August 11, 2023
North Carolina Department of Environmental Quality
Division of Waste Management
Solid Waste Section
2090 U.S. Highway 70
Swannanoa, NC 28778
Attn: Ms. Claire Osborn (submitted electronically)
Re: Construction Certification Report - Dual Containment Leachate Force Main
Marshall Industrial Landfill No.1
Permit No.: 1812-INDUS
Marshall Steam Station
Terrell, North Carolina 28682
Dear Ms. Osborn,
526 South Church St.
Charlotte, NC 28202
Mailing Address
P.O. Box 1006
Mail Code EC 13K.
Charlotte, NC 28201-1006
Duke Energy Carolinas, LLC (Duke Energy) completed construction of the dual containment
leachate forcemain associated with the Industrial Landfill No.1 (Permit No. 1812-INDUS-2008)
located in Terrell, North Carolina. Duke Energy is providing the enclosed "Construction Certification
Report - Dual Containment Leachate Force Main" as the final Construction Quality Assurance
documentation.
This submittal is being transmitted electronically only. If you have any questions or need additional
information regarding this submittal, please contact me at Ashley.Healy(aD_duke-energy.com or
(717) 982-0986.
Regards,
J4�4&
Ashley Healy, P.G.
Environmental Services
Attachments: Construction Certification Report - Dual Containment Leachate Force Main -
Industrial Landfill No. 1, Duke Energy Marshall Steam Station (S&ME, Inc., 2023)
cc (via e-mail): Sarah Moutos, NCDEQ
Ed Mussler, NCDEQ
Sherri Stanley, NCDEQ
Elizabeth Werner, NCDEQ
www.duke-energy.com Page 1 of 2
Jordan Russ, NCDEQ
John Metcalf, Duke Energy
Scott Saunders, Duke Energy
Chris Varner, Duke Energy
Tyler Hardin, Duke Energy
Kim Witt, Duke Energy
Ed Sullivan, Duke Energy
Sharon Korleski, S&ME
Michael Romanello, S&ME
www.duke-energy.com Page 2 of 2
Construction Certification Report
Dual Containment Leachate Force Main
Facility: Duke Energy Marshall Steam Station
Industrial Landfill No.1
Permit No. 1812-INDUS-2008
Location: Terrell, Catawba County, North Carolina
Date: August 11, 2023
Prepared for:
DUKE Duke Energy Carolinas, LLC
En 400 South Tryon Street
ENERGY Charlotte, North Carolina, 28202
Prepared By:
S&ME, Inc.
2016 Ayrsley Town Blvd., Suite 2-A
Charlotte, NC 28273
704-S23-4726
NC PE Firm License No. F-0176
Construction Certification Report - Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
Table of Contents
1.0 Introduction.......................................................................................................................1
1.1 Certification Report Organization...........................................................................................................1
1.2 Purpose....................................................................................................................................................... 2
1.3 Reference Documents................................................................................................................................ 2
1.4 Project Organization (Entity, Role & Key Personnel)...........................................................................3
1.5 Project Description.................................................................................................................................... 3
2.0 Construction Quality Assurance....................................................................................4
2.1 Leachate Force Main Piping & Vaults....................................................................................................4
2.1.1 Material.............................................................................................................................................4
2.1.2 Assembly........................................................................................................................................... 4
2.1.3 Installation........................................................................................................................................ 5
2.1.4 Pressure Testing................................................................................................................................5
2.2 Nonconformance Notices......................................................................................................................... 5
3.0 Project Documentation....................................................................................................6
3.1 Deviations from Regulatory Approved Permit to Construct..............................................................6
3.2 Construction Submittals........................................................................................................................... 6
3.3 As -Built Drawings..................................................................................................................................... 6
4.0 Engineering Certification................................................................................................6
List of As -built Drawings
Dual Containment Leachate Force Main Plan and Profile As -built
Appendices
Appendix I - CQA Site Documentation: Daily Field Reports and Site Photographs
Appendix II - As -Built Drawings
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
1.0 Introduction
This Certification Report documents the construction of a replacement section of Leachate Force Main (LFM)
associated with the Marshall Steam Station Industrial Landfill No. 1 (Permit 1812-INDUS-2008). The Marshall
Steam Station is in Terrell, North Carolina. The existing LFM alignment extends from the Industrial Landfill to the
Lined Retention Basin (LRB). It was recently modified to divert flow to and from the Leachate Basin prior to
discharge to the LRB. This design modification to the LFM was included in the Industrial Landfill (ILF) No 1. Phase
2 PTC package (October 1, 2020).
Due to the required, amended closure of the Structural Fill (CCB0031) and construction of stability features, the
design of the ILF LFM was further modified in the Structural Fill Amended Closure Plan (May 16, 2022). The
modifications to the LFM included 1) conveyance to and from the Leachate Basin, 2) dual containment for the
portion of the LFM that is located within the Structural Fill limits, and 3) relocation of the LFM outside of the
northern stability feature. The Structural Fill Amended Closure Plan including the design modifications for the ILF
LFM was approved by NCDEQ on July 12, 2022.
The LFM alignment is routed along the eastern crest of the onsite Structural Fill (CCB0031). The replacement LFM
construction is limited to the portion located within the footprint of the Structural Fill, where Final Closure
construction necessitated replacement and a partial relocation. A portion of the LFM runs directly adjacent to the
MAR-145 industrial stormwater channel. As a result, dual containment high density polyethylene (HDPE) piping
was selected to reduce environmental risk. The dual contained piping reduces the potential of a leachate release
to the MAR-145 stormwater pond. In addition, the dual contained piping will help preserve the integrity of the
Structural Fill closure system in the event of a failure of the carrier pipe. As part of the Structural Fill Closure
Construction, the existing 12-inch diameter LFM within the Structural Fill Limits was either removed or is schedule
abandoned in -place.
The Structural Fill occupies a waste footprint area of approximately 84 acres and is estimated to contain about
6,490,000 tons (about 8.8 million cubic yards) of in -place Coal Combustion Products (CCP). It is located on the
north side of the Marshall Steam Station Property, between the railroad right-of-way adjacent to Sherrills Ford
Road and Steam Plant Road to the west and the transmission corridor to the east, adjacent the new Leachate
Basin and Future Landfill Phases. The approximate center of the Structural Fill site is at Latitude 35°36'50" N,
Longitude-80°58'49" W. Its closest boundary (northwest corner) is approximately 2,600 feet southeast of the
intersection of Sherrill's Ford Road and Island Point Road.
1.1 Certification Report Organization
The Certification Report for the Dual Containment Leachate Force Main is organized into the following sections:
Section 1 — Introduction: Provides a brief overview of the project, reference documents, and key
personnel;
Section 2 — Construction Quality Assurance (CQA): Describes CQA documentation specific to the
Construction Elements;
August 11, 2023
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
Section 3 — Project Documentation: Summary of pertinent construction document clarifications and
product submittals, and As -built survey;
Section 4 — Engineering Certification.
1.2 Purpose
The purpose of this report is to document that construction of the dual containment section of force main was
performed and completed in accordance with the approved CQA Plan, the conditions of the Permit to Construct
and the requirements of Title 15A of the North Carolina Administrative Code (NCAC) Subchapter 13B Rule 0.1624.
Provided in this Certification Report are the CQA documentation related to construction observations and testing
data compiled during construction. This report has been prepared as required by, and in accordance with, North
Carolina Regulation 15A NCAC 13B.1624(b)(16).
1.3 Reference Documents
The Dual Containment Leachate Transmission Force Main was constructed in accordance with the following
documents.
Issued for Permit to Construct (PTC) Drawings, Marshall Steam Station, Structural Fill Closure Plan
Drawings, prepared for Duke Energy Carolinas, LLC, prepared by AECOM, Revision C, May 4, 2022.
Technical Specifications, Duke Energy Marshall Structural Fill Final Cover Construction, Permit No. CCB-
0037, Issued for Construction (IFC), prepared for Duke Energy Carolinas, LLC, prepared by AECOM, Revision
0, dated September 12, 2022.
Issued for Construction (IFC) Drawings, Marshall Steam Station, Structural Fill Closure Plan Drawings,
prepared for Duke Energy Carolinas, LLC, prepared by AECOM, Revision 0, September 12, 2022, and
Revision 1 dated February 28, 2023.
Construction Quality Assurance Plan, Marshall Steam Station, Structural Fill (Permit # CCB-0037) Catawba
County, North Carolina, prepared for Duke Energy Carolinas, LLC, prepared by AECOM, 1600 Perimeter
Park Drive, Morrisville, NC 27560, Revision 0, dated May 25, 2021.
Issued for Construction (IFC) Drawings, Marshall Steam Station, Industrial Landfill No. 7, Phase 2 (Cells 5
and 6) Expansion, Leachate Storage Plan Drawing No 76, prepared for Duke Energy Carolinas, LLC,
prepared by AECOM, Revision 0, dated April 1, 2021; Revision 001, dated September 28, 2021,
The conformance of the construction materials and installation methods were documented during construction in
accordance with the Permit to Construct documents listed herein, as approved by the NCDEQ. Any amendments
during construction are described in Section 4 of this report.
August 11, 2023
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
1.4 Project Organization (Entity, Role & Key Personnel)
Key project personnel, companies and their role involved with the construction of the Leachate Basin are as
follows:
Owner
Duke Energy Carolinas, LLC
400 South Tryon St., Charlotte, NC 28202
Phone No.: 704-594-6200
General Contractor
Trans Ash, Inc.
617 Shepard Dr., Cincinnati, OH 45215
Phone No.: 513-733-4770
Surveyor
Trans Ash, Inc.
617 Shepard Dr., Cincinnati, OH 45215
Phone No.: 513-733-4770
1.5 Project Description
Design Engineer
AECOM Technical Services of North Carolina
1600 Perimeter Park Dr., Ste. 400, Morrisville, NC 27560
Phone No.: 919-461-1100
COA Engineer
S&ME Inc.
1600 Ayrsley Town Blvd, Ste. 2-A, Charlotte, NC 28273
Phone No.: 704-524-4726
Leachate Force Main Installer/Subcontractor
WNC White Corporation
3563 Skyland Drive, Sylva, NC 28779
Phone No.: 828-477-4895
The Structural Fill Closure Construction consists of subgrade embankment fill, excavation of stacked ash from the
north stability feature, and installation of a geosynthetic cover system. The cover system is comprised of a
structured geomembrane overlain by a geotextile and two (2) feet of cover soil. On the north and west slope, the
cover system consists of a geomembrane-engineered turf system.
The existing LFM enters the Structural Fill at the northeast corner, then traverses the top deck along the east and
south sides. The LFM exits the limits of the Structural Fill at the southern entrance. The tie-in points for the dual
containment LFM replacement section are located on the top deck at the northeast corner, and near the southern
entrance, just outside of the Structural Fill limits. The horizontal alignment of the dual containment section
generally follows the existing LFM alignment, except where it is relocated around the north stability feature. The
total length of dual contained LFM is approximately 3,980 feet.
New vault structures were constructed near each tie-in location and house air release valves. Two additional
vaults were installed near the center for tie-in of the Leachate Basin inlet and discharge force main piping
constructed as part of the ILF Phase 2 Expansion project. A separate vault was installed to house a butterfly valve
just upstream of the tie-in with the Leachate Basin inlet force main. The Leachate Basin tie-in vaults were directly
connected with force main piping as a temporary bypass of the Leachate Basin. NCDEQ approved operation of
the Leachate Basin on July 25, 2023, and the temporary bypass was closed off. The temporary bypass will be
August 11, 2023
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013 I
permanently removed from service following satisfactory operation of the Leachate Basin during an initial
observation period.
Excavation of stacked ash for the North Stability Feature was conducted and completed prior to construction of
the LFM Relocation. To avoid disruption in service, temporary single wall HDPE force main piping was constructed
on top of the cover system subgrade adjacent to the final LFM alignment prior to the excavation task.
As part of the Structural Fill Closure Construction, the existing 12-inch diameter LFM within the Structural Fill limits
was removed with the exception of an approximate 500-foot section on the south end which is scheduled to be
abandoned in -place.
2.0 Construction Quality Assurance
S&ME provided a CQA Technician to perform CQA field services on an as -needed basis during construction of the
LFM. S&ME's observations and field testing were generally limited to part-time field observations of installation
and piping commissioning tests. For each day on site, the CQA technicians prepared a daily field report
summarizing the observed construction activities and completed CQA documentation forms and obtained site
photographs.
Daily field reports (typically including 1 or 2 photographs) for CQA documentation associated with the dual
containment force main and HDPE vault installation/construction between May 11, 2023, to July 12, 2023, are
presented in Appendix I -Section 1.
2.1 Leachate Force Main Piping & Vaults
2.1.1 Material
The prefabricated sections of dual containment force main pipe consist of a 12-inch diameter solid wall carrier
pipe inside an 18-inch diameter solid wall containment pipe. Both the carrier and the containment piping consist
of HDPE DR 17 pipe.
Except for a concrete vault housing a butterfly valve, the new vaults installed for the work consist of 60-inch
diameter DR 32.5 HDPE. The vaults are approximately 4-foot tall. A 1-inch thick, HDPE sheet stock rub sheet, 8-
foot in diameter was welded to the bottom of each vault. The HDPE vaults contain assemblies that allowed for the
transition between single wall and dual containment force main piping. The vaults also include air release valves
and ball valves to allow for the ability to isolate sections of the force main.
2.1.2 Assembly
The sections of dual containment LFM piping were joined together using butt -fusion welding. Electrofusion
couplers were used at each transition to the existing LFM. Welding was performed by WNC White Corporation.
Pipe Butt Fusion Data Logger Reports were submitted by Trans Ash via the construction submittal process to Duke
Energy personnel for review and approval.
August 11, 2023 4
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina
S&ME Project No. 212013
2.1.3 Installation
Installation of the LFM was performed by Trans Ash and subcontractor WNC White during the months of May,
June and July 2023. After staging the force main piping along the adjacent exposed subgrade, the pipe was lifted
and set into place directly on the geotextile that overlays the closure geomembrane. The vaults were also
installed over the geomembrane and geotextile. A layer of cushion geocomposite was installed underneath each
vault above the cap system.
Cover soil was placed around and over the LFM to a minimum thickness as indicated on the drawings. Detectable
metallic warning tape was installed over the LFM. S&ME observed placement of the dual containment pipe into
the final location and the placement of cover soil over the pipe.
2.1.4 Pressure Testing
The Contractor conducted hydrostatic and pneumatic pressure testing of the Dual Containment LFM in
accordance with the Technical Specifications and the Contractor's approved submittal of testing procedures.
The Contractor conducted the hydrostatic pressure test of the carrier pipe on July 6, 2023, in general accordance
with ASTM F2164. Prior to the test, the pipe was flushed to remove potential debris. The carrier pipe was slowly
filled with water to purge air from the pipe. The pipe was pressurized to 75 psi internal pressure (1.5 times the
working pressure) and held for four (4) hours for the initial expansion phase. Following the pressurizing/initial
expansion phase, the pressure was dropped to 65 psi for the testing phase and monitored for one (1) hour in
accordance with the testing requirements and project specifications. S&ME observed and documented the
hydrostatic pressure testing for adherence to the testing requirements and confirmed passing criteria was
achieved. The test results met the project requirements as documented in S&ME's daily report dated July 10,
2023.
The Contractor conducted pneumatic testing of the containment pipe on July 10, 2023. The pipe was pressurized
with air to 5 psi and held for 2.5 hours. Air pressure was observed to be maintained during this time.
2.2 Nonconformance Notices
A "nonconformance" is defined as a more significant deviation from the project requirements or procedures that
results in the occurrence of a condition adverse to quality (CQA). A "discrepancy" is defined as a construction
anomaly (e.g., failing nondestructive test result, improper test frequency, etc.) that can readily be corrected in the
field without extensive rework and within a reasonable time frame. If project "Issues" become elevated in the level
of concern, or have the potential to be incorporated into the completed construction prior to remedy, a formal
Nonconformance Report (NCR) is issued by Duke Energy or S&ME.
There were no formal Nonconformance Notices pertaining to the construction elements issued by S&ME
associated with the CQA activities documented in this report volume.
August 11, 2023
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina
S&ME Project No. 212013
3.0 Project Documentation
Duke Energy retained electronic copies of all project records generated during this construction. S&ME retained
duplicate project records deemed applicable to Construction Quality Assurance, such as design updates during
construction, pertinent product data and submittals, and as -built records. The following sections summarize this
information.
3.1 Deviations from Regulatory Approved Permit to Construct
There were no deviations from the regulatory approved permit to construct design plans.
3.2 Construction Submittals
Construction submittals included product data, fusion reports, pressure testing procedure for dual containment
pipe and leachate force main pressure testing results. These were submitted for approval by the Design Engineer
or Duke Energy. Submittal information is available upon request.
3.3 As -Built Drawings
As -built drawings documenting the installation of the dual containment LFM and the associate vault structures
were prepared by the Contractor following completion of the work. The drawings are sealed by a Professional
Surveyor registered in the state of North Carolina. S&ME reviewed the drawings for completeness and project
document requirements. As shown on the Leachate Basin Tie -In Plan As -Built, the temporary bypass between the
Leachate Basin force main piping tie-in vaults incorporated a butterfly valve. The temporary bypass will be
permanently closed off by removing the valve and fusing blind flanges on the ends of the pipe stub outs.
The As -built drawings are presented in Appendix II and summarized in the table below.
As -Built Drawing Title
Dual Containment Leachate Force Main Plan As -Built
Issued Date..
8/11/2023
. .
Trans Ash
Dual Containment Leachate Force Main Plan As -Built
8/11/2023
Trans Ash
Leachate Basin Tie -In Plan As -Built
8/11/2023
Trans Ash
4.0 Engineering Certification
Construction observations and field testing results indicate that the Dual Containment Leachate Force Main and
associated structures were constructed in accordance with the approved Structural Fill Amended Closure Plan, and
the requirements of Title 15A of the North Carolina Administrative Code (NCAC) Subchapter 13B Rule 0.1624 as
noted herein. A Certification Statement, signed and sealed by the CQA Certifying Engineer, who is a Professional
Engineer registered in the state of North Carolina, is provided herein. Certification Statements other for the
Structural Fill Closure, Leachate Basin and Landfill Expansion Construction Components are provided separately.
August 11, 2023
Construction Certification Report — Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
CONSTRUCTION CERTIFICATION STATEMENT
FOR
DUKE ENERGY — MARSHALL STEAM STATION
INDUSTRIAL LANDFILL NO. 1
PERMIT NO. INDUS-1812-2008
CONSTRUCTION CERTIFICATION REPORT
DUAL CONTAINMENT LEACHATE FORCE MAIN
OWNER: DUKE ENERGY CAROLINAS, LLC
OPERATOR: DUKE ENERGY CAROLINAS, LLC
by:
S&ME, Inc.
1600 Ayrsley Town Blvd. Road, Suite A-2
Charlotte, NC 28273
I hereby certify that the results of construction quality assurance activities conducted by S&ME Inc., as summarized in
this Certification Report, indicates that the Marshall Steam Station Dual Wall Leachate Transmission Force Main was
constructed in general accordance with the approved Construction Quality Assurance Plan, the conditions of the Permit
to Construct, and the requirements of Title 15A of the North Carolina Administrative Code (NCAC) Subchapter 13B Rule
0.1624.
Sharon Y. Korleski, P.E.
N.C. Registration No. 25846
Certifying Engineer
August 11, 2023
Appendices
Construction Certification Report - Dual Containment Leachate Force Main
Marshall Steam Station, Industrial Landfill No. 1
Terrell, Catawba County, North Carolina s
S&ME Project No. 212013
APPENDICES LIST
Appendix I - CQA Site Documentation: Daily Field Reports and Construction Photos
Appendix 11- As -Built Drawings
August 11, 2023
Appendix I - CQA Site Documentation:
Daily Field Reports and Site Photographs
DAILY REPORT Report #: DR-000020
Report Date: 08/03/2023
S&ME, Inc. Client: Project:
9751 Southern Pine Boulevard
Charlotte, NC 28273 Duke Energy Corp 212013D
Phone: 704-523-4726 P.O. Box 37929, ST25B Marshall PV Structural Fill Closure
Fax: 704-525-3953 Charlotte, NC 28237 8320 NC Hwy 150E
Terrell, NC 28682
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
05/11/2023 - MICHAEL T. ROMANELLO - Periodic -
Activity: CQA Project Manager Site Visit
Observations
• Personnel from S&ME, Duke Energy, and Trans Ash met onsite for a Quality Walkdown
• Trans Ash subcontractor White Corp was observed fusing dual containment PE force main
pipe on the top deck of the Structural Fill (east berm, south end)
• Meeting participants discussed the approach to move and place the force main into final
position once the cover system is installed.
• Trans Ash plans to move long sections of the force main from fusing area and stage along the
east berm adjacent to the proposed alignment.
• Geomembrane and geotextile cover system, being installed from the west, will stop once it
reaches the force main alignment to allow Trans Ash to work from the subgrade area.
• Trans Ash will utilize an excavator to lift and move force main into final location, taking caution
not to drag the piping over the cover system.
Dual Containment PE Pipe fusing in progress
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
06/09/2023 - DAVID A. CALABRIS - Periodic -
Activity: Leachate Force Main Placement
• Trans Ash and subcontractor White Corp began moving the fused Leachate Force Main onto
the cover system.
• Force Main was previously fused and staged along the eastern berm.
• Crews used an excavator - which operated on the subgrade - to move the pipe into final
position directly on top of the geotextile.
• Placement started at the north end.
The presence of S&ME at the project site shall not be construed as an acceptance or approval of activities at the
site. S&ME is at the site to perform specific services and has certain responsibilities which are limited to those
specifically authorized in our agreement with our client. The results of tests or observations performed are only
applicable to the time and location of the tests or observations. Testing frequency is dependent on our being
informed of work in progress at the site and staffing level. In no event shall S&ME be responsible for the safety or
means and methods of other parties at the project site.
Page 1
DAILY REPORT
Report #: DR-000020
Report Date: 08/03/2023
11=
S&ME, Inc.
9751 Southern Pine Boulevard
Charlotte, NC 28273
Phone:704-523-4726
Fax:704-525-3953
Client:
Duke Energy Corp
P.O. Box 37929, ST25B
Charlotte, NC 28237
Project:
212013D
Marshall PV Structural Fill Closure
8320 NC Hwy 150E
Terrell, NC 28682
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
07/06/2023 - DAVID A. CALABRIS - Periodic -
Activities: Hydrostatic test of dual containment LFM carrier pipe
Observations
• Trans Ash/White Corp performed hydrostatic pressure test of the 12" carrier pipe today.
• Contractors set up near the center at the Leachate Basin tie-in and conducted the test on the
entire length of relocated force main on the structural fill.
• Pipe was previously flushed and setup with testing apparatus and blind flanges on the ends.
• Contractors pressurized pipe to 75 psi for the 4 hours (initial expansion)
• After 4 hours, pressure was dropped to 65 psi and the 1 hour test phase began in
accordance with ASTM F 2164.
• Initial and final readings of the pressure gage indicated a change of less than 5% indicating a
passing test
75 psi gage reading for initial expansion phase.
65 psi at end of 1 hr test
The presence of S&ME at the project site shall not be construed as an acceptance or approval of activities at the
site. S&ME is at the site to perform specific services and has certain responsibilities which are limited to those
specifically authorized in our agreement with our client. The results of tests or observations performed are only
applicable to the time and location of the tests or observations. Testing frequency is dependent on our being
informed of work in progress at the site and staffing level. In no event shall S&ME be responsible for the safety or
means and methods of other parties at the project site.
Page 2
DAILY REPORT Report #: DR-000020
Report Date: 08/03/2023
S&ME, Inc. Client: Project:
9751 Southern Pine Boulevard
Charlotte, NC 28273 Duke Energy Corp 212013D
Phone: 704-523-4726 P.O. Box 37929, ST25B Marshall PV Structural Fill Closure
Fax: 704-525-3953 Charlotte, NC 28237 8320 NC Hwy 150E
Terrell, NC 28682
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
07/08/2023 - DAVID A. CALABRIS - Periodic -
Activity: Pneumatic testing of dual containment LFM containment pipe
• Trans Ash an WNC White prepared carrier pipe for air pressure test of both the north and
south segments.
• Due to high air temperatures and sun exposure, Contractors were unable to reach the
planned pressure.
• Testing phase was scheduled for early hours of Monday, July 10.
COA - Polyethylene Pipe - Observations - Generally Conforms with Required
07/10/2023 - DAVID A. CALABRIS - Continuous -
Activity: Pneumatic testing of dual containment LFM containment pipe
• Trans Ash an WNC White were onsite at 4am and began preparations for air pressure testing
of the carrier pipe - both the north and south segments.
• Contractors introduced air pressure to 5 psi.
• Pressure was observed to be maintained for 2.5 hours in accordance with the approved test
plan.
The presence of S&ME at the project site shall not be construed as an acceptance or approval of activities at the
site. S&ME is at the site to perform specific services and has certain responsibilities which are limited to those
specifically authorized in our agreement with our client. The results of tests or observations performed are only
applicable to the time and location of the tests or observations. Testing frequency is dependent on our being
informed of work in progress at the site and staffing level. In no event shall S&ME be responsible for the safety or
means and methods of other parties at the project site.
Page 3
DAILY REPORT
Report #: DR-000020
Report Date: 08/03/2023
11=
S&ME, Inc.
9751 Southern Pine Boulevard
Charlotte, NC 28273
Phone:704-523-4726
Fax:704-525-3953
Client:
Duke Energy Corp
P.O. Box 37929, ST25B
Charlotte, NC 28237
,a •� �� j . f. i.R�f a .
Arl
f f
f�
t
_ fI
• 'f
1!�
Gage reading at start of test: 5 psi
Project:
212013D
Marshall PV Structural Fill Closure
8320 NC Hwy 150E
Terrell, NC 28682
Gage reading at end of test: 5 psi
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
07/11/2023 - DAVID A. CALABRIS - Periodic -
Activity: Dual Containment Force Main Tie -In
Observations
• Trans Ash/WNC White were observed to be working on the tie-in of the dual containment
force main to the existing LFM at the south end of the Structural Fill.
• Crews continued excavation around the tie-in area
• Crew completed the tie-in to the existing single wall LFM with an electrofusion coupling.
The presence of S&ME at the project site shall not be construed as an acceptance or approval of activities at the
site. S&ME is at the site to perform specific services and has certain responsibilities which are limited to those
specifically authorized in our agreement with our client. The results of tests or observations performed are only
applicable to the time and location of the tests or observations. Testing frequency is dependent on our being
informed of work in progress at the site and staffing level. In no event shall S&ME be responsible for the safety or
means and methods of other parties at the project site.
Page 4
DAILY REPORT
Report #: DR-000020
Report Date: 08/03/2023
11=
S&ME, Inc.
9751 Southern Pine Boulevard
Charlotte, NC 28273
Phone:704-523-4726
Fax:704-525-3953
Tie-in at South End of Structural Fill
Client:
Duke Energy Corp
P.O. Box 37929, ST25B
Charlotte, NC 28237
Project:
212013D
Marshall PV Structural Fill Closure
8320 NC Hwy 150E
Terrell, NC 28682
I
Electrofusion coupling
CQA - Polyethylene Pipe - Observations - Generally Conforms with Required
07/12/2023 - DAVID A. CALABRIS - Periodic -
Activity: Dual Containment Force Main Tie -In
Sunny/80s
Observations:
• White Corp completed the tie in of the Dual Containment Force Main to the existing force
main on the north end of the Structural Fill.
• Connection from dual containment to single wall was made with an electrofusion coupler
Electrofusion Coupler
The presence of S&ME at the project site shall not be construed as an acceptance or approval of activities at the
site. S&ME is at the site to perform specific services and has certain responsibilities which are limited to those
specifically authorized in our agreement with our client. The results of tests or observations performed are only
applicable to the time and location of the tests or observations. Testing frequency is dependent on our being
informed of work in progress at the site and staffing level. In no event shall S&ME be responsible for the safety or
means and methods of other parties at the project site.
Page 5
Appendix II - As -Built Drawings
DocuSign Envelope ID: 6A5BA9CC-F4C2-4FOF-AB69-8B82DC93C443
40
77
MARSHALL
150
16
CAKE NORMAN
321
485
85
M
-L
-K
STRUCTURAL
Fl,tilts , —
CELL
5
CELL
r
Pv 6N�1,
STRUCTURAL FUTURE PHASES
FILL LEACHATE - q J 11
/ BASIN PH1804
ASE II A
GATE 29 x--L
AREA T
� ;KEA #1
FGD LANDFILL
I II 1804 <
_ LAYDOWN PHASE I
BASIN #2
TRAILERS
.AREA #4 P�u
VICINITY MAP
(NOT TO SCALE) LAKE
N RMAN
MARSHALL
GATE STEAM STATIO
18 a _ °❑
NC HIGHWAY 150
ago
890
— B9o_
--- ��
O
C)�
NON
N
TIE INTO EXISTING 12"
INDUSTRIAL LANDFILL If 1 LEACHA TE PIPE
g50 /
80o
r
,f
/ 715� 880 -
SSE,888
$gS
0
O
0
O
O
O
�
O
N
L)
N
�
N
M
-F-
N
N
STRUCTURAL FILL (C13130031)
O
0
0
0
+
+
--i
+ +
+
d'
�
r
� �
LEACHA TE BASIN DISCHARGE FORCEMAIN
Surveyor's Certificate
The control for this project was provided by Christopher Blake Sexton, PLS L-5347, as shown on survey by Trans Ash titled "Marshall Steam Station
Industrial Landfill No. 1 (1812-Indus), Phase 2 (Cell 5 and 6) Expansion, Cell 5 Underdrain Top of Rock Topographic Survey" dated 2021-10-27.
(1) Class of survey: AA
(2) Positional accuracy: 0.03'
(3) Type of GPS field procedure: RTK
(4) Dates of survey: 2021-10-16
(5) Datum/Epoch: NAD83 (2011)
(6) Published/Fixed-control used: Control provided by client for site calibration. Used NGS Steam monument for check on control provided by client.
(7) Geoid model: None, control provided by client for site calibration.
(8) Combined grid factor(s): 0.999857660 centered on TA1 Base (see Marshall control information on face of this map).
(9) Units: US Survey Foot
I, Adam M. Naylor, certify that this topographic survey was completed under my direct and responsible charge from an actual survey made under my
supervision; that this ground survey was performed at the 95 percent confidence level to meet Federal Geographic Data Committee Standards; that this
survey was performed to meet the requirements for a topographic/planimetric survey to the accuracy of Class AA and vertical accuracy when applicable to
the Class A standard, and that the original data was obtained on 07-01-2023: that the survey was completed on 07-17-2023; contours shown hereon as
broken lines may not meet the stated standard; and all coordinates are referenced to North Carolina State Plane Coordinate System, NAD 83 (2011) and all
elevations are based on NAVD 88. DocuSigned by:
a N (hr
24DE925DA5F9473... ;`�� �FESSlp !9*
Q •• [�ocu Signed by:
EAL
Adam M. Naylor, North Carolina PLS L-5493 LS5493 [24—DE925DA5F9473
For and on behalf of Trans Ash =
2502
— N. 684807
E: 1412068
EL: 835. JO
LEACHA TE BASIN INLET FORCEMAIN
NOTES:
1. CONTOUR INTERVAL IS TWO(2) FOOT. ELEVATIONS SHOWN HEREON ARE RELATIVE TO NORTH AMERICAN VERTICAL DATUM
1988.
2. SURVEY PERFORMED FROM 07-01-2022 TO 07-17-2023. SURVEY INFORMATION SHOWN HEREON WAS DERIVED FROM
RANDOM AND PREDETERMINED GROUND SHOTS UTILIZING A TRIMBLE SPS986 GPS RECEIVER.
3. SURFACE AND SUB -SURFACE UTILITIES SHOWN HEREON ARE BASED UPON SURFACE OBSERVATIONS AND PUBLIC
RECORDS AND OTHER DOCUMENTS PROVIDED TO THE SURVEYOR. TRANS ASH CANNOT GUARANTEE ABSOLUTE
ACCURACY OR THAT THERE ARE NO OMISSIONS IN LOCATION OF UNDERGROUND UTILITIES. THEREFORE TRANS ASH
DISCLAIMS ALL LIABILITY FOR ANY DAMAGES BASED ON UTILITY INFORMATION PROVIDED BY THIS SURVEY. USER OF THIS
INFORMATION ASSUMES ALL RISK AND NOTICE IS HEREBY GIVEN THAT NORTH CAROLINA 811 UTILITY LOCATION SERVICE IS
TO BE NOTIFIED PRIOR TO ANY EXCAVATION OF THE SITE AS REQUIRED BY LAW.
4. EXCEPT AS SPECIFICALLY STATED OR SHOWN ON THIS SURVEY, THIS SURVEY DOES NOT PURPORT TO REFLECT ANY OF THE
FOLLOWING WHICH MAY BE APPLICABLE TO SUBJECT PROPERTY: EASEMENTS, OTHER THAN POSSIBLE EASEMENTS THAT
WERE VISIBLE AT THE TIME OF THIS SURVEY, BUILDING SETBACK LINES, RESTRICTIVE COVENANTS, SUBDIVISION
RESTRICTIONS, ZONING OR OTHER LAND -USE REGULATIONS, AND OTHER FACTS THAT AN ACCURATE AND CURRENT TITLE
SEARCH MAY DISCLOSE. SURVEYOR WAS NOT FURNISHED A TITLE REPORT.
S. ALL DISTANCES SHOWN HEREON ARE HORIZONTAL GROUND DISTANCES IN U.S. SURVEY FEET.
6. THIS MAP DOES NOT MEET G.S. 47-30 AND IS NOT TO BE USED FOR RECORDING OR CONVEYANCE.
North - As Noted
NORTH CAROLINA STATE PLANE COORDINATE SYSTEM,
NORTH AMERICAN DATUM (NAD) 1983 (2011), US SURVEY FOOT
POINT NORTHING EASTING ELEVATION DESCRIPTION
A
685720
1411729
889.1
TIE INTO EXISTING 12 IN FORCE MAIN
B
685711
1411728
891.7
TOP OF HDPE VAULT
C
685706
1411727
889.8
TOP OF PIPE AT VA U LT
D
684378
1411927
888.4
TOP OF PIPE AT VAULT
E
684375
1411926
890.4
TOP OF CONCRETE VAULT
F
684365
1411929
888.4
TOP OF PI PE AT VAULT
G
684360
1411930
890.3
TOP OF HDPE VAULT
H
684345
1411932
889.8
TOP OF HDPE VAULT
I
684342
1411939
889.2
TOP OF CONCRETE VAULT
J
684340
1411933
887.6
TOP OF PI PE AT VAULT
K
682545
1411776
889.6
TOP OF PI PE AT VAULT
L
682541
1411774
890.5
TOP OF HDPE VAULT
M
682532
1411771
889.2
TIE INTO EXISTING 12 IN FORCE MAIN
B
C_
MARSHALL CONTROL INFORMATION
FIXED STATION REFERENCE INFORMATION
NAME: TA1 BASE
LATITUDE: N035° 36' 13.81895"
LONGITUDE: W080° 58' 11.47354"
ELLIPSOID HEIGHT: 705.48 USFT
GRID COORDINATES (USFT):
NORTHING: 680506.142
EASTING: 1414495.162
ELEVATION: 809.17'
COMBINE FACTOR: 0.999857660
CENTERED ON TA1 BASE.
GRAPHIC SCALE 1"150'
0 150 300 450
TIE INTO EXISTING 12"
INDUSTR/AL LANDFILL i 1 LEA CHA TE PIPE
LEGEND:
18 INCH DUAL WALL HDPE PIPE
SINGLE WALL 12 IN HDPE PIPE
MAJOR CONTOUR- SUBGRADE
MINOR CONTOUR- SUBGRADE
STRUCTURAL FILL LIMIT OF WASTE
J
M
D
110
00
00
cn
fV
Pa
0Q
0
Z
J
a
z
_J
0
�
O�I00
z<
<
G
W
J
Q
=
LU
UO
�
=
V
LU
J
z
z
O
J
oc
LU
lz
LU
O
LL
rl
z
JLU
LL
z
Q
J
z
O
O
U
Uz
J
Q
o00
0
fV
0
,1
w
M
N
CD
00
U_
Z
Z
�
Z
Q
__ i
0
u..i
J
Q
LU>z
i
Q
>
LU
W
LU
0
OC
aCf
<
>
0
V)
�
o
Q
L,
N
1
r
E
vf)
o E
y U
c in
U � N
�a
0
" > L
E
in
v z
L
a M
L
N v_
J
1111111111011111
E
(3)
U
rn
0
M
v
Ln
0
U
c COPYRIGHT TRANS ASH, INC. 2023
DocuSign Envelope ID: 6A5BA9CC-F4C2-4FOF-AB69-8B82DC93C443
DocuSign Envelope ID: 6A5BA9CC-F4C2-4FOF-AB69-8B82DC93C443