HomeMy WebLinkAboutWS-5119_17591_CA_RPTS_20121018_MonitoringRptMONITORING REPORT
ELECTRIC SUPPLY COMPANY
327 WEST RUSSELL AVENUE
HIGH POINT, GUILFORD CO, NCS&ME PROJECT NO. 1354-12-174NCDENR INCIDENT NO. 17591
Prepared for:
North Carolina Department of Environment and Natural Resources
Division of Waste Management
Underground Storage Tank Section
1637 Mail Service Center
Raleigh, North Carolina 27699
Attention: Linda Blalock
Prepared by:
S&ME, Inc.
3718 Old Battleground Road
Greensboro, North Carolina 27410
___________________________ _______________________
Paul Penninger, LSS Wayne H. Watterson, P.E.
Project Manager Senior Engineer
October 18, 2012
Monitoring Report – #17591 Electric Supply Company S&ME Project No. 1354-12-174
327 West Russell Avenue, High Point, North Carolina October 18, 2012
i
TABLE OF CONTENTS
1 Site Identification....................................................................................................... 1
1.1 Site Identification................................................................................................ 1
1.2 Contact Information............................................................................................ 1
1.3 Release Information:........................................................................................... 1
2 Site History................................................................................................................. 2
3 Soil Quality Monitoring ............................................................................................ 2
3.1 Soil Sampling...................................................................................................... 2
3.2 Soil Analytical Results........................................................................................ 3
4 Receptor Survey......................................................................................................... 3
5 Conclusions and Recommendations......................................................................... 4
TABLES
1 Summary of Soil Sampling Results
FIGURES
1 Site Location Map
2 Aerial Photograph
3 Potential Receptor Map
4 Soil Sample Locations
APPENDICES
I Laboratory Report and Chain of Custody Form
II Receptor Survey Documentation
Monitoring Report – #17591 Electric Supply Company S&ME Project No. 1354-12-174
327 West Russell Avenue, High Point, North Carolina October 18, 2012
2
2 SITE HISTORY
The site is located at 327 West Russell Avenue in High Point, Guilford County, North
Carolina. The property is currently vacant. A remnant concrete slab and asphalt
pavement are still present at the site. Diesel impacts were reported in the area of the
former diesel underground storage tank (UST) and dispenser on the subject property.
The site location and vicinity are shown on Figure 1, and the site and pertinent features
are shown on Figure 2.
One 2,000-gallon diesel UST was removed in June 1997. Analysis of the UST closure
soil sample S-2, collected from the floor of the UST excavation at a depth of 11 feet
below the land surface (ft-bls), resulted in Total Petroleum Hydrocarbons (TPH)
compounds of 470 parts per million (ppm) by Method 5030 and 8,500 ppm by Method
3550 in June 1997. TPH results for sample S-1, collected from the north end of the UST
excavation, were below 10 ppm. Analysis of the dispenser closure soil sample P-1,
collected at a depth of 2.5 ft-bls, resulted in TPH of 50 ppm by Method 5030 and 3,200
ppm by Method 3550.
A preliminary subsurface investigation provided in November 1997 by others included
three soil borings ranging from 14 to 33 ft-bls. Boring B-2 was in the UST excavation
backfill. Six soil samples were collected and analyzed for TPH. No TPH compounds
were detected by Method 5030. TPH compounds were detected in five of the six samples
by Method 3550 at concentrations ranging from 10 ppm to 11.2 ppm. The only
contaminant detected in a groundwater sample from temporary monitoring well TMW-1,
located south of the UST excavation at boring B-1, was Xylenes at a concentration of
2.72 ppb. Groundwater was measured at TMW-1 at approximately 28 ft-bls.
The preliminary subsurface investigation concluded that the soil contamination identified
during tank closure was minor and localized in close proximity to the former UST. The
concentration of Xylenes in the groundwater sample from TMW-1 was near the method
detection limit and below the remediation guidelines for this compound.
S&ME submits this Monitoring Report for the above referenced site. This report was
prepared in accordance with Contract # 16-1713-2C for the Central Region, S&ME’s
Proposal No. 1584-12-P160, dated June 7, 2012, and as approved with NCDENR’s Task
Authorization No. 01, dated July 18, 2012.
3 SOIL QUALITY MONITORING
3.1 Soil Sampling
Due to the absence of surface features to identify the precise locations of the former
diesel UST and dispenser, S&ME performed three soil probes each to a depth of 10 ft-bls
to identify the south end of the UST excavation near the location of prior soil sample S-2,
and four soil probes to a depth of 5 ft-bls to identify the former dispenser and former soil
sample P-1 location. The July 27, 2012, soil probe locations are shown on Figure 4
relative to the previous soil sample locations and the suspected locations of the former
UST system components.
Monitoring Report – #17591 Electric Supply Company S&ME Project No. 1354-12-174
327 West Russell Avenue, High Point, North Carolina October 18, 2012
3
Based on the presence of apparent fill soil to an approximate depth of 8 ft-bls overlying
soil exhibiting apparent petroleum stains and odor in soil probe GP-1, and on the
observation of apparent residual soils in probes GP-2 and GP-3, soil probe GP-1 was
performed at or near the location of closure soil sample S-1. Headspace field screening
for volatile organic vapors by a photo-ionization detector (PID) resulted in 60 ppm in soil
sample GP-1. Observations of soil sample collected from soil probes GP-4 through GP-
7, and the PID headspace field screening measurement of 4 ppm for soil sample GP-4,
soil probe GP-4 was performed at or near the location of closure soil sample P-1.
Soil sample from soil probe GP-1-10’ (10 ft-bls) representing the former UST basin and
soil sample GP-4-3’ (3 ft-bls) representing the former dispenser were prepared for
laboratory analysis of volatile organic compounds (VOCs) by methods 8260 and
semivolatile organic compounds (SVOCs) by method 8270, and for volatile petroleum
hydrocarbons (VPH) and extractable petroleum hydrocarbons (EPH) by the MADEP
Methods. The soil samples were transferred by hand using disposable latex gloves to
laboratory-prepared containers. The soil sample containers were placed into a chilled
cooler and submitted to a dedicated courier for delivery to Prism Laboratories.
3.2 Soil Analytical Results
One VOC was detected in soil sample GP-4-3 (Acetone at 0.096 ppm) at a concentration
below the corresponding Soil-to-Groundwater (STG) Maximum Soil Contaminant
Concentration (MSCC). One VOC was detected in soil sample GP-1-10 (Phenanthrene
at 3.4 ppm-J) at a concentration below the corresponding STG MSCC. The J laboratory
modifier indicated the concentration was detected below the method reporting limit and
was estimated. Two target analytes (C9-C18 Aliphatics, C9-C22 Aromatics) were also
detected in soil sample GP-1-10 at concentrations greater than the STG MSCCs, but less
than the Residential MSCCs. The target analyte, C19-C36 Aliphatics, was detected at
320 mg/kg, which is less that the Residential MSCC. There is no STG MSCC for C19-
C36 Aliphatics. A copy of the laboratory analytical results and chain-of-custody form is
included in Appendix I. The soil analytical data are summarized on Table 1.
4 RECEPTOR SURVEY
S&ME conducted a visual survey of properties located within a 1,500 feet radius of the
site) on July 27, 2012. No water supply well structures were observed within 1,500 feet
from the source area. S&ME observed water meter vaults at the subject property and
properties in the surrounding vicinity
S&ME performed a receptor survey for the adjoining Electric Supply Company site
located at 515 West Greene Street (Incident #17590) during September 2011. The
release locations for Incidents 17590 and 17591 are located within 200 feet of each other.
S&ME submitted a Well Survey Questionnaire to 12 property owners of 19 properties
located within 500 feet of the source area, based on Guilford County GIS website. Well
Survey Questionnaires were also sent to the property owners of 300A Oak Street and 501
West High Avenue. S&ME received a Domestic Return Receipt documenting delivery
of the form to 10 property owners. One survey form was returned undelivered.
Monitoring Report – #17591 Electric Supply Company S&ME Project No. 1354-12-174
327 West Russell Avenue, High Point, North Carolina October 18, 2012
4
S&ME received 16 completed survey forms from nine property owners. Each form
stated that no water supply well is located on the corresponding property and that public
water is their source of drinking water, including 300A High Street. One form stated that
the property is vacant. Copies of the returned forms and Domestic Return Receipts are
included in Appendix II.
Based on the USGS topographic map and the GIS aerial map for the surrounding area,
the nearest surface water body is an intermittent stream located approximately 510 feet
southeast of the source area (Figure 1 and Figure 3).
The source area is not known to be located within a Wellhead Protection Area as defined
in 42 USC 300h-7(e), based upon a review of the corresponding webpage of the Public
Water Supply Section of the Division of Environmental Health.
No basements were observed by S&ME on the property. No public underground utilities
were identified intersecting or adjacent to the former UST basin prior to field activities.
Two places of public assembly were observed within a 1,500 feet radius from the site,
including the Salvation Army located approximately 750 feet to the east northeast, and
Southside Recreation Center located approximately 1,100 feet to the south, as shown on
Figure 3.
5 CONCLUSIONS AND RECOMMENDATIONS
A soil monitoring event and receptor study was conducted at the Electric Supply
Company site located at 327 West Russell Avenue in High Point, Guilford County, North
Carolina, to assess current petroleum impacts to soil from a release from a former diesel
UST system that was located on the subject site.
The findings at the site are as follows:
No water supply wells were identified within 1,500 feet of the source area, and
municipal water service is available to the subject and surrounding properties.
No surface water bodies were identified within 500 feet of the source area.
Soil impacts are greater than the Soil to Groundwater MSCC, but less than the
Residential MSCC.
The 1997 groundwater sample from temporary well TMW-1 indicated no target
compound above the NCAC 2L standards.
Based on the above, the recommended risk classification of the site is Low Risk,
and the recommended land use classification is Industrial/Commercial.
Based on these findings, S&ME recommends the incident be closed with a No Further
Action status.
TABLES
Sample ID S-1 S-2 P-1 B1-A B1-B B1-C B2-A B2-B B3-A GP-1-10 GP-4-3
Depth (below ground) 11 ft. 11 ft. 2.5 ft. 13.5 ft. 19.5 ft. 31.5 ft. 15 ft. 22 ft. 14 ft. 10 ft. 3 ft.
Sample Date 6/3/1997 6/3/1997 6/3/1997 11/28-29/1997 11/28-29/1997 11/28-29/1997 11/28-29/1997 11/28-29/1997 11/28-29/1997 7/27/2012 7/27/2012
OVM Field Screening (ppm)NA NA NA NA NA NA NA NA NA 60 3.8 - - - -
mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
EPA 8015-5030 GRO BDL 470 50 BDL BDL BDL BDL BDL BDL NA NA 10 - - -
EPA 8015-3550 DRO BDL 8,500 3,200 BDL 10.0 10.1 11.3 11.0 11.2 NA NA 10 - - -
EPA Method 8260B
Acetone NA NA NA NA NA NA NA NA NA BDL 0.096 -24 14,000 360,000
EPA Method 8270C
Phenanthrene NA NA NA NA NA NA NA NA NA 3.4 - J BDL -56 469 12,264
MADEP METHODS
C5-C8 Aliphatics NA NA NA NA NA NA NA NA NA BDL BDL -68 939 24,528
C9-C18-Aliphatics NA NA NA NA NA NA NA NA NA 966 BDL -540 1,500 40,000
C19-C36 Aliphatics NA NA NA NA NA NA NA NA NA 320 BDL -NS 31,000 810,000
C9-C22 Aromatics NA NA NA NA NA NA NA NA NA 444 BDL -31 469 12,264
Only detected compounds are displayed
mg/kg = milligram per kilogram
MSCC = Maximum Soil Contaminant Concentration
NA = Not Analyzed
BDL = Below Detection Limit
NS = No MSCC established
J- Detected but below the Reporting Limit, estimated concentration.
OVM = Organic Vapor Meter
Results in BOLD exceed the corresponding Action Level or Soil-to-Groundwater MSCC
Results underlined exceed the corresponding Residential MSCC
Note: no detected analyte concentration exceeds the corresponding Residential or Industrial/Commercial MSCC
Action
Level
Industrial/
Commercial
MSCC
S&ME, Inc. Project No. 1354-12-174
TABLE 1
SUMMARY OF SOIL SAMPLING RESULTS
Electric Supply Company
327 Russell Avenue, High Point, N.C.
NCDENR Incident No. 17591
Soil-to-
Groundwater
MSCC
Residential
MSCC
FIGURES
0GRAPHIC SCALE1,0005001,000SCALE: 1" = 1,000'PROJECT NO.DATE:FIGURE NO.SCALE:WWW.SMEINC.COM3718 OLD BATTLEGROUND ROADGREENSBORO, NC 27410PH. 336-288-7180FAX. 336-288-8980DRAWN BY:CHECKED BY:DRAWING PATH:Q:\1354\12\12-174 - ELECTRICAL SUPPLY-327 RUSSELL AVE\Electrical Supply.dwgSITE LOCATION MAPELECTRIC SUPPLY COMPANY327 RUSSELL AVENUE1354-12-1741SEPT. 2012AS SHOWNALBRDMHIGH POINT, NORTH CAROLINAINCIDENT No. 17591SITE/2&$7,21
1
:SOURCE: HIGH POINT WEST, NC USGS TOPOGRAPHIC MAP, 7.5-MINUTE SERIES, DATED 1969, PHOTOREVISED 1987COPYRIGHT: USGSSCALE: 1" = 1,000'
0GRAPHIC SCALE10050100SCALE: 1" = 100'PROJECT NO.DATE:FIGURE NO.SCALE:WWW.SMEINC.COM3718 OLD BATTLEGROUND ROADGREENSBORO, NC 27410PH. 336-288-7180FAX. 336-288-8980DRAWN BY:CHECKED BY:DRAWING PATH:Q:\1354\12\12-174 - ELECTRICAL SUPPLY-327 RUSSELL AVE\Electrical Supply.dwgSITE PLANELECTRIC SUPPLY COMPANY327 RUSSELL AVENUE1354-12-1742SEPT. 2012AS SHOWNALBRDMHIGH POINT, NORTH CAROLINAINCIDENT No. 17591RUSSELL AVEOAK STOAK ST
/2&$7,21
1
:SOURCES: Aerial - nconemap.com Parcels - Guilford Co. GIS SCALE: 1" = 100'FORMER UST LOCATION
0GRAPHIC SCALE500250500SCALE: 1" = 500'PROJECT NO.DATE:FIGURE NO.SCALE:WWW.SMEINC.COM3718 OLD BATTLEGROUND ROADGREENSBORO, NC 27410PH. 336-288-7180FAX. 336-288-8980DRAWN BY:CHECKED BY:DRAWING PATH:Q:\1354\12\12-174 - ELECTRICAL SUPPLY-327 RUSSELL AVE\Electrical Supply.dwgPOTENTIALRECEPTOR MAPELECTRIC SUPPLY COMPANY327 RUSSELL AVENUE1354-12-1743SEPT. 2012AS SHOWNALBRDMHIGH POINT, NORTH CAROLINAINCIDENT No. 17591/2&$7,21
1
:SOURCES: Aerial - nconemap.com Parcels - Guilford Co. GIS SCALE: 1" = 500'Salvation Army301 W. Green DriveSouth Side Recreation Center401 Taylor AvenueW. RUSSELL AVEOAK ST
W. GRIMES AVEGRAYSON STTAYLOR AVES. ELM STW. GREEN STS. LINDSAY STTOMLINSON STW. ENGLISH RD1,500'1,000'500'
////////////////////////xxxxxxxxxx x x x x x x x x x x x x0GRAPHIC SCALE201020SCALE: 1" = 20'PROJECT NO.DATE:FIGURE NO.SCALE:WWW.SMEINC.COM3718 OLD BATTLEGROUND ROADGREENSBORO, NC 27410PH. 336-288-7180FAX. 336-288-8980DRAWN BY:CHECKED BY:DRAWING PATH:Q:\1354\12\12-174 - ELECTRICAL SUPPLY-327 RUSSELL AVE\Electrical Supply.dwgSOIL SAMPLELOCATION MAPELECTRIC SUPPLY COMPANY327 RUSSELL AVENUE1354-12-1744OCT. 2012AS SHOWNALBRDMHIGH POINT, NORTH CAROLINAINCIDENT No. 17591/2&$7,21
1
:SOURCES:Aerial - nconemap.comParcels - Guilford Co.GISBase Map - "Site Detail Map,327 Russell Avenue,High Point, NC", byPyramid Environmental,Figure 2, dated June1997.SCALE: 1" = 20'FORMER UST LOCATIONFORMER PUMP LOCATIONGP-7GP-5GP-6GP-1/S-1GP-2GP-3GP-4/P-1S-1PRODUCT LINEPROPERTY BOUNDARY
BUILDINGLEGEND- UST REMOVAL SOIL SAMPLE LOCATION (6-3-97)- PREVIOUS SOIL SAMPLE LOCATION (11-28-97)- GEOPROBE LOCATIONASPHALTCONCRETE
FENCE
OVERHEAD POWER LINE
FENCEB-1 (CONVERTED TO TMW-1)B-2B-3
APPENDIX I
Laboratory Report, Chain of Custody Form and
Soil Sampling Field Data Forms
APPENDIX II
Receptor Survey Documentation