HomeMy WebLinkAboutMO-30288_0_CA_SCH_20231212_Pilot Travel Center 7976SITE CHECK REPORT – DIESEL DISPENSER #23
PILOT TRAVEL CENTER #7976
1006 Charlotte Highway
Troutman, Iredell County, North Carolina
NCDEQ Facility ID #00-0-0000032304
2725 E. Millbrook Road, Suite 121
Raleigh, North Carolina 27604
Telephone 919-871-0999
Fax 737-207-8261
www.oneatlas.com
December 1, 2023
Mr. Dan Graham
North Carolina Department of Environmental Quality
Mooresville Regional Office
Division of Waste Management – UST Section
610 East Center Avenue, Suite 301
Mooresville, North Carolina 28115
Re: Site Check Report – Diesel Dispenser 23
Pilot Travel Center #7976
1006 Charlotte Highway
Troutman, Iredell County, North Carolina
NCDEQ Facility ID #00-0-0000032304
Dear Mr. Graham:
ATC Associates of North Carolina, LLC (ATC), on behalf of Pilot Travel Centers, LLC, is submitting this Site
Check Report for the referenced facility. This site check was prepared in response to approximately 1 inch of
diesel fuel being observed in the under dispenser containment (UDC) of diesel dispenser #23.
If you have any questions or require additional information, please contact our office at (919) 871-0999.
Sincerely,
ATC Associates of North Carolina, LLC
Maureen Jackson, P.G. Sam Wakefield
Senior Project Manager Program Manager
cc: Joey Cupp, Pilot Travel Centers, LLC
Pilot Travel Centers #7976 December 1, 2023
NCDEQ Facility ID #00-0-0000032304 Site Check Report-Diesel Dispenser #23
ATC Associates of North Carolina
B.
1.
2.
3.
4.
5.
C.
1.
2.
Carolina, to advance one soil boring as close as possible to diesel dispenser #23. The soil
On November 10, 2023, ATC personnel contracted with Ameriprobe of Huntersville, North Site Check Procedure
leaking. On this date, the filters were replaced and it was determined the leak had ceased.
On November 30, 2023, a Jones & Frank technician found the filters under diesel dispenser 23 via e-mail correspondence. A copy of the UST-17A is provided in Attachment I.
behalf of Pilot, submitted a UST-17A: UST Suspected Release 24 Hour Notice to the NCDEQ of diesel dispenser #23. No visual leaks were seen on this date. On October 12, 2023, ATC, on On October 11, 2023, approximately 1 inch of diesel fuel was noted in the bottom of the UDC UST System Testing
Site Check Procedures
Figures 1 and 2, respectively.
identified within 1,000 feet of the source area. A topographic map and site map are attached as supplied to the area; however, it appears at least three water supply wells have been previously commercial area in proximity to Interstate-77 in Troutman, North Carolina. Public water is The subject property and surrounding area are fairly level. The subject property is located in a building, several gasoline and diesel dispenser islands, and other petroleum fueling equipment. The subject property consists of a Pilot Travel Center Truck Stop with one convenience store Provide a Brief Description of Site Characteristics
appears incident #24101 has ongoing free product recovery activities from a diesel release.
6, 2002, and UST incident #40728 was issued a Notice of NFA on December 18, 2018. It 40728). UST incident #23692 was issued a Notice of No Further Action (NFA) on September releases appear to have occurred at this location (UST incident numbers 24101, 23692, and Based on a review of available file information on NCDEQ’s website, three previous UST Describe relation of location of current UST system to historical UST releases.
No ASTs or surface spills are known to exist at the site.
Provide Non-UST Information
See Table 2.
Provide UST Information
See Table 1.
Provide UST Owner and Operator Information
Site History
Pilot Travel Centers #7976 December 1, 2023
NCDEQ Facility ID #00-0-0000032304 Site Check Report-Diesel Dispenser #23
ATC Associates of North Carolina
boring was advanced to approximately 6 feet below ground surface (bgs), using a
field-decontaminated, stainless-steel hand auger and a macro-core sampler. The location of the
soil boring [labelled SB-1(6’)] is provided on Figure 2.
3. Soil Excavation Activities
Soil excavation was not performed as part of this site check.
D. Site Investigation
1. Field Screening
The soil sample was collected at an approximate depth of 6 feet below ground surface (bgs).
Upon collection, the soil sample was screened with a photoionization detector (PID). The
respective PID reading is provided in Table 3.
2. Soil Sampling Information
On November 10, 2023, ATC personnel contracted with Ameriprobe of Huntersville, North
Carolina, to advance one soil boring as close as possible to diesel dispenser #23. The soil
boring was advanced to approximately 6 feet bgs, using a field-decontaminated, stainless steel
hand auger and a macro-core sampler. A soil sample was collected at an approximate depth of
6 feet bgs. The soil encountered at the sampling depth consisted of brown clayey silt.
The soil sample was shipped to a N.C. certified laboratory in a chilled cooler following proper
chain-of-custody procedures. The soil sample was requested to be analyzed by Total Petroleum
Hydrocarbons (TPH)-Gasoline Range Organics (GRO) and TPH-Diesel Range Organics
(DRO).
3. Groundwater and Surface Sampling Information
Groundwater and surface water samples were not collected during the site check activities.
4. Quality Control Measures
The soil sample was placed in laboratory provided jars and vials. The sample was immediately
placed on ice and contained in a cooler during transportation. The sample was transported by
courier under a chain-of-custody to the laboratory for analyses.
5. Investigation Results
Laboratory analytical results of the soil sample collected in proximity to diesel dispenser #23
did not detect TPH-GRO or TPH-DRO concentrations above established State Action Levels.
Laboratory analytical results are provided in Table 3. A copy of the laboratory report and
chain-of-custody documents are provided in Attachment II.
Pilot Travel Centers #7976 December 1, 2023
NCDEQ Facility ID #00-0-0000032304 Site Check Report-Diesel Dispenser #23
ATC Associates of North Carolina
E. Conclusion and Recommendations
Laboratory analytical results of the soil sample collected in proximity to diesel dispenser #23
did not detect TPH-GRO or TPH-DRO concentrations above established State Action Levels.
Based on available information, it appears a release has not occurred from the UDC of diesel
dispenser #23.
F. Figures
Figure 1 – Topographic Map
Figure 2 – Site Map
G. Tables
Table 1 – UST Owner and Operator Information
Table 2 – UST/AST System Information
Table 3 – Soil Analytical Results
H. Attachments
I – Notifications and Testing Results
II – Laboratory Report and Chain-of-Custody Document
TABLES
TABLE 1
UST OWNER AND OPERATOR INFORMATION
PILOT TRAVEL CENTER #7976
1006 CHARLOTTE HIGHWAY
TROUTMAN, IREDELL COUNTY, NORTH CAROLINA
NCDEQ FACILITY ID #00-0-0000032304
Revision Date:11/30/2023 Incident Number and Name:Pilot Travel Center #7976
UST ID Number All Facility ID Number 00-0-0000032304
City State Zip Telephone Number
Knoxville TN 37909 865-474-3106
City State Zip Telephone Number
As Above
Street Address
Dates of Operation (MM/DD/YY to MM/DD/YY)Name of Owner
Dates of Operation (MM/DD/YY to MM/DD/YY)Name of Operator
5508 Lonas Road
Pilot Travel Centers, LLC 1991 to present
Street Address
TABLE 2
UST/AST SYSTEM INFORMATION
PILOT TRAVEL CENTER #7976
1006 CHARLOTTE HIGHWAY
TROUTMAN, IREDELL COUNTY, NORTH CAROLINA
NCDEQ FACILITY ID #00-0-0000032304
Revision Date:11/30/2023
UST ID Number
Current/Last
Contents
Previous
Contents
Capacity
(gallons)
Construction
Details
Tank
Dimensions
Description of
Associated
Piping and
Pumps
Date Tank
Installed Status of UST
Was Release
Associates with
the UST System?
1 Diesel None 20,000 DW Steel Unknown Unknown 01/01/91 Active No
2 Diesel None 20,000 DW Steel Unknown Unknown 01/01/91 Active No
3 Gasoline (Prem)None 10,000 DW Steel Unknown Unknown 01/01/91 Active No
4 Gasoline (Reg)None 10,000 DW Steel Unknown Unknown 01/01/91 Active No
5 Gasoline (Reg)None 10,000 DW Steel Unknown Unknown 01/01/91 Active No
AST ID Number
Current/Last
Contents
Previous
Contents
Capacity
(gallons)
Construction
Details
Tank
Dimensions
Description of
Associated
Piping and
Pumps
Date Tank
Installed Status of AST
Was Release
Associates with
the AST System?
Incident Number and Name:Pilot Travel Center #7976
None associated with this site
TABLE 3
SOIL ANALYTICAL RESULTS
PILOT TRAVEL CENTER #7976
1006 CHARLOTTE HIGHWAY
TROUTMAN, IREDELL COUNTY, NORTH CAROLINA
NCDEQ FACILITY ID #00-0-0000032304
TP
H
-
G
R
O
TP
H
-
D
R
O
SB-1 (6')
Diesel
Dispenser
#23
6 0.0 11/10/23 0.0918J 1.97J
50 100
Notes:
1. Concentrations are reported in milligrams per kilogram (mg/kg).
2. PID denotes photoionization detector.
4. J denotes compound concentration estimated by the project laboratory.
State Action Level (mg/kg)
3. PPM denotes parts per million.
Sampling
ID
Sampling
Location
Sampling
Depth
(feet)
PID
Reading
(ppm)
Sampling
Date
EPA Method 8015
FIGURES
PR
O
P
E
R
T
Y
B
O
U
N
D
A
R
Y
SB-1
ATTACHMENT I
NOTIFCATIONS AND TESTING RESULTS
UST-17A UST Suspected Release 24 Hour Notice
Do not use this form to report a 24 hour notice of a Pollution Incident. You must use form UST-61, 24 Hour Release and UST Leak
Reporting Form.
➢ This form must be used to report to DEQ, within 24 hours of discovery, a Suspected Release from any of the following:
a) Failed or inconclusive leak detection or tightness test results. This includes positive test results, such as “Increase”, which
indicates the level in the UST system has increased more than 0.2 gph.
b) Unusual operating conditions which can include, but are not limited to: the erratic behavior of dispensing equipment; the
unexplained presence of water in the tank; the presence of fuel in containment sumps or interstitial spaces; or the degradation of
any equipment or element of an underground storage tank system to the point where that equipment or element can not reasonably
be expected to perform its intended function.
c) Internal inspection results such as, perforations, corrosion holes, weld failures, or other similar defects that indicate a release
could have occurred.
➢ If you have more than four UST systems to report suspected releases, then attach additional sheets of the UST-17A form. You only
need to list the UST systems at your site that have suspected releases.
➢ Within 7 days of discovery, submit a UST-17B form to document the response activities taken to investigate the suspected release.
➢ Please submit this form to: NCDEQ/DWM, UST Section
1646 Mail Service Center
Raleigh, North Carolina 27699-1646
OR
Fax to (919) 715-1117 OR UST.Permits@ncdenr.gov
I. UST OWNER II. UST FACILITY
Name:
Name:
Facility ID:
Address:
Address:
City:
State:
Zip:
City:
County:
Person Reporting:
Title of Person Reporting:
Telephone Number:
( )
Date Submitted:
III. UST INFORMATION
Tank Number / Size: / / / /
Product Stored:
Location and/or source of
suspected release: (check all that apply)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in comments)
Leak detection method or
other observation that
indicates a suspected
release. (e.g., ATG, SIR,
visual contamination, fuel
in sump, etc.):
Failed/Inconclusive date or
date that leak detection
method suspected release discovered:
IV. COMMENTS
UST-17A Revised 10/2018 http://www.wastenotnc.org/
ATTACHMENT II
LABORATORY REPORT AND
CHAIN-OF-CUSTODY DOCUMENTS
ANALYTICAL REPORT
November 20, 2023
ATC Group Services - NC Pilot
Sample Delivery Group:L1677352
Samples Received:11/13/2023
Project Number:7976-605-13
Description:Pilot 7976
Report To:Maureen Jackson
609A Piner Road Suite 115
Wilmington, NC 28409
Entire Report Reviewed By:
November 20, 2023
[Preliminary Report]
Jeff Carr
Project Manager
Results relate only to the items tested or calibrated and are reported as rounded values. This test report shall not be
reproduced, except in full, without written approval of the laboratory. Where applicable, sampling conducted by Pace
Analytical National is performed per guidance provided in laboratory standard operating procedures ENV-SOP-MTJL-0067 and
ENV-SOP-MTJL-0068. Where sampling conducted by the customer, results relate to the accuracy of the information provided,
and as the samples are received.
Pace Analytical National
12065 Lebanon Rd Mount Juliet, TN 37122 615-758-5858 800-767-5859 www.pacenational.com
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 1 of 11
November 20, 2023
Jeff Carr
Project Manager
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 1 of 11
TABLE OF CONTENTS
Cp: Cover Page 1
Tc: Table of Contents 2
Ss: Sample Summary 3
Cn: Case Narrative 4
Sr: Sample Results 5
SB-1 (6') L1677352-01 5
Qc: Quality Control Summary 6
Total Solids by Method 2540 G-2011 6
Volatile Organic Compounds (GC) by Method 8015D/GRO 7
Semi-Volatile Organic Compounds (GC) by Method 8015C 8
Gl: Glossary of Terms 9
Al: Accreditations & Locations 10
Sc: Sample Chain of Custody 11
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 2 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 2 of 11
SAMPLE SUMMARY
Collected by Collected date/time Received date/time
SB-1 (6') L1677352-01 Solid N Reel 11/10/23 09:55 11/13/23 09:00
Method Batch Dilution Preparation Analysis Analyst Location
date/time date/time
Total Solids by Method 2540 G-2011 WG2171345 1 11/17/23 17:28 11/17/23 17:41 KDW Mt. Juliet, TN
Volatile Organic Compounds (GC) by Method 8015D/GRO WG2172689 1 11/15/23 10:20 11/16/23 19:09 NCD Mt. Juliet, TN
Semi-Volatile Organic Compounds (GC) by Method 8015C WG2172197 1 11/16/23 21:04 11/17/23 15:36 JAS Mt. Juliet, TN
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 3 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 3 of 11
CASE NARRATIVE
All sample aliquots were received at the correct temperature, in the proper containers, with the
appropriate preservatives, and within method specified holding times, unless qualified or notated within
the report. Where applicable, all MDL (LOD) and RDL (LOQ) values reported for environmental samples
have been corrected for the dilution factor used in the analysis. All Method and Batch Quality Control
are within established criteria except where addressed in this case narrative, a non-conformance form
or properly qualified within the sample results. By my digital signature below, I affirm to the best of my
knowledge, all problems/anomalies observed by the laboratory as having the potential to affect the
quality of the data have been identified by the laboratory, and no information or data have been
knowingly withheld that would affect the quality of the data.
[Preliminary Report]
Jeff Carr
Project Manager
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 4 of 11
Jeff Carr
Project Manager
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 4 of 11
SAMPLE RESULTS - 01
L1677352
SB-1 (6')
Collected date/time: 11/10/23 09:55
Total Solids by Method 2540 G-2011
Result Qualifier Dilution Analysis Batch
Analyte %date / time
Total Solids 75.0 1 11/17/2023 17:41 WG2171345
Volatile Organic Compounds (GC) by Method 8015D/GRO
Result (dry)Qualifier MDL (dry)RDL (dry)Dilution Analysis Batch
Analyte mg/kg mg/kg mg/kg date / time
TPH (GC/FID) Low Fraction 0.0918 B J 0.0289 0.133 1 11/16/2023 19:09 WG2172689
(S)
a,a,a-Trifluorotoluene(FID)90.6 77.0-120 11/16/2023 19:09 WG2172689
Semi-Volatile Organic Compounds (GC) by Method 8015C
Result (dry)Qualifier MDL (dry)RDL (dry)Dilution Analysis Batch
Analyte mg/kg mg/kg mg/kg date / time
TPH (GC/FID) High Fraction 1.97 J 1.03 5.34 1 11/17/2023 15:36 WG2172197
(S) o-Terphenyl 62.0 18.0-148 11/17/2023 15:36 WG2172197
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 5 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 5 of 11
QUALITY CONTROL SUMMARYWG2171345
Total Solids by Method 2540 G-2011 L1677352-01
Method Blank (MB)
(MB) R4001697-1 11/17/23 17:41
MB Result MB Qualifier MB MDL MB RDL
Analyte %%%
Total Solids 0.000
L1677357-01 Original Sample (OS) • Duplicate (DUP)
(OS) L1677357-01 11/17/23 17:41 • (DUP) R4001697-3 11/17/23 17:41
Original Result DUP Result Dilution DUP RPD DUP Qualifier DUP RPD
Limits
Analyte %%%%
Total Solids 86.9 86.8 1 0.128 10
Laboratory Control Sample (LCS)
(LCS) R4001697-2 11/17/23 17:41
Spike Amount LCS Result LCS Rec.Rec. Limits LCS Qualifier
Analyte %%%%
Total Solids 50.0 50.0 100 90.0-110
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 6 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 6 of 11
QUALITY CONTROL SUMMARYWG2172689
Volatile Organic Compounds (GC) by Method 8015D/GRO L1677352-01
Method Blank (MB)
(MB) R4001057-3 11/16/23 16:14
MB Result MB Qualifier MB MDL MB RDL
Analyte mg/kg mg/kg mg/kg
TPH (GC/FID) Low Fraction 0.0248 J 0.0217 0.100
(S)
a,a,a-Trifluorotoluene(FID)91.7 77.0-120
Laboratory Control Sample (LCS)
(LCS) R4001057-1 11/16/23 15:05
Spike Amount LCS Result LCS Rec.Rec. Limits LCS Qualifier
Analyte mg/kg mg/kg %%
TPH (GC/FID) Low Fraction 5.50 5.85 106 72.0-127
(S)
a,a,a-Trifluorotoluene(FID) 102 77.0-120
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 7 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 7 of 11
QUALITY CONTROL SUMMARYWG2172197
Semi-Volatile Organic Compounds (GC) by Method 8015C L1677352-01
Method Blank (MB)
(MB) R4001362-1 11/17/23 11:54
MB Result MB Qualifier MB MDL MB RDL
Analyte mg/kg mg/kg mg/kg
TPH (GC/FID) High Fraction U 0.769 4.00
(S) o-Terphenyl 60.8 18.0-148
Laboratory Control Sample (LCS)
(LCS) R4001362-2 11/17/23 12:07
Spike Amount LCS Result LCS Rec.Rec. Limits LCS Qualifier
Analyte mg/kg mg/kg %%
TPH (GC/FID) High Fraction 50.0 28.4 56.8 50.0-150
(S) o-Terphenyl 54.1 18.0-148
L1677177-07 Original Sample (OS) • Matrix Spike (MS) • Matrix Spike Duplicate (MSD)
(OS) L1677177-07 11/17/23 14:18 • (MS) R4001362-3 11/17/23 14:31 • (MSD) R4001362-4 11/17/23 14:44
Spike Amount
(dry)
Original Result
(dry)MS Result (dry)MSD Result
(dry)MS Rec.MSD Rec.Dilution Rec. Limits MS Qualifier MSD Qualifier RPD RPD Limits
Analyte mg/kg %%%%%
TPH (GC/FID) High Fraction 50.9 U 29.3 29.9 57.5 59.5 1 50.0-150 2.14 20
(S) o-Terphenyl 50.8 50.6 18.0-148
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 8 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 8 of 11
GLOSSARY OF TERMS
Guide to Reading and Understanding Your Laboratory Report
The information below is designed to better explain the various terms used in your report of analytical results from the Laboratory. This is not
intended as a comprehensive explanation, and if you have additional questions please contact your project representative.
Results Disclaimer - Information that may be provided by the customer, and contained within this report, include Permit Limits, Project Name, Sample ID, Sample Matrix, Sample Preservation, Field Blanks, Field Spikes, Field Duplicates, On-Site Data, Sampling Collection Dates/Times, and Sampling Location. Results relate to the accuracy of this information provided, and as the samples are received.
Abbreviations and Definitions
(dry)Results are reported based on the dry weight of the sample. [this will only be present on a dry report basis for soils].
MDL Method Detection Limit.
MDL (dry)Method Detection Limit.
RDL Reported Detection Limit.
RDL (dry)Reported Detection Limit.
Rec.Recovery.
RPD Relative Percent Difference.
SDG Sample Delivery Group.
(S)
Surrogate (Surrogate Standard) - Analytes added to every blank, sample, Laboratory Control Sample/Duplicate and
Matrix Spike/Duplicate; used to evaluate analytical efficiency by measuring recovery. Surrogates are not expected to be
detected in all environmental media.
U Not detected at the Reporting Limit (or MDL where applicable).
Analyte The name of the particular compound or analysis performed. Some Analyses and Methods will have multiple analytes
reported.
Dilution
If the sample matrix contains an interfering material, the sample preparation volume or weight values differ from the
standard, or if concentrations of analytes in the sample are higher than the highest limit of concentration that the
laboratory can accurately report, the sample may be diluted for analysis. If a value different than 1 is used in this field, the
result reported has already been corrected for this factor.
Limits
These are the target % recovery ranges or % difference value that the laboratory has historically determined as normal
for the method and analyte being reported. Successful QC Sample analysis will target all analytes recovered or
duplicated within these ranges.
Original Sample The non-spiked sample in the prep batch used to determine the Relative Percent Difference (RPD) from a quality control
sample. The Original Sample may not be included within the reported SDG.
Qualifier
This column provides a letter and/or number designation that corresponds to additional information concerning the result
reported. If a Qualifier is present, a definition per Qualifier is provided within the Glossary and Definitions page and
potentially a discussion of possible implications of the Qualifier in the Case Narrative if applicable.
Result
The actual analytical final result (corrected for any sample specific characteristics) reported for your sample. If there was
no measurable result returned for a specific analyte, the result in this column may state “ND” (Not Detected) or “BDL”
(Below Detectable Levels). The information in the results column should always be accompanied by either an MDL
(Method Detection Limit) or RDL (Reporting Detection Limit) that defines the lowest value that the laboratory could detect
or report for this analyte.
Uncertainty
(Radiochemistry)Confidence level of 2 sigma.
Case Narrative (Cn)
A brief discussion about the included sample results, including a discussion of any non-conformances to protocol
observed either at sample receipt by the laboratory from the field or during the analytical process. If present, there will
be a section in the Case Narrative to discuss the meaning of any data qualifiers used in the report.
Quality Control
Summary (Qc)
This section of the report includes the results of the laboratory quality control analyses required by procedure or
analytical methods to assist in evaluating the validity of the results reported for your samples. These analyses are not
being performed on your samples typically, but on laboratory generated material.
Sample Chain of
Custody (Sc)
This is the document created in the field when your samples were initially collected. This is used to verify the time and
date of collection, the person collecting the samples, and the analyses that the laboratory is requested to perform. This
chain of custody also documents all persons (excluding commercial shippers) that have had control or possession of the
samples from the time of collection until delivery to the laboratory for analysis.
Sample Results (Sr)
This section of your report will provide the results of all testing performed on your samples. These results are provided
by sample ID and are separated by the analyses performed on each sample. The header line of each analysis section for
each sample will provide the name and method number for the analysis reported.
Sample Summary (Ss)This section of the Analytical Report defines the specific analyses performed for each sample ID, including the dates and
times of preparation and/or analysis.
Qualifier Description
B The same analyte is found in the associated blank.
J The identification of the analyte is acceptable; the reported value is an estimate.
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 9 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 9 of 11
Pace Analytical National 12065 Lebanon Rd Mount Juliet, TN 37122
Alabama 40660 Nebraska NE-OS-15-05
Alaska 17-026 Nevada TN000032021-1
Arizona AZ0612 New Hampshire 2975
Arkansas 88-0469 New Jersey–NELAP TN002
California 2932 New Mexico ¹TN00003
Colorado TN00003 New York 11742
Connecticut PH-0197 North Carolina Env375
Florida E87487 North Carolina ¹DW21704
Georgia NELAP North Carolina ³41
Georgia ¹923 North Dakota R-140
Idaho TN00003 Ohio–VAP CL0069
Illinois 200008 Oklahoma 9915
Indiana C-TN-01 Oregon TN200002
Iowa 364 Pennsylvania 68-02979
Kansas E-10277 Rhode Island LAO00356
Kentucky ¹ ⁶KY90010 South Carolina 84004002
Kentucky ²16 South Dakota n/a
Louisiana AI30792 Tennessee ¹ ⁴2006
Louisiana LA018 Texas T104704245-20-18
Maine TN00003 Texas ⁵LAB0152
Maryland 324 Utah TN000032021-11
Massachusetts M-TN003 Vermont VT2006
Michigan 9958 Virginia 110033
Minnesota 047-999-395 Washington C847
Mississippi TN00003 West Virginia 233
Missouri 340 Wisconsin 998093910
Montana CERT0086 Wyoming A2LA
A2LA – ISO 17025 1461.01 AIHA-LAP,LLC EMLAP 100789
A2LA – ISO 17025 ⁵1461.02 DOD 1461.01
Canada 1461.01 USDA P330-15-00234
EPA–Crypto TN00003
ACCREDITATIONS & LOCATIONS
¹ Drinking Water ² Underground Storage Tanks ³ Aquatic Toxicity ⁴ Chemical/Microbiological ⁵ Mold ⁶ Wastewater n/a Accreditation not applicable
* Not all certifications held by the laboratory are applicable to the results reported in the attached report.
* Accreditation is only applicable to the test methods specified on each scope of accreditation held by Pace Analytical.
1 Cp
2Tc
3Ss
4Cn
5Sr
6Qc
7Gl
8Al
9Sc
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 13:36 10 of 11
ACCOUNT:PROJECT:SDG:DATE/TIME:PAGE:
ATC Group Services - NC Pilot 7976-605-13 L1677352 11/20/23 14:10 10 of 11