-On Vent -
Training Room
Office
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-025
411504192-0025
Spray-On Vent -
Training Room
Office
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-026
411504192-0026
Spray-On Vent -
Training Room
Office
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-027
411504192-0027
Surfacing Ceiling
Texture - Hall
White
Fibrous
Homogeneous
Chrysotile3%Ca Carbonate5%
Non-fibrous (other)92%
F2-028
411504192-0028
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F2-029
411504192-0029
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
6Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-030
411504192-0030
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F2-031
411504192-0031
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F2-032
411504192-0032
Black Window
Caulk - Audience
Develop.
Black
Fibrous
Homogeneous
Chrysotile3%Cellulose4%Non-fibrous (other)93%
F2-033
411504192-0033
Black Window
Caulk - Audience
Develop.
Stop Positive (Not Analyzed)
F2-034-Mastic
411504192-0034
Carpet Mastic &
Leveler - Audience
Develop.
Tan None Detected
Fibrous
Homogeneous
Synthetic1%
Cellulose<1%
Ca Carbonate5%
Non-fibrous (other)94%
F2-034-Leveler
411504192-0034A
Carpet Mastic &
Leveler - Audience
Develop.
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F2-035
411504192-0035
Carpet Mastic -
Audience Develop.
Tan None Detected
Non-Fibrous
Homogeneous
Synthetic2%
Cellulose<1%
Non-fibrous (other)98%
F2-036-Floor Tile
411504192-0036
12"x12" VFT, Tan
w/ White Flecks -
Audience Dev.
Vault
Tan/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
7Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-036-Mastic
411504192-0036A
12"x12" VFT, Tan
w/ White Flecks -
Audience Dev.
Vault
Black
Fibrous
Homogeneous
Chrysotile3%Non-fibrous (other)97%
F2-037-Floor Tile
411504192-0037
12"x12" VFT, Tan
w/ White Flecks -
Audience Dev.
Vault
Tan/Black None Detected
Fibrous
Homogeneous
Non-fibrous (other)100%
F2-037-Mastic
411504192-0037A
12"x12" VFT, Tan
w/ White Flecks -
Audience Dev.
Vault
Stop Positive (Not Analyzed)
F2-038
411504192-0038
1'x1', Rough -
Mech Room
Audience Develp
Gray None Detected
Fibrous
Homogeneous
Min. Wool70%
Cellulose10%
Non-fibrous (other)20%
F2-039
411504192-0039
1'x1', Rough -
Mech Room
Audience Develp
Gray/White None Detected
Fibrous
Homogeneous
Min. Wool70%
Cellulose10%
Non-fibrous (other)20%
F2-040
411504192-0040
Portable Wall
Insulation - Data
Process
Gray None Detected
Fibrous
Heterogeneous
Min. Wool5%
Cellulose55%
Perlite10%
Non-fibrous (other)30%
F2-041
411504192-0041
Portable Wall
Insulation - Data
Process
Gray/White None Detected
Fibrous
Homogeneous
Cellulose55%
Min. Wool5%
Perlite10%
Non-fibrous (other)30%
F2-042
411504192-0042
HVAC Caulk,
Black - Data Proc
Mech Room 392
Black
Fibrous
Homogeneous
Chrysotile4%Non-fibrous (other)96%
8Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504192
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Second Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F2-043
411504192-0043
HVAC Caulk,
Black - Data Proc
Mech Room 392
Stop Positive (Not Analyzed)
9THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/23/2015 3:38:59 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 15:38:59
Kristie Elliott (20)
Maria Cao (36)
OrderID: 411504692
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504692
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Kevin Headd
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:07/09/15 1:30 PM
CO
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/10/2015Analysis Date:
7/9/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
2-A1
411504692-0001
Caulk 2nd Floor White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
2-A2
411504692-0002
Caulk 2nd Floor White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
2-B1
411504692-0003
Caulk 2nd Floor Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
2-B2
411504692-0004
Caulk 2nd Floor White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
3-A1
411504692-0005
Caulk 3rd Floor Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
3-A2
411504692-0006
Caulk 3rd Floor White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
3-B1
411504692-0007
Caulk 3rd Floor Tan
Fibrous
Homogeneous
Chrysotile3%Ca Carbonate5%
Non-fibrous (other)92%
3-B2
411504692-0008
Caulk 3rd Floor White
Non-Fibrous
Homogeneous
Chrysotile4%Ca Carbonate10%
Non-fibrous (other)86%
1THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 7/10/2015 9:54:51 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 07/10/2015 09:54:51
Eric Loomis (4)
Maria Cao (4)
OrderID: 411504179
Page 1 Of 2
OrderID: 411504179
Page 2 Of 2
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-001
411504179-0001
Floor Coating,
Black - Mail Room
Black
Fibrous
Homogeneous
Chrysotile2%Cellulose8%Non-fibrous (other)90%
F3-002
411504179-0002
Floor Coating,
Black - Mail Room
Stop Positive (Not Analyzed)
F3-003
411504179-0003
Floor Coating,
Black - Mail Room
Stop Positive (Not Analyzed)
F3-004
411504179-0004
Slate-Like
Flooring - Mail
Room Office
Black
Fibrous
Homogeneous
Chrysotile2%Cellulose8%Non-fibrous (other)90%
F3-005
411504179-0005
Slate-Like
Flooring - Mail
Room Office
Stop Positive (Not Analyzed)
F3-006-Drywall
411504179-0006
Drywall & Joint
Compound - Mail
Room
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose10%
Glass1%
Non-fibrous (other)89%
F3-006-Joint
Compound
411504179-0006A
Drywall & Joint
Compound - Mail
Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
F3-007-Drywall
411504179-0007
Drywall & Joint
Compound - Mail
Room
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose5%
Glass1%
Non-fibrous (other)94%
1Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-007-Joint
Compound
411504179-0007A
Drywall & Joint
Compound - Mail
Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
F3-008-Drywall
411504179-0008
Drywall & Joint
Compound - Mail
Room
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose10%Non-fibrous (other)90%
F3-008-Joint
Compound
411504179-0008A
Drywall & Joint
Compound - Mail
Room
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F3-009
411504179-0009
1'x1' CT, Rough -
Mail Room Office
Brown/White None Detected
Fibrous
Homogeneous
Cellulose10%
Min. Wool85%
Non-fibrous (other)5%
F3-010
411504179-0010
1'x1' CT, Rough -
Mail Room Office
Gray None Detected
Fibrous
Homogeneous
Min. Wool70%
Cellulose15%
Non-fibrous (other)15%
F3-011
411504179-0011
2'x2' CT, Pin-
Holed - Mail Room
Office
Tan/White None Detected
Fibrous
Homogeneous
Cellulose60%
Min. Wool2%
Perlite20%
Non-fibrous (other)18%
F3-012
411504179-0012
2'x2' CT, Pin-
Holed - Mail Room
Office
Gray None Detected
Fibrous
Homogeneous
Cellulose60%
Min. Wool2%
Perlite10%
Non-fibrous (other)28%
F3-013-Cove Base
411504179-0013
Cove Base &
Mastic - Mail
Room Office
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
2Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-013-Mastic
411504179-0013A
Cove Base &
Mastic - Mail
Room Office
Beige None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-014-Cove Base
411504179-0014
Cove Base &
Mastic - Mail
Room Office
Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F3-014-Mastic
411504179-0014A
Cove Base &
Mastic - Mail
Room Office
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F3-015-Carpet
Mastic
411504179-0015
Carpet Mastic -
Mail Room Office
Yellow None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-015-Black Layer
411504179-0015A
Carpet Mastic -
Mail Room Office
Black
Fibrous
Homogeneous
Chrysotile2%Cellulose8%Non-fibrous (other)90%
F3-016-Carpet
Mastic
411504179-0016
Carpet Mastic -
Mail Room Office
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-016-Black Layer
411504179-0016A
Carpet Mastic -
Mail Room Office
Stop Positive (Not Analyzed)
F3-017
411504179-0017
Stone-Pebble
Column Caulk -
Locker Room Mail
Room
Beige
Non-Fibrous
Homogeneous
Chrysotile3%Non-fibrous (other)97%
3Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-018
411504179-0018
Black Window
Caulk - Mail Room
Black
Fibrous
Homogeneous
Chrysotile5%Non-fibrous (other)95%
F3-019
411504179-0019
Black Window
Caulk - Mail Room
Stop Positive (Not Analyzed)
F3-020-Floor Tile
411504179-0020
Brown Flooring w/
White & Dark
Brown Smears -
Mail Room Locker
Room
Brown
Non-Fibrous
Homogeneous
Chrysotile2%Ca Carbonate5%
Non-fibrous (other)93%
F3-020-Mastic
411504179-0020A
Brown Flooring w/
White & Dark
Brown Smears -
Mail Room Locker
Room
Brown None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-021-Floor Tile
411504179-0021
Brown Flooring w/
White & Dark
Brown Smears -
Mail Room Locker
Room
Stop Positive (Not Analyzed)
F3-021-Mastic
411504179-0021A
Brown Flooring w/
White & Dark
Brown Smears -
Mail Room Locker
Room
Brown None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-022-Skim Coat
411504179-0022
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
4Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-022-Rough Coat
411504179-0022A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
F3-022-Beige Layer
411504179-0022B
Plaster - Hall Beige None Detected
Non-Fibrous
Homogeneous
Ca Carbonate25%
Non-fibrous (other)75%
F3-023-Skim Coat
411504179-0023
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F3-023-Rough Coat
411504179-0023A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
F3-024-Skim Coat
411504179-0024
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F3-024-Rough Coat
411504179-0024A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
F3-025-Skim Coat
411504179-0025
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
5Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-025-Rough Coat
411504179-0025A
Plaster - Hall Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Quartz20%
Ca Carbonate5%
Non-fibrous (other)75%
F3-026-Skim Coat
411504179-0026
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
F3-026-Rough Coat
411504179-0026A
Plaster - Hall Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
F3-027-Skim Coat
411504179-0027
Plaster - Hall White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
F3-027-Rough Coat
411504179-0027A
Plaster - Hall Gray None Detected
Non-Fibrous
Homogeneous
Quartz30%
Ca Carbonate5%
Non-fibrous (other)65%
F3-028-Drywall
411504179-0028
Drywall & Joint
Compound -
Operating Center
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose30%
Glass1%
Non-fibrous (other)69%
F3-028-Joint
Compound
411504179-0028A
Drywall & Joint
Compound -
Operating Center
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
6Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-028-Tape
411504179-0028B
Drywall & Joint
Compound -
Operating Center
Beige None Detected
Fibrous
Homogeneous
Cellulose100%Non-fibrous (other)0%
F3-029-Drywall
411504179-0029
Drywall & Joint
Compound -
Operating Center
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose60%Non-fibrous (other)40%
F3-029-Joint
Compound
411504179-0029A
Drywall & Joint
Compound -
Operating Center
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
F3-030
411504179-0030
Corner Wall
Caulk - Operating
Center
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
F3-031-Top Mastic
411504179-0031
12x12 Tan w/
White Flecks -
Operating A/P
Beige None Detected
Non-Fibrous
Homogeneous
Synthetic<1%Ca Carbonate10%
Non-fibrous (other)90%
F3-031-Floor Tile
411504179-0031A
12x12 Tan w/
White Flecks -
Operating A/P
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F3-031-Bottom
Mastic
411504179-0031B
12x12 Tan w/
White Flecks -
Operating A/P
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-032-Top Mastic
411504179-0032
12x12 Tan w/
White Flecks -
Operating A/P
Beige None Detected
Non-Fibrous
Homogeneous
Synthetic<1%Ca Carbonate5%
Non-fibrous (other)95%
7Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-032-Floor Tile
411504179-0032A
12x12 Tan w/
White Flecks -
Operating A/P
Tan None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
F3-032-Bottom
Mastic
411504179-0032B
12x12 Tan w/
White Flecks -
Operating A/P
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-033-Flooring
411504179-0033
Lt. Gray Linoleum
w/ Stone-Design -
Storage Room
Gray/Tan None Detected
Fibrous
Homogeneous
Cellulose20%
Synthetic2%
Non-fibrous (other)78%
F3-033-Mastic
411504179-0033A
Lt. Gray Linoleum
w/ Stone-Design -
Storage Room
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-034-Flooring
411504179-0034
Lt. Gray Linoleum
w/ Stone-Design -
Storage Room
Gray None Detected
Fibrous
Homogeneous
Cellulose15%
Synthetic2%
Non-fibrous (other)83%
F3-034-Mastic
411504179-0034A
Lt. Gray Linoleum
w/ Stone-Design -
Storage Room
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate5%
Non-fibrous (other)95%
F3-035-Flooring
411504179-0035
Lt. Brown
Linoleum w/ Stone-
Design - Hall
Gray/Tan None Detected
Fibrous
Homogeneous
Cellulose10%
Synthetic2%
Non-fibrous (other)88%
F3-035-Mastic
411504179-0035A
Lt. Brown
Linoleum w/ Stone-
Design - Hall
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
8Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-036-Flooring
411504179-0036
Lt. Brown
Linoleum w/ Stone-
Design - Hall
Brown/Tan None Detected
Fibrous
Homogeneous
Cellulose15%
Synthetic2%
Non-fibrous (other)83%
F3-036-Mastic
411504179-0036A
Lt. Brown
Linoleum w/ Stone-
Design - Hall
Tan None Detected
Non-Fibrous
Homogeneous
Cellulose2%Non-fibrous (other)98%
F3-037-Flooring
411504179-0037
Dark Brown
Linoleum w/ Stone-
Design - Café
Brown
Fibrous
Homogeneous
Chrysotile25%Cellulose1%Non-fibrous (other)74%
F3-037-Mastic
411504179-0037A
Dark Brown
Linoleum w/ Stone-
Design - Café
Rust None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-038-Flooring
411504179-0038
Dark Brown
Linoleum w/ Stone-
Design - Café
Stop Positive (Not Analyzed)
F3-038-Mastic
411504179-0038A
Dark Brown
Linoleum w/ Stone-
Design - Café
Brown None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-039
411504179-0039
Black Sealant -
Kitchen
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-040
411504179-0040
Black Sealant -
Kitchen
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
9Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-041
411504179-0041
2x2 Ceiling Tile,
Smooth, Off-
White - Cafeteria
& Kitchen
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose10%
Glass1%
Non-fibrous (other)89%
F3-042
411504179-0042
2x2 Ceiling Tile,
Smooth, Off-
White - Cafeteria
& Kitchen
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose5%
Glass1%
Non-fibrous (other)94%
F3-043-Flooring
411504179-0043
Dark Blue Gray
Linoleum w/ Small
Stone Design -
Storage Room
Gray/Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F3-043-Mastic
411504179-0043A
Dark Blue Gray
Linoleum w/ Small
Stone Design -
Storage Room
Beige None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-044-Flooring
411504179-0044
Dark Blue Gray
Linoleum w/ Small
Stone Design -
Storage Room
Gray/Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F3-044-Mastic
411504179-0044A
Dark Blue Gray
Linoleum w/ Small
Stone Design -
Storage Room
Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
F3-045-Floor Tile
411504179-0045
12"x12" VFT,
White w/ Brown
Flecks
Beige
Non-Fibrous
Homogeneous
Chrysotile3%Ca Carbonate20%
Non-fibrous (other)77%
10Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504179
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/19/15 9:15 AM
CO Building - Third Floor
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/23/2015Analysis Date:
6/18/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
F3-045-Mastic
411504179-0045A
12"x12" VFT,
White w/ Brown
Flecks
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-046-Floor Tile
411504179-0046
12"x12" VFT,
White w/ Brown
Flecks
Stop Positive (Not Analyzed)
F3-046-Mastic
411504179-0046A
12"x12" VFT,
White w/ Brown
Flecks
Black None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
F3-047
411504179-0047
Surfacing Ceiling
Texture - Hall
White/Beige
Fibrous
Homogeneous
Chrysotile4%Ca Carbonate5%
Non-fibrous (other)91%
F3-048
411504179-0048
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F3-049
411504179-0049
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F3-050
411504179-0050
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
F3-051
411504179-0051
Surfacing Ceiling
Texture - Hall
Stop Positive (Not Analyzed)
11THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/23/2015 4:55:13 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/23/2015 16:55:13
Kristie Elliott (45)
Maria Cao (27)
OrderID: 411504234
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504234
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Warehouse
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
WH-001-Drywall
411504234-0001
Drywall & Joint
Compound
Brown/Gray None Detected
Fibrous
Heterogeneous
Cellulose50%Non-fibrous (other)50%
WH-001-Joint
Compound
411504234-0001A
Drywall & Joint
Compound
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate40%
Non-fibrous (other)60%
WH-002-Drywall
411504234-0002
Drywall & Joint
Compound
Brown/Gray None Detected
Fibrous
Homogeneous
Cellulose20%Non-fibrous (other)80%
WH-002-Joint
Compound
411504234-0002A
Drywall & Joint
Compound
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
WH-003
411504234-0003
Wall Caulk White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate5%
Non-fibrous (other)95%
WH-004
411504234-0004
Wall Caulk White None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Ca Carbonate5%
Non-fibrous (other)95%
WH-005-Floor Tile
411504234-0005
12x12 VFT, Black Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
WH-005-Mastic
411504234-0005A
12x12 VFT, Black Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
1Test Report PLM-7.28.9 Printed: 6/24/2015 5:02:36 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 17:02:36
Erin Guzowski (12)
Maria Cao (11)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504234
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Warehouse
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
WH-006-Floor Tile
411504234-0006
12x12 VFT, Black Black None Detected
Non-Fibrous
Homogeneous
Ca Carbonate30%
Non-fibrous (other)70%
WH-006-Mastic
411504234-0006A
12x12 VFT, Black Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
WH-007-Floor Tile
411504234-0007
12x12 VFT, White Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
WH-007-Mastic
411504234-0007A
12x12 VFT, White Tan None Detected
Non-Fibrous
Homogeneous
Cellulose<1%Non-fibrous (other)100%
WH-008-Floor Tile
411504234-0008
12x12 VFT, White White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate35%
Non-fibrous (other)65%
WH-008-Mastic
411504234-0008A
12x12 VFT, White Tan None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
WH-008-Leveler
411504234-0008B
12x12 VFT, White Gray None Detected
Non-Fibrous
Homogeneous
Quartz10%
Ca Carbonate5%
Non-fibrous (other)85%
WH-009
411504234-0009
Undersink Coating Gray None Detected
Fibrous
Homogeneous
Cellulose5%Ca Carbonate5%
Non-fibrous (other)90%
2Test Report PLM-7.28.9 Printed: 6/24/2015 5:02:36 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 17:02:36
Erin Guzowski (12)
Maria Cao (11)
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504234
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Diana Lanier
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/22/15 8:40 AM
CO Bldg. - Warehouse
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/24/2015Analysis Date:
6/19/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
WH-010
411504234-0010
Undersink Coating Gray None Detected
Non-Fibrous
Homogeneous
Cellulose4%Ca Carbonate5%
Non-fibrous (other)91%
WH-011
411504234-0011
2x2 CT, Pin-Holed,
Smooth
Gray None Detected
Fibrous
Heterogeneous
Cellulose60%
Min. Wool5%
Perlite10%
Non-fibrous (other)25%
WH-012
411504234-0012
2x2 CT, Pin-Holed,
Smooth
Gray None Detected
Fibrous
Heterogeneous
Cellulose55%
Min. Wool10%
Perlite10%
Non-fibrous (other)25%
WH-013-Drywall
411504234-0013
Drywall & Joint
Compound
Gray None Detected
Fibrous
Homogeneous
Cellulose5%
Glass1%
Non-fibrous (other)94%
WH-013-Joint
Compound
411504234-0013A
Drywall & Joint
Compound
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate40%
Non-fibrous (other)60%
WH-014
411504234-0014
Floor Caulk Gray None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
WH-015
411504234-0015
Floor Caulk Gray None Detected
Non-Fibrous
Homogeneous
Non-fibrous (other)100%
3THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/24/2015 5:02:36 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/24/2015 17:02:36
Erin Guzowski (12)
Maria Cao (11)
OrderID: 411504501
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504501
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Kevin Headd
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:07/01/15 1:30 PM
CO
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
7/2/2015Analysis Date:
7/1/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
SH-001
411504501-0001
Shed - Roof
Shingle
Black None Detected
Fibrous
Homogeneous
Glass5%Quartz8%
Ca Carbonate10%
Non-fibrous (other)77%
SH-002
411504501-0002
Shed - Roof
Shingle
Black None Detected
Non-Fibrous
Homogeneous
Glass8%Quartz5%
Ca Carbonate5%
Non-fibrous (other)82%
SH-003
411504501-0003
Shed - Window
Caulk
White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
SH-004
411504501-0004
Shed - Window
Caulk
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
WHE-001
411504501-0005
Warehouse - Ext.
Window Caulk
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
WHE-002
411504501-0006
Warehouse - Ext.
Window Caulk
Gray None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
CO3-200
411504501-0007
Floor 3 - Belts on
Machinery
Gray/Black None Detected
Fibrous
Homogeneous
Synthetic60%
Cellulose3%
Non-fibrous (other)37%
CO3-201
411504501-0008
Floor 3 - Belts on
Machinery
Brown/Gray None Detected
Fibrous
Heterogeneous
Synthetic70%
Cellulose5%
Non-fibrous (other)25%
1THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 7/2/2015 10:38:48 AM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 07/02/2015 10:38:48
Erin Guzowski (4)
Eric Loomis (4)
OrderID: 411504440
Page 1 Of 1
EMSL Analytical, Inc.
376 Crompton Street, Charlotte, NC 28273
Phone/Fax:(704) 525-2205 / (704) 525-2382
http://www.EMSL.com charlottelab@emsl.com
411504440
CustomerID:ATCA72
CustomerPO:
ProjectID:
EMSL Order:
Attn:Kevin Headd
Cardno
7606 Whitehall Executive Center Drive
Suite 800
Charlotte, NC 28273
Received:06/30/15 12:50 PM
CO
Fax:(704) 529-3272
Phone:(704) 529-3200
Project:
6/30/2015Analysis Date:
6/29/2015Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy
WH-200
411504440-0001
Warehouse HVAC
Caulk
Gray None Detected
Limited sample submitted, result cannot be verified.
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
WH-201
411504440-0002
Warehouse HVAC
Caulk
Gray None Detected
Limited sample submitted, result cannot be verified.
Non-Fibrous
Homogeneous
Ca Carbonate20%
Non-fibrous (other)80%
D-1
411504440-0003
Exterior Deck
Textured Ceiling
Brown/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
D-2
411504440-0004
Exterior Deck
Textured Ceiling
Brown/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate15%
Non-fibrous (other)85%
D-3
411504440-0005
Exterior Deck
Textured Ceiling
Brown/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
D-4
411504440-0006
Exterior Deck
Textured Ceiling
Brown/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
D-5
411504440-0007
Exterior Deck
Textured Ceiling
Brown/White None Detected
Non-Fibrous
Homogeneous
Ca Carbonate10%
Non-fibrous (other)90%
1THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.9 Printed: 6/30/2015 3:26:29 PM
Lee Plumley, Laboratory Manager
or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Charlotte, NC NVLAP Lab Code 200841-0, VA 3333 00312
Initial report from 06/30/2015 15:26:29
Erin Guzowski (4)
Kyle Collins (3)
ATTACHMENT 4
ASBESTOS INSPECTOR AND LABORATORY ACCREDITATIONS
Un
i
t
e
d
S
t
a
t
e
s
D
e
p
a
r
t
m
e
n
t
o
f
C
o
m
m
e
r
c
e
Na
t
i
o
n
a
l
I
n
s
t
i
t
u
t
e
o
f
S
t
a
n
d
a
r
d
s
a
n
d
T
e
c
h
n
o
l
o
g
y
Ce
r
t
i
f
i
c
a
t
e
o
f
A
c
c
r
e
d
i
t
a
t
i
o
n
t
o
I
S
O
/
I
E
C
1
7
0
2
5
:
2
0
0
5
NV
L
A
P
L
A
B
C
O
D
E
:
2
0
0
8
4
1
-
0
EM
S
L
A
n
a
l
y ti
c
a
l
,
I
n
c
.
Ch
a
r
l
o
t
t
e
,
N
C
is
a
c
c
r
e
d
i
t
e
d
b
y
t
h
e
N
a
t
i
o
n
a
l
V
o
l
u
n
t
a
r
y
L
a
b
o
r
a
t
o
r
y
A
c
c
r
e
d
i
t
a
t
i
o
n
P
r
o
g
r
a
m
f
o
r
s
p
e
c
i
f
i
c
s
e
r
v
i
c
e
s
,
li
s
t
e
d
o
n
t
h
e
S
c
o
p
e
o
f
A
c
c
r
e
d
i
t
a
t
i
o
n
,
f
o
r
:
As
b
e
s
t
o
s
F
i
b
e
r
A
n
a
l
y
s
i
s
20
1
5
-
0
6
-
0
2
t
h
r
o
u
g
h
2
0
1
6
-
0
6
-
3
0
Ef
f
e
c
t
i
v
e
D
a
t
e
s
Fo
r
t
h
e
N
a
t
i
o
n
a
l
V
o
l
u
n
t
a
r
y
L
a
b
o
r
a
t
o
r
y
A
c
c
r
e
d
i
t
a
t
i
o
n
P
r
o
g
r
a
m
Th
i
s
l
a
b
o
r
a
t
o
r
y
i
s
a
c
c
r
e
d
i
t
e
d
i
n
a
c
c
o
r
d
a
n
c
e
w
i
t
h
t
h
e
r
e
c
o
g
n
i
z
e
d
I
n
t
e
r
n
a
t
i
o
n
a
l
S
t
a
n
d
a
r
d
I
S
O
/
I
E
C
1
7
0
2
5
:
2
0
0
5
.
Th
i
s
a
c
c
r
e
d
i
t
a
t
i
o
n
d
e
m
o
n
s
t
r
a
t
e
s
t
e
c
h
n
i
c
a
l
c
o
m
p
e
t
e
n
c
e
f
o
r
a
d
e
f
i
n
e
d
s
c
o
p
e
a
n
d
t
h
e
o
p
e
r
a
t
i
o
n
o
f
a
l
a
b
o
r
a
t
o
r
y
q
u
a
l
i
t
y
ma
n
a
g
e
m
e
n
t
s
y
s
t
e
m
(
r
e
f
e
r
t
o
j
o
i
n
t
I
S
O
-
I
L
A
C
-
I
A
F
C
o
m
m
u
n
i
q
u
e
d
a
t
e
d
J
a
n
u
a
r
y
2
0
0
9
)
.
National Voluntary
Laboratory Accreditation Program
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
Page 1 of 1
For the National Voluntary Laboratory Accreditation Program
Effective 2015-06-02 through 2016-06-30
EMSL Analytical, Inc.
376 Crompton Street
Charlotte, NC 28273
Mr. Lee Plumley
Phone: 704-525-2205 Fax: 704-525-2382
Email: lplumley@emsl.com
http://www.emsl.com
ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 200841-0
Bulk Asbestos Analysis
Code Description
18/A01 EPA 600/M4-82-020: Interim Method for the Determination of Asbestos in Bulk Insulation Samples
18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials
Airborne Asbestos Analysis
Code Description
18/A02 U.S. EPA's "Interim Transmission Electron Microscopy Analytical Methods-Mandatory and
Nonmandatory-and Mandatory Section to Determine Completion of Response Actions" as found in
40 CFR, Part 763, Subpart E, Appendix A.
ATTACHMENT 5
PHOTOGRAPHIC DOCUMENTATION
Asbestos Survey
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
Cardno Project Number 199GSG1501
Photo #1: Charlotte Observer Building.
Photo #2: View northwest across South Church Street from the Charlotte Observer Building
toward the Charlotte Observer Warehouse, located below the parking deck, with address 621
South Poplar Street.
Asbestos Survey
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
Cardno Project Number 199GSG1501
Photo #3: View across the roof of the Charlotte Observer Building.
Photo #4: View of Hot Water Supply (HWS) and Hot Water Return (HWR) pipe insulation ACM
observed at the site.
Asbestos Survey
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
Cardno Project Number 199GSG1501
Photo #5: View of piping runs observed in the Basement, consisting of ACM and non-ACM
pipe insulation.
Photo #6: View of Black Caulk ACM observed on vertical duct system, as well as other
locations at the site.
Asbestos Survey
The Charlotte Observer
600 South Tryon Street
Charlotte, North Carolina
Cardno Project Number 199GSG1501
Photo #7: View across the Mail Room located on the 3rd floor of the Charlotte Observer
Building. Note, black surface coating ACM, below which is black slate-like ACM.
Photo #8: View of Basement Tunnel connecting the Charlotte Observer Building to the
Charlotte Observer Warehouse. The Tunnel runs under South Church Street. Note, ACM and
non-ACM pipe insulation.
ATTACHMENT 6
ASSUMPTIONS AND LIMITATIONS
The Charlotte Observer
Asbestos Survey
July 16, 2015
ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in this report are based only on
conditions that were noted during Cardno’s survey of the Charlotte Observer Building site at 600 South
Tryon Street in Charlotte, North Carolina. The site survey area includes a warehouse, with address 620 South
Poplar Street that is connected to the Charlotte Observer Building by a basement tunnel that crosses under
South Church Street. The site was surveyed for ACM on June 17-20, 2015, June 29, July 1, and July 9, 2015.
The selection of sample locations and frequency of sampling was based on Cardno’s observations and
the assumption that like materials in the same area are homogeneous in content. ACM may exist in
concealed areas that were not investigated or identified. Additional ACM may be present on site in
inaccessible or concealed spaces. These spaces include, but are not limited to, pipe chases, spaces
between wall/ceiling/door cavities, interior of mechanical components such as boiler cavities, interior
ducts, areas beneath the foundation, etc. If future maintenance/renovation/demolition activities make
these areas accessible, Cardno recommends that a thorough assessment of these spaces be conducted
at that time to identify and confirm the presence or absence of additional ACM. Until then, such
unidentified materials should be treated as assumed ACM in accordance with 40 CFR 763.
The report is designed to aid the client in understanding the extent of ACM issues as they pertain to the
planned renovation/demolition areas of the site building areas. Under no circumstances is the report
to be utilized as a bidding document or as a project specification document since it does not have
all the components required to serve as an Asbestos Abatement Project Design document or an
Abatement Workplan.
Our professional services have been performed, our findings obtained, and our conclusions and
recommendations prepared in accordance with customary principles and practices in the fields of
environmental science and engineering. This statement is in lieu of other statements either expressed or
implied. This report does not warrant against future operations or conditions, nor does it warrant against
operations or conditions present of a type or at a location not investigated. Cardno ATC assumes no
responsibility for the investigation, remediation, abatement, or other potential liabilities associated with
environmental impact at, or from, the project site or structure, regardless of the date of occurrence.