HomeMy WebLinkAboutNCD980602163_20011206_Warren County PCB Landfill_SERB C_No. 87 - Nonshrink Grout Data Literature-OCRTRANSMITTAL COVER PAGE
WARREN COUNTY PCB LANDFILL DETOXIFICATION PROJECT
IT Corp. Project #827062
Submitted By: IT Corporation -200 Horizon Center Boulevard, Trenton, New Jersey 08691
Transmittal Number (chronological sequence): _Q.21
Transmittal Date: 12/6/01
Submittal Register Item Number: 87
Resubmittal: No_..X Yes __
Specification Section: 03600 1.02 A
Description: Manufacturer's Literature on Grout used to repair crack between pads 3 and 4
Drawing/Detail Number: NI A
Subcontractor/Supplier Blair
Comments: NIA
Number of Copies Submitted: _4_
Number of Copies to be Returned to Contractor_0'"-_
Earth Tech Engineer's Receipt Signature: ___________________ _
Comments:
Receipt Date:
Engineer's Approval
Comments:
Reviewer's Signature
Project Manager's Signature
D A. "Reviewed and approved, no exceptions taken"
D B. "Reviewed and approved with comments
D C. "Revise and Resubmit"
Date -------------------------
_______________ Date ________ _
'
Dec 05 01 04:09p BlairDuron Res~oration 9198334955
(
THE EUCLID CHEMICAL COMPANY (216) s31 -9222
19218 REDWOOD ROAD (800) 321-7628
• CLEVELAND, OH 44110 FAX (216) 531-9596
NS GROUT
♦ ♦ ♦ ♦ ♦
NON-SHRINK, NON-STAIN, NON-METALLIC
NS GROUT is designed for critical use where high
strength, non-staining characteristics and positive ex-
pansion are required. It contains only natural aggregate
and an expansive cementitious binder. It is extremely
flowabfe, and when cured, appears similar in appear-
ance to concrete.
PRIMARY APPLICATIONS
• Pumps
• Fans
• Motors
• Compressors
• Generators
• Machine bases of all types
• Anchor bolts
• Column baseplates
FEATURES/ BENEFITS
• Non-staining natural aggregate for better appearance
• Non-shrink performance provides excellent bearing
• Flowable and self-leveling
• High strength
• Appearance of plain concrete
• Does not contain any added chloride ions
SPECIFICATION / COMPLIANCES
• Meets the requirements of CAD C-621, Corps of
Engineers Specification for Non-Shrink Grout.
• Shows positive expansion when tested in accordance
with ASTM Specification C-1090, Standard Test
Method for Measuring Changes in Height of Cylindri-
cal Specimens from Hydraulic-Cement Grout.
• Meets the performance requirements of ASTM C-
1107, Grades A & Bas well as Grade C, combination
volume adjusting grout standard specification for
packaged dry, hydraulic-cement grout (non-shrink-
able}.
IE.CHNICAL INFORMATION
Typical Engineering Data
The followlng results were developed under laboratory
conditions.
Flowable Consistency
1.0 gal/50 lb (3.8 liter/22.7 kg}
Flow Rate: ASTM C-939 & CAD C-621
120% Flow (flow table)
Compressive Strength
2" (50 mm) cubes (ASTM C-109)
~ Strength
3 days 5,000 psi (34 MPa)
7 days 7,000 psi (48 MPa)
14 days 8,000 psi (55 MPa)
28 days 9,000 psi (62 MPa)
Expansion
Tested in Accordance with CAD C-621
3 days .01%
7 days .06%
14 days .06%
28 days .06%
Fluid Consistency
1.2 gal/SO lb (4.5 liter/22.7 kg)
Flow Rate: ASTM C-939 & CAD C-621
20 to 30 seconds (Flow Cone)
Compressive Strength
2" (50 mm) cubes (ASTM C-109)
~ Strength
3 days 4,000 psi (28 MPa)
7 days 6,000 psi (41 MPa)
14 days 6,500 psi (45 MPa)
28 days 7,000 psi {48 MPa)
Expansion
Tested in Accordance with CAD C-621
3 days .01%
7 days .06%
14 days .06%
28 days .06%
Setting Time ASTM C-191
Initial Set 3 hrs 5 mins.
Final Set 4 hrs 47 mins
A Holderchem / RPM Company
p.4
)
'
Dec 05 01 04:09p BlairDuron Res~oration 9198334955
Appearance
NS GROUT is a free flowing powder designed to be
mixed with water. After mixing and placing, the color
may initially appear much darker than the surrounding
concrete. While this color will lighten up substantially as
the concrete cures and dries out, the grout may always
appear somewhat darker than the surrounding con-
crete.
PACKAGING / YIELD
NS GROUT is packaged in 50 lb (22.7 kg) bags and
yields 0.45 ft3 (0.013 m3) of fluid grout when mixed with
1.2 gal (4.5 liter) of water.
50 lb (22. 7 kg) of NS GROUT and 25 lbs (11.3 kg} of
3/8" (9.5 mm) pea gravel will yield approximately 0.60
ft3 (.017 m3) of flowable consistency grout. Use pea
gravel for deep fills only.
DIRECTIONS FOR USE
The contractor and engineer are encouraged to con-
sult and review the Euclid Chemical bulletin "Applica-
tion Instructions -Cementitlous Grouting." The docu-
ment offers instructions detailing the general installa-
tion of Euclid Chemlcar manufactured cement-based
grout products.
Note: If the contractor is not familiar with standard
grout placement techniques, a pre-job meeting is sug-
gested to review the project details unique to the par-
ticular job. Contact your local Euclid Chemical repre-
sentative for additional information.
The information given here is offered in particular
support to the mixing and placing of NS GROUT. This
information should be used in conjunction with the
Application Instructions guide mentioned above.
Mixing:
Consistency Estimated Water Content*
Fluid 1.2 gal/50 lb bag (4.5 liter/22.7 kg)
Flowable 1.0 gal/50 lb bag (3.8 liter/22.7 kg)
Plastic .9 gal/50 lb bag (3.4 liter/22.7 kg)
• Do not add water in an amount that will cause
bleeding or segregation. More or less water may be
required to achieve a 25 second flow or the desired
placing consistency, depending on temperature and
other variables. Do not add sand or cement to the grout
since this action will change its precision grouting
·characteristics.
Do not use this product at a flow cone rate of less than
20 seconds it checking flow rates on the job site (see
CRD-C-611 of ASTM C-939 for flow cone method).
Where NS GROUT will be placed at a thickness over
2" (50.8 mm), up 25 lb (11 .3 kg) of pea gravel may be
added to each bag of grout. Note that the water demand
to achieve a certain flow level of the grout will change.
Do not add sufficient water to promote bleeding of the
grout.
Placing-NS GROUT sets more rapidly than plain
mortars; therefore, place quickly and continuously. If
placing this product in hot weather, use of cold water
will increase the working time.
Curing and Sealing-Proper curing procedures are
importanl to ensure the durability and quality of the
grout. Wet cure the grout until the forms are stripped.
Then, cure the grout with a high solids curing com-
pound, such as SUPER REZ-SEAL, SUPER FLOOR
COAT or SUPER AQUA-CURE VOX as described in
the general grouting Application Instructions guide.
Curing Compound must be ordered separately.
CLEAN-UP
Clean tools and equipment with water before the
material hardens.
PRECAUTIONS/ LIMITATIONS
• Do not add any admixture or fluidifiers.
• Proper curing is required.
• Employ cold weather or hot weather grouting prac-
tices as the temperatures dictates.
• Store materials in a dry place.
• Do not allow to freeze until 4000 psi (27.6 MPa)
attained.
• Do not use as a topping.
• Do not use material at temperatures that may cause
premature freezing.
• Rate of strength gain is significantly affected at
temperature extremes.
Form NS Grout-4.96
p.5
WARRANTY: lhe Eur.lid Chemic.al Company ("Euclid1 solP.ty and ft•pre!.Sly wenZ11nls lhnt its products sh;till hP f,c,c, lrom rlclem in rn11lerlat~ tt•H:t wo~manshlp for &he (6) months from the dale Cit pllr'Chase. Unless
aulhorized In wri1ino by Mt\lficor ot Eucl;d. no other repu1:,ent.:,1~s m Sl;llements ntada hy Euclttt Ot its reprvsenlillivcs. In writing°' orally. shall al\er this warranly. EUCLID MAKES NO WAAAANTIES, IMPUEO OR
OTHERWISE, AS TO THE MEACliANT~BILITY OR FITNESS FOIi OIIDINARY OR PARTICUL.An PURPOSES OF ITS PnOOUCTS AND EXCLUDES THE SAME. 11 any Euclid ,.-oduci foil• lo e<>nlonn wto, ttio
warran1y, Euclid wiU replace lhe p,oducl al no cost \o Buyor. Reptacemcnl of 11ny Pfodud '°'h,ill bl' tho Role ~nd c•clul\ive •~m~cJy availAt>!e and hu')let shall hRvl:I no claim kw Incidental or consequellti■I damages. Any
w1111~n1y clu•m n'lll!;I ho mode wilhh, une t I) year uom the dale ol lhn claimed breach. EucUd does not authorize at1yone on ils behl\lf to malce 11ni,, wrinen or oral MMernenls which In anyw11.y airer Eucild', inslaOetion
informc1tk>n o, inslructions In \Is produc;t literillure °' oo ill p.%ck.,QinQ labAIS Ariy install<'lllon ol Eur.lid P'oducls whtth lni\,: lo c.nnlo,m wilh su(h in~lilll;llioo ir1fot1Mllon or inst,uc1ionG shall void 1h15 warranty. Protluct
demon~rafiOos. ii any. arf done lor lnuslralive purposes only <'Ind dn not constiluta A w3r,eflly or wilu,,,11y 111\P.rahrin ol any k1nr1 Buyer shill! be solely r~sponsible tor delerminir\ij the suilabrntv or Euclid's 0<ot1or.1, In,
lhe 8vyer'4 intended purposes.
0