Loading...
HomeMy WebLinkAboutFA-30295_0_CA_SCH_20231009 AECOM AECOM 919.461.1100 tel. 6000 Fairview Road, Suite 200 919.461.1415 fax Charlotte, NC 28210 October 9, 2023 Ms. Sarah Brown AECOM Project # 60702558-017 NCDEQ Fayetteville Regional Office 225 Green Street, Suite 714 Fayetteville, North Carolina 28301 Subject: Site Check Report Speedway #6985 5170 NC 42 West, Garner, NC 27529 Facility ID# 00-0-34594 Dear Ms. Brown: AECOM Technical Services, Inc. of North Carolina (AECOM) on behalf of Speedway, LLC (Speedway) is presenting this Site Check Report for the above referenced store (Figure 1). On September 6, 2023, a third-party tester discovered a line tightness failure corresponding to the 10,000-gallon premium underground storage tank (UST). A UST-17B form was filed with the North Carolina Department of Environmental Quality (NCDEQ), included as Attachment A. To determine if a release may have occurred to the environment, assessment activities were conducted as documented in this report. A soil boring log has been included as Attachment B, and the laboratory report for the samples collected during the site check has been included as Attachment C. One previous release has been associated with this site – Incident #42117 from September 2017 closed with no further action in August 2018. SITE ACTIVITIES Soil Sampling On September 20, 2023, AECOM met with Sweetwater Utility Exploration (Sweetwater) at the site to collect a soil sample – SB-1 near the 10,000-gallon premium spill bucket (Figure 2). Sweetwater air knifed the soil borings to a depth of approximately 3 feet below ground surface (bgs), then AECOM used a hand auger to collect the soil sample. The sample was collected at approximately 3 feet bgs and screened with a photoionization detector (PID). A soil boring log is included as Attachment B. AECOM bottled the sample for laboratory analysis for total petroleum hydrocarbons for gasoline range organics (TPH-GRO). The samples were submitted to Pace Analytical Services in Huntersville, North Carolina for analysis at the Huntersville, North Carolina laboratory. AECOM Page 2 RESULTS Based on laboratory analysis, the soil sample collected from SB-1 did not exceed the soil contamination action level established by NCDEQ. Laboratory analysis did not detect concentrations of TPH-GRO in sample SB-1. The laboratory report is included in Attachment C. CONCLUSIONS AND RECOMMENDATIONS Based on laboratory analysis of the soil sample collected near the 10,000-gallon premium UST spill bucket, no NCDEQ action levels were exceeded. AECOM, on behalf of Speedway recommends that this release be closed out with no further action. If you have any questions, please call Nicole Long, AECOM Project Manager, at (704) 649-6586. Sincerely, AECOM Diamond Clark Nicole Long Environmental Scientist I Project Manager diamond.clark@aecom.com nicole.long@aecom.com Marie Treiber Regional Senior Project Manager Marie.Treiber@aecom.com cc: Speedway Project File Figure 1 Site Location Map Figure 2 Site Plan Attachments: A – UST-17B Form B – Soil Boring Log C – Laboratory Analytical Report AECOM Page 2 Professional Certification Page I, Brett G. Schaefer, a Licensed Engineer for AECOM Technical Services of North Carolina, Inc., do certify that the information contained in this report is correct and accurate to the best of my knowledge. _________________________________ Brett G. Schaefer, PE AECOM Technical Services of North Carolina, Inc. AECOM Technical Services of North Carolina, Inc. is licensed to practice geology in North Carolina. The certification number of the company or corporation is F-0458. 2,0002,000 SITE LOCATION FIGURE 1SITE LOCATION MAP Source: Topo USGS 7.5 Minute Topographic Map Quadrangle: Edmondson, NC Copyright: 2022 National Geographic Society DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:File: C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6985 Garner\6985 Garner.dwg Layout: Site Location Map Date: 06 Oct, 2023 Xrefs:00 SCALE IN FEET: NOTE: ALL MAP FEATURES ARE APPROXIMATE IN SCALE AND LOCATION. N I. DUMITRUOCTOBER 2023 N. LONG Speedway Store #6985 5170 NC-42 Garner, NC 27529 60702558 Speedway LLC. Propane ASTShedsTrashEnclosureBillboardAirCanopy &GasolineDispenserIslandsTank FieldTank FieldCanopy & DieselDispenser IslandsSpeedway Store #6985/ Wendy'sSignS o n - L a n P a r k w a yN C H i g h w a y 4 2A l l e yA l l e y GrassGrassGrassAsphalt ConcreteConcreteAsphaltConcreteConcrete AsphaltVent PipeVent PipesSB-1SCALE IN FEET:30300DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6985 Garner\6985 Garner.dwg, 10/6/2023 2:26 PM, Dumitru, Ionut, PDF995.pc3, User32767, 1'-0" = 1'-0"N I. DUMITRUOCTOBER 2023N. LONGFIGURE 2SITE PLANLEGENDCommunicationsNOTE: ALL MAP FEATURES ARE APPROXIMATEIN SCALE AND LOCATION.Speedway Store #69855170 NC-42Garner, NC 2752960702558Speedway LLC.Unknown Utility LineApproximate Site Property BoundaryFenceProduct DispenserUnderground Storage TankUtility Pole / Power PoleLight Post / Traffic LightCatch Basin / Stormwater InletOverhead WireBuried Electric LineNatural Gas LineProduct PipingApproximate Property BoundaryApproximate Building FootprintSB-1Soil Sample Locationand Identification ATTACHMENT A UST-17B FORM Premium line tightness testing failed 9/6/2023. Issue attributed to flex connector in STP sump. Liquid in Premium STP sump was removed. STP sump was hydro tested with failing results. The Premium line is out of service until repaired. Repair scheduled for 9/7/2023 and Site check pending. ATTACHMENT B SOIL BORING LOG Checked by ________Nicole Long_____________________Date:__10/5/23_________________ PROJECT NAME: Speedway #6985 PROJECT NUMBER: 60702558 SB-1 SITE LOCATION: 5170 NC 42 West, Garner, NC 27529 SHEET: 1 of 1 GENERAL LOCATION ON-SITE: PUL spill bucket RIG TYPE: N/A DEPTH TO WATER - OBSERVED IN BORING (feet): N/A BORING DIAMETER: FIELD GEOLOGIST: Kade Porterfield DRILLING CONTRACTOR: Sweetwater DATE STARTED: September 20, 2023 DRILLING METHOD: Hand Auger DATE FINISHED: September 20, 2023 BORING DEPTH: 3 feet bgs WEATHER: PRE-DIG METHODS: Air Knife Depth (ft)Lab Sample IDLab Sample Depth (ft.)PID Reading (ppm)Sampling MethodMATERIALS: Main component, additional components, color, moisture, plasticity, density/consistency, odor or other descriptive information Hand Auger NOTES: BGS - Below ground surface Field Instrument QA/QC: Model & Serial Numbers - Mini Rae 3000 592-912390 Calibration Gas Lot # 302-40262687 0-1 SB-12-3 1-2 Concrete Red silty clay Brown medium/fine grain sand3 ft bgs 4.0 ATTACHMENT C LABORATORY ANALYTICAL REPORT #=CL# September 29, 2023 LIMS USE: FR - NICOLE LONG LIMS OBJECT ID: 92689679 92689679 Project: Pace Project No.: RE: Nicole Long AECOM 6000 Fairview Road, Suite 200 Charlotte, NC 28210 SPEEDWAY 6985 GARNER Dear Nicole Long: Enclosed are the analytical results for sample(s) received by the laboratory on September 21, 2023. The results relate only to the samples included in this report. Results reported herein conform to the applicable TNI/NELAC Standards and the laboratory's Quality Manual, where applicable, unless otherwise noted in the body of the report. The test results provided in this final report were generated by each of the following laboratories within the Pace Network: • Pace Analytical Services - Charlotte If you have any questions concerning this report, please feel free to contact me. Sincerely, Bonnie Vang bonnie.vang@pacelabs.com Project Manager 704-977-0968 Enclosures REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 1 of 13 #=CP# CERTIFICATIONS Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Pace Analytical Services Charlotte South Carolina Laboratory ID: 99006 9800 Kincey Ave. Ste 100, Huntersville, NC 28078 North Carolina Drinking Water Certification #: 37706 North Carolina Field Services Certification #: 5342 North Carolina Wastewater Certification #: 12 South Carolina Laboratory ID: 99006 South Carolina Certification #: 99006001 South Carolina Drinking Water Cert. #: 99006003 Florida/NELAP Certification #: E87627 Kentucky UST Certification #: 84 Louisiana DoH Drinking Water #: LA029 Virginia/VELAP Certification #: 460221 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 2 of 13 #=SS# SAMPLE SUMMARY Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Lab ID Sample ID Matrix Date Collected Date Received 92689679001 SB-1 Solid 09/20/23 14:00 09/21/23 14:34 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 3 of 13 #=SA# SAMPLE ANALYTE COUNT Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Lab ID Sample ID Method Analytes Reported LaboratoryAnalysts 92689679001 SB-1 EPA 8015C 2 PASI-CTEG SW-846 1 PASI-CKDF PASI-C = Pace Analytical Services - Charlotte REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 4 of 13 #=HO# SUMMARY OF DETECTION Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Parameters AnalyzedResult Lab Sample ID Report Limit QualifiersUnitsMethod Client Sample ID 92689679001 SB-1 Percent Moisture 9.5 %09/25/23 17:16 N20.10SW-846 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 5 of 13 #=AR# ANALYTICAL RESULTS Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Sample:SB-1 Lab ID:92689679001 Collected:09/20/23 14:00 Received:09/21/23 14:34 Matrix:Solid Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions. Parameters Results Units DF Prepared Analyzed CAS No.QualMDLLimit Report Analytical Method: EPA 8015C Preparation Method: EPA 5030B Pace Analytical Services - Charlotte Gasoline Range Organics Gas Range Organics (C6-C10)ND mg/kg 09/26/23 18:1209/26/23 12:427.2 2.0 1 Surrogates 4-Bromofluorobenzene (S)94 %09/26/23 18:12 460-00-409/26/23 12:4266-130 1 Analytical Method: SW-846 Pace Analytical Services - Charlotte Percent Moisture Percent Moisture 9.5 %09/25/23 17:16 N20.10 0.10 1 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 09/29/2023 08:18 AM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 6 of 13 #=QC# QUALITY CONTROL DATA Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result. QC Batch: QC Batch Method: Analysis Method: Analysis Description: 802076 EPA 5030B EPA 8015C Gasoline Range Organics Laboratory:Pace Analytical Services - Charlotte Associated Lab Samples:92689679001 Parameter Units Blank Result Reporting Limit Qualifiers METHOD BLANK:4154662 Associated Lab Samples:92689679001 Matrix:Solid AnalyzedMDL Gas Range Organics (C6-C10)mg/kg ND 6.0 09/26/23 16:031.7 4-Bromofluorobenzene (S)%95 66-130 09/26/23 16:03 Parameter Units LCS Result % Rec Limits Qualifiers% RecConc. 4154663LABORATORY CONTROL SAMPLE: LCSSpike Gas Range Organics (C6-C10)mg/kg 47.949.7 96 70-130 4-Bromofluorobenzene (S)%99 66-130 Parameter Units MS Result % Rec Limits Qualifiers% RecConc. 4154665MATRIX SPIKE SAMPLE: MSSpike Result 92689802001 Gas Range Organics (C6-C10)mg/kg 69.872.6 95 57-154ND 4-Bromofluorobenzene (S)%94 66-130 Parameter Units Dup Result Max RPD QualifiersRPDResult 92689683001 4154664SAMPLE DUPLICATE: Gas Range Organics (C6-C10)mg/kg ND 30<8.2 4-Bromofluorobenzene (S)%9696 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 09/29/2023 08:18 AM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 7 of 13 #=QC# QUALITY CONTROL DATA Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result. QC Batch: QC Batch Method: Analysis Method: Analysis Description: 801896 SW-846 SW-846 Dry Weight/Percent Moisture Laboratory:Pace Analytical Services - Charlotte Associated Lab Samples:92689679001 Parameter Units Dup Result Max RPD QualifiersRPDResult 92689624007 4153862SAMPLE DUPLICATE: Percent Moisture %27.4 N2112530.7 Parameter Units Dup Result Max RPD QualifiersRPDResult 92689612006 4153868SAMPLE DUPLICATE: Percent Moisture %21.3 N232520.6 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 09/29/2023 08:18 AM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 8 of 13 #=QL# QUALIFIERS Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER DEFINITIONS DF - Dilution Factor, if reported, represents the factor applied to the reported data due to dilution of the sample aliquot. ND - Not Detected at or above adjusted reporting limit. TNTC - Too Numerous To Count J - Estimated concentration above the adjusted method detection limit and below the adjusted reporting limit. MDL - Adjusted Method Detection Limit. PQL - Practical Quantitation Limit. RL - Reporting Limit - The lowest concentration value that meets project requirements for quantitative data with known precision and bias for a specific analyte in a specific matrix. S - Surrogate 1,2-Diphenylhydrazine decomposes to and cannot be separated from Azobenzene using Method 8270. The result for each analyte is a combined concentration. Consistent with EPA guidelines, unrounded data are displayed and have been used to calculate % recovery and RPD values. LCS(D) - Laboratory Control Sample (Duplicate) MS(D) - Matrix Spike (Duplicate) DUP - Sample Duplicate RPD - Relative Percent Difference NC - Not Calculable. SG - Silica Gel - Clean-Up U - Indicates the compound was analyzed for, but not detected. Acid preservation may not be appropriate for 2 Chloroethylvinyl ether. A separate vial preserved to a pH of 4-5 is recommended in SW846 Chapter 4 for the analysis of Acrolein and Acrylonitrile by EPA Method 8260. N-Nitrosodiphenylamine decomposes and cannot be separated from Diphenylamine using Method 8270. The result reported for each analyte is a combined concentration. Reported results are not rounded until the final step prior to reporting. Therefore, calculated parameters that are typically reported as "Total" may vary slightly from the sum of the reported component parameters. Pace Analytical is TNI accredited. Contact your Pace PM for the current list of accredited analytes. TNI - The NELAC Institute. ANALYTE QUALIFIERS The lab does not hold NELAC/TNI accreditation for this parameter but other accreditations/certifications may apply. A complete list of accreditations/certifications is available upon request.N2 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 09/29/2023 08:18 AM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 9 of 13 #=CR# QUALITY CONTROL DATA CROSS REFERENCE TABLE Pace Project No.: Project: 92689679 SPEEDWAY 6985 GARNER Lab ID Sample ID QC Batch Method QC Batch Analytical Method Analytical Batch 92689679001 802076 802132SB-1 EPA 5030B EPA 8015C 92689679001 801896SB-1 SW-846 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 09/29/2023 08:18 AM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 10 of 13 Page 11 of 13 Page 12 of 13 Page 13 of 13