June 16, 2023
Mr. James Brown AECOM Project # 60702558.002
North Carolina Department of Environmental Quality
Division of Waste Management – UST Section
Fayetteville Regional Office
225 Green Street, Suite 714, Systel Building
Fayetteville, North Carolina 28301
Subject: Site Check Report
Speedway #6991
110 W. Martin Luther King, Jr. Blvd Roseboro, NC 28382
Facility ID# 0-036875
Dear Mr. Brown:
AECOM Technical Services, Inc. of North Carolina (AECOM) on behalf of Speedway, LLC
(Speedway) is presenting this Site Check Report for the above referenced store (Figure 1). On
January 3, 2023, fuel was discovered in the submersible turbine pump (STP) for the 15,000-gallon
regular unleaded (RUL) gasoline UST and failed hydrostatic testing on January 6, 2023. UST-17A
Form & UST-17B Form were filed with the North Carolina Department of Environmental Quality
(NCDEQ) on January 4, 2023, and January 6, 2023, and are included as Attachment A. To
determine if a release may have occurred to the environment, assessment activities were
conducted as documented in this report. A soil boring log has been included as Attachment B,
and the laboratory report for the soil sample taken during the site check has been included as
Attachment C.
There are no active or historical release incidents associated with the Site.
SITE ACTIVITIES
Soil Sampling
On May 18, 2023, AECOM met with Sweetwater Utility Exploration (Sweetwater) at the site to
collect soil sample (SB-1 (RUL) 3’) from near the STP for the 15,000-gallon RUL UST (Figure 2).
Sweetwater air knifed the soil boring to a depth of approximately 3 feet below ground surface (bgs),
then AECOM used a hand auger to collect the soil sample. The soil sample was collected at
approximately 3 feet bgs and screened with a photoionization detector (PID). A soil boring log is
included as Attachment B. AECOM bottled the sample for laboratory analysis for total petroleum
hydrocarbons for gasoline range organics (TPH-GRO). The sample was submitted to Pace
Analytical Services in Huntersville, North Carolina for analysis at the Huntersville, North Carolina
laboratory.
AECOM
Site Check Report June 2023
Speedway 6991 Page 2
Roseboro, North Carolina
RESULTS
Based on laboratory analysis, a detectable concentration of TPH-GRO was not reported in the soil
sample SB-1 (RUL) 3’. The laboratory report is included in Attachment C.
CONCLUSIONS AND RECOMMENDATIONS
Based on this information, a release at the site does not appear to have occurred. AECOM, on
behalf of Speedway recommends that this potential release receive a no further action (NFA).
If you have any questions, please call Nicole Long, AECOM Project Manager, at (704) 649-6586.
Sincerely,
AECOM
Elizabeth Andrews Nicole Long
Environmental Scientist I Project Manager
elizabeth.andrews@aecom.com nicole.long@aecom.com
Marie Treiber
Regional Senior Project Manager
Marie.Treiber@aecom.com
cc: Speedway Project File
Figure 1 Site Location Map
Figure 2 Site Map
Attachments: A – UST-17A Form & UST-17B Form
B – Soil Boring Log
C – Laboratory Analytical Report
AECOM
Site Check Report June 2023
Speedway 6991 Page 3
Roseboro, North Carolina
Professional Certification Page
I, Brett G. Schaefer, a Licensed Engineer for AECOM Technical Services of North Carolina,
Inc., do certify that the information contained in this report is correct and accurate to the best of
my knowledge.
_________________________________
Brett G. Schaefer, PE
AECOM Technical Services of North Carolina, Inc.
AECOM Technical Services of North Carolina, Inc. is licensed to practice engineering in North
Carolina. The certification number of the company or corporation is F-0458.
2,0002,000
SITE LOCATION
FIGURE 1SITE LOCATION MAP
Source: Topo USGS 7.5 Minute Topographic Map
Quadrangle: Roseboro, NC
Copyright: 2022 National Geographic Society
DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:File: C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6991 Roseboro\6991 Roseboro.dwg Layout: Site Location Map Date: 14 Jun, 2023 Xrefs:00
SCALE IN FEET:
NOTE: ALL MAP FEATURES ARE APPROXIMATE
IN SCALE AND LOCATION.
N
I. DUMITRUJUNE 2023 N. LONG
Speedway Store #6991
110 West Martin Luther King Boulevard
Roseboro, NC 28382
60702558
Speedway LLC.
W e s t M a r t i n L u t h e r K i n g B o u l e v a r d ( N. C. H i g h w a y 2 4 )SpeedwayStore #6991SignCanopy &Dispenser IslandsTrashEnclosureTank FieldFreezerAir /VacuumDieselSatellitePumpsSB-1SCALE IN FEET:30300DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6991 Roseboro\6991 Roseboro.dwg, 6/14/2023 6:57 PM, Dumitru, Ionut, PDF995.pc3, User32767, 1'-0" = 1'-0"NI. DUMITRUJUNE 2023N. LONGFIGURE 2SITE PLANLEGENDNOTE: ALL MAP FEATURES ARE APPROXIMATEIN SCALE AND LOCATION.Speedway Store #6991110 West Martin Luther King BoulevardRoseboro, NC 2838260702558Speedway LLC.Approximate Site Property BoundaryFenceProduct DispenserUnderground Storage TankUtility Pole / Power PoleLight Post / Traffic LightCatch Basin / Stormwater InletOverhead WireSoil Boring LocationApproximate Property BoundaryApproximate Building FootprintFire HydrantTreeline
ATTACHMENT A
UST-17A FORM & UST-17B FORM
UST-17B UST Suspected Release 7 Day Notice
This form must be used to report to DEQ, within 7 days of discovery, the investigation results for a Suspected Release from any of the following:
a) Failed or inconclusive leak detection or tightness test results. This includes positive test results, such as “Increase”, which indicates the level in the
UST system has increased more than 0.2 gph.
b) Unusual operating conditions which can include, but are not limited to, the erratic behavior of dispensing equipment; the unexplained presence of
water in the tank; the presence of fuel in containment sumps or interstitial spaces; or the degradation of any equipment or element of an underground
storage tank system to the point where that equipment or element can not reasonably be expected to perform its intended function.
c) Internal inspection results such as, perforations, corrosion holes, weld failures, or other similar defects that indicate a release could have occurred.
If you have more than four UST systems to report suspected release investigations, then attach additional sheets of the UST-17B form.
Please submit this form along with the supporting documentation to:
NCDEQ/DWM, UST Section
1646 Mail Service Center
Raleigh, North Carolina 27699-1646
OR
Fax to (919) 715-1117 OR UST.Permits@ncdenr.gov
I. UST OWNER II. UST FACILITY
Name:
Name:
Facility ID:
Address:
Address:
City:
State:
Zip:
City:
County:
Person Reporting:
Title of Person Reporting:
Telephone Number:
( )
III. INVESTIGATION RESULTS
Tank Number / Size: / / / /
Product Stored:
Reason for Suspected
Release Investigation
(Check all that apply):
You must attach the
supporting documentation
specified in the footnote for
the reason(s) selected.
Data entry error 1
Dispensing fuel while
test is being conducted 2
Faulty equipment 3
Incorrect stick or meter
reading 1
Incorrect tank chart 4
Internal Inspection 5
Meter not calibrated 6
Other (Attach
explanation)1
Tank/Dispenser
containment sump contains liquid 7
Tilted tank 8
Unknown 1
Data entry error 1
Dispensing fuel while
test is being conducted 2
Faulty equipment 3
Incorrect stick or meter
reading 1
Incorrect tank chart 4
Internal Inspection 5
Meter not calibrated 6
Other (Attach
explanation)1
Tank/Dispenser
containment sump contains liquid 7
Tilted tank 8
Unknown 1
Data entry error 1
Dispensing fuel while
test is being conducted 2
Faulty equipment 3
Incorrect stick or meter
reading 1
Incorrect tank chart 4
Internal Inspection 5
Meter not calibrated 6
Other (Attach
explanation)1
Tank/Dispenser
containment sump contains liquid 7
Tilted tank 8
Unknown 1
Data entry error 1
Dispensing fuel while
test is being conducted 2
Faulty equipment 3
Incorrect stick or meter
reading 1
Incorrect tank chart 4
Internal Inspection 5
Meter not calibrated 6
Other (Attach
explanation)1
Tank/Dispenser
containment sump contains liquid 7
Tilted tank 8
Unknown 1
1 Conduct a tank and/or line tightness test and attach the results, along with all of the supporting data sheets for the test method, to this form for submittal.
The summary page listing the results by itself is not acceptable. If the tightness test results are fail, then you must repair or replace your UST system and
conduct a site check in accordance with 15A NCAC 2N .0603.
2 Provide sales receipts or other comparable documentation that shows fuel was being dispensed from the UST during the test.
3 Provide invoices (with a description of the work completed) or other documentation that shows the equipment has been repaired.
4 Correct your leak detection results using the correct tank chart and submit copies with this form.
5 Repair the UST in accordance with the manufacturer’s instructions or a national standard (e.g., PEI API 1631) and conduct a site check in accordance with
15A NCAC 2N .0603. If the UST is not repaired, then it must be permanently closed in accordance with the latest version of the UST Sections Guidelines
for Tank Closure.
6 Correct your leak detection results using the amount your meter was adjusted following calibration and submit copies of the meter calibration and leak
detection results with this form.
7 Conduct a tightness test (e.g., hydrostatic test) of the sump and submit the test result along with this form. If the test results are fail, then you must repair
or replace the containment sump and conduct a site check in accordance with 15A NCAC 2N .0603.
8 Submit documentation from your UST equipment contractor explaining how they determined the UST was tilted. Correct your leak detection results using a
tank chart adjusted for the tilt and submit with this form.
Note: Tank, piping, spill bucket and containment sump replacements must be done in accordance with 15A NCAC 2N .0900
UST-17B Revised 10/2015 http://www.wastenotnc.org/web/wm/
Speedwal LLC
500 Speedway Dr
Enon OH 45323
Speedway #6991 036875
110 W Martin Luther King Jr. Blvd
ROSEBORO Sampson
Daniel Gum Environmental Specialist 937 301-2689
1 15,000
RUL
The RUL STP sump failed hydrostatic testing. A site check will be conducted.
Repairs have been contracted to Tideland Construction.
2
STP
SPEEDWAY Legacy 7-ELEVEN #46881/6991
110 W MLK JR BLVD ROSEBORO SAMPSON
Tanknology, Inc.800-964-1250 testreporting@tanknology.com
Gleston Marcelle 01/06/2023
43
9
30 MIN
1325 1425
23 22.75
POSSIBE LEAKING CONDUIT
UST-17A UST Suspected Release 24 Hour Notice
Do not use this form to report a 24 hour notice of a Pollution Incident. You must use form UST-61, 24 Hour Release and UST Leak
Reporting Form.
¾This form must be used to report to DEQ, within 24 hours of discovery, a Suspected Release from any of the following:
a) Failed or inconclusive leak detection or tightness test results. This includes positive test results, such as “Increase”, which
indicates the level in the UST system has increased more than 0.2 gph.
b)Unusual operating conditions which can include, but are not limited to: the erratic behavior of dispensing equipment; the
unexplained presence of water in the tank; the presence of fuel in containment sumps or interstitial spaces; or the degradation of
any equipment or element of an underground storage tank system to the point where that equipment or element can not reasonably
be expected to perform its intended function.
c)Internal inspection results such as, perforations, corrosion holes, weld failures, or other similar defects that indicate a release
could have occurred.
¾If you have more than four UST systems to report suspected releases, then attach additional sheets of the UST-17A form. You only
need to list the UST systems at your site that have suspected releases.
¾Within 7 days of discovery, submit a UST-17B form to document the response activities taken to investigate the suspected release.
¾Please submit this form to: NCDEQ/DWM, UST Section
1646 Mail Service Center
Raleigh, North Carolina 27699-1646
OR
Fax to (919) 715-1117 OR UST.Permits@ncdenr.gov
I. UST OWNER II. UST FACILITY
Name:Name:Facility ID:
Address:Address:
City:State:Zip:City:County:
Person Reporting:Title of Person Reporting:Telephone Number:
()
Date Submitted:
III. UST INFORMATION
Tank Number / Size:////
Product Stored:
Location and/or source of
suspected release:(check all that apply)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in
comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in
comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in
comments)
Tank
Piping
Tank Sump
Dispenser Sump
Spill Bucket
Internal Inspection
Other (Explain in
comments)
Leak detection method or
other observation that
indicates a suspected
release. (e.g., ATG, SIR,
visual contamination, fuel
in sump, etc.):
Failed/Inconclusive date or
date that leak detection
method suspected release discovered:
IV. COMMENTS
UST-17A Revised 10/2018 http://www.wastenotnc.org/
Speedway LLC
500 Speedway Dr
Enon OH 45323
Speedway #6991 036875
110 W Martin Luther King Jr. Blvd
Roseboro Sampson
Daniel Gum Environmental Specialist 937 301-2689
1 15,000
RUL
■
Visual observation; product
in STP sump
1/3/2023
Fuel was discovered in the Regular STP sump on 1/3/23 and repairs were dispatched to a maintenance vendor. The regular line passed
testing and a hydrostatic test is scheduled for 1/6/23.
1/4/2023
ATTACHMENT B
SOIL BORING LOG
NA NA
NA NA
1.6 NA
2.9 NA
3.1 Hand
Auger
Checked by _Frank Beecher___________________________Date:___6/9/2023________________
PROJECT NAME: Speedway 6991 PROJECT NUMBER: 60702558.002
SITE LOCATION: 110 W. Martin Luther King Jr. Blvd, Roseboro, NC SHEET: 1 of 1GENERAL LOCATION ON-SITE: Near the STP for the 15,000-gallon RUL
UST
FIELD GEOLOGIST: Frank Beecher
DRILLING CONTRACTOR: Sweetwater DATE STARTED: May 18, 2023
DRILLING METHOD:DATE FINISHED: May 18, 2023 BORING DEPTH: 3 feet bgs
RIG TYPE: NA DEPTH TO WATER - OBSERVED IN BORING (feet): NA BORING DIAMETER:
WEATHER: 80s & Cloudy PRE-DIG METHODS: Air Knife
Depth (ft)Lab Sample IDLab Sample Depth (ft.)PID Reading (ppm)Sampling MethodMATERIALS:
Main component, additional components, color, moisture, plasticity, density/consistency, odor or
other descriptive information
NOTES: Boring terminated at 3' bgs per scope of work (SOW).
Field Instrument QA/QC:
Model & Serial Numbers - MiniRAE 3000+ PID; Serial #592-927841
Calibration Gas Lot # 302-402335531-1
Orange Clay/Silt
Concrete
Gravel
Orange-brown Clay/Silt
Brown Clay/Silt
0-6"
6"-8"
8"-1'
1'-2'
2'-3'3 ft bgs
NA
NA
NA
ATTACHMENT C
LABORATORY ANALYTICAL REPORT
#=CL#
May 23, 2023
LIMS USE: FR - NICOLE LONG
LIMS OBJECT ID: 92668345
92668345
Project:
Pace Project No.:
RE:
Nicole Long
AECOM
6000 Fairview Rd.
Suite 200
Charlotte, NC 28210
SPEEDWAY 6991/60702558
Dear Nicole Long:
Enclosed are the analytical results for sample(s) received by the laboratory on May 19, 2023. The results relate only to the
samples included in this report. Results reported herein conform to the applicable TNI/NELAC Standards and the
laboratory's Quality Manual, where applicable, unless otherwise noted in the body of the report.
The test results provided in this final report were generated by each of the following laboratories within the Pace Network:
• Pace Analytical Services - Charlotte
If you have any questions concerning this report, please feel free to contact me.
Sincerely,
Bonnie Vang
bonnie.vang@pacelabs.com
Project Manager
(704)875-9092
Enclosures
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 1 of 12
#=CP#
CERTIFICATIONS
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Pace Analytical Services Charlotte
South Carolina Laboratory ID: 99006
9800 Kincey Ave. Ste 100, Huntersville, NC 28078
North Carolina Drinking Water Certification #: 37706
North Carolina Field Services Certification #: 5342
North Carolina Wastewater Certification #: 12
South Carolina Laboratory ID: 99006
South Carolina Certification #: 99006001
South Carolina Drinking Water Cert. #: 99006003
Florida/NELAP Certification #: E87627
Kentucky UST Certification #: 84
Louisiana DoH Drinking Water #: LA029
Virginia/VELAP Certification #: 460221
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 2 of 12
#=SS#
SAMPLE SUMMARY
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Lab ID Sample ID Matrix Date Collected Date Received
92668345001 SB-1 (RUL) 3'Solid 05/18/23 12:40 05/19/23 09:49
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 3 of 12
#=SA#
SAMPLE ANALYTE COUNT
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Lab ID Sample ID Method
Analytes
Reported LaboratoryAnalysts
92668345001 SB-1 (RUL) 3'EPA 8015C 2 PASI-CTEG
SW-846 1 PASI-CKDF
PASI-C = Pace Analytical Services - Charlotte
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 4 of 12
#=HO#
SUMMARY OF DETECTION
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Parameters AnalyzedResult
Lab Sample ID
Report Limit QualifiersUnitsMethod
Client Sample ID
92668345001 SB-1 (RUL) 3'
Percent Moisture 19.9 %05/19/23 15:03 N20.10SW-846
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 5 of 12
#=AR#
ANALYTICAL RESULTS
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Sample:SB-1 (RUL) 3'Lab ID:92668345001 Collected:05/18/23 12:40 Received:05/19/23 09:49 Matrix:Solid
Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions.
Parameters Results Units DF Prepared Analyzed CAS No.QualMDLLimit
Report
Analytical Method: EPA 8015C Preparation Method: EPA 5030B
Pace Analytical Services - Charlotte
Gasoline Range Organics
Gas Range Organics (C6-C10)ND mg/kg 05/19/23 22:5905/19/23 14:1810.5 2.9 1
Surrogates
4-Bromofluorobenzene (S)101 %05/19/23 22:59 460-00-405/19/23 14:1866-130 1
Analytical Method: SW-846
Pace Analytical Services - Charlotte
Percent Moisture
Percent Moisture 19.9 %05/19/23 15:03 N20.10 0.10 1
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 6 of 12
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
775711
EPA 5030B
EPA 8015C
Gasoline Range Organics
Laboratory:Pace Analytical Services - Charlotte
Associated Lab Samples:92668345001
Parameter Units
Blank
Result
Reporting
Limit Qualifiers
METHOD BLANK:4025236
Associated Lab Samples:92668345001
Matrix:Solid
AnalyzedMDL
Gas Range Organics (C6-C10)mg/kg ND 6.0 05/19/23 19:331.7
4-Bromofluorobenzene (S)%102 66-130 05/19/23 19:33
Parameter Units
LCS
Result
% Rec
Limits Qualifiers% RecConc.
4025237LABORATORY CONTROL SAMPLE:
LCSSpike
Gas Range Organics (C6-C10)mg/kg 50.249.8 101 70-130
4-Bromofluorobenzene (S)%102 66-130
Parameter Units
MS
Result
% Rec
Limits Qualifiers% RecConc.
4025239MATRIX SPIKE SAMPLE:
MSSpike
Result
92667891014
Gas Range Organics (C6-C10)mg/kg 95.284.4 111 57-154ND
4-Bromofluorobenzene (S)%103 66-130
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92667891013
4025238SAMPLE DUPLICATE:
Gas Range Organics (C6-C10)mg/kg ND 30ND
4-Bromofluorobenzene (S)%102100
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 7 of 12
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
775722
SW-846
SW-846
Dry Weight/Percent Moisture
Laboratory:Pace Analytical Services - Charlotte
Associated Lab Samples:92668345001
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92668387001
4025363SAMPLE DUPLICATE:
Percent Moisture %14.4 N222514.7
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92668385005
4025364SAMPLE DUPLICATE:
Percent Moisture %13.5 N212513.4
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 8 of 12
#=QL#
QUALIFIERS
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
DEFINITIONS
DF - Dilution Factor, if reported, represents the factor applied to the reported data due to dilution of the sample aliquot.
ND - Not Detected at or above adjusted reporting limit.
TNTC - Too Numerous To Count
J - Estimated concentration above the adjusted method detection limit and below the adjusted reporting limit.
MDL - Adjusted Method Detection Limit.
PQL - Practical Quantitation Limit.
RL - Reporting Limit - The lowest concentration value that meets project requirements for quantitative data with known precision and
bias for a specific analyte in a specific matrix.
S - Surrogate
1,2-Diphenylhydrazine decomposes to and cannot be separated from Azobenzene using Method 8270. The result for each analyte is
a combined concentration.
Consistent with EPA guidelines, unrounded data are displayed and have been used to calculate % recovery and RPD values.
LCS(D) - Laboratory Control Sample (Duplicate)
MS(D) - Matrix Spike (Duplicate)
DUP - Sample Duplicate
RPD - Relative Percent Difference
NC - Not Calculable.
SG - Silica Gel - Clean-Up
U - Indicates the compound was analyzed for, but not detected.
Acid preservation may not be appropriate for 2 Chloroethylvinyl ether.
A separate vial preserved to a pH of 4-5 is recommended in SW846 Chapter 4 for the analysis of Acrolein and Acrylonitrile by EPA
Method 8260.
N-Nitrosodiphenylamine decomposes and cannot be separated from Diphenylamine using Method 8270. The result reported for
each analyte is a combined concentration.
Reported results are not rounded until the final step prior to reporting. Therefore, calculated parameters that are typically reported as
"Total" may vary slightly from the sum of the reported component parameters.
Pace Analytical is TNI accredited. Contact your Pace PM for the current list of accredited analytes.
TNI - The NELAC Institute.
ANALYTE QUALIFIERS
The lab does not hold NELAC/TNI accreditation for this parameter but other accreditations/certifications may apply. A
complete list of accreditations/certifications is available upon request.N2
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 9 of 12
#=CR#
QUALITY CONTROL DATA CROSS REFERENCE TABLE
Pace Project No.:
Project:
92668345
SPEEDWAY 6991/60702558
Lab ID Sample ID QC Batch Method QC Batch Analytical Method
Analytical
Batch
92668345001 775711 775798SB-1 (RUL) 3'EPA 5030B EPA 8015C
92668345001 775722SB-1 (RUL) 3'SW-846
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 10 of 12
Page 11 of 12
Page 12 of 12