August 21, 2018
Sherida Parks
Wayne County Public Schools
1603 Salem Church Road
Goldsboro, NC 27530
Reference: Spill Bucket Site Check Report
Wayne County Bus Garage
1603 Salem Church Rd, Goldsboro, NC 27530
NCDEQ Facility ID #0-000607
Dear Ms. Parks:
Contained herein is a report summarizing Site Check activities for the above referenced facility.
These activities were conducted pursuant to a request by Gina Williams of the NCDEQ Permits
and Inspections branch. Holes and/or failed integrity test results were noted in gasoline and
diesel spill buckets during a recent site inspection and subsequent integrity testing conducted by
Petroleum Equipment Service of Wilson, NC (PES). The D1 and D4 and spill buckets have been
repaired by installation of liners.
On August 10, 2018, Henry Nemargut Engineering Services mobilized personnel and drilling
equipment to the site to assess the condition of in-situ soils in the gasoline and diesel spill bucket
areas. Due to the presence of pea gravel in the UST basins, samples were obtained from auger
borings initiated from the edge of the UST basins. The borings were advanced to allow
collection of soil samples beneath outside of the pea gravel backfill from native soils above the
water table which was noted at a depth of approximately 4’ below grade. The sample obtained
from the gsaoline spill bucket area was labeled U2 and was submitted to Pace Analytical, Inc. for
analyses according to EPA Method TPH-GRO as recommended by the NCDEQ for gasoline
investigations. The samples obtained from the diesel spill bucket areas were labeled D1 and D4
and were submitted to Pace Analytical, Inc. for analyses according to EPA Methods TPH-
DRO/GRO as recommended by the NCDEQ for diesel investigations. The soil samples were
obtained as specified in the collection, preservation, and handling section of the specific method.
Each container was labeled with sample location, analyses to be performed, time, date, and the
sampler's name. They were then placed in a cooler and chilled with ice to approximately 4oC in
preparation for transportation to the analytical laboratory utilizing EPA approved chain of
custody procedures.
The laboratory result for samples D4 and U2 indicated TPH-GRO/DRO levels below laboratory
detection limits and below the NCDEQ action levels for these compound groups. The sample
from the D1 spill bucket area indicated TPH-DRO compounds at a level of 288 mg/kg, above the
NCDEQ Action Level of 100 mg/kg. The D1 sampled yielded a TPH-GRO result of 9.5 mg/kg,
below the Action Level of 50 mg/kg for these compounds. A copy of the laboratory analytical
report and the chain of custody record for the soil samples collected from this site are contained
in Appendix A.
Based on the results from the laboratory soil analyses, Henry Nemargut Engineering Services
recommends that a copy of this report be forwarded to:
Ms. Sylvia Hunneke
WaRO NCDEQ – UST Section
943 Washington Square Mall
Washington, NC 27889
Ms. Parks, please contact me at (336) 316-0452 if you have questions regarding this report.
Sincerely,
Henry Nemargut, P.E.
Henry Nemargut Engineering Services
FIGURE
Figure 1: Soil Sample Locations
D4
U2
D1
APPENDIX A
LABORATORY ANALYTICAL RESULTS
#=CL#
August 20, 2018
LIMS USE: FR - HENRY NEMARGUT
LIMS OBJECT ID: 92395472
92395472
Project:
Pace Project No.:
RE:
Henry Nemargut
Henry Nemargut Engineering
2211 Chestnut Street
Wilmington, NC 28405
Wayne Co. Bus Garage 8/10
Dear Henry Nemargut:
Enclosed are the analytical results for sample(s) received by the laboratory on August 11, 2018. The
results relate only to the samples included in this report. Results reported herein conform to the most
current, applicable TNI/NELAC standards and the laboratory's Quality Assurance Manual, where
applicable, unless otherwise noted in the body of the report.
If you have any questions concerning this report, please feel free to contact me.
Sincerely,
Taylor Ezell
taylor.ezell@pacelabs.com
Project Manager
(704)875-9092
Enclosures
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 1 of 17
#=CP#
CERTIFICATIONS
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Charlotte Certification IDs
9800 Kincey Ave. Ste 100, Huntersville, NC 28078
Louisiana/NELAP Certification # LA170028
North Carolina Drinking Water Certification #: 37706
North Carolina Field Services Certification #: 5342
North Carolina Wastewater Certification #: 12
South Carolina Certification #: 99006001
Florida/NELAP Certification #: E87627
Kentucky UST Certification #: 84
Virginia/VELAP Certification #: 460221
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 2 of 17
#=SS#
SAMPLE SUMMARY
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Lab ID Sample ID Matrix Date Collected Date Received
92395472001 D4 Solid 08/10/18 14:30 08/11/18 10:30
92395472002 U2 Solid 08/10/18 14:50 08/11/18 10:30
92395472003 D1 Solid 08/10/18 15:05 08/11/18 10:30
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 3 of 17
#=SA#
SAMPLE ANALYTE COUNT
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Lab ID Sample ID Method
Analytes
Reported LaboratoryAnalysts
92395472001 D4 EPA 8015C Modified 2 PASI-CSEM
EPA 8015C Modified 2 PASI-CCL
ASTM D2974-87 1 PASI-CKDF
92395472002 U2 EPA 8015C Modified 2 PASI-CCL
ASTM D2974-87 1 PASI-CKDF
92395472003 D1 EPA 8015C Modified 2 PASI-CSEM
EPA 8015C Modified 2 PASI-CCL
ASTM D2974-87 1 PASI-CKDF
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 4 of 17
#=HO#
SUMMARY OF DETECTION
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Parameters AnalyzedResult
Lab Sample ID
Report Limit QualifiersUnitsMethod
Client Sample ID
92395472001 D4
Percent Moisture 19.9 % 08/11/18 22:550.10ASTM D2974-87
92395472002 U2
Percent Moisture 5.2 % 08/11/18 22:550.10ASTM D2974-87
92395472003 D1
Diesel Range Organics(C10-C28) 288 mg/kg 08/16/18 14:386.3EPA 8015C Modified
Gas Range Organics (C6-C10) 9.5 mg/kg 08/18/18 21:036.0EPA 8015C Modified
Percent Moisture 19.6 % 08/11/18 23:320.10ASTM D2974-87
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 5 of 17
#=AR#
ANALYTICAL RESULTS
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Sample: D4 Lab ID: 92395472001 Collected: 08/10/18 14:30 Received: 08/11/18 10:30 Matrix: Solid
Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions.
Parameters Results Units DF Prepared Analyzed CAS No. QualReport Limit
Analytical Method: EPA 8015C Modified Preparation Method: EPA 35468015 GCS THC-Diesel
Diesel Range Organics(C10-C28) ND mg/kg 08/16/18 14:3808/15/18 15:046.3 1
Surrogates
n-Pentacosane (S) 74 % 08/16/18 14:38 629-99-208/15/18 15:0441-119 1
Analytical Method: EPA 8015C Modified Preparation Method: EPA 5030BGasoline Range Organics
Gas Range Organics (C6-C10) ND mg/kg 08/18/18 20:0408/15/18 11:538.2 1
Surrogates
4-Bromofluorobenzene (S) 94 % 08/18/18 20:04 460-00-408/15/18 11:5370-167 1
Analytical Method: ASTM D2974-87Percent Moisture
Percent Moisture 19.9 % 08/11/18 22:550.10 1
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 6 of 17
#=AR#
ANALYTICAL RESULTS
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Sample: U2 Lab ID: 92395472002 Collected: 08/10/18 14:50 Received: 08/11/18 10:30 Matrix: Solid
Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions.
Parameters Results Units DF Prepared Analyzed CAS No. QualReport Limit
Analytical Method: EPA 8015C Modified Preparation Method: EPA 5030BGasoline Range Organics
Gas Range Organics (C6-C10) ND mg/kg 08/18/18 17:0708/15/18 11:535.0 1
Surrogates
4-Bromofluorobenzene (S) 99 % 08/18/18 17:07 460-00-408/15/18 11:5370-167 1
Analytical Method: ASTM D2974-87Percent Moisture
Percent Moisture 5.2 % 08/11/18 22:550.10 1
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 7 of 17
#=AR#
ANALYTICAL RESULTS
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Sample: D1 Lab ID: 92395472003 Collected: 08/10/18 15:05 Received: 08/11/18 10:30 Matrix: Solid
Results reported on a "dry weight" basis and are adjusted for percent moisture, sample size and any dilutions.
Parameters Results Units DF Prepared Analyzed CAS No. QualReport Limit
Analytical Method: EPA 8015C Modified Preparation Method: EPA 35468015 GCS THC-Diesel
Diesel Range Organics(C10-C28)288 mg/kg 08/16/18 14:3808/15/18 15:046.3 1
Surrogates
n-Pentacosane (S) 67 % 08/16/18 14:38 629-99-208/15/18 15:0441-119 1
Analytical Method: EPA 8015C Modified Preparation Method: EPA 5030BGasoline Range Organics
Gas Range Organics (C6-C10)9.5 mg/kg 08/18/18 21:0308/15/18 11:536.0 1
Surrogates
4-Bromofluorobenzene (S) 109 % 08/18/18 21:03 460-00-408/15/18 11:5370-167 1
Analytical Method: ASTM D2974-87Percent Moisture
Percent Moisture 19.6 % 08/11/18 23:320.10 1
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 8 of 17
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
425061
EPA 5030B
EPA 8015C Modified
Gasoline Range Organics
Associated Lab Samples: 92395472001, 92395472002, 92395472003
Parameter Units
Blank
Result
Reporting
Limit Qualifiers
METHOD BLANK: 2350666
Associated Lab Samples:92395472001, 92395472002, 92395472003
Matrix: Solid
Analyzed
Gas Range Organics (C6-C10) mg/kg ND 6.0 08/18/18 15:09
4-Bromofluorobenzene (S) % 97 70-167 08/18/18 15:09
Parameter Units
LCS
Result
% Rec
Limits Qualifiers% RecConc.
2350667LABORATORY CONTROL SAMPLE:
LCSSpike
Gas Range Organics (C6-C10) mg/kg 49.250 98 70-165
4-Bromofluorobenzene (S) % 97 70-167
Parameter Units
MS
Result
% Rec
Limits Qualifiers% RecConc.
2352396MATRIX SPIKE SAMPLE:
MSSpike
Result
92395473001
Gas Range Organics (C6-C10) mg/kg 63.364 94 47-187ND
4-Bromofluorobenzene (S) % 85 70-167
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92395373002
2350668SAMPLE DUPLICATE:
Gas Range Organics (C6-C10) mg/kg ND 30ND
4-Bromofluorobenzene (S) % 90 998
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 9 of 17
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
425103
EPA 3546
EPA 8015C Modified
8015 Solid GCSV
Associated Lab Samples: 92395472001, 92395472003
Parameter Units
Blank
Result
Reporting
Limit Qualifiers
METHOD BLANK: 2350854
Associated Lab Samples:92395472001, 92395472003
Matrix: Solid
Analyzed
Diesel Range Organics(C10-C28) mg/kg ND 5.0 08/16/18 13:26
n-Pentacosane (S) % 59 41-119 08/16/18 13:26
Parameter Units
LCS
Result
% Rec
Limits Qualifiers% RecConc.
2350855LABORATORY CONTROL SAMPLE:
LCSSpike
Diesel Range Organics(C10-C28) mg/kg 35.065.8 53 49-113
n-Pentacosane (S) % 56 41-119
Parameter Units
MS
Result
% Rec
Limits Qualifiers% RecConc.
2350856MATRIX SPIKE SAMPLE:
MSSpike
Result
92395029009
Diesel Range Organics(C10-C28) mg/kg 45.082.9 52 10-146ND
n-Pentacosane (S) % 57 41-119
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92395029009
2350857SAMPLE DUPLICATE:
Diesel Range Organics(C10-C28) mg/kg ND 30ND
n-Pentacosane (S) % 62 1571
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 10 of 17
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
424509
ASTM D2974-87
ASTM D2974-87
Dry Weight/Percent Moisture
Associated Lab Samples: 92395472001, 92395472002
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92394910003
2348137SAMPLE DUPLICATE:
Percent Moisture % 20.9 4 2521.7
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92395472002
2348138SAMPLE DUPLICATE:
Percent Moisture % 5.1 2 255.2
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 11 of 17
#=QC#
QUALITY CONTROL DATA
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
QC Batch:
QC Batch Method:
Analysis Method:
Analysis Description:
424510
ASTM D2974-87
ASTM D2974-87
Dry Weight/Percent Moisture
Associated Lab Samples: 92395472003
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92395239001
2348139SAMPLE DUPLICATE:
Percent Moisture % 16.4 1 2516.6
Parameter Units
Dup
Result
Max
RPD QualifiersRPDResult
92395473016
2348140SAMPLE DUPLICATE:
Percent Moisture % 12.4 9 2511.3
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 12 of 17
#=QL#
QUALIFIERS
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
DEFINITIONS
DF - Dilution Factor, if reported, represents the factor applied to the reported data due to dilution of the sample aliquot.
ND - Not Detected at or above adjusted reporting limit.
TNTC - Too Numerous To Count
J - Estimated concentration above the adjusted method detection limit and below the adjusted reporting limit.
MDL - Adjusted Method Detection Limit.
PQL - Practical Quantitation Limit.
RL - Reporting Limit - The lowest concentration value that meets project requirements for quantitative data with known precision and
bias for a specific analyte in a specific matrix.
S - Surrogate
1,2-Diphenylhydrazine decomposes to and cannot be separated from Azobenzene using Method 8270. The result for each analyte is
a combined concentration.
Consistent with EPA guidelines, unrounded data are displayed and have been used to calculate % recovery and RPD values.
LCS(D) - Laboratory Control Sample (Duplicate)
MS(D) - Matrix Spike (Duplicate)
DUP - Sample Duplicate
RPD - Relative Percent Difference
NC - Not Calculable.
SG - Silica Gel - Clean-Up
U - Indicates the compound was analyzed for, but not detected.
Acid preservation may not be appropriate for 2 Chloroethylvinyl ether.
A separate vial preserved to a pH of 4-5 is recommended in SW846 Chapter 4 for the analysis of Acrolein and Acrylonitrile by EPA
Method 8260.
N-Nitrosodiphenylamine decomposes and cannot be separated from Diphenylamine using Method 8270. The result reported for
each analyte is a combined concentration.
Pace Analytical is TNI accredited. Contact your Pace PM for the current list of accredited analytes.
TNI - The NELAC Institute.
LABORATORIES
Pace Analytical Services - CharlottePASI-C
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 13 of 17
#=CR#
QUALITY CONTROL DATA CROSS REFERENCE TABLE
Pace Project No.:
Project:
92395472
Wayne Co. Bus Garage 8/10
Lab ID Sample ID QC Batch Method QC Batch Analytical Method
Analytical
Batch
92395472001 425103 425264D4EPA 3546 EPA 8015C Modified
92395472003 425103 425264D1EPA 3546 EPA 8015C Modified
92395472001 425061 425089D4EPA 5030B EPA 8015C Modified
92395472002 425061 425089U2EPA 5030B EPA 8015C Modified
92395472003 425061 425089D1EPA 5030B EPA 8015C Modified
92395472001 424509D4ASTM D2974-87
92395472002 424509U2ASTM D2974-87
92395472003 424510D1ASTM D2974-87
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.Date: 08/20/2018 12:42 PM
Pace Analytical Services, LLC
9800 Kincey Ave. Suite 100
Huntersville, NC 28078
(704)875-9092
Page 14 of 17
Page 15 of 17
Page 16 of 17
Page 17 of 17