HomeMy WebLinkAboutWS-27755_47273_CA_SCH_20200609
SITE CHECK
BP (AMOCO) FOOD SHOP - GRAHAM
924 EAST HARDEN STREET
GRAHAM, ALAMANCE COUNTY, NORTH CAROLINA
PREPARED FOR:
MR. MICHAEL TOMPKINS
MCLEOD OIL COMPANY, INC.
PO BOX 100
MEBANE, NORTH CAROLINA 27302
PREPARED BY:
PILOT GEOLOGICAL, PLLC
PO BOX 128
KERNERSVILLE, NORTH CAROLINA 27285
JUNE 9, 2020
PILOT PROJECT NO. 5837
SITE INFORMATION
Site Name and Location BP (Amoco) Food Shop - Graham
924 East Harden Street
Graham, North Carolina
Incident No. Pending
Facility ID: 00-0-0000031886
Latitude and Longitude: 36 03’ 39.87” N; 79 22’ 48.76” W
Land Use Category: Commercial
Contacts
Owner of UST: McLeod Oil Company, Inc.
PO Box 100
Mebane, North Carolina 27302
(919) 563-3172
Primary Contact: Mr. Michael Tompkins
McLeod Oil Company, Inc.
(919) 563-3172
Consultant: Pilot Geological, PLLC
PO Box 128
Kernersville, North Carolina 27285
(336) 310-4527
Drilling Contractor: 3D Environmental Investigations, LLC
2157 Mocksville Highway
Statesville, North Carolina 28625
(704) 657-7785
Laboratory: Research and Analytical Laboratories, Inc.
106 Short Street
Kernersville, North Carolina 27284
(336) 996-2841
Laboratory I.D. # 34
Release Information: Laboratory analysis of a groundwater sample collected on May 26, 2020 during site
check activities detected petroleum compounds above the North Carolina 2L Groundwater Quality
Standards. The estimated quantity of the release is unknown. Free product was not observed during the
assessment activities.
Table of Contents
1.0 SITE HISTORY ................................................................................................................................1
1.1 UST Information ......................................................................................................................1
2.0 FIELD ACTIVITIES ..........................................................................................................................1
2.1 Soil Sampling ...........................................................................................................................1
2.2 Groundwater Sampling and Monitoring Well Installation .........................................................1
3.0 LABORATORY ANALYTICAL RESULTS ..............................................................................................2
3.1 Groundwater Sample Analysis .................................................................................................2
4.0 CONCLUSIONS ..............................................................................................................................2
5.0 RECOMMENDATIONS ...................................................................................................................3
6.0 QUALIFICATIONS OF REPORT ........................................................................................................3
DRAWINGS
Drawing 1 USGS Topographic Map
Drawing 2 Site Map
Drawing 3 Sample Location Map
TABLE OF CONTENTS
(continued)
TABLES
Table 1 UST Information
Table 2 Monitoring Well Construction Information
Table 3 Summary of Groundwater Analytical Results
APPENDICIES
Appendix A Monitoring Well Construction Record
Appendix B Laboratory Data Sheets and Chain of Custody Records
Site Check
924 East Harden Street
Graham, North Carolina
Pilot Project 5837
June 9, 2020
1
1.0 SITE HISTORY
The site is located at 924 East Harden Street in Graham, North Carolina (Drawings 1 and 2). The site
is currently developed with a gasoline station that contains an underground storage tank (UST)
system consisting of two 8,000-gallon gasoline USTs and one 10,000-gallon gasoline UST. Pilot
was requested to provide site check services related to the Notice of Regulatory Requirements
(NORR) issued by the North Carolina Department of Environmental Quality (NCDEQ) dated May
11, 2020 requesting soil sampling in the vicinity of the spill buckets.
Project information was provided through conversations between Mr. Michael Tompkins of McLeod
Oil Company, Inc. and Mr. Jason Ricks of Pilot.
1.1 UST Information
The current active UST system at the site consists of two 8,000-gallon gasoline USTs and one
10,000-gallon gasoline UST. The approximate locations of the USTs are shown on Drawing 3. UST
information is summarized in Table 1.
2.0 FIELD ACTIVITIES
The field activities were completed by Pilot on May 22 and 26, 2020. The field activities consisted
of installing a monitoring well using a Geoprobe® drill rig. The Geoprobe® consists of a hydraulic
jack mounted on an ATV (All-Terrain Vehicle) capable of driving various forms of groundwater
and soil sampling probes into the ground to depths equivalent of auger refusal. The Geoprobe®
subcontractor used for this project was 3D Environmental Investigations, LLC. Prior to initiating
the, the Geoprobe® drill rig and associated down-hole equipment were decontaminated with a
high-pressure steam cleaner.
2.1 Soil Sampling
Soil samples were not collected based on pea gravel being located around each of the three UST
spill buckets
2.2 Groundwater Sampling and Monitoring Well Installation
Based on the presence of the pea gravel around the UST spill buckets, a permanent monitoring
well (MW-1, Drawing 3) was advanced to an approximate depth of 17 feet below ground surface
(bgs) for the installation of a permanent monitoring well using direct push technology (DPT).
Probe refusal was encountered at approximately 17 feet bgs. The monitoring well was
constructed with 1-inch I.D. schedule 40 PVC flushed-threaded casing and screen. The PVC screen
and casing were lowered to the bottom of the borehole. A 12-foot length of slotted well screen
with machined 0.010-inch slot widths and threaded bottom plug were installed at the bottom of
the well. A solid section of PVC casing was placed above the screened interval and extended to a
Site Check
924 East Harden Street
Graham, North Carolina
Pilot Project 5837
June 9, 2020
2
point approximately 0.5 foot below the ground surface. The annular space around the well was
filled with washed fine filter sand to approximately one foot above the top of the screen. A
minimum 1-foot thick seal of bentonite pellets was placed immediately above the sand pack. The
top of the well casing was equipped with a lockable, water-tight well plug and a metal securable
cover was placed over the monitoring well. The Monitoring Well Construction Record is included in
Appendix A.
A groundwater sample was collected the monitoring well using a peristaltic pump and new length
of polyethylene tubing. Prior to sampling, approximately three well volumes were purged from
the monitoring well. The monitoring well was purged to remove silt and sediment from the
groundwater and collect a representative sample of groundwater. After the purging was
completed, groundwater a sample was collected in the sample containers provided by the
laboratory. Pilot personnel wore a new pair of disposable nitrile gloves during the purging and
sampling. Each container was labeled and placed in a cooler containing ice to maintain the
samples at approximately 4 Celsius. The samples were then transported to Research and
Analytical Laboratories, Inc. (R&A) for chemical analysis. The groundwater samples collected
were analyzed for volatile organic compounds (VOCs) using Standard Method 6200B, for volatile
petroleum hydrocarbons (VPH) using the MADEP Method, for ethylene dibromide (EDB) using
EPA Method 504.1 and for lead. A chain of custody was maintained and is included in Appendix
B.
3.0 LABORATORY ANALYTICAL RESULTS
3.1 Groundwater Sample Analysis
Laboratory analysis of the groundwater sample collected from monitoring well MW-1 detected
targeted compounds above the North Carolina 2L Groundwater Quality Standards (2L Standards).
Ethanol was not detected in the groundwater sample. A summary of the groundwater analytical
results is presented in Table 3. The laboratory data sheets are included in the Appendix B.
4.0 CONCLUSIONS
Based on the results of the Site Check, Pilot concludes the following:
Laboratory analysis of the groundwater samples collected from monitoring well MW-1 detected
targeted compounds above the 2L Standards. Ethanol was not detected in the groundwater
sample. The lack of ethanol and free product appear to indicate that an active release is not
occurring. The leak detection systems and annual test have also not indicated that there is an
active release.
Site Check
924 East Harden Street
Graham, North Carolina
Pilot Project 5837
June 9, 2020
3
5.0 RECOMMENDATIONS
Pilot recommends that the current property owner/responsible party submit a copy of this report
to the NCDEQ, UST Section for their review.
6.0 QUALIFICATIONS OF REPORT
The activities and evaluative approaches used in this assessment are consistent with those
normally employed in assessment projects of this type. Our evaluation of site conditions has
been based on our understanding of the site project information and the data obtained during
our field activities.
DRAWINGS
USGS Topographic Map
924 East Harden Street
Graham, Alamance County, NC
Pilot Project G-5837
Drawing 1
USGS Topographic Map
Mebane and Burlington, NC
Quadrangles
Scale: 1” = 2,000’
LEGEND
Site Boundary
Site Map
924 East Harden Street
Graham, Alamance County, NC
Pilot Project G-5837
Drawing 1
Google Earth
Interactive Mapping Software
Scale : 1”= 175’
LEGEND
Site Boundary
U. UST System
U
See Drawing 3
Sample Location Map
924 East Harden Street
Graham, Alamance County, NC
Pilot Project G-5837
Drawing 3
Google Earth
Interactive Mapping Software
Scale : 1”= 15’
LEGEND
Site Boundary
Approximate Monitoring Well Location
MW-1
TABLES
UST ID NumberOwner Last ContentsPrevious ContentsCapacity (in Gallons)Construction DetailsTank DimensionsInstallation DateStatus ReleaseFRP = Fiberglass Reinforced PlasticFRP N/A 10/16/1990 Active NoTable 1 - UST Information924 East Harden StreetGraham, North Carolina10/16/1990 Active No1Gasoline Gasoline 10,000 FRP N/AMcLeod Oil Company PO Box 100 Mebane, North Carolina 273023Gasoline Gasoline FRP N/A 10/16/1990 Active No8,0002Gasoline Gasoline 8,000
Monitoring Well IDDate InstalledWell Diameter (inches)Elevation (TOC) Total DepthScreened Interval (feet)Sand IntervalBentonite IntervalMW-1 5/22/2020 1 -- 17 5-17 4-17 3-4Table 2 - Monitoring Well Construction Information924 East Harden StreetGraham, North Carolina
504.1Sample IDApproximate Water Level (ft. BGS)Groundwater Elevation (ft.)Sample Collection DateBenzeneEthylbenzeneI-PropylbenzeneNaphthaleneN-ButylbenzeneN-Propylbenzenep-IsopropyltolueneToluene1,2,4-Trimethylbenzene1,3,5-TrimethylbenzeneTotal XylenesEDBLeadC5-C8 AliphaticsC9-C12 AliphaticsC9-C10 AromaticsMW-1 11.29 -- 5/26/2020108 373 40.2 143 22.2 116 27.8 476 1,320 383 2,470BQL16.1 2,640 24,900 11,4001 600 70 6 70 70 25 600 400 400 500 0.02 15 400 700 2005,000 84,500 25,000 6,000 6,900 30,000 11,700 260,000 28,500 25,000 85,500 50 15,000 NS NS NS= Concentration Exceeds the 2L Standard= Concentration Exceeds the GCLsppb = Parts Per BillionBGS = Below Ground SurfaceN/A = Not ApplicableNS = No StandardNC 2L Standard (ppb)GCLs (ppb)Table 3 - Summary of Groundwater Analytical Results924 East Harden StreetGraham, North CarolinaTargeted CompoundsVPH 6200BComparison Criteria
APPENDIX A
APPENDIX B