ESP Associates P.A ESP is submitting this letter as an addendum to our Report of
Preliminary Subsurface Exploration dated May 26 2006 We understand that Beazer Homes
has requested allowable shallow foundation bearing capacity recommendations for specific areas
of the site utilizing the current site plan information
Our analysis began with review of our previous report of Preliminary Subsurface
Exploration dated May 26 2006
the Mactec report titled Report of Preliminary Geotechnical
Exploration dated April 18 2005 and the Preliminary Grading Plan provided by Tumbull
Sigmon Design dated August 2006 The referenced plan includes proposed roadway grades
but does not include any site grading information in building pad areas nor does it include
current topography During our analysis we have made very general assumptions regarding
potential grade changes in specific areas of the site In general we have assumed the eastern
portion of the site would be cut as much as 10 feet the western and western central portions of
the site would consist of filling operations potentially as high as to 10 feet with the central
portion of the site remaining approximately on grade In addition many areas of existing fill and
debris were encountered in our previous exploration These materials were predominately
surveying
P0 Box 7030 Charlotte NC 2824 704 583-4949 Fax 704 583-4950
wwwespassoc jates corn
Addendum to Report of Preliminary Subsuiface Exploration ESP Project No E4-UD42.300
West End Development August 18 2006
observed to be unsuitable in nature and will require undercutting This analysis assumes that all
existing fill encountered on the site will be undercut Any suitable existing fill soils that are
removed may be replaced in structural areas Any unsuitable soils that were undercut shall be
placed in non-structural areas or removed from the site It is our understanding that the surface
layer of gravel located on-site is planned for re-use as structural fill material It is recommended
that representative from our office be present during
all undercutting operations
in order to
assist in delineating the unsuitable fill from any fill that may be re-used
The following recommendations are general in nature and are based on the above assumptions
and information If more specific analysis on individual buildings and/or specific areas of the
site become necessary additional field exploration would be required Please refer to the
attached Preliminary Grading Plan for more specific locations
The following sections outline our allowable bearing pressure recommendations for fbundations
bearing on residual soils and newly placed structural fill The recommendations are based on
anticipated building settlement potentials of inch total and V2 inch differential These
recommendations assume all existing fill will be removed and replaced
Allowable bearing capacity recommendations for building foundations bearing in RESIDUAL
SOILS
Note N-value equal to or greater than 20 blows per foot bp
Note N-value equal to or greater than bpf
Note value equal to or greater than bpf
Addendum to Report ofPreliminary Subsurface Exploration ESP Project No E4-UD42.300WestEndDevelopmentAugust18 2006
Allowable bearing capacity recommendations for building foundations bearing in
STRUCTURAL FILL SOILS
Area Recommended Allowable Based On
Bearing Pressure psf
3000 Notes
Note Structural fill compacted to at least 95%of the soils Standard Proctor maximum dry density
Note The maximum dry density of the fill material must be at least 100 pounds per cubic foot pcf
Due to the limited testing performed and the wide spacing of test pits and borings the possibility
of deleterious inclusions and variable density material in variety of areas of the site is likelyWewouldalsoliketopomtoutthatourexperienceindicatesrockinweatheredboulderand
massive form varies erratically in location and depth in the Piedmont Geologic Province which
contains Charlotte North Carolina Therefore there is always potential that these materials
could be encountered at shallow depths between the exploration locations If more detailed
evaluation in specific areas of the site or specific building areas is desired additional field
evaluations can be performed All foundation excavations should be evaluated in the field by
representative of the geotechnical engineer to verify consistency with our previous findings
The analysis and recommendations submitted herein are based in part upon the data obtained
from the subsurface explorations The nature and extent of variations between the borings and
test pits will not be known until construction is underway If variations appear evident then we
request the opportunity to re-evaluate the recommendations of this report Also once final site
grading plan is available our recommendations should be re-evaluated for any possible
changes to the above soil bearing pressures In the event that any changes in the nature
design or location of the structures are planned the conclusions and recommendations contained
in this report will not be considered valid unless the changes are reviewed and conclusions
modified or verified in writing by ESP
The information contained in this letter is provided with respect to proposed building
foundations only The information shall not be utilized for other purposes and/or structures
planned for the site
Addendum to Report of Preliminary Subsurface Exploration ESP Project No E4-UD42.300
West End Development August 18 2006
ESP appreciates the opportunity to assist you during this phase of the project If you should have
any questions concerning this report or if we may be of further assistance please contact us
Sincerely
ESF Associates P.A
ennifer Payne
Project Manager
Brian Welch PE
N.C Registration No 21615
JAP/BFW/mb
Copies Submitted
Attachments Area Plan Figure
LiD43OO SHEET TITLE
SCALE N1S
DATEAIRJ.II
PROJECTDAV.1V DUNCHECKED BYRPWFIGURE
WEST END AREA PLAN
WEST END SITE
1TI ESP ASSOCIATES 14
flIl
372 Croinpten Street
Charlotte 1/C 28273 704 504 4015