Loading...
HomeMy WebLinkAboutFA-30106_0_CA_SCH_20230814 AECOM AECOM 704.522.0330 tel. 6000 Fairview Road, Suite 200 Charlotte, NC 28210 June 16, 2023 Mr. James Brown AECOM Project # 60702558.002 North Carolina Department of Environmental Quality Division of Waste Management – UST Section Fayetteville Regional Office 225 Green Street, Suite 714, Systel Building Fayetteville, North Carolina 28301 Subject: Site Check Report Speedway #6991 110 W. Martin Luther King, Jr. Blvd Roseboro, NC 28382 Facility ID# 0-036875 Dear Mr. Brown: AECOM Technical Services, Inc. of North Carolina (AECOM) on behalf of Speedway, LLC (Speedway) is presenting this Site Check Report for the above referenced store (Figure 1). On January 3, 2023, fuel was discovered in the submersible turbine pump (STP) for the 15,000-gallon regular unleaded (RUL) gasoline UST and failed hydrostatic testing on January 6, 2023. UST-17A Form & UST-17B Form were filed with the North Carolina Department of Environmental Quality (NCDEQ) on January 4, 2023, and January 6, 2023, and are included as Attachment A. To determine if a release may have occurred to the environment, assessment activities were conducted as documented in this report. A soil boring log has been included as Attachment B, and the laboratory report for the soil sample taken during the site check has been included as Attachment C. There are no active or historical release incidents associated with the Site. SITE ACTIVITIES Soil Sampling On May 18, 2023, AECOM met with Sweetwater Utility Exploration (Sweetwater) at the site to collect soil sample (SB-1 (RUL) 3’) from near the STP for the 15,000-gallon RUL UST (Figure 2). Sweetwater air knifed the soil boring to a depth of approximately 3 feet below ground surface (bgs), then AECOM used a hand auger to collect the soil sample. The soil sample was collected at approximately 3 feet bgs and screened with a photoionization detector (PID). A soil boring log is included as Attachment B. AECOM bottled the sample for laboratory analysis for total petroleum hydrocarbons for gasoline range organics (TPH-GRO). The sample was submitted to Pace Analytical Services in Huntersville, North Carolina for analysis at the Huntersville, North Carolina laboratory. AECOM Site Check Report June 2023 Speedway 6991 Page 2 Roseboro, North Carolina RESULTS Based on laboratory analysis, a detectable concentration of TPH-GRO was not reported in the soil sample SB-1 (RUL) 3’. The laboratory report is included in Attachment C. CONCLUSIONS AND RECOMMENDATIONS Based on this information, a release at the site does not appear to have occurred. AECOM, on behalf of Speedway recommends that this potential release receive a no further action (NFA). If you have any questions, please call Nicole Long, AECOM Project Manager, at (704) 649-6586. Sincerely, AECOM Elizabeth Andrews Nicole Long Environmental Scientist I Project Manager elizabeth.andrews@aecom.com nicole.long@aecom.com Marie Treiber Regional Senior Project Manager Marie.Treiber@aecom.com cc: Speedway Project File Figure 1 Site Location Map Figure 2 Site Map Attachments: A – UST-17A Form & UST-17B Form B – Soil Boring Log C – Laboratory Analytical Report AECOM Site Check Report June 2023 Speedway 6991 Page 3 Roseboro, North Carolina Professional Certification Page I, Brett G. Schaefer, a Licensed Engineer for AECOM Technical Services of North Carolina, Inc., do certify that the information contained in this report is correct and accurate to the best of my knowledge. _________________________________ Brett G. Schaefer, PE AECOM Technical Services of North Carolina, Inc. AECOM Technical Services of North Carolina, Inc. is licensed to practice engineering in North Carolina. The certification number of the company or corporation is F-0458. 2,0002,000 SITE LOCATION FIGURE 1SITE LOCATION MAP Source: Topo USGS 7.5 Minute Topographic Map Quadrangle: Roseboro, NC Copyright: 2022 National Geographic Society DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:File: C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6991 Roseboro\6991 Roseboro.dwg Layout: Site Location Map Date: 14 Jun, 2023 Xrefs:00 SCALE IN FEET: NOTE: ALL MAP FEATURES ARE APPROXIMATE IN SCALE AND LOCATION. N I. DUMITRUJUNE 2023 N. LONG Speedway Store #6991 110 West Martin Luther King Boulevard Roseboro, NC 28382 60702558 Speedway LLC. W e s t M a r t i n L u t h e r K i n g B o u l e v a r d ( N. C. H i g h w a y 2 4 )SpeedwayStore #6991SignCanopy &Dispenser IslandsTrashEnclosureTank FieldFreezerAir /VacuumDieselSatellitePumpsSB-1SCALE IN FEET:30300DATE:DRAWN BY:REVIEWED BY:PROJECT NO.:C:\Users\AlexandruIonut.Dumit\AECOM\Convenience Store - 7-Eleven\North Carolina\6991 Roseboro\6991 Roseboro.dwg, 6/14/2023 6:57 PM, Dumitru, Ionut, PDF995.pc3, User32767, 1'-0" = 1'-0"NI. DUMITRUJUNE 2023N. LONGFIGURE 2SITE PLANLEGENDNOTE: ALL MAP FEATURES ARE APPROXIMATEIN SCALE AND LOCATION.Speedway Store #6991110 West Martin Luther King BoulevardRoseboro, NC 2838260702558Speedway LLC.Approximate Site Property BoundaryFenceProduct DispenserUnderground Storage TankUtility Pole / Power PoleLight Post / Traffic LightCatch Basin / Stormwater InletOverhead WireSoil Boring LocationApproximate Property BoundaryApproximate Building FootprintFire HydrantTreeline ATTACHMENT A UST-17A FORM & UST-17B FORM UST-17B UST Suspected Release 7 Day Notice  This form must be used to report to DEQ, within 7 days of discovery, the investigation results for a Suspected Release from any of the following: a) Failed or inconclusive leak detection or tightness test results. This includes positive test results, such as “Increase”, which indicates the level in the UST system has increased more than 0.2 gph. b) Unusual operating conditions which can include, but are not limited to, the erratic behavior of dispensing equipment; the unexplained presence of water in the tank; the presence of fuel in containment sumps or interstitial spaces; or the degradation of any equipment or element of an underground storage tank system to the point where that equipment or element can not reasonably be expected to perform its intended function. c) Internal inspection results such as, perforations, corrosion holes, weld failures, or other similar defects that indicate a release could have occurred.  If you have more than four UST systems to report suspected release investigations, then attach additional sheets of the UST-17B form.  Please submit this form along with the supporting documentation to: NCDEQ/DWM, UST Section 1646 Mail Service Center Raleigh, North Carolina 27699-1646 OR Fax to (919) 715-1117 OR UST.Permits@ncdenr.gov I. UST OWNER II. UST FACILITY Name: Name: Facility ID: Address: Address: City: State: Zip: City: County: Person Reporting: Title of Person Reporting: Telephone Number: ( ) III. INVESTIGATION RESULTS Tank Number / Size: / / / / Product Stored: Reason for Suspected Release Investigation (Check all that apply): You must attach the supporting documentation specified in the footnote for the reason(s) selected. Data entry error 1 Dispensing fuel while test is being conducted 2 Faulty equipment 3 Incorrect stick or meter reading 1 Incorrect tank chart 4 Internal Inspection 5 Meter not calibrated 6 Other (Attach explanation)1 Tank/Dispenser containment sump contains liquid 7 Tilted tank 8 Unknown 1 Data entry error 1 Dispensing fuel while test is being conducted 2 Faulty equipment 3 Incorrect stick or meter reading 1 Incorrect tank chart 4 Internal Inspection 5 Meter not calibrated 6 Other (Attach explanation)1 Tank/Dispenser containment sump contains liquid 7 Tilted tank 8 Unknown 1 Data entry error 1 Dispensing fuel while test is being conducted 2 Faulty equipment 3 Incorrect stick or meter reading 1 Incorrect tank chart 4 Internal Inspection 5 Meter not calibrated 6 Other (Attach explanation)1 Tank/Dispenser containment sump contains liquid 7 Tilted tank 8 Unknown 1 Data entry error 1 Dispensing fuel while test is being conducted 2 Faulty equipment 3 Incorrect stick or meter reading 1 Incorrect tank chart 4 Internal Inspection 5 Meter not calibrated 6 Other (Attach explanation)1 Tank/Dispenser containment sump contains liquid 7 Tilted tank 8 Unknown 1 1 Conduct a tank and/or line tightness test and attach the results, along with all of the supporting data sheets for the test method, to this form for submittal. The summary page listing the results by itself is not acceptable. If the tightness test results are fail, then you must repair or replace your UST system and conduct a site check in accordance with 15A NCAC 2N .0603. 2 Provide sales receipts or other comparable documentation that shows fuel was being dispensed from the UST during the test. 3 Provide invoices (with a description of the work completed) or other documentation that shows the equipment has been repaired. 4 Correct your leak detection results using the correct tank chart and submit copies with this form. 5 Repair the UST in accordance with the manufacturer’s instructions or a national standard (e.g., PEI API 1631) and conduct a site check in accordance with 15A NCAC 2N .0603. If the UST is not repaired, then it must be permanently closed in accordance with the latest version of the UST Sections Guidelines for Tank Closure. 6 Correct your leak detection results using the amount your meter was adjusted following calibration and submit copies of the meter calibration and leak detection results with this form. 7 Conduct a tightness test (e.g., hydrostatic test) of the sump and submit the test result along with this form. If the test results are fail, then you must repair or replace the containment sump and conduct a site check in accordance with 15A NCAC 2N .0603. 8 Submit documentation from your UST equipment contractor explaining how they determined the UST was tilted. Correct your leak detection results using a tank chart adjusted for the tilt and submit with this form. Note: Tank, piping, spill bucket and containment sump replacements must be done in accordance with 15A NCAC 2N .0900 UST-17B Revised 10/2015 http://www.wastenotnc.org/web/wm/ Speedwal LLC 500 Speedway Dr Enon OH 45323 Speedway #6991 036875 110 W Martin Luther King Jr. Blvd ROSEBORO Sampson Daniel Gum Environmental Specialist 937 301-2689 1 15,000 RUL The RUL STP sump failed hydrostatic testing. A site check will be conducted. Repairs have been contracted to Tideland Construction. 2 STP SPEEDWAY Legacy 7-ELEVEN #46881/6991 110 W MLK JR BLVD ROSEBORO SAMPSON Tanknology, Inc.800-964-1250 testreporting@tanknology.com Gleston Marcelle 01/06/2023 43 9 30 MIN 1325 1425 23 22.75 POSSIBE LEAKING CONDUIT UST-17A UST Suspected Release 24 Hour Notice Do not use this form to report a 24 hour notice of a Pollution Incident. You must use form UST-61, 24 Hour Release and UST Leak Reporting Form. ¾This form must be used to report to DEQ, within 24 hours of discovery, a Suspected Release from any of the following: a) Failed or inconclusive leak detection or tightness test results. This includes positive test results, such as “Increase”, which indicates the level in the UST system has increased more than 0.2 gph. b)Unusual operating conditions which can include, but are not limited to: the erratic behavior of dispensing equipment; the unexplained presence of water in the tank; the presence of fuel in containment sumps or interstitial spaces; or the degradation of any equipment or element of an underground storage tank system to the point where that equipment or element can not reasonably be expected to perform its intended function. c)Internal inspection results such as, perforations, corrosion holes, weld failures, or other similar defects that indicate a release could have occurred. ¾If you have more than four UST systems to report suspected releases, then attach additional sheets of the UST-17A form. You only need to list the UST systems at your site that have suspected releases. ¾Within 7 days of discovery, submit a UST-17B form to document the response activities taken to investigate the suspected release. ¾Please submit this form to: NCDEQ/DWM, UST Section 1646 Mail Service Center Raleigh, North Carolina 27699-1646 OR Fax to (919) 715-1117 OR UST.Permits@ncdenr.gov I. UST OWNER II. UST FACILITY Name:Name:Facility ID: Address:Address: City:State:Zip:City:County: Person Reporting:Title of Person Reporting:Telephone Number: () Date Submitted: III. UST INFORMATION Tank Number / Size://// Product Stored: Location and/or source of suspected release:(check all that apply) Tank Piping Tank Sump Dispenser Sump Spill Bucket Internal Inspection Other (Explain in comments) Tank Piping Tank Sump Dispenser Sump Spill Bucket Internal Inspection Other (Explain in comments) Tank Piping Tank Sump Dispenser Sump Spill Bucket Internal Inspection Other (Explain in comments) Tank Piping Tank Sump Dispenser Sump Spill Bucket Internal Inspection Other (Explain in comments) Leak detection method or other observation that indicates a suspected release. (e.g., ATG, SIR, visual contamination, fuel in sump, etc.): Failed/Inconclusive date or date that leak detection method suspected release discovered: IV. COMMENTS UST-17A Revised 10/2018 http://www.wastenotnc.org/ Speedway LLC 500 Speedway Dr Enon OH 45323 Speedway #6991 036875 110 W Martin Luther King Jr. Blvd Roseboro Sampson Daniel Gum Environmental Specialist 937 301-2689 1 15,000 RUL ■ Visual observation; product in STP sump 1/3/2023 Fuel was discovered in the Regular STP sump on 1/3/23 and repairs were dispatched to a maintenance vendor. The regular line passed testing and a hydrostatic test is scheduled for 1/6/23. 1/4/2023 ATTACHMENT B SOIL BORING LOG NA NA NA NA 1.6 NA 2.9 NA 3.1 Hand Auger Checked by _Frank Beecher___________________________Date:___6/9/2023________________ PROJECT NAME: Speedway 6991 PROJECT NUMBER: 60702558.002 SITE LOCATION: 110 W. Martin Luther King Jr. Blvd, Roseboro, NC SHEET: 1 of 1GENERAL LOCATION ON-SITE: Near the STP for the 15,000-gallon RUL UST FIELD GEOLOGIST: Frank Beecher DRILLING CONTRACTOR: Sweetwater DATE STARTED: May 18, 2023 DRILLING METHOD:DATE FINISHED: May 18, 2023 BORING DEPTH: 3 feet bgs RIG TYPE: NA DEPTH TO WATER - OBSERVED IN BORING (feet): NA BORING DIAMETER: WEATHER: 80s & Cloudy PRE-DIG METHODS: Air Knife Depth (ft)Lab Sample IDLab Sample Depth (ft.)PID Reading (ppm)Sampling MethodMATERIALS: Main component, additional components, color, moisture, plasticity, density/consistency, odor or other descriptive information NOTES: Boring terminated at 3' bgs per scope of work (SOW). Field Instrument QA/QC: Model & Serial Numbers - MiniRAE 3000+ PID; Serial #592-927841 Calibration Gas Lot # 302-402335531-1 Orange Clay/Silt Concrete Gravel Orange-brown Clay/Silt Brown Clay/Silt 0-6" 6"-8" 8"-1' 1'-2' 2'-3'3 ft bgs NA NA NA ATTACHMENT C LABORATORY ANALYTICAL REPORT #=CL# May 23, 2023 LIMS USE: FR - NICOLE LONG LIMS OBJECT ID: 92668345 92668345 Project: Pace Project No.: RE: Nicole Long AECOM 6000 Fairview Rd. Suite 200 Charlotte, NC 28210 SPEEDWAY 6991/60702558 Dear Nicole Long: Enclosed are the analytical results for sample(s) received by the laboratory on May 19, 2023. The results relate only to the samples included in this report. Results reported herein conform to the applicable TNI/NELAC Standards and the laboratory's Quality Manual, where applicable, unless otherwise noted in the body of the report. The test results provided in this final report were generated by each of the following laboratories within the Pace Network: • Pace Analytical Services - Charlotte If you have any questions concerning this report, please feel free to contact me. Sincerely, Bonnie Vang bonnie.vang@pacelabs.com Project Manager (704)875-9092 Enclosures REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 1 of 12 #=CP# CERTIFICATIONS Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Pace Analytical Services Charlotte South Carolina Laboratory ID: 99006 9800 Kincey Ave. Ste 100, Huntersville, NC 28078 North Carolina Drinking Water Certification #: 37706 North Carolina Field Services Certification #: 5342 North Carolina Wastewater Certification #: 12 South Carolina Laboratory ID: 99006 South Carolina Certification #: 99006001 South Carolina Drinking Water Cert. #: 99006003 Florida/NELAP Certification #: E87627 Kentucky UST Certification #: 84 Louisiana DoH Drinking Water #: LA029 Virginia/VELAP Certification #: 460221 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 2 of 12 #=SS# SAMPLE SUMMARY Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Lab ID Sample ID Matrix Date Collected Date Received 92668345001 SB-1 (RUL) 3'Solid 05/18/23 12:40 05/19/23 09:49 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 3 of 12 #=SA# SAMPLE ANALYTE COUNT Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Lab ID Sample ID Method Analytes Reported LaboratoryAnalysts 92668345001 SB-1 (RUL) 3'EPA 8015C 2 PASI-CTEG SW-846 1 PASI-CKDF PASI-C = Pace Analytical Services - Charlotte REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 4 of 12 #=HO# SUMMARY OF DETECTION Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Parameters AnalyzedResult Lab Sample ID Report Limit QualifiersUnitsMethod Client Sample ID 92668345001 SB-1 (RUL) 3' Percent Moisture 19.9 %05/19/23 15:03 N20.10SW-846 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC. Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 5 of 12 #=AR# ANALYTICAL RESULTS Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Sample:SB-1 (RUL) 3'Lab ID:92668345001 Collected:05/18/23 12:40 Received:05/19/23 09:49 Matrix:Solid Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions. Parameters Results Units DF Prepared Analyzed CAS No.QualMDLLimit Report Analytical Method: EPA 8015C Preparation Method: EPA 5030B Pace Analytical Services - Charlotte Gasoline Range Organics Gas Range Organics (C6-C10)ND mg/kg 05/19/23 22:5905/19/23 14:1810.5 2.9 1 Surrogates 4-Bromofluorobenzene (S)101 %05/19/23 22:59 460-00-405/19/23 14:1866-130 1 Analytical Method: SW-846 Pace Analytical Services - Charlotte Percent Moisture Percent Moisture 19.9 %05/19/23 15:03 N20.10 0.10 1 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 6 of 12 #=QC# QUALITY CONTROL DATA Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result. QC Batch: QC Batch Method: Analysis Method: Analysis Description: 775711 EPA 5030B EPA 8015C Gasoline Range Organics Laboratory:Pace Analytical Services - Charlotte Associated Lab Samples:92668345001 Parameter Units Blank Result Reporting Limit Qualifiers METHOD BLANK:4025236 Associated Lab Samples:92668345001 Matrix:Solid AnalyzedMDL Gas Range Organics (C6-C10)mg/kg ND 6.0 05/19/23 19:331.7 4-Bromofluorobenzene (S)%102 66-130 05/19/23 19:33 Parameter Units LCS Result % Rec Limits Qualifiers% RecConc. 4025237LABORATORY CONTROL SAMPLE: LCSSpike Gas Range Organics (C6-C10)mg/kg 50.249.8 101 70-130 4-Bromofluorobenzene (S)%102 66-130 Parameter Units MS Result % Rec Limits Qualifiers% RecConc. 4025239MATRIX SPIKE SAMPLE: MSSpike Result 92667891014 Gas Range Organics (C6-C10)mg/kg 95.284.4 111 57-154ND 4-Bromofluorobenzene (S)%103 66-130 Parameter Units Dup Result Max RPD QualifiersRPDResult 92667891013 4025238SAMPLE DUPLICATE: Gas Range Organics (C6-C10)mg/kg ND 30ND 4-Bromofluorobenzene (S)%102100 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 7 of 12 #=QC# QUALITY CONTROL DATA Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result. QC Batch: QC Batch Method: Analysis Method: Analysis Description: 775722 SW-846 SW-846 Dry Weight/Percent Moisture Laboratory:Pace Analytical Services - Charlotte Associated Lab Samples:92668345001 Parameter Units Dup Result Max RPD QualifiersRPDResult 92668387001 4025363SAMPLE DUPLICATE: Percent Moisture %14.4 N222514.7 Parameter Units Dup Result Max RPD QualifiersRPDResult 92668385005 4025364SAMPLE DUPLICATE: Percent Moisture %13.5 N212513.4 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 8 of 12 #=QL# QUALIFIERS Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 DEFINITIONS DF - Dilution Factor, if reported, represents the factor applied to the reported data due to dilution of the sample aliquot. ND - Not Detected at or above adjusted reporting limit. TNTC - Too Numerous To Count J - Estimated concentration above the adjusted method detection limit and below the adjusted reporting limit. MDL - Adjusted Method Detection Limit. PQL - Practical Quantitation Limit. RL - Reporting Limit - The lowest concentration value that meets project requirements for quantitative data with known precision and bias for a specific analyte in a specific matrix. S - Surrogate 1,2-Diphenylhydrazine decomposes to and cannot be separated from Azobenzene using Method 8270. The result for each analyte is a combined concentration. Consistent with EPA guidelines, unrounded data are displayed and have been used to calculate % recovery and RPD values. LCS(D) - Laboratory Control Sample (Duplicate) MS(D) - Matrix Spike (Duplicate) DUP - Sample Duplicate RPD - Relative Percent Difference NC - Not Calculable. SG - Silica Gel - Clean-Up U - Indicates the compound was analyzed for, but not detected. Acid preservation may not be appropriate for 2 Chloroethylvinyl ether. A separate vial preserved to a pH of 4-5 is recommended in SW846 Chapter 4 for the analysis of Acrolein and Acrylonitrile by EPA Method 8260. N-Nitrosodiphenylamine decomposes and cannot be separated from Diphenylamine using Method 8270. The result reported for each analyte is a combined concentration. Reported results are not rounded until the final step prior to reporting. Therefore, calculated parameters that are typically reported as "Total" may vary slightly from the sum of the reported component parameters. Pace Analytical is TNI accredited. Contact your Pace PM for the current list of accredited analytes. TNI - The NELAC Institute. ANALYTE QUALIFIERS The lab does not hold NELAC/TNI accreditation for this parameter but other accreditations/certifications may apply. A complete list of accreditations/certifications is available upon request.N2 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 9 of 12 #=CR# QUALITY CONTROL DATA CROSS REFERENCE TABLE Pace Project No.: Project: 92668345 SPEEDWAY 6991/60702558 Lab ID Sample ID QC Batch Method QC Batch Analytical Method Analytical Batch 92668345001 775711 775798SB-1 (RUL) 3'EPA 5030B EPA 8015C 92668345001 775722SB-1 (RUL) 3'SW-846 REPORT OF LABORATORY ANALYSIS This report shall not be reproduced, except in full, without the written consent of Pace Analytical Services, LLC.Date: 05/23/2023 05:06 PM Pace Analytical Services, LLC 9800 Kincey Ave. Suite 100 Huntersville, NC 28078 (704)875-9092 Page 10 of 12 Page 11 of 12 Page 12 of 12