HomeMy WebLinkAboutWA-26293_9839_CA_RPTS_20170815PERIODIC MONITORING REPORT
MCAS CHERRY POINT
UST CLOSURE AND MANAGEMENT PROGRAM
FOR UST SITES
VOLUME I
FIRST SEMESTER 2017
(JANUARY 2017 THROUGH JUNE 2017)
MCAS CHERRY POINT
AUGUST 15, 2017
WARNING: This document is "FOR OFFICIAL USE ONLY" and it contains info
that may be exempt from public release under the FOi Act (5 U.S.C. 552). It
is to be handled IAW DoD policy and is not to be released to the public or
personnel who do not have a valid "need-to-know" without prior approval of
an authorized DoD official.
CONTRACT NO. N40085-14-D-8408
DELIVERY ORDER NO. 0008
SOC GROUP, INC. PROJECT NO. 6265
CATLIN ENGINEERS AND SCIENTISTS PROJECT NO. 217001
PREPARED BY:
CATLIN ENGINEERS AND SCIENTISTS
P.O. BOX 10279
WILMINGTON, NORTH CAROLINA 28404-0279
(910) 452-5861
SOC GROUP, INC.
1108 TIDEWATER DRIVE
NORFOLK, VA 23504
(757) 965-8496
NC CORPORATE LICENSURE NUMBER FOR ENGINEERING SERVICES: C-0585
NC CORPORATE NUMBER FOR GEOLOGY SERVICES: C-118
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS
PERIODIC MONITORING REPORT
MCAS CHERRY POINT UST CLOSURE AND MANAGEMENT PROGRAM
FOR UST SITES
SITES AT MCAS CHERRY POINT, NORTH CAROLINA
INTRODUCTION
NARRATIVE
TABLE I INDEX OF SITES FOR THIS REPORT
TABLE II CAMP SAMPLING SCHEDULE
TABLE III INDEX OF CLOSED SITES SINCE 1998
TABLE IV HISTORY OF NC REGULATORY STANDARDS
TABLE V INDEX OF INJECTION PERMIT SITES
TABLE VI FREE PRODUCT RECOVERY TOTAL (LAST TWO YEARS)
FIGURE I FACILITY LOCATIONS MAP
FIGURE II MCAS CHERRY POINT SITE LOCATIONS MAP
1.0 SITE 121
EXECUTIVE SUMMARY
TABLE 1.1A SITE 121 FIELD MEASUREMENTS
TABLE 1.1B SITE 121 HISTORICAL FIELD MEASUREMENT DATA
TABLE 1.2A SITE 121 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 1.2B SITE 121 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 1.3A SITE 121 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 1.3B SITE 121 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 1.1 SITE 121 FREE PRODUCT PLUME MAP AS OF MAY 2017
FIGURE 1.2 SITE 121 EPA METHOD 602 BY SM 6200B COLORIMETRY AND
PLUME IN EXCESS OF 2L AS OF MAY 2017
FIGURE 1.3 SITE 121 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF MAY 2017
2.0 SITE 130
EXECUTIVE SUMMARY
TABLE 2.1A SITE 130 FIELD MEASUREMENTS
TABLE 2.1B SITE 130 HISTORICAL FIELD MEASUREMENT DATA
TABLE 2.2A SITE 130 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - SM 6200B
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
2.0 SITE 130 - (cont.)
TABLE 2.2B SITE 130 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 2.2C SITE 130 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 2.3A SITE 130 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 2.3B SITE 130 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 2.1 SITE 130 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 2.2A SITE 130 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF 2L –
UST COMPOUNDS AS OF AUGUST 2016 – UPPER SURFICIAL
AQUIFER
FIGURE 2.2B SITE 130 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF 2L –
UST COMPOUNDS AS OF FEBRUARY 2017 – LOWER SURFICIAL
AQUIFER
FIGURE 2.3A SITE 130 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF AUGUST 2016 – UPPER
SURFICIAL AQUIFER
FIGURE 2.3B SITE 130 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017 – LOWER
SURFICIAL AQUIFER
3.0 SITE 133
EXECUTIVE SUMMARY
TABLE 3.1A SITE 133 FIELD MEASUREMENTS
TABLE 3.1B SITE 133 HISTORICAL FIELD MEASUREMENT DATA
TABLE 3.2A SITE 133 GROUNDWATER LABORATORY ANALYTICAL RESULTS -
SM 6200B
TABLE 3.2B SITE 133 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 3.3A SITE 133 GROUNDWATER LABORATORY ANALYTICAL RESULTS -
EPA METHOD 610 BY EPA METHOD 625
TABLE 3.3B SITE 133 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD 625
FIGURE 3.1 SITE 133 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 3.2A SITE 133 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF 2L
– UST COMPOUNDS AS OF AUGUST 2016 – UPPER SURFICAL
AQUIFER
FIGURE 3.2B SITE 133 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF 2L
– UST COMPOUNDS AS OF FEBRUARY 2017 – LOWER SURFICAL
AQUIFER
FIGURE 3.3A SITE 133 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF AUGUST 2016 – UPPER
SURFICIAL AQUIFER
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
3.0 SITE 133 - (cont.)
FIGURE 3.3B SITE 133 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017 – LOWER
SURFICIAL AQUIFER
4.0 SITE 137
EXECUTIVE SUMMARY
TABLE 4.1A SITE 137 FIELD MEASUREMENTS
TABLE 4.1B SITE 137 HISTORICAL FIELD MEASUREMENT DATA
TABLE 4.2A SITE 137 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - SM 6200B
TABLE 4.2B SITE 137 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 4.2C SITE 137 HISTORICAL GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 4.3A SITE 137 GROUNDWATER LABORATORY ANALYTICAL RESULTS -
EPA METHOD 610 BY EPA METHOD 625
TABLE 4.3B SITE 137 HISTORICAL GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
FIGURE 4.1 SITE 137 FREE PRODUCT PLUME MAP AS OF MAY 2017
FIGURE 4.2 SITE 137 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF
2L – UST COMPOUNDS - AS OF MAY 2017
FIGURE 4.3 SITE 137 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF MAY 2017
5.0 SITE 1083
EXECUTIVE SUMMARY
TABLE 5.1A SITE 1083 FIELD MEASUREMENTS
TABLE 5.1B SITE 1083 HISTORICAL FIELD MEASUREMENT DATA
TABLE 5.2A SITE 1083 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 5.2B SITE 1083 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 5.3A SITE 1083 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 5.3B SITE 1083 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
FIGURE 5.1 SITE 1083 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 5.2 SITE 1083 EPA METHOD 602 BY SM 6200B COLORIMETRY AND
PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017
FIGURE 5.3 SITE 1083 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF
FEBRUARY 2017
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
6.0 SITE 1640
EXECUTIVE SUMMARY
TABLE 6.1A SITE 1640 FIELD MEASUREMENTS
TABLE 6.1B SITE 1640 HISTORICAL FIELD MEASUREMENT DATA
TABLE 6.2A SITE 1640 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 6.2B SITE 1640 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 6.3A SITE 1640 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 6.3B SITE 1640 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
TABLE 6.4A SITE 1640 GROUNDWATER LABORATORY ANALYTICAL
RESULTS – MADEP VPH/EPH
TABLE 6.4B SITE 1640 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS – MADEP VPH/EPH
FIGURE 6.1 SITE 1640 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 6.2A SITE 1640 EPA METHOD 602 BY SM 6200B COLORIMETRY AND
PLUME IN EXCESS OF 2L AS OF AUGUST 2016– UPPER SURFICIAL
AQUIFER
FIGURE 6.2B SITE 1640 EPA METHOD 602 BY SM 6200B COLORIMETRY AND
PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017 – LOWER
SURFICIAL AQUIFER
FIGURE 6.3A SITE 1640 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF AUGUST 2016 - UPPER
SURFICIAL AQUIFER
FIGURE 6.3B SITE 1640 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017 – LOWER
SURFICIAL AQUIFER
FIGURE 6.4A SITE 1640 MADEP VPH/EPH COLORIMETRY AND PLUME IN
EXCESS OF 2L AS OF AUGUST 2016 - UPPER SURFICIAL AQUIFER
FIGURE 6.4B SITE 1640 MADEP VPH/EPH COLORIMETRY AND PLUME IN
EXCESS OF 2L AS OF FEBRUARY 2017 – LOWER SURFICIAL
AQUIFER
7.0 SITE 3996
EXECUTIVE SUMMARY
TABLE 7.1A SITE 3996 FIELD MEASUREMENTS
TABLE 7.1B SITE 3996 HISTORICAL FIELD MEASUREMENT DATA
TABLE 7.2A SITE 3996 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - SM 6200B
TABLE 7.2B SITE 3996 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 7.2C SITE 3996 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
7.0 SITE 3996 - (cont.)
TABLE 7.3A SITE 3996 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 7.3B SITE 3996 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 7.1 SITE 3996 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 7.2 SITE 3996 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF
2L - UST COMPOUNDS AS OF FEBRUARY 2017
FIGURE 7.3 SITE 3996 EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017
8.0 SITE 4075
EXECUTIVE SUMMARY
TABLE 8.1A SITE 4075 FIELD MEASUREMENTS
TABLE 8.1B SITE 4075 HISTORICAL FIELD MEASUREMENT DATA
TABLE 8.2A SITE 4075 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - SM 6200B
TABLE 8.2B SITE 4075 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 8.3A SITE 4075 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 8.3B SITE 4075 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 8.1 SITE 4075 FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 8.2A SITE 4075 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF
2L – UST COMPOUNDS AS OF AUGUST 2016 – UPPER
SURFICIAL AQUIFER
FIGURE 8.2B SITE 4075 SM 6200B COLORIMETRY AND PLUME IN EXCESS OF
2L – UST COMPOUNDS AS OF FEBRUARY 2017 – LOWER
SURFICIAL AQUIFER
FIGURE 8.3A SITE 4075 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF AUGUST
2016 – UPPER SURFICIAL AQUIFER
FIGURE 8.3B SITE 4075 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF
FEBRUARY 2017 – LOWER SURFICIAL AQUIFER
9.0 SITE PIT 6
EXECUTIVE SUMMARY
TABLE 9.1A SITE PIT 6 FIELD MEASUREMENTS
TABLE 9.1B SITE PIT 6 HISTORICAL FIELD MEASUREMENT DATA
TABLE 9.2A SITE PIT 6 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
9.0 SITE PIT 6 - (cont.)
TABLE 9.2B SITE PIT 6 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 9.3A SITE PIT 6 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 9.3B SITE PIT 6 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 9.1 SITE PIT 6 FREE PRODUCT PLUME MAP AS OF MAY 2017
FIGURE 9.2 SITE PIT 6 EPA METHOD 602 BY SM 6200B COLORIMETRY AND
PLUME IN EXCESS OF 2L AS OF MAY 2017
FIGURE 9.3 SITE PIT 6 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF MAY 2017
10.0 SITE PIT 12
EXECUTIVE SUMMARY
11.0 SITE PIT 15
EXECUTIVE SUMMARY
TABLE 11.1A SITE PIT 15 FIELD MEASUREMENTS
TABLE 11.1B SITE PIT 15 HISTORICAL FIELD MEASUREMENT DATA
TABLE 11.2A SITE PIT 15 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 11.2B SITE PIT 15 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 11.2C SITE PIT 15 SURFACE WATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 11.2D SITE PIT 15 HISTORICAL SURFACE WATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 11.3A SITE PIT 15 GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 11.3B SITE PIT 15 HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
TABLE 11.3C SITE PIT 15 SURFACE WATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 11.3D SITE PIT 15 HISTORICAL SURFACE WATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 11.1 SITE PIT 15 FREE PRODUCT PLUME MAP AS OF MAY 2017
FIGURE 11.2 SITE PIT 15 EPA METHOD 602 BY SM 6200B COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF MAY 2017
FIGURE 11.3 SITE PIT 15 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF MAY 2017
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
12.0 SITE SEGMENT 20
EXECUTIVE SUMMARY
TABLE 12.1A SITE SEGMENT 20 FIELD MEASUREMENTS
TABLE 12.1B SITE SEGMENT 20 HISTORICAL FIELD MEASUREMENT DATA
TABLE 12.2A SITE SEGMENT 20 GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 12.2B SITE SEGMENT 20 HISTORICAL GROUNDWATER
LABORATORY ANALYTICAL RESULTS - SM 6200B
TABLE 12.2C SITE SEGMENT 20 HISTORICAL GROUNDWATER
LABORATORY ANALYTICAL RESULTS - EPA METHOD 602 BY
SM 6200B
TABLE 12.3A SITE SEGMENT 20 GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
TABLE 12.3B SITE SEGMENT 20 HISTORICAL GROUNDWATER
LABORATORY ANALYTICAL RESULTS - EPA METHOD 610 BY
EPA METHOD 625
TABLE 12.4A SITE SEGMENT 20 GROUNDWATER LABORATORY
ANALYTICAL RESULTS - MADEP VPH/EPH
TABLE 12.4B SITE SEGMENT 20 HISTORICAL GROUNDWATER
LABORATORY ANALYTICAL RESULTS - MADEP VPH/EPH
FIGURE 12.1 SITE SEGMENT 20 FREE PRODUCT PLUME MAP AS OF MAY
2017
FIGURE 12.2 SITE SEGMENT 20 SM 6200B COLORIMETRY AND PLUME IN
EXCESS OF 2L AS OF MAY 2017
FIGURE 12.3 SITE SEGMENT 20 EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF MAY 2017
FIGURE 12.4 SITE SEGMENT 20 MADEP VPH/EPH COLORIMETRY AND PLUME
IN EXCESS OF 2L AS OF MAY 2017
13.0 SITE TFB
EXECUTIVE SUMMARY
TABLE 13.1A SITE TFB FIELD MEASUREMENTS
TABLE 13.1B SITE TFB HISTORICAL FIELD MEASUREMENT DATA
TABLE 13.2A SITE TFB GROUNDWATER LABORATORY ANALYTICAL
RESULTS - SM 6200B
TABLE 13.2B SITE TFB HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - SM 6200B
TABLE 13.3A SITE TFB GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 610 BY EPA METHOD 625
TABLE 13.3B SITE TFB HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
FIGURE 13.1 SITE TFB FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
FIGURE 13.2A SITE TFB SM 6200B COLORIMETRY AND PLUME IN EXCESS OF
2L AS OF AUGUST 2016 – UPPER SURFICIAL AQUIFER
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE OF CONTENTS – continued
13.0 SITE TFB - (cont.)
FIGURE 13.2B SITE TFB SM 6200B COLORIMETRY AND PLUME IN EXCESS
OF 2L AS OF FEBRUARY 2017 – LOWER SURFICIAL AQUIFER
FIGURE 13.2C SITE TFB SM 6200B COLORIMETRY AND PLUME IN EXCESS
OF 2L AS OF FEBRUARY 2017 – UPPER YORKTOWN AQUIFER
FIGURE 13.3A SITE TFB EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF AUGUST
2016 – UPPER SURFICIAL AQUIFER
FIGURE 13.3B SITE TFB EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF
FEBRUARY 2017 – LOWER SURFICIAL AQUIFER
FIGURE 13.3C SITE TFB EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF
FEBRUARY 2017 – UPPER YORKTOWN AQUIFER
14.0 SITE TFD
EXECUTIVE SUMMARY
15.0 SITE 2ND LAAD
EXECUTIVE SUMMARY
TABLE 15.1A SITE 2ND LAAD FIELD MEASUREMENT DATA
TABLE 15.1B SITE 2ND LAAD HISTORICAL FIELD MEASUREMENT DATA
TABLE 15.2A SITE 2ND LAAD GROUNDWATER LABORATORY ANALYTICAL
RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 15.2B SITE 2ND LAAD HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 602 BY SM 6200B
TABLE 15.3A SITE 2ND LAAD GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
TABLE 15.3B SITE 2ND LAAD HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - EPA METHOD 610 BY EPA METHOD
625
TABLE 15.4A SITE 2ND LAAD GROUNDWATER LABORATORY ANALYTICAL
RESULTS - MADEP VPH/EPH
TABLE 15.4B SITE 2ND LAAD HISTORICAL GROUNDWATER LABORATORY
ANALYTICAL RESULTS - MADEP VPH/EPH
FIGURE 15.1 SITE 2ND LAAD FREE PRODUCT PLUME MAP AS OF FEBRUARY
2017
FIGURE 15.2 SITE 2ND LAAD EPA METHOD 602 BY SM 6200B COLORIMETRY
AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017
FIGURE 15.3 SITE 2ND LAAD EPA METHOD 610 BY EPA METHOD 625
COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF
FEBRUARY 2017
FIGURE 15.4 SITE 2ND LAAD MADEP VPH/EPH COLORIMETRY AND PLUME
IN EXCESS OF 2L AS OF FEBRUARY 2017
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
INTRODUCTION
The purpose of this Periodic Monitoring Report is to present the results of recent monitoring
events performed at petroleum release sites located at Marine Corps Air Station Cherry Point
(MCAS Cherry Point). Monitoring and reporting is being performed in accordance with the
MCAS Cherry Point UST Closure and Management Program adopted by MCAS Cherry Point
Environmental Affairs Department. A listing of sites for which sampling results are included in
this Periodic Monitoring Report is presented in Table I and locations of these sites are shown
on Figure I and Figure II.
This Periodic Monitoring Report is designed such that all data and information pertaining to any
individual site is contained entirely within one section of the report and each section is devoted
entirely to one site. Therefore, each section serves as a stand-alone monitoring report for the
respective site. Each section begins with an Executive Summary which provides information
about location, monitoring, groundwater hydraulics, free-phase product plumes, dissolved-
phase plumes, potential receptors, and remediation at the site. Each Executive Summary is
supported by several site-specific tables and figures.
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE I
INDEX OF SITES FOR THIS REPORT
SITE NAME NCDEQ
INCIDENT NO. SITE LOCATION REPORT
SECTION NO.
121 31238 MCAS Cherry Point 1.0
130 31591 MCAS Cherry Point 2.0
133 7144, 9739, 9741 MCAS Cherry Point 3.0
137 6443 MCAS Cherry Point 4.0
1083 9839 MCAS Cherry Point 5.0
1640 9274 MCAS Cherry Point 6.0
3996 31591 MCAS Cherry Point 7.0
4075 6360, 9950, 9140
9276 MCAS Cherry Point 8.0
Pit 6 31501 MCAS Cherry Point 9.0
Pit 12 31356 MCAS Cherry Point 10.0
Pit 15 18715 MCAS Cherry Point 11.0
Segment 20 31312 MCAS Cherry Point 12.0
TFB 6359 MCAS Cherry Point 13.0
TFD 9265 MCAS Cherry Point 14.0
2nd LAAD 38152 MCAS Cherry Point 15.0
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE II
CAMP SAMPLING SCHEDULE
SECTION SITE ID
GW
MONITORIN
G
FREQUENCY
PROPOSED
SAMPLING
DATES
AIR
SAMPLING
FREQUENCY
WASTE
STREAM
SAMPLING
FREQUENCY
1 121 Annual May 2018 NA NA
2 130
Semi-Annual -
Upper August 2017 Annual - 4th
Quarter 2017 NA Semi-Annual -
Lower February 2018
3 133
Semi-Annual -
Upper August 2017
NA Annual - 4th
Quarter 2017Semi-Annual -
Lower February 2018
4 137 Annual May 2018 Annual - 4th
Quarter 2017
Annual - 4th
Quarter 2017
5 1083 Semi-Annual August 2017 NA NA Semi-Annual February 2018
6 1640
Semi-Annual -
Upper August 2017
NA NA Semi-Annual -
Lower February 2018
7 3996
Annual August 2017
Annual - 4th
Quarter 2017 NA Semi-Annual
– 74GW23
Only
February 2018
8 4075
Semi-Annual -
Upper August 2017
NA Annual - 4th
Quarter 2017Semi-Annual -
Lower February 2018
9 Pit 6 Annual May 2018 Annual - 4th
Quarter 2017 NA
10 Pit 12 No Sampling Planned
11 Pit 15 Annual May 2018 NA NA
12
Segment 20 Annual May 2018
NA NA Segment 20
Potable
Well
Semi-Annual November 2017
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE II - continued
CAMP SAMPLING SCHEDULE
SECTION SITE ID
GW
MONITORING
FREQUENCY
PROPOSED
SAMPLING
DATES
AIR
SAMPLING
FREQUENCY
WASTE
STREAM
SAMPLING
FREQUENCY
13 TFB
Semi-Annual –
Upper August 2017 Annual - 4th
Quarter 2017 NA Semi-Annual –
Lower/York February 2018
14 TFD No Sampling Planned
15 2nd LAAD Semi-Annual August 2017 Annual - 4th
Quarter 2017 NA February 2018
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE III
INDEX OF CLOSED SITES SINCE 1998
SITE NAME SITE LOCATION NCDEQ
INCIDENT NO.
DATE CLOSED
BY NCDEQ
8048 MCAS Cherry Point Not Issued 2/11/1998
1021 MCAS Cherry Point Not Issued 12/11/1998
1648 MCAS Cherry Point 14837 12/11/1998
497 MCAS Cherry Point 18514 12/18/1998
1779 MCAS Cherry Point Not Issued 12/18/1998
248 MCAS Cherry Point Not Issued 12/18/1998
3916 MCAS Cherry Point Not Issued 1/11/1999
1010 MCAS Cherry Point 19235 3/11/1999
1228 MCAS Cherry Point 19236 3/11/1999
1290 MCAS Cherry Point 19234 3/11/1999
498 MCAS Cherry Point 13133 12/7/1999
160 MCAS Cherry Point 13132 12/7/1999
85 MCAS Cherry Point 11277 2/10/2000
1786-3* MCAS Cherry Point 9273 2/10/2000
491* MCAS Cherry Point 12516 5/7/2000
1005-2 MCAS Cherry Point 8990 5/7/2000
1696 MCAS Cherry Point 14837 5/7/2000
3907* MCAS Cherry Point 14573 5/7/2000
8052 MCAS Cherry Point 7493 8/31/2000
487* MCAS Cherry Point 8308 10/17/2000
3904* MCAS Cherry Point 15120 2/21/2001
MTFP* MCAS Cherry Point 9839 7/26/2001
Old CP Hydrant MCAS Cherry Point Not Issued 8/28/2001
Atlantic Hydrant
System MCAS Cherry Point Not Issued 4/2/2002
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE III - continued
INDEX OF CLOSED SITES SINCE 1998
SITE NAME SITE LOCATION NCDEQ
INCIDENT NO.
DATE CLOSED
BY NCDEQ
1786* MCAS Cherry Point 9373 9/13/2002
Pit 6 MCAS Cherry Point 31023 11/26/2002
296* MCAS Cherry Point 9951 1/22/2003
Hertford #4 MCAS Cherry Point 31069 1/28/2003
TFC* MCAS Cherry Point 6906 3/11/2003
1701 MCAS Cherry Point Not Issued 3/12/2003
3982 MCAS Cherry Point Not Issued 6/9/2003
7012 MCAS Cherry Point 15275 10/20/2003
927* MCAS Cherry Point Not Issued 3/29/2004
Segment 22 JP-5
Pipeline MCAS Cherry Point 31269 5/4/2004
Segment 24 JP-5
Pipeline MCAS Cherry Point 31271 5/5/2004
Segment 2 JP-5
Pipeline MCAS Cherry Point 31272 5/6/2004
Segment 1 JP-5
Pipeline MCAS Cherry Point 31273 5/7/2004
Segment 14 JP-5
Pipeline MCAS Cherry Point 31285 6/2/2004
Segment 15 JP-5
Pipeline MCAS Cherry Point 31287 6/2/2004
Segment 16 JP-5
Pipeline MCAS Cherry Point 31286 6/2/2004
8052/TAFDS MCAS Cherry Point Not Issued 9/9/2004
Lifts A and B MCAS Cherry Point Part of 6360 12/13/2004
Pit 1 MCAS Cherry Point 31390 12/17/2004
82-AT MCAS Cherry Point 32128 6/20/2005
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE III – continued
INDEX OF CLOSED SITES SINCE 1998
SITE NAME SITE LOCATION NCDEQ
INCIDENT NO.
DATE CLOSED
BY NCDEQ
82-Bogue MCAS Cherry Point Not Issued 9/21/2005
84-Bogue MCAS Cherry Point 32254 9/21/2005
85-Bogue MCAS Cherry Point 32255 9/21/2005
86-Bogue MCAS Cherry Point 32256 9/21/2005
1783* MCAS Cherry Point 9275 10/27/2005
486* MCAS Cherry Point 9264 11/7/2005
1958 MCAS Cherry Point 31600 5/8/2006
MWSS-274 MCAS Cherry Point 85579 8/7/2006
1672* MCAS Cherry Point 6905 3/19/2007
TFB Transfer Lines
(Soils Only) MCAS Cherry Point 6359 3/2/2009
TAFDS MCAS Cherry Point 15256 1/5/2010
100 Gates Road MCAS Cherry Point 31974 1/11/2010
1773* MCAS Cherry Point 31691 3/2/2010
P-120 Sec 1 GW1 MCAS Cherry Point 31956 5/5/2010
P-120 Sec 1 GW2 MCAS Cherry Point 31956 5/5/2010
P-120 Sec 2 GW2 MCAS Cherry Point 38073 10/20/2010
56 Gates Road MCAS Cherry Point 38151 12/3/2010
64 Gates Road MCAS Cherry Point 38149 12/13/2010
62 Gates Road MCAS Cherry Point 38157 1/3/2011
29 Gates Road MCAS Cherry Point 38164 1/11/2011
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE III – continued
INDEX OF CLOSED SITES SINCE 1998
SITE NAME SITE LOCATION NCDEQ
INCIDENT NO.
DATE CLOSED
BY NCDEQ
68 Gates Road MCAS Cherry Point 38150 2/1/2011
66 Gates Road MCAS Cherry Point 38174 3/3/2011
137 Conveyance
Piping MCAS Cherry Point 31920 3/14/2011
P-120 Sec 2 GW1
(Fuel Hydrant System) MCAS Cherry Point 38069 6/30/2011
P-120 Sec 2 GW2 MCAS Cherry Point 38069 6/30/2011
24 Gates Road MCAS Cherry Point 38246 10/19/2011
Lanham Housing,
Site 621 MCAS Cherry Point 38247 10/19/2011
9 Gates UST MCAS Cherry Point 38266 1/23/2012
NADEP Washrack
Pipeline MCAS Cherry Point 93139 4/10/2012
1640 Tarmac MCAS Cherry Point Not Issued 4/12/2012
Lanham Housing,
Nash Road MCAS Cherry Point 38338 12/4/2013
78 Catawba, Nugent
Cove MCAS Cherry Point 38495 5/29/2014
Tower Valve Box* MCAS Cherry Point 31252 2/19/2015
Pit 12 MCAS Cherry Point 31356 September 2017
* Indicates site was included in the UST Closure and Management Program
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE IV
HISTORY OF NC REGULATORY STANDARDS
Parameter Previous NC 2L
Standard (ug/L)
Current/Interim
NC 2L
Standard (ug/L)
Effective Change Date
of Current/Interim NC
2L Standard
Acetochlor NE 100 1/1/2010
Acetochlor ESA NE 1000 1/1/2010
Acetochlor OXA NE 1000 1/1/2010
Acetophenone NE 700 4/1/2011
Acrolein NE 4 10/1/2010
Alachlor NE 0.4 8/1/2010
Aldrin NE 0.002 10/1/2010
Ammonia NE 1,500 8/1/2010
Antimony NE 1 8/1/2010
Benzaldehyde NE 700 4/1/2011
Benzyl Alcohol NE 700 10/1/2010
Beryllium NE 4 10/1/2010
Bromomethane NE 10 8/1/2010
Butanol, n- (n-butyl alcohol) NE 700 8/1/2010
Butanol, sec- (sec-butyl alcohol) NE 10,000 10/1/2010
Butanol, tert- (tert-butyl alcohol) NE 10 6/1/2011
Carbazole NE 2 4/1/2011
4-Chlorotoluene NE 24 10/1/2010
Cobalt NE 1 10/1/2010
Dalapon NE 200 8/1/2010
Dibenzofuran NE 28 5/24/1999
1,4-Dibromobenzene NE 70 8/1/2010
Dibromomethane NE 70 10/1/2010
Dichloroacetic Acid NE 0.7 10/1/2010
1,2-Dichloroethylene, mixed
isomers NE 60 10/1/2010
2,4-Dichlorophenol NE 0.98 8/1/2010
DDE NE 0.1 8/1/2010
Dinoseb NE 7 8/1/2010
Diphenyl Ether NE 100 4/1/2011
2,4-Dinitrotoluene NE 0.1 4/1/2011
Diquat NE 20 8/1/2010
Endosulfan sulfate NE 40 4/1/2011
Endothall NE 100 8/1/2010
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE IV – continued
HISTORY OF NC REGULATORY STANDARDS
Parameter Previous NC 2L
Standard (ug/L)
Current/Interim
NC 2L
Standard (ug/L)
Effective Change Date
of Current/Interim NC
2L Standard
Ethanol (ethyl alcohol) NE 4,000 4/1/2011
Ethyl tert-butyl ether (ETBE) NE 47 4/1/2011
alpha-Hexachlorocyclohexane NE 0.006 4/1/2011
beta-Hexachlorocyclohexane NE 0.02 4/1/2011
2-Hexanone NE 40 4/1/2011
4-Isopropyltoluene (p-cymene) NE 25 4/1/2011
Methyl Isobutyl Ketone NE 100 12/1/2010
Methyl Methacrylate NE 25 8/1/2010
1-Methylnaphthalene NE 1 4/1/2011
2-Methyl phenol (o-cresol) NE 400 4/1/2011
Perchlorate & Perchlorate Salts NE 2 12/1/2010
Perfluorooctanoic acid (PFOA;C8) NE 2 12/6/2006
Picramic Acid NE 0.7 10/1/2010
Polychlorinated Biphenyls NE 0.09 10/1/2010
Propylene Glycol NE 140,000 7/16/2012
Tert-Amyl Methyl Ether (TAME) NE 128 4/1/2011
1,2,4,5-Tetrachlorobenzene NE 2 8/1/2010
1,1,1,2-Tetrachloroethane NE 1 8/1/2010
Thallium NE 0.2 10/1/2010
Tin NE 2,000 10/1/2010
1,1,2-Trichloroethane NE 0.6 8/1/2010
2,4,5-Trichlorophenol NE 63 10/1/2010
2,4,6-Trichlorophenol NE 4 10/1/2010
Vanadium (excluding vanadium
pentoxide) NE 0.3 10/1/2010
Vinyl Acetate NE 88 10/1/2010
NE = Not established
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
TABLE V
INDEX OF INJECTION PERMIT SITES
SITE
NAME
PERMIT
No.
INJECTION
TYPE
DATE PERMIT
APPLICATION
RECEIVED BY
NCDEQ
DATE
PERMIT
APPROVED
BY NCDEQ
DATE
PERMIT
MODIFIED
DATE OF
PERMIT
EXPIRATION
DATE FINAL
PROJECT
EVALUATION
RECEIVED
BY NCDEQ
NCDEQ
CLOSEOUT
DATE
121
WI0700208
GW Tracer,
Surfactant,
nutrients,
bacteria
2/3/11
10/6/11 Mod.
6/4/13 Ext.
6/21/11
10/31/11Mod
6/30/13 Ext.
10/6/11 6/30/18 1/15/15
Not
Applicable
Yet
1083
WQ0035748 Surfactant
Recirculation
1/6/12
Renewal
9/16/13
4/6/12
Renewal
11/8/13
Renewed
11/8/13
Original
3/31/14
Renewed
3/31/19
Not Submitted
Yet
Not
Applicable
Yet
1773
WI0700106
Surfactant
5/10/07 8/20/07 Currently
None 8/31/09 2/25/09 3/25/11
8049
WI0800160 Surfactant 12/5/08
6/15/09 Mod.
3/25/09
6/16/09
Mod.
6/15/09 2/28/11 6/7/10 4/13/11
8049
WI800336
ORC™
Filter Socks 5/13/13 5/14/13 Currently
None Unknown Not Applicable Not
Applicable
Pit 11
WI0700227 RegenOx™ 5/31/11 7/14/11 Currently
None 6/30/13
Report
Submitted by
EAD
3/20/13
Not
Applicable
Yet
Pit 11 Mod
WI0700208
Surfactant,
nutrients,
bacteria
10/6/11
(Mod. of Bldg.
121 permit)
10/31/11
(Mod. of
Bldg. 121
permit)
10/6/11 5/31/13
Report
Submitted by
EAD
3/20/13
Not
Applicable
Yet
TVB
WI0700255
Surfactant,
nutrients,
bacteria
10/19/11 12/15/11 Currently
None 11/31/14
Report
Submitted by
EAD 7/14/14
7/24/14
2nd LAAD
WI0700320 Ambient Air 3/14/13 3/20/13 Currently
None Unknown Not Applicable Not
Applicable
Site 121 130 133 137 1083 1640 3996 4075 B &
PIT 12 4075 C PIT 6 PIT 15 SEGMENT
20*TFB TFD *2nd
LAAD PIT 11 MCCS
Month Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Product
(gal)
Jul-15 0 0 0 0 0 0 0 119 400 0 0 0 0 0 0 0 0
Aug-15 0 0 0 0 0 0 0 89 400 0 0 0 0 0 0 0 0
Sep-15 0 0 0 6 0 0 0 138 488 0 3 0 0 0 0 0 0
Oct-15 0 0 6 0 0 0 0 24 192 0 10 0 0 0 0 0 0
Nov-15 0 3 3 0 0 0 0 57 202 3 10 0 0 0 0 0 0
Dec-15 0 3 6 0 0 0 0 55 343 0 14 0 0 0 0 0 0
Jan-16 0 0 12 0 0 0 0 35 248 0 26 0 0 0 0 0 0
Feb-16 0 0 9 10 0 0 0 71 175 0 2 0 0 0 0 0 0
Mar-16 0 0 3 15 0 0 0 82 176 0 7 0 0 0 0 0 0
Apr-16 0 0 6 8 0 0 0 52 253 0 1 0 0 0 0 0 0
May-16 0 0 2 13 0 0 0 10 422 0 0 0 0 0 0 0 0
Jun-16 0 0 4 11 0 0 0 48 366 0 0 0 0 0 0 0 0
Jul-16 0 2 4 7 0 0 0 47 371 0 0 0 0 0 0 0 0
Aug-16 0 2 2 6 0 0 0 25 255 0 4 0 0 0 0 0 0
Sep-16 0 0 2 6 0 0 0 20 161 0 0 0 0 0 0 0 0
Oct-16 0 0 3 3 0 0 0 21 181 0 1 0 0 0 0 0 0
Nov-16 0 0 5 34 0 0 0 28 144 0 2 0 0 0 0 0 0
Dec-16 0 0 1 9 0 0 0 56 307 0 3 0 0 0 0 0 0
Jan-17 0 0 0 18 0 0 0 47 550 0 4 0 0 0 0 0 0
Feb-17 0 0 2 11 0 0 0 41 385 0 5 0 0 0 0 0 0
Mar-17 0 0 2 50 0 0 0 72 435 0 13 0 0 0 0 0 0
Apr-17 0 0 0 30 0 0 0 74 310 0 6 0 2 0 0 0 0
May-17 0 0 1 51 0 0 0 91 437 0 6 0 0 0 0 0 0
Jun-17 0 2 2 27 0 0 0 75 349 0 5 0 2 0 0 0 0
Totals 0.00 12.00 75.00 315.00 0.00 0.00 0.00 1,377.00 7,550.00 3.00 122.00 0.00 4.00 0.00 0.00 0.00 0.00
Average 0.00 0.50 3.13 13.13 0.00 0.00 0.00 57.38 314.58 0.13 5.08 0.00 0.17 0.00 0.00 0.00 0.00
TABLE VI
FREE PRODUCT RECOVERY TOTAL (LAST TWO YEARS)
Note: At sites with free product systems where interim product recovery is performed (i.e. bailing, pumping, etc.), the recovered product is emptied into the system; therefore, the interim product recovery volume is included
in the total product volume on this table.
* = Free Product currently not being recovered at site.
MCAS Cherry Point FY-017; Table VI_FPTotals_thru JUN 2017.xlsx
CATLIN Project No. 217001
CATLIN Engineers and Scientists
August 2017
MCAS Cherry Point
58
33
70
17
70
17
Data Source: Adapted from NCOneMaps.com
FIGUREPROJECTTITLE
JOB NO.DATE SCALE DRAWN BY CHECKED BY
IFACILITY LOCATIONS MAP
217001 JULY 2017 NO SCALE THW SAC
MCAS CHERRY POINTUST CLOSURE ANDMANAGEMENT PROGRAM
S:\GIS Projects\CPLTM\GIS\Sites\CAMP Figure 1.mxd
SECTION 5.0
OF THE
PERIODIC MONITORING REPORT
MCAS CHERRY POINT UST CLOSURE AND MANAGEMENT PROGRAM
FOR UST SITES
MONITORING EVENT:
FIRST SEMESTER 2017
(JANUARY 2017 THROUGH JUNE 2017)
SITE-SPECIFIC MONITORING REPORT
FOR
SITE 1083
NCDEQ INCIDENT NO. 9839
WARNING: This document is "FOR OFFICIAL USE ONLY" and it contains info
that may be exempt from public release under the FOi Act (5 U.S.C. 552). It
is to be handled IAW DoD policy and is not to be released to the public or
personnel who do not have a valid "need-to-know" without prior approval of
an authorized DoD official.
MCAS Cherry Point FY-17; 217001VOL 1.RPT39
CATLIN Project No. 217001
CATLIN Engineers and Scientists
August 2017
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
5.0 EXECUTIVE SUMMARY
SITE 1083
5.1 Site Information
5.1.1 Site Location: MCAS Cherry Point
5.1.2 Incident Number(s): 9839
5.1.3 NC State Plane Coordinates (NAD83): x = 2,632,699.36; y = 426,278.98
5.1.4 Risk Classification: MCAS temporarily assigned INTERMEDIATE risk due to
the presence of free-phase product and the proximity to surface waters.
5.1.5 Source Type(s): JP-5 (Pipeline)
5.2 Monitoring Event Information
5.2.1 Sampling Performed By: SDC Group, Inc./GES (Semi-Annual)
5.2.2 Date(s) of This Monitoring Event: 2/20/2017
5.2.3 Date(s) of Previous Monitoring Event: 8/30/2016
5.2.4 Reason(s) for This Monitoring Event:
Track migration and attenuation of dissolved-phase plume.
Track migration and/or volume reduction of free-phase product plume.
5.2.5 Site Monitoring Status at Time of This Event:
Interim and product recovery monitoring.
5.3 Groundwater Hydraulics
5.3.1 Hydraulic Conductivity: 7.0 feet/day
5.3.2 Effective Porosity: 0.25
5.3.3 Hydraulic Gradient: 0.0027 feet/feet
5.3.4 Average Linear Groundwater Flow Velocity: 0.0743 feet/day
5.3.5 Groundwater Flow Direction: East-Northeast. See Figure 5.1
5.3.6 Range of Measured Water Table Elevations: Ranges from -1.79 feet in well
41PR99 to 9.31 feet in well 41GW30 during the First Semester 2017 sampling
event. See Tables 5.1A.
5.3.7 Significant Changes from Previously Reported Data: None.
5.4 Free Product Plume
5.4.1 Free Product Present?: Yes
5.4.2 Free Product Thickness Measured: During the First Semester 2017 sampling
event, 100 wells were gauged. Of these, six (6) wells contained free product with
free product thicknesses ranging from 0.01 feet in wells 41PR202 to 0.05 feet in
monitoring well 41PR220. See Tables 5.1A through 5.1B.
5.4.3 Plume Size and Location: See Figure 5.1.
5.4.4 Free Product Removed from Site This Period: None.
5.4.5 Significant Changes from Previously Reported Data: Overall a reduction in the
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
extent and thickness of free-phase product has been observed in the areas which
were remediated by surfactant/recirculation activities. However, areas of residual
free-phase product remain at the subject site.
5.5 Dissolved-Phase Plume
5.5.1 Plume Concentrations: See Table 5.2A through 5.3B.
5.5.2 Plume Size and Location: See Figure 5.2.
5.5.3 Significant Changes from Previously Reported Data:
EPA Method 602 by SM 6200B
During the First Quarter (February 2016) monitoring event, concentrations of
Benzene exceeding the 2L Standard were revealed in monitoring wells 41GW02R,
41GW25, 41GW36, 41PR82, 41PR203, 41PR212, 41PR220 and 41PR230.
Monitoring wells 41GW02R, 41GW25, 41GW36, 41PR79, 41PR82, 41PR203,
41PR220 and 41PR230 exhibited concentrations of Benzene exceeding the 2L
Standard during the Second Quarter (May 2016) monitoring event. During the
previous Second Semester (August 2016) monitoring event, no samples were
analyzed for EPA 602 constituents.
During the current (February 2017) monitoring event, samples were again
analyzed for EPA Method 602 by SM 6200B and monitoring wells 41GW25,
41GW113 and 41PR230 revealed Benzene concentrations exceeding the 2L
Standard. The EPA Method 602 plume has been modified to more accurately
represent boundaries of the current monitoring event’s free-phase product and
analytical data. See Table 5.2A and 5.2B.
EPA Method 610 by EPA Method 625/ EPA Method 8260B
During the previous Second Semester (August 2016) monitoring event, no
samples were analyzed for EPA 610 constituents. Instead, EPA Method 8260B
was used to analyze for Naphthalene only. These results revealed Naphthalene
concentrations exceeding the 2L Standard in monitoring wells 41GW02R,
41GW03R, 41GW06, 41GW25, 41GW32, 41GW36, 41GW64, 41GW106,
41PR76, 41PR79, 41PR81, 41PR82, 41PR200, 41PR201, 41PR203, 41PR210,
41PR211, 41PR212, 41PR213, 41PR214, 41PR215, 41PR220, 41PR221 and
41PR230.
During the current (February 2017) monitoring event, samples were again
analyzed for EPA 610 constituents and the following wells revealed Naphthalene
concentrations exceeding the 2L Standards: 41GW25, 41GW36, 41GW43,
41GW64, 41PR72, 41PR73, 41PR76, 41PR200, 41PR203 and 41PR230.
Monitoring wells 41GW36, 41GW64 and GWPR76 also revealed concentrations of
2-Methylnaphthalene exceeding the 2L Standards. In addition, the 6 wells that
contained free-phase product are also illustrated as non-compliant with the 2L
Standards. The EPA Method 610 plume has been modified to more accurately
represent the boundaries of the current monitoring event’s free-phase product and
analytical data. See Tables 5.3A through 5.3B and Figure 5.2.
Please note that site monitoring/recovery wells were not sampled if they were
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
inaccessible or found to contain free-phase product.
5.6 Remedial System Air Monitoring Data and Effluent Discharge Data
5.6.1 Air Contaminant Concentrations: Not Applicable
5.6.2 Effluent Discharge Contaminant Concentrations: Not Applicable
5.7 Potential Receptors
5.7.1 Contaminated Water Supply Well(s)?: No
5.7.2 Potable Water Supply Well Within 1,000 Feet of Source Area?: No
5.7.3 Any Water Supply Well Within 250 Feet of Source Area?: No
5.7.4 Surface Water Body Within 500 Feet?: Yes. Unnamed tributary to Hancock
Creek.
5.7.5 Past Evidence of Vapors?: No
5.7.6 Significant Changes from Previously Reported Data?: None
5.8 Remediation
5.8.1 Status: Gathering additional assessment data that will be utilized to evaluate
remediation alternatives
5.8.2 Type: Previously Surfactant Recirculation and AFVR
5.8.3 Progress: Completed four rounds of surfactant recirculation
5.8.4 Construction Contractor: CATLIN/ETEC (Surfactant Recirculation System)
5.8.5 Operating Contractor: SDC Group, Inc/GES
5.9 Observations and Comments
5.9.1 Historical: In late 2010/early 2011, CATLIN recommended surfactant
injection/extraction recirculation to remove the remaining free-phase product at the
site. Injection permitting discussions prompted a meeting with the NCDEQ UIC
Injection Branch, to discuss the possibility of a Base Wide re-circulation permit for
MCAS Cherry Point.
Further evaluations and discussions prompted CATLIN to recommend a series of
surfactant recirculation events on site, utilizing a mobile surfactant
injection/recirculation trailer unit. A demonstration of the mobile trailer unit was
performed by a private vendor on May 13th, 2011.
In August 2011, CATLIN developed and Cherry Point EAD submitted the CAPA
report to the Washington Regional office of NCDEQ for the surfactant recirculation
events to be implemented at the subject site. The CAPA was approved by
NCDEQ on November 16, 2011. In January 2012, a Base-Wide Non-Discharge
permit with Building 1083 Site Specific Attachments was submitted to NCDEQ UIC
Branch. The permit was issued on April 6, 2012. CATLIN prepared and submitted
a Workplan in July 2012 and MCAS ordered the mobile trailer system. The mobile
surfactant trailer for MCAS Cherry Point was delivered in early August 2012.
In late July/early August 2012, CATLIN installed 18 additional recovery wells to be
used in the surfactant recirculation activities at three areas on-site (Area A, B and
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
C). All additional recovery wells were installed prior to the mobile surfactant
injection/recirculation system start-up. Field activities began in August 2012 and
one round of surfactant recirculation and nutrient injection was completed at Areas
A, B, and C by November 2012. From early January 2013 through early March
2013 a second round of surfactant recirculation and nutrient injection was
completed at Areas A, B, and C. Gauging data collected from March 2013 through
May 2013 revealed free-phase product reappeared at Areas A and B. As free-
phase product remained at Areas A and B as of June 2013, a third round of
surfactant recirculation and nutrient injection was completed at Areas A and B
from July 2013 through October 2013.
Gauging data from the First Semester 2014 revealed that minor amounts of free-
phase product remained at two areas (Area A and B); therefore, an additional
surfactant recirculation event was recommended. Also, AFVR events were
conducted in May 2014 at the areas of “outlying” free-phase product (i.e. beyond
the limits of Areas A, B and C) at wells 41GW05, 41GW43, 41PR68 and 41PR83.
However, no measureable thickness of free-phase product was recorded from any
of these wells during the AFVR events.
Gauging data from the Second Semester 2014 indicated that free-phase product
thicknesses rebounded slightly at two areas (Area A and B) since the last
surfactant recirculation event; therefore, an additional surfactant recirculation
event was planned for the Spring/Summer of 2015. Also, an additional AFVR
event was conducted in October 2014 at well 41PR83 which was calculated to
have recovered less than a hundredth of a gallon of free-phase product. In
addition, in December 2014 monitoring wells 41GW02 and 41GW03 (Area A) were
removed and replaced with four-inch diameter wells 41GW02R and 41GW03R
which should enhance surfactant recirculation/recovery at these locations during
the planned, upcoming activities.
The fourth round of surfactant recirculation at Area A commenced on May 5, 2015
and was completed on May 19, 2015. Surfactant recirculation activities began at
Area B in early June 2015; however, due to a construction project in the vicinity of
Area B the surfactant recirculation activities had to be suspended. The
construction project was completed and the surfactant recirculation activities were
restarted in this area in mid-July 2015. The surfactant recirculation activities were
completed at Area B in mid-November 2015. Gauging data from the Second
Semester 2015 revealed that free-phase product rebounded at one well at Area A
and three wells at Area B revealed free-phase product in November and
December 2015.
Quarterly groundwater sampling events were conducted in February 2016 and
May 2016 in accordance with the Non-Discharge Permit associated with the
surfactant recirculation project at the subject site. The results from these sampling
events (and review of historical sampling events over the past five years) indicated
that dissolved-phase contaminant concentrations remained relatively unchanged
and the dissolved-phase plume is generally stable and not migrating. However,
residual free-phase product continued to persist at the subject site and additional
surfactant recirculation events are not planned at this time.
MCAS Cherry Point FY-17; 217001VOL1.RPT39 CATLIN Engineers and Scientists
CATLIN Project No. 217001 August 2017
Residual free-phase product continued to persist at the subject site based on
gauging data from the Second Semester 2016. A project to fully delineate the
extent of residual free-phase product and dissolved-phase groundwater
contamination started in August 2016 and was completed in May 2017. As part of
this project all on-site monitoring wells (approximately 100) were sampled for
Naphthalene in August 2016. The results of this sampling indicated that the
dissolved-phase Naphthalene plume was generally delineated. The data also
indicated that the highest Naphthalene concentration was 428 ug/L which was
above the 2L GWQS of 6 ug/L but well below the GCL of 6,000 ug/L.
Current: As part of the above-stated delineation project 23 borings and temporary
wells were installed, gauged and sampled during March through May 2017. The
results from the sampling of the temporary wells were used in conjunction with the
August 2016 site-wide Naphthalene data to fully delineate the dissolved-phase
plume. Also, select on-site wells were sampled in February 2017 and these
results were comparable to the August 2016 analytical results.
The borings/temporary wells were also used to delineate the extent of the residual
free-phase product at the subject site. All of the data collected from the above-
stated project was utilized to develop an updated Conceptual Site Model for the
site which was completed in May 2017. The updated Conceptual Site Model will
be utilized to evaluate potential remedial alternative technologies for the subject
site. Also, based on the updated Conceptual Site Model it was determined that a
petroleum vapor intrusion investigation is necessary. This investigation will be
conducted at the subject site during the Second Semester 2017. Also, another
semi-annual groundwater sampling event of select on-site monitoring wells is
planned in August 2017.
SITE 1083
TABLE 5.1A
FIELD MEASUREMENTS
Well No TYPE STICKUPTOC
2/20/2017Date Measured:
Product Thickness DTW/DTP BGSDTW/DTP
Corrected
GW Elevation
-0.8214.88T-II41GW02R 0.00 11.1810.36 4.52
-0.5714.93T-II41GW03R 0.00 12.5912.02 2.91
-0.1415.76T-II41GW05 0.02 12.4412.30 3.46
-0.2515.75T-II41GW06 0.00 12.8212.57 3.18
-0.3616.14T-II41GW21 0.00 12.6712.31 3.83
-0.4714.63T-II41GW22 0.00 8.698.22 6.41
-0.4213.88T-II41GW23 0.00 10.9110.49 3.39
-0.288.72T-II41GW24 0.00 4.804.52 4.20
-0.3216.18T-II41GW25 0.00 11.4911.17 5.01
2.529.42T-II41GW26 0.00 4.687.20 2.22
-0.4913.51T-II41GW27 0.00 8.457.96 5.55
2.3612.06T-II41GW28 0.00 6.959.31 2.75
2.3010.40T-II41GW29 0.00 5.758.05 2.35
-0.4214.78T-III41GW30 0.00 5.895.47 9.31
-0.2513.15T-II41GW31 0.00 10.9610.71 2.44
-0.7014.60T-II41GW32 0.00 10.609.90 4.70
-0.1513.25T-III41GW33 0.00 10.9110.76 2.49
-0.2714.93T-II41GW34 0.00 9.519.24 5.69
1.2810.18T-III41GW35 0.00 6.808.08 2.10
-1.7815.12RW41GW36 0.00 12.3510.57 4.55
-1.618.39RW41GW37 0.00 6.705.09 3.30
5.7616.24T-II41GW38 0.00 4.3510.11 6.13
2.9416.67T-II41GW39 0.00 9.7512.69 3.98
-0.2412.66T-II41GW40 0.00 11.3211.08 1.58
-0.4314.87T-II41GW41 0.00 13.6113.18 1.69
-0.4614.64T-II41GW42 0.00 10.159.69 4.95
-1.4714.83RW41GW43 0.00 17.1615.69 -0.86
-0.5715.73T-II41GW44 0.00 11.2110.64 5.09
2.7516.55Unknown41GW45 0.00 9.3312.08 4.47
2.8710.77T-II41GW46 0.00 5.308.17 2.60
-0.4315.97T-II41GW62 0.00 11.6011.17 4.80
Page 1
Notes: 1. T-l = Type l monitoring well
T-II = Type II monitoring well
T-III = Type III monitoring well
RW = Recovery well
2. TOC = Top of well casing elevation, in feet relative to Mean Sea Level.
3. STICK UP = Height of well casing above land surface in feet.
4. DTW = Depth to water (in feet) from top of well casing.
5. DTP = Depth to product (in feet) from top of well casing.
6. Product thickness is measured in feet.
7. DTW/DTP BGS = Depth to water/depth to product below ground surface in feet.
8. GW Elevation = Ground water elevation (adjusted for product) in feet.
9. A zero ("0.00") in the product thickness column indicates no measureable thickness.
10. Stick up values were not available for wells with no values in the STICK UP and
DTW/DTP BGS columns.
11. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Well No TYPE STICKUPTOC
2/20/2017Date Measured:
Product Thickness DTW/DTP BGSDTW/DTP
Corrected
GW Elevation
-0.5415.56T-II41GW63 0.00 11.0310.49 5.07
-0.3114.39T-II41GW64 0.00 9.569.25 5.14
-0.2313.17T-II41GW65 0.00 8.107.87 5.30
-0.3312.67T-II41GW66 0.00 10.179.84 2.83
-0.1215.98T-II41GW102 0.00 10.1610.04 5.94
-0.0916.01T-III41GW103 0.00 11.0210.93 5.08
-0.6615.24T-II41GW104 0.00 10.8810.22 5.02
-0.6315.77T-II41GW105 0.00 11.3710.74 5.03
-0.4816.12T-II41GW106 0.00 10.9810.50 5.62
-0.5616.14T-II41GW107 0.00 13.9613.40 2.74
-0.2415.06T-III41GW108 0.00 13.3913.15 1.91
-0.6615.94T-II41GW111 0.00 12.2611.60 4.34
-0.1716.23T-II41GW112 0.00 11.3911.22 5.01
-0.2114.19T-II41GW113 0.00 9.399.18 5.01
-0.1214.48T-III41GW114 0.00 10.6610.54 3.94
-0.4915.18T-II41GW119 0.00 9.138.64 6.54
-1.2214.28RW41PR67 0.00 10.349.12 5.16
-1.4514.75RW41PR68 0.00 12.3210.87 3.88
-0.9515.65RW41PR69 0.00 11.7410.79 4.86
-1.2114.99RW41PR70 0.00 11.2610.05 4.94
-0.9414.36RW41PR71 0.00 10.349.40 4.96
-0.9714.63RW41PR72 0.00 10.629.65 4.98
-0.9015.40RW41PR73 0.00 11.3010.40 5.00
-0.8715.73RW41PR74 0.00 11.8711.00 4.73
-0.7815.02RW41PR75 0.00 10.9010.12 4.90
-1.2814.42RW41PR76 0.00 10.549.26 5.16
-1.5115.29RW41PR77 0.00 10.488.97 6.32
-1.7314.37RW41PR78 0.00 10.518.78 5.59
-1.3313.77RW41PR79 0.00 7.596.26 7.51
-1.2814.52RW41PR80 0.00 10.158.87 5.65
-1.4113.99RW41PR81 0.00 14.0612.65 1.34
-1.6514.35RW41PR82 0.00 10.078.42 5.93
-1.0314.97RW41PR83 0.00 10.979.94 5.03
-1.8112.99RW41PR84 0.00 11.9310.12 2.87
-1.4713.03RW41PR85 0.00 11.7810.31 2.72
-1.1913.61RW41PR86 0.00 11.8810.69 2.92
-0.8713.83RW41PR87 0.00 11.3110.44 3.39
-0.8112.89RW41PR88 0.00 11.1010.29 2.60
-1.0912.11RW41PR89 0.00 10.729.63 2.48
Page 2
Notes: 1. T-l = Type l monitoring well
T-II = Type II monitoring well
T-III = Type III monitoring well
RW = Recovery well
2. TOC = Top of well casing elevation, in feet relative to Mean Sea Level.
3. STICK UP = Height of well casing above land surface in feet.
4. DTW = Depth to water (in feet) from top of well casing.
5. DTP = Depth to product (in feet) from top of well casing.
6. Product thickness is measured in feet.
7. DTW/DTP BGS = Depth to water/depth to product below ground surface in feet.
8. GW Elevation = Ground water elevation (adjusted for product) in feet.
9. A zero ("0.00") in the product thickness column indicates no measureable thickness.
10. Stick up values were not available for wells with no values in the STICK UP and
DTW/DTP BGS columns.
11. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Well No TYPE STICKUPTOC
2/20/2017Date Measured:
Product Thickness DTW/DTP BGSDTW/DTP
Corrected
GW Elevation
-1.2112.09RW41PR90 0.00 10.659.44 2.65
-0.9111.39RW41PR91 0.00 9.298.38 3.01
-0.879.23RW41PR92 0.00 7.176.30 2.93
-1.339.87RW41PR93 0.00 8.647.31 2.56
0.009.57RW41PR94 0.00 6.646.64 2.93
-1.109.30RW41PR95 0.00 8.026.92 2.38
-1.346.96RW41PR96 0.00 8.467.12 -0.16
-0.1410.46RW41PR97 0.00 8.468.32 2.14
0.118.01RW41PR98 0.00 6.126.23 1.78
0.446.94RW41PR99 0.00 8.298.73 -1.79
-0.6914.41RW41PR100 0.00 10.169.47 4.94
-1.1115.39RW41PR101 0.00 11.3510.24 5.15
-0.5815.92RW41PR200 0.00 11.5210.94 4.98
-0.3016.40RW41PR201 0.00 11.7311.43 4.97
-0.3916.11RW41PR202 0.01 10.4010.01 6.10
-0.2916.21RW41PR203 0.00 11.2010.91 5.30
-0.3016.00RW41PR204 0.00 10.9510.65 5.35
-0.4015.60RW41PR210 0.00 11.8311.43 4.17
-0.4615.44RW41PR211 0.00 12.1911.73 3.71
-0.3715.43RW41PR212 0.00 12.5012.13 3.30
-0.2215.28RW41PR213 0.00 12.6312.41 2.87
-0.4015.30RW41PR214 0.00 12.6812.28 3.02
-0.4215.58RW41PR215 0.00 12.2111.79 3.79
-0.2815.82RW41PR216 0.02 12.0111.73 4.09
-0.4715.53RW41PR217 0.02 11.5911.12 4.41
-0.2715.23RW41PR218 0.02 11.4311.16 4.07
-0.1915.81RW41PR219 0.00 11.2811.09 4.72
-0.2815.92RW41PR220 0.05 11.9511.67 4.24
-0.2915.81RW41PR221 0.00 11.6111.32 4.49
-0.2215.88RW41PR230 0.00 11.0410.82 5.06
Page 3
Notes: 1. T-l = Type l monitoring well
T-II = Type II monitoring well
T-III = Type III monitoring well
RW = Recovery well
2. TOC = Top of well casing elevation, in feet relative to Mean Sea Level.
3. STICK UP = Height of well casing above land surface in feet.
4. DTW = Depth to water (in feet) from top of well casing.
5. DTP = Depth to product (in feet) from top of well casing.
6. Product thickness is measured in feet.
7. DTW/DTP BGS = Depth to water/depth to product below ground surface in feet.
8. GW Elevation = Ground water elevation (adjusted for product) in feet.
9. A zero ("0.00") in the product thickness column indicates no measureable thickness.
10. Stick up values were not available for wells with no values in the STICK UP and
DTW/DTP BGS columns.
11. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.58NMT41GW02R 8/30/2016 14.88 -0.82 9.3 10.12
7.02NMT41GW02R 9/6/2016 14.88 -0.82 7.86 8.68
6.19NMT41GW02R 10/5/2016 14.88 -0.82 8.69 9.51
5.32NMT41GW02R 11/3/2016 14.88 -0.82 9.56 10.38
4.08NMT41GW02R 12/2/2016 14.88 -0.82 10.8 11.62
4.71NMT41GW02R 1/9/2017 14.88 -0.82 10.17 10.99
4.52NMT41GW02R 2/20/2017 14.88 -0.82 10.36 11.18
4.39NMT41GW02R 3/1/2017 14.88 -0.82 10.49 11.31
4.30NMT41GW02R 4/3/2017 14.88 -0.82 10.58 11.40
4.74NMT41GW02R 5/1/2017 14.88 -0.82 10.14 10.96
3.75NMT41GW02R 6/5/2017 14.88 -0.82 11.13 11.95
5.03NMT41GW03R 8/30/2016 14.93 -0.57 9.9 10.47
6.90NMT41GW03R 9/6/2016 14.93 -0.57 8.03 8.60
5.93NMT41GW03R 10/5/2016 14.93 -0.57 9 9.57
4.52NMT41GW03R 11/3/2016 14.93 -0.57 10.41 10.98
3.20NMT41GW03R 12/2/2016 14.93 -0.57 11.73 12.30
5.59NMT41GW03R 1/9/2017 14.93 -0.57 9.34 9.91
2.91NMT41GW03R 2/20/2017 14.93 -0.57 12.02 12.59
3.42NMT41GW03R 3/1/2017 14.93 -0.57 11.51 12.08
3.29NMT41GW03R 4/3/2017 14.93 -0.57 11.64 12.21
3.64NMT41GW03R 5/1/2017 14.93 -0.57 11.29 11.86
2.99NMT41GW03R 6/5/2017 14.93 -0.57 11.94 12.51
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 1BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
3.98NMT41GW05 8/30/2016 15.76 -0.14 11.78 11.92
5.450.0341GW05 9/6/2016 15.76 -0.14 10.3 10.44
5.710.0141GW05 10/5/2016 15.76 -0.14 10.05 10.19
4.46NMT41GW05 11/3/2016 15.76 -0.14 11.3 11.44
3.28NMT41GW05 12/2/2016 15.76 -0.14 12.48 12.62
4.270.0241GW05 1/9/2017 15.76 -0.14 11.49 11.63
3.460.0241GW05 2/20/2017 15.76 -0.14 12.3 12.44
3.36NMT41GW05 3/1/2017 15.76 -0.14 12.4 12.54
3.310.0141GW05 4/3/2017 15.76 -0.14 12.45 12.59
3.570.0141GW05 5/1/2017 15.76 -0.14 12.19 12.33
2.750.0241GW05 6/5/2017 15.76 -0.14 13.01 13.15
4.09NMT41GW06 8/30/2016 15.75 -0.25 11.66 11.91
5.67NMT41GW06 9/6/2016 15.75 -0.25 10.08 10.33
5.52NMT41GW06 10/5/2016 15.75 -0.25 10.23 10.48
3.83NMT41GW06 11/3/2016 15.75 -0.25 11.92 12.17
2.58NMT41GW06 12/2/2016 15.75 -0.25 13.17 13.42
4.12NMT41GW06 1/9/2017 15.75 -0.25 11.63 11.88
3.18NMT41GW06 2/20/2017 15.75 -0.25 12.57 12.82
2.85NMT41GW06 3/1/2017 15.75 -0.25 12.9 13.15
2.95NMT41GW06 4/3/2017 15.75 -0.25 12.8 13.05
3.27NMT41GW06 5/1/2017 15.75 -0.25 12.48 12.73
2.29NMT41GW06 6/5/2017 15.75 -0.25 13.46 13.71
4.00NMT41GW21 8/30/2016 16.14 -0.36 12.14 12.50
3.83NMT41GW21 2/20/2017 16.14 -0.36 12.31 12.67
5.08NMT41GW22 8/30/2016 14.63 -0.47 9.55 10.02
6.41NMT41GW22 2/20/2017 14.63 -0.47 8.22 8.69
3.43NMT41GW23 8/30/2016 13.88 -0.42 10.45 10.87
3.39NMT41GW23 2/20/2017 13.88 -0.42 10.49 10.91
4.90NMT41GW24 8/30/2016 8.72 -0.28 3.82 4.10
4.20NMT41GW24 2/20/2017 8.72 -0.28 4.52 4.80
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 2BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.33NMT41GW25 8/30/2016 16.18 -0.32 10.85 11.17
5.01NMT41GW25 2/20/2017 16.18 -0.32 11.17 11.49
2.75NMT41GW26 8/30/2016 9.42 2.52 6.67 4.15
2.22NMT41GW26 2/20/2017 9.42 2.52 7.2 4.68
6.11NMT41GW27 8/30/2016 13.51 -0.49 7.4 7.89
5.55NMT41GW27 2/20/2017 13.51 -0.49 7.96 8.45
3.22NMT41GW28 8/30/2016 12.06 2.36 8.84 6.48
2.75NMT41GW28 2/20/2017 12.06 2.36 9.31 6.95
1.70NMT41GW29 8/30/2016 10.4 2.3 8.7 6.40
2.35NMT41GW29 2/20/2017 10.4 2.3 8.05 5.75
7.14NMT41GW30 8/30/2016 14.78 -0.42 7.64 8.06
9.31NMT41GW30 2/20/2017 14.78 -0.42 5.47 5.89
2.34NMT41GW31 8/30/2016 13.15 -0.25 10.81 11.06
2.44NMT41GW31 2/20/2017 13.15 -0.25 10.71 10.96
5.00NMT41GW32 8/30/2016 14.6 -0.7 9.6 10.30
4.70NMT41GW32 2/20/2017 14.6 -0.7 9.9 10.60
2.65NMT41GW33 8/30/2016 13.25 -0.15 10.6 10.75
2.49NMT41GW33 2/20/2017 13.25 -0.15 10.76 10.91
5.40NMT41GW34 8/30/2016 14.93 -0.27 9.53 9.80
5.69NMT41GW34 2/20/2017 14.93 -0.27 9.24 9.51
2.10NMT41GW35 2/20/2017 10.18 1.28 8.08 6.80
5.04NMT41GW36 8/30/2016 15.12 -1.78 10.08 11.86
6.31NMT41GW36 9/6/2016 15.12 -1.78 8.81 10.59
6.49NMT41GW36 10/5/2016 15.12 -1.78 8.63 10.41
5.51NMT41GW36 11/3/2016 15.12 -1.78 9.61 11.39
4.15NMT41GW36 12/2/2016 15.12 -1.78 10.97 12.75
5.32NMT41GW36 1/9/2017 15.12 -1.78 9.8 11.58
4.55NMT41GW36 2/20/2017 15.12 -1.78 10.57 12.35
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 3BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
3.65NMT41GW37 8/30/2016 8.39 -1.61 4.74 6.35
3.30NMT41GW37 2/20/2017 8.39 -1.61 5.09 6.70
5.27NMT41GW38 8/30/2016 16.24 5.76 10.97 5.21
6.13NMT41GW38 2/20/2017 16.24 5.76 10.11 4.35
4.18NMT41GW39 8/30/2016 16.67 2.94 12.49 9.55
3.98NMT41GW39 2/20/2017 16.67 2.94 12.69 9.75
1.80NMT41GW40 8/30/2016 12.66 -0.24 10.86 11.10
1.58NMT41GW40 2/20/2017 12.66 -0.24 11.08 11.32
2.47NMT41GW41 8/30/2016 14.87 -0.43 12.399 12.83
1.69NMT41GW41 2/20/2017 14.87 -0.43 13.18 13.61
5.48NMT41GW42 8/30/2016 14.64 -0.46 9.16 9.62
4.95NMT41GW42 2/20/2017 14.64 -0.46 9.69 10.15
5.41NMT41GW43 8/30/2016 14.83 -1.47 9.42 10.89
6.12NMT41GW43 9/6/2016 14.83 -1.47 8.71 10.18
7.79NMT41GW43 10/5/2016 14.83 -1.47 7.04 8.51
6.65NMT41GW43 11/3/2016 14.83 -1.47 8.18 9.65
5.65NMT41GW43 12/2/2016 14.83 -1.47 9.18 10.65
5.39NMT41GW43 1/9/2017 14.83 -1.47 9.44 10.91
-0.86NMT41GW43 2/20/2017 14.83 -1.47 15.69 17.16
5.35NMT41GW44 8/30/2016 15.73 -0.57 10.38 10.95
5.09NMT41GW44 2/20/2017 15.73 -0.57 10.64 11.21
4.56NMT41GW45 8/30/2016 16.55 2.75 11.99 9.24
4.47NMT41GW45 2/20/2017 16.55 2.75 12.08 9.33
3.30NMT41GW46 8/30/2016 10.77 2.87 7.47 4.60
2.60NMT41GW46 2/20/2017 10.77 2.87 8.17 5.30
4.98NMT41GW62 8/30/2016 15.97 -0.43 10.99 11.42
4.80NMT41GW62 2/20/2017 15.97 -0.43 11.17 11.60
5.34NMT41GW63 8/30/2016 15.56 -0.54 10.22 10.76
5.07NMT41GW63 2/20/2017 15.56 -0.54 10.49 11.03
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 4BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.22NMT41GW64 8/30/2016 14.39 -0.31 9.17 9.48
5.14NMT41GW64 2/20/2017 14.39 -0.31 9.25 9.56
6.22NMT41GW65 8/30/2016 13.17 -0.23 6.95 7.18
5.30NMT41GW65 2/20/2017 13.17 -0.23 7.87 8.10
4.27NMT41GW66 8/30/2016 12.67 -0.33 8.4 8.73
2.83NMT41GW66 2/20/2017 12.67 -0.33 9.84 10.17
6.05NMT41GW102 8/30/2016 15.98 -0.12 9.93 10.05
5.94NMT41GW102 2/20/2017 15.98 -0.12 10.04 10.16
5.28NMT41GW103 8/30/2016 16.01 -0.09 10.73 10.82
5.08NMT41GW103 2/20/2017 16.01 -0.09 10.93 11.02
5.27NMT41GW104 8/30/2016 15.24 -0.66 9.97 10.63
5.02NMT41GW104 2/20/2017 15.24 -0.66 10.22 10.88
5.34NMT41GW105 8/30/2016 15.77 -0.63 10.43 11.06
5.03NMT41GW105 2/20/2017 15.77 -0.63 10.74 11.37
6.38NMT41GW106 8/30/2016 16.12 -0.48 9.74 10.22
7.22NMT41GW106 9/6/2016 16.12 -0.48 8.9 9.38
7.63NMT41GW106 10/5/2016 16.12 -0.48 8.49 8.97
6.72NMT41GW106 11/3/2016 16.12 -0.48 9.4 9.88
5.38NMT41GW106 12/2/2016 16.12 -0.48 10.74 11.22
6.51NMT41GW106 1/9/2017 16.12 -0.48 9.61 10.09
5.62NMT41GW106 2/20/2017 16.12 -0.48 10.5 10.98
5.38NMT41GW106 3/1/2017 16.12 -0.48 10.74 11.22
5.36NMT41GW106 4/3/2017 16.12 -0.48 10.76 11.24
5.37NMT41GW106 5/1/2017 16.12 -0.48 10.75 11.23
4.70NMT41GW106 6/5/2017 16.12 -0.48 11.42 11.90
3.12NMT41GW107 8/30/2016 16.14 -0.56 13.02 13.58
2.74NMT41GW107 2/20/2017 16.14 -0.56 13.4 13.96
1.21NMT41GW108 8/30/2016 15.06 -0.24 13.85 14.09
1.91NMT41GW108 2/20/2017 15.06 -0.24 13.15 13.39
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 5BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.52NMT41GW111 8/30/2016 15.94 -0.66 10.42 11.08
4.34NMT41GW111 2/20/2017 15.94 -0.66 11.6 12.26
5.57NMT41GW112 8/30/2016 16.23 -0.17 10.66 10.83
5.01NMT41GW112 2/20/2017 16.23 -0.17 11.22 11.39
5.29NMT41GW113 8/30/2016 14.19 -0.21 8.9 9.11
5.01NMT41GW113 2/20/2017 14.19 -0.21 9.18 9.39
3.64NMT41GW114 8/30/2016 14.48 -0.12 10.84 10.96
3.94NMT41GW114 2/20/2017 14.48 -0.12 10.54 10.66
6.23NMT41GW119 8/30/2016 15.18 -0.49 8.95 9.44
6.54NMT41GW119 2/20/2017 15.18 -0.49 8.64 9.13
5.52NMT41PR67 8/30/2016 14.28 -1.22 8.76 9.98
5.16NMT41PR67 2/20/2017 14.28 -1.22 9.12 10.34
5.38NMT41PR68 8/30/2016 14.75 -1.45 9.37 10.82
3.88NMT41PR68 2/20/2017 14.75 -1.45 10.87 12.32
5.29NMT41PR69 8/30/2016 15.65 -0.95 10.36 11.31
4.86NMT41PR69 2/20/2017 15.65 -0.95 10.79 11.74
5.54NMT41PR70 8/30/2016 14.99 -1.21 9.45 10.66
4.94NMT41PR70 2/20/2017 14.99 -1.21 10.05 11.26
5.29NMT41PR71 8/30/2016 14.36 -0.94 9.07 10.01
4.96NMT41PR71 2/20/2017 14.36 -0.94 9.4 10.34
5.22NMT41PR72 8/30/2016 14.63 -0.97 9.41 10.38
5.92NMT41PR72 9/6/2016 14.63 -0.97 8.71 9.68
6.47NMT41PR72 10/5/2016 14.63 -0.97 8.16 9.13
6.36NMT41PR72 11/3/2016 14.63 -0.97 8.27 9.24
5.24NMT41PR72 12/2/2016 14.63 -0.97 9.39 10.36
5.31NMT41PR72 1/9/2017 14.63 -0.97 9.32 10.29
4.98NMT41PR72 2/20/2017 14.63 -0.97 9.65 10.62
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 6BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.24NMT41PR73 8/30/2016 15.4 -0.9 10.16 11.06
8.01NMT41PR73 9/6/2016 15.4 -0.9 7.39 8.29
6.51NMT41PR73 10/5/2016 15.4 -0.9 8.89 9.79
6.51NMT41PR73 11/3/2016 15.4 -0.9 8.89 9.79
5.36NMT41PR73 12/2/2016 15.4 -0.9 10.04 10.94
5.27NMT41PR73 1/9/2017 15.4 -0.9 10.13 11.03
5.00NMT41PR73 2/20/2017 15.4 -0.9 10.4 11.30
5.29NMT41PR74 8/30/2016 15.73 -0.87 10.44 11.31
4.73NMT41PR74 2/20/2017 15.73 -0.87 11 11.87
5.56NMT41PR75 8/30/2016 15.02 -0.78 9.46 10.24
4.90NMT41PR75 2/20/2017 15.02 -0.78 10.12 10.90
5.44NMT41PR76 8/30/2016 14.42 -1.28 8.98 10.26
5.16NMT41PR76 2/20/2017 14.42 -1.28 9.26 10.54
7.00NMT41PR77 8/30/2016 15.29 -1.51 8.29 9.80
7.77NMT41PR77 9/6/2016 15.29 -1.51 7.52 9.03
8.05NMT41PR77 10/5/2016 15.29 -1.51 7.24 8.75
5.52NMT41PR77 11/3/2016 15.29 -1.51 9.77 11.28
5.51NMT41PR77 12/2/2016 15.29 -1.51 9.78 11.29
7.45NMT41PR77 1/9/2017 15.29 -1.51 7.84 9.35
6.32NMT41PR77 2/20/2017 15.29 -1.51 8.97 10.48
6.05NMT41PR77 3/1/2017 15.29 -1.51 9.24 10.75
6.06NMT41PR77 4/3/2017 15.29 -1.51 9.23 10.74
5.90NMT41PR77 5/1/2017 15.29 -1.51 9.39 10.90
4.85NMT41PR77 6/5/2017 15.29 -1.51 10.44 11.95
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 7BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.460.0341PR78 8/30/2016 14.37 -1.73 8.9 10.63
6.80NMT41PR78 9/6/2016 14.37 -1.73 7.57 9.30
7.14NMT41PR78 10/5/2016 14.37 -1.73 7.23 8.96
6.64NMT41PR78 11/3/2016 14.37 -1.73 7.73 9.46
5.36NMT41PR78 12/2/2016 14.37 -1.73 9.01 10.74
6.58NMT41PR78 1/9/2017 14.37 -1.73 7.79 9.52
5.59NMT41PR78 2/20/2017 14.37 -1.73 8.78 10.51
5.28NMT41PR78 3/1/2017 14.37 -1.73 9.09 10.82
5.16NMT41PR78 4/3/2017 14.37 -1.73 9.21 10.94
4.93NMT41PR78 5/1/2017 14.37 -1.73 9.44 11.17
4.32NMT41PR78 6/5/2017 14.37 -1.73 10.05 11.78
6.39NMT41PR79 8/30/2016 13.77 -1.33 7.38 8.71
7.94NMT41PR79 9/6/2016 13.77 -1.33 5.83 7.16
8.25NMT41PR79 10/5/2016 13.77 -1.33 5.52 6.85
6.97NMT41PR79 11/3/2016 13.77 -1.33 6.8 8.13
5.42NMT41PR79 12/2/2016 13.77 -1.33 8.35 9.68
8.05NMT41PR79 1/9/2017 13.77 -1.33 5.72 7.05
7.51NMT41PR79 2/20/2017 13.77 -1.33 6.26 7.59
6.44NMT41PR80 8/30/2016 14.52 -1.28 8.08 9.36
7.61NMT41PR80 9/6/2016 14.52 -1.28 6.91 8.19
7.96NMT41PR80 10/5/2016 14.52 -1.28 6.56 7.84
6.78NMT41PR80 11/3/2016 14.52 -1.28 7.74 9.02
5.59NMT41PR80 12/2/2016 14.52 -1.28 8.93 10.21
7.30NMT41PR80 1/9/2017 14.52 -1.28 7.22 8.50
5.65NMT41PR80 2/20/2017 14.52 -1.28 8.87 10.15
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 8BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
4.02NMT41PR81 8/30/2016 13.99 -1.41 9.97 11.38
5.77NMT41PR81 9/6/2016 13.99 -1.41 8.22 9.63
5.58NMT41PR81 10/5/2016 13.99 -1.41 8.41 9.82
3.22NMT41PR81 11/3/2016 13.99 -1.41 10.77 12.18
2.31NMT41PR81 12/2/2016 13.99 -1.41 11.68 13.09
6.15NMT41PR81 1/9/2017 13.99 -1.41 7.84 9.25
1.34NMT41PR81 2/20/2017 13.99 -1.41 12.65 14.06
5.41NMT41PR82 8/30/2016 14.35 -1.65 8.94 10.59
6.59NMT41PR82 9/6/2016 14.35 -1.65 7.76 9.41
6.81NMT41PR82 10/5/2016 14.35 -1.65 7.54 9.19
5.28NMT41PR82 11/3/2016 14.35 -1.65 9.07 10.72
3.89NMT41PR82 12/2/2016 14.35 -1.65 10.46 12.11
5.54NMT41PR82 1/9/2017 14.35 -1.65 8.81 10.46
5.93NMT41PR82 2/20/2017 14.35 -1.65 8.42 10.07
4.14NMT41PR82 3/1/2017 14.35 -1.65 10.21 11.86
4.19NMT41PR82 4/3/2017 14.35 -1.65 10.16 11.81
4.48NMT41PR82 5/1/2017 14.35 -1.65 9.87 11.52
4.54NMT41PR82 6/5/2017 14.35 -1.65 9.81 11.46
6.430.0241PR83 8/30/2016 14.97 -1.03 8.54 9.57
7.58NMT41PR83 9/6/2016 14.97 -1.03 7.39 8.42
7.720.0241PR83 10/5/2016 14.97 -1.03 7.25 8.28
6.08NMT41PR83 11/3/2016 14.97 -1.03 8.89 9.92
4.83NMT41PR83 12/2/2016 14.97 -1.03 10.14 11.17
6.57NMT41PR83 1/9/2017 14.97 -1.03 8.4 9.43
5.03NMT41PR83 2/20/2017 14.97 -1.03 9.94 10.97
4.80NMT41PR83 3/1/2017 14.97 -1.03 10.17 11.20
4.69NMT41PR83 4/3/2017 14.97 -1.03 10.28 11.31
4.98NMT41PR83 5/1/2017 14.97 -1.03 9.99 11.02
4.00NMT41PR83 6/5/2017 14.97 -1.03 10.97 12.00
3.65NMT41PR84 8/30/2016 12.99 -1.81 9.34 11.15
2.87NMT41PR84 2/20/2017 12.99 -1.81 10.12 11.93
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 9BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
3.21NMT41PR85 8/30/2016 13.03 -1.47 9.82 11.29
2.72NMT41PR85 2/20/2017 13.03 -1.47 10.31 11.78
3.52NMT41PR86 8/30/2016 13.61 -1.19 10.09 11.28
2.92NMT41PR86 2/20/2017 13.61 -1.19 10.69 11.88
3.15NMT41PR87 8/30/2016 13.83 -0.87 10.68 11.55
3.39NMT41PR87 2/20/2017 13.83 -0.87 10.44 11.31
2.91NMT41PR88 8/30/2016 12.89 -0.81 9.98 10.79
2.60NMT41PR88 2/20/2017 12.89 -0.81 10.29 11.10
2.82NMT41PR89 8/30/2016 12.11 -1.09 9.29 10.38
2.48NMT41PR89 2/20/2017 12.11 -1.09 9.63 10.72
3.01NMT41PR90 8/30/2016 12.09 -1.21 9.08 10.29
2.65NMT41PR90 2/20/2017 12.09 -1.21 9.44 10.65
3.52NMT41PR91 8/30/2016 11.39 -0.91 7.87 8.78
3.01NMT41PR91 2/20/2017 11.39 -0.91 8.38 9.29
3.20NMT41PR92 8/30/2016 9.23 -0.87 6.03 6.90
2.93NMT41PR92 2/20/2017 9.23 -0.87 6.3 7.17
3.26NMT41PR93 8/30/2016 9.87 -1.33 6.61 7.94
2.56NMT41PR93 2/20/2017 9.87 -1.33 7.31 8.64
2.70NMT41PR94 8/30/2016 9.57 0 6.87 6.87
2.93NMT41PR94 2/20/2017 9.57 0 6.64 6.64
2.81NMT41PR95 8/30/2016 9.3 -1.1 6.49 7.59
2.38NMT41PR95 2/20/2017 9.3 -1.1 6.92 8.02
2.98NMT41PR96 8/30/2016 6.96 -1.34 3.98 5.32
-0.16NMT41PR96 2/20/2017 6.96 -1.34 7.12 8.46
2.71NMT41PR97 8/30/2016 10.46 -0.14 7.75 7.89
2.14NMT41PR97 2/20/2017 10.46 -0.14 8.32 8.46
2.49NMT41PR98 8/30/2016 8.01 0.11 5.52 5.41
1.78NMT41PR98 2/20/2017 8.01 0.11 6.23 6.12
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 10BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
2.71NMT41PR99 8/30/2016 6.94 0.44 4.23 3.79
-1.79NMT41PR99 2/20/2017 6.94 0.44 8.73 8.29
6.01NMT41PR100 8/30/2016 14.41 -0.69 8.4 9.09
4.94NMT41PR100 2/20/2017 14.41 -0.69 9.47 10.16
5.39NMT41PR101 8/30/2016 15.39 -1.11 10 11.11
5.15NMT41PR101 2/20/2017 15.39 -1.11 10.24 11.35
5.46NMT41PR200 8/30/2016 15.92 -0.58 10.46 11.04
6.28NMT41PR200 9/6/2016 15.92 -0.58 9.64 10.22
6.61NMT41PR200 10/5/2016 15.92 -0.58 9.31 9.89
6.12NMT41PR200 11/3/2016 15.92 -0.58 9.8 10.38
4.99NMT41PR200 12/2/2016 15.92 -0.58 10.93 11.51
5.63NMT41PR200 1/9/2017 15.92 -0.58 10.29 10.87
4.98NMT41PR200 2/20/2017 15.92 -0.58 10.94 11.52
4.78NMT41PR200 3/1/2017 15.92 -0.58 11.14 11.72
4.63NMT41PR200 4/3/2017 15.92 -0.58 11.29 11.87
4.86NMT41PR200 5/1/2017 15.92 -0.58 11.06 11.64
4.14NMT41PR200 6/5/2017 15.92 -0.58 11.78 12.36
6.36NMT41PR201 8/30/2016 16.4 -0.3 10.04 10.34
6.87NMT41PR201 9/6/2016 16.4 -0.3 9.53 9.83
7.14NMT41PR201 10/5/2016 16.4 -0.3 9.26 9.56
5.97NMT41PR201 11/3/2016 16.4 -0.3 10.43 10.73
4.77NMT41PR201 12/2/2016 16.4 -0.3 11.63 11.93
6.08NMT41PR201 1/9/2017 16.4 -0.3 10.32 10.62
4.97NMT41PR201 2/20/2017 16.4 -0.3 11.43 11.73
4.66NMT41PR201 3/1/2017 16.4 -0.3 11.74 12.04
4.70NMT41PR201 4/3/2017 16.4 -0.3 11.7 12.00
4.80NMT41PR201 5/1/2017 16.4 -0.3 11.6 11.90
3.960.0241PR201 6/5/2017 16.4 -0.3 12.44 12.74
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 11BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
6.200.0441PR202 8/30/2016 16.11 -0.39 9.9 10.29
7.340.0441PR202 9/6/2016 16.11 -0.39 8.76 9.15
7.380.0541PR202 10/5/2016 16.11 -0.39 8.72 9.11
6.78NMT41PR202 11/3/2016 16.11 -0.39 9.33 9.72
5.710.0641PR202 12/2/2016 16.11 -0.39 10.39 10.78
6.870.0441PR202 1/9/2017 16.11 -0.39 9.23 9.62
6.100.0141PR202 2/20/2017 16.11 -0.39 10.01 10.40
5.930.0241PR202 3/1/2017 16.11 -0.39 10.18 10.57
5.820.0241PR202 4/3/2017 16.11 -0.39 10.29 10.68
5.550.0441PR202 5/1/2017 16.11 -0.39 10.55 10.94
4.810.0441PR202 6/5/2017 16.11 -0.39 11.29 11.68
5.40NMT41PR203 8/30/2016 16.21 -0.29 10.81 11.10
6.25NMT41PR203 9/6/2016 16.21 -0.29 9.96 10.25
6.74NMT41PR203 10/5/2016 16.21 -0.29 9.47 9.76
6.47NMT41PR203 11/3/2016 16.21 -0.29 9.74 10.03
4.40NMT41PR203 12/2/2016 16.21 -0.29 11.81 12.10
5.69NMT41PR203 1/9/2017 16.21 -0.29 10.52 10.81
5.30NMT41PR203 2/20/2017 16.21 -0.29 10.91 11.20
5.31NMT41PR203 3/1/2017 16.21 -0.29 10.9 11.19
4.96NMT41PR203 4/3/2017 16.21 -0.29 11.25 11.54
5.10NMT41PR203 5/1/2017 16.21 -0.29 11.11 11.40
4.39NMT41PR203 6/5/2017 16.21 -0.29 11.82 12.11
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 12BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.660.0241PR204 8/30/2016 16 -0.3 10.34 10.64
6.63NMT41PR204 9/6/2016 16 -0.3 9.37 9.67
6.96NMT41PR204 10/5/2016 16 -0.3 9.04 9.34
6.51NMT41PR204 11/3/2016 16 -0.3 9.49 9.79
5.38NMT41PR204 12/2/2016 16 -0.3 10.62 10.92
5.82NMT41PR204 1/9/2017 16 -0.3 10.18 10.48
5.35NMT41PR204 2/20/2017 16 -0.3 10.65 10.95
5.30NMT41PR204 3/1/2017 16 -0.3 10.7 11.00
5.05NMT41PR204 4/3/2017 16 -0.3 10.95 11.25
5.20NMT41PR204 5/1/2017 16 -0.3 10.8 11.10
4.49NMT41PR204 6/5/2017 16 -0.3 11.51 11.81
5.21NMT41PR210 8/30/2016 15.6 -0.4 10.39 10.79
6.61NMT41PR210 9/6/2016 15.6 -0.4 8.99 9.39
6.34NMT41PR210 10/5/2016 15.6 -0.4 9.26 9.66
5.28NMT41PR210 11/3/2016 15.6 -0.4 10.32 10.72
3.77NMT41PR210 12/2/2016 15.6 -0.4 11.83 12.23
5.21NMT41PR210 1/9/2017 15.6 -0.4 10.39 10.79
4.17NMT41PR210 2/20/2017 15.6 -0.4 11.43 11.83
3.94NMT41PR210 3/1/2017 15.6 -0.4 11.66 12.06
4.03NMT41PR210 4/3/2017 15.6 -0.4 11.57 11.97
4.29NMT41PR210 5/1/2017 15.6 -0.4 11.31 11.71
2.64NMT41PR210 6/5/2017 15.6 -0.4 12.96 13.36
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 13BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
4.47NMT41PR211 8/30/2016 15.44 -0.46 10.97 11.43
5.96NMT41PR211 9/6/2016 15.44 -0.46 9.48 9.94
5.77NMT41PR211 10/5/2016 15.44 -0.46 9.67 10.13
4.61NMT41PR211 11/3/2016 15.44 -0.46 10.83 11.29
3.30NMT41PR211 12/2/2016 15.44 -0.46 12.14 12.60
4.46NMT41PR211 1/9/2017 15.44 -0.46 10.98 11.44
3.71NMT41PR211 2/20/2017 15.44 -0.46 11.73 12.19
3.37NMT41PR211 3/1/2017 15.44 -0.46 12.07 12.53
3.55NMT41PR211 4/3/2017 15.44 -0.46 11.89 12.35
3.87NMT41PR211 5/1/2017 15.44 -0.46 11.57 12.03
2.98NMT41PR211 6/5/2017 15.44 -0.46 12.46 12.92
2.91NMT41PR212 8/30/2016 15.43 -0.37 12.52 12.89
5.41NMT41PR212 9/6/2016 15.43 -0.37 10.02 10.39
4.83NMT41PR212 10/5/2016 15.43 -0.37 10.6 10.97
3.89NMT41PR212 11/3/2016 15.43 -0.37 11.54 11.91
2.95NMT41PR212 12/2/2016 15.43 -0.37 12.48 12.85
3.49NMT41PR212 1/9/2017 15.43 -0.37 11.94 12.31
3.30NMT41PR212 2/20/2017 15.43 -0.37 12.13 12.50
4.69NMT41PR212 3/1/2017 15.43 -0.37 10.74 11.11
2.49NMT41PR212 4/3/2017 15.43 -0.37 12.94 13.31
2.96NMT41PR212 5/1/2017 15.43 -0.37 12.47 12.84
1.69NMT41PR212 6/5/2017 15.43 -0.37 13.74 14.11
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 14BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
3.25NMT41PR213 8/30/2016 15.28 -0.22 12.03 12.25
3.59NMT41PR213 9/6/2016 15.28 -0.22 11.69 11.91
4.79NMT41PR213 10/5/2016 15.28 -0.22 10.49 10.71
3.49NMT41PR213 11/3/2016 15.28 -0.22 11.79 12.01
2.25NMT41PR213 12/2/2016 15.28 -0.22 13.03 13.25
3.76NMT41PR213 1/9/2017 15.28 -0.22 11.52 11.74
2.87NMT41PR213 2/20/2017 15.28 -0.22 12.41 12.63
2.55NMT41PR213 3/1/2017 15.28 -0.22 12.73 12.95
2.60NMT41PR213 4/3/2017 15.28 -0.22 12.68 12.90
2.84NMT41PR213 5/1/2017 15.28 -0.22 12.44 12.66
1.880.0241PR213 6/5/2017 15.28 -0.22 13.4 13.62
5.50NMT41PR214 8/30/2016 15.3 -0.4 9.8 10.20
5.59NMT41PR214 9/6/2016 15.3 -0.4 9.71 10.11
5.65NMT41PR214 10/5/2016 15.3 -0.4 9.65 10.05
3.90NMT41PR214 11/3/2016 15.3 -0.4 11.4 11.80
2.65NMT41PR214 12/2/2016 15.3 -0.4 12.65 13.05
3.89NMT41PR214 1/9/2017 15.3 -0.4 11.41 11.81
3.02NMT41PR214 2/20/2017 15.3 -0.4 12.28 12.68
2.36NMT41PR214 3/1/2017 15.3 -0.4 12.94 13.34
2.88NMT41PR214 4/3/2017 15.3 -0.4 12.42 12.82
3.33NMT41PR214 5/1/2017 15.3 -0.4 11.97 12.37
2.34NMT41PR214 6/5/2017 15.3 -0.4 12.96 13.36
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 15BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
4.50NMT41PR215 8/30/2016 15.58 -0.42 11.08 11.50
6.12NMT41PR215 9/6/2016 15.58 -0.42 9.46 9.88
5.76NMT41PR215 10/5/2016 15.58 -0.42 9.82 10.24
4.62NMT41PR215 11/3/2016 15.58 -0.42 10.96 11.38
3.490.0141PR215 12/2/2016 15.58 -0.42 12.09 12.51
4.81NMT41PR215 1/9/2017 15.58 -0.42 10.77 11.19
3.79NMT41PR215 2/20/2017 15.58 -0.42 11.79 12.21
3.670.0341PR215 3/1/2017 15.58 -0.42 11.9 12.32
3.51NMT41PR215 4/3/2017 15.58 -0.42 12.07 12.49
3.88NMT41PR215 5/1/2017 15.58 -0.42 11.7 12.12
2.980.0441PR215 6/5/2017 15.58 -0.42 12.59 13.01
5.160.0341PR216 8/30/2016 15.82 -0.28 10.65 10.93
6.940.0241PR216 9/6/2016 15.82 -0.28 8.88 9.16
6.590.0441PR216 10/5/2016 15.82 -0.28 9.22 9.50
5.27NMT41PR216 11/3/2016 15.82 -0.28 10.55 10.83
4.06NMT41PR216 12/2/2016 15.82 -0.28 11.76 12.04
5.250.0241PR216 1/9/2017 15.82 -0.28 10.57 10.85
4.090.0241PR216 2/20/2017 15.82 -0.28 11.73 12.01
4.310.0241PR216 3/1/2017 15.82 -0.28 11.51 11.79
4.65NMT41PR216 4/3/2017 15.82 -0.28 11.17 11.45
4.570.0241PR216 5/1/2017 15.82 -0.28 11.25 11.53
3.310.0141PR216 6/5/2017 15.82 -0.28 12.51 12.79
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 16BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.240.0241PR217 8/30/2016 15.53 -0.47 10.29 10.76
6.72NMT41PR217 9/6/2016 15.53 -0.47 8.81 9.28
6.710.0441PR217 10/5/2016 15.53 -0.47 8.81 9.28
5.57NMT41PR217 11/3/2016 15.53 -0.47 9.96 10.43
4.390.0241PR217 12/2/2016 15.53 -0.47 11.14 11.61
5.320.0141PR217 1/9/2017 15.53 -0.47 10.206 10.68
4.410.0241PR217 2/20/2017 15.53 -0.47 11.12 11.59
4.410.0141PR217 3/1/2017 15.53 -0.47 11.12 11.59
4.30NMT41PR217 4/3/2017 15.53 -0.47 11.23 11.70
4.65NMT41PR217 5/1/2017 15.53 -0.47 10.88 11.35
3.660.0241PR217 6/5/2017 15.53 -0.47 11.87 12.34
4.570.0241PR218 8/30/2016 15.23 -0.27 10.66 10.93
6.81NMT41PR218 9/6/2016 15.23 -0.27 8.42 8.69
6.530.0241PR218 10/5/2016 15.23 -0.27 8.7 8.97
4.96NMT41PR218 11/3/2016 15.23 -0.27 10.27 10.54
3.59NMT41PR218 12/2/2016 15.23 -0.27 11.64 11.91
5.59NMT41PR218 1/9/2017 15.23 -0.27 9.64 9.91
4.070.0241PR218 2/20/2017 15.23 -0.27 11.16 11.43
3.900.0241PR218 3/1/2017 15.23 -0.27 11.33 11.60
3.41NMT41PR218 4/3/2017 15.23 -0.27 11.82 12.09
4.34NMT41PR218 5/1/2017 15.23 -0.27 10.89 11.16
3.04NMT41PR218 6/5/2017 15.23 -0.27 12.19 12.46
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 17BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.860.0341PR219 8/30/2016 15.81 -0.19 9.94 10.13
7.370.0241PR219 9/6/2016 15.81 -0.19 8.44 8.63
7.220.0141PR219 10/5/2016 15.81 -0.19 8.59 8.78
6.02NMT41PR219 11/3/2016 15.81 -0.19 9.79 9.98
4.47NMT41PR219 12/2/2016 15.81 -0.19 11.34 11.53
6.12NMT41PR219 1/9/2017 15.81 -0.19 9.69 9.88
4.72NMT41PR219 2/20/2017 15.81 -0.19 11.09 11.28
4.88NMT41PR219 3/1/2017 15.81 -0.19 10.93 11.12
4.61NMT41PR219 4/3/2017 15.81 -0.19 11.2 11.39
5.110.0141PR219 5/1/2017 15.81 -0.19 10.7 10.89
4.010.0241PR219 6/5/2017 15.81 -0.19 11.8 11.99
5.44NMT41PR220 8/30/2016 15.92 -0.28 10.48 10.76
6.92NMT41PR220 9/6/2016 15.92 -0.28 9 9.28
6.96NMT41PR220 10/5/2016 15.92 -0.28 8.96 9.24
5.85NMT41PR220 11/3/2016 15.92 -0.28 10.07 10.35
2.540.0341PR220 12/2/2016 15.92 -0.28 13.37 13.65
5.50NMT41PR220 1/9/2017 15.92 -0.28 10.42 10.70
4.240.0541PR220 2/20/2017 15.92 -0.28 11.67 11.95
4.590.0341PR220 3/1/2017 15.92 -0.28 11.32 11.60
4.38NMT41PR220 4/3/2017 15.92 -0.28 11.54 11.82
4.67NMT41PR220 5/1/2017 15.92 -0.28 11.25 11.53
3.81NMT41PR220 6/5/2017 15.92 -0.28 12.11 12.39
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 18BOLD ITALICS
TABLE 5.1B
SITE 1083
HISTORICAL FIELD MEASUREMENT DATA
Well ID Date
Corrected GWT
ElevationProduct ThicknessTOCStickupDTW/DTP DTW/DTP BGS
5.16NMT41PR221 8/30/2016 15.81 -0.29 10.65 10.94
6.68NMT41PR221 9/6/2016 15.81 -0.29 9.13 9.42
6.46NMT41PR221 10/5/2016 15.81 -0.29 9.35 9.64
5.41NMT41PR221 11/3/2016 15.81 -0.29 10.4 10.69
4.59NMT41PR221 12/2/2016 15.81 -0.29 11.22 11.51
5.53NMT41PR221 1/9/2017 15.81 -0.29 10.28 10.57
4.49NMT41PR221 2/20/2017 15.81 -0.29 11.32 11.61
4.63NMT41PR221 3/1/2017 15.81 -0.29 11.18 11.47
4.41NMT41PR221 4/3/2017 15.81 -0.29 11.4 11.69
4.72NMT41PR221 5/1/2017 15.81 -0.29 11.09 11.38
3.660.0141PR221 6/5/2017 15.81 -0.29 12.15 12.44
5.37NMT41PR230 8/30/2016 15.88 -0.22 10.51 10.73
5.06NMT41PR230 2/20/2017 15.88 -0.22 10.82 11.04
Notes: 1. NMT = No Measurable Thickness
2. NM = Not Measured
3. Data in BOLD ITALICS indicates measurable thicknesses of product detected
4. TBM = To Be Measured
5. Corrected GW Elevation based on Specific Gravity of JP-5 (0.82)
Page 19BOLD ITALICS
PARAMETERUNITSGCL41GW105
41GW107
41GW112
41GW113
41GW25
41GW32
41GW32Dup
41GW36
41GW43
41GW44
41GW64
41PR101
41GW27
41PR200
41PR203
41PR213
41PR230
41PR68
41PR69
41PR72
41PR73
41PR74
41PR67
GROUNDWATER LABORATORY ANALYTICAL RESULTSSITE 1083TABLE 5.2ADate Sampled:2/20/2017EPA METHOD 602 BY SM 6200B41GW111
2L GWQS41PR75
41PR76
41PR78
41PR79
41PR80
41PR8141PR8341PR8441PR8541PR8641PR87
ug/L1,2-Dichlorobenzene20,000.000020.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/L1,3-Dichlorobenzene61,500.0000200.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/L1,4-Dichlorobenzene6,000.00006.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzene5,000.00001.00000.0 0.00.0 2.03 3.47 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 4.42 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LEthylbenzene84,500.0000600.00000.0 0.00.0 0.0 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.99 0.0 3.98 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LToluene260,000.0000600.00000.0 0.00.0 3.06 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LTotal Xylenes85,500.0000500.00000.0 0.00.0 0.0 3.97 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.22 5.5 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0Totals:0.000.000.000.005.0912.240.000.000.000.000.000.000.000.003.227.490.008.40.000.000.000.000.000.000.000.000.000.000.000.000.000.000.000.000.00Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202 2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2088 Version, Change 3 effective December 1, 2013 3. ug/L = Micrograms per Liter 4. A zero ("0.0") in the results column indicates concentration is either below detection limit or below quantitation limit 5. A zero ("0.0000") in the 2L GWQS column indicates the 2L standard is equal to the laboratory detection limit 6. A zero ("0.0000") in the GCL column indicates a GCL has not been establishedPage 1
CEquip_ Rinsate
GROUNDWATER LABORATORY ANALYTICAL RESULTSSITE 1083TABLE 5.2A (Continued)2/21/2017Date Sampled:EPA METHOD 602 BY SM 6200B2L GWQSUNITSPARAMETERGCL1,2-Dichlorobenzene20,000.000020.00000.00ug/L1,3-Dichlorobenzene61,500.0000200.00000.00ug/L1,4-Dichlorobenzene6,000.00006.00000.00ug/LBenzene5,000.00001.00000.00ug/LEthylbenzene84,500.0000600.00000.00ug/LToluene260,000.0000600.00000.00ug/LTotal Xylenes85,500.0000500.00000.00ug/LTotals:0.00Page 2Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202 2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013 3. ug/L = Micrograms per Liter 4. A zero ("0.00") in the results column indicates concentration is either below detection limit or below quantitation limit 5. A zero ("0.0000") in the 2L GWQS column indicates the 2L standard is equal to the laboratory detection limit 6. A zero ("0.0000") in the GCL column indicates a GCL has not been established
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/14/2012 BQL 12.7 BQL BQL BQL41GW02
11/12/2013 2.7 4.38 0.76 4.24 BQL41GW02
2/23/2016 1.34 4.79 BQL BQL BQL41GW02R
5/3/2016 2.57 4.24 BQL 3.63 BQL41GW02R
8/15/2012 BQL 5.7 BQL BQL BQL41GW03
2/23/2016 BQL 8.31 BQL 12.8 BQL41GW03R
5/3/2016 BQL 3.25 BQL 7.54 BQL41GW03R
2/21/2012 BQL BQL BQL BQL BQL41GW06
11/12/2013 BQL 0.33 BQL 1.28 BQL41GW06
8/13/2014 1.39 2.64 BQL 1.49 BQL41GW06
3/11/2015 1.49 1.68 BQL 1.44 BQL41GW06
8/26/2015 BQL BQL BQL BQL BQL41GW06
2/24/2016 BQL BQL BQL BQL BQL41GW06
5/4/2016 BQL BQL BQL BQL BQL41GW06
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 1
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL BQL BQL41GW23
8/14/2012 BQL BQL BQL BQL BQL41GW23
2/20/2013 BQL BQL BQL BQL BQL41GW23
11/12/2013 BQL BQL BQL BQL BQL41GW23
8/13/2014 BQL BQL BQL BQL BQL41GW23
3/11/2015 BQL BQL BQL BQL BQL41GW23
3/11/2015 BQL BQL BQL BQL BQL41GW23Dup
8/26/2015 BQL BQL BQL BQL BQL41GW23
2/23/2016 BQL BQL BQL BQL BQL41GW23
5/4/2016 BQL BQL BQL BQL BQL41GW23
8/13/2014 5.41 8.41 BQL 4.61 BQL41GW25
3/11/2015 6.24 7.81 BQL 3.73 BQL41GW25
8/26/2015 14.2 12.7 BQL 4.83 BQL41GW25
2/24/2016 6.09 7.05 BQL 4.6 BQL41GW25
5/4/2016 7.65 4.72 BQL BQL BQL41GW25
2/20/2017 3.47 4.8 BQL 3.97 BQL41GW25
2/21/2012 BQL BQL BQL BQL BQL41GW27
8/15/2012 BQL BQL BQL BQL BQL41GW27
2/20/2017 BQL BQL BQL BQL BQL41GW27
2/21/2012 BQL BQL BQL BQL BQL41GW31
8/14/2012 BQL BQL BQL BQL BQL41GW31
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 2
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/20/2017 BQL BQL BQL BQL BQL41GW32
2/20/2017 BQL BQL BQL BQL BQL41GW32Dup
2/21/2012 BQL BQL BQL BQL BQL41GW33
2/21/2012 BQL BQL BQL BQL BQL41GW33Dup
8/14/2012 BQL BQL BQL BQL BQL41GW33
8/14/2012 BQL BQL BQL BQL BQL41GW33Dup
2/20/2013 BQL BQL BQL BQL BQL41GW33
2/20/2013 BQL BQL BQL BQL BQL41GW33Dup
11/12/2013 BQL BQL BQL BQL BQL41GW33
11/12/2013 BQL BQL BQL BQL BQL41GW33Dup
8/13/2014 BQL BQL BQL BQL BQL41GW33
8/13/2014 BQL BQL BQL BQL BQL41GW33Dup
3/11/2015 BQL BQL BQL BQL BQL41GW33
8/26/2015 BQL BQL BQL BQL BQL41GW33
2/23/2016 BQL BQL BQL BQL BQL41GW33
2/23/2016 BQL BQL BQL BQL BQL41GW33Dup
5/3/2016 BQL BQL BQL BQL BQL41GW33
5/3/2016 BQL BQL BQL BQL BQL41GW33Dup
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 3
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL BQL BQL41GW36
8/15/2012 BQL BQL BQL BQL BQL41GW36
2/20/2013 1.2 1.9 BQL 9.4 BQL41GW36
11/12/2013 1.03 BQL BQL 0.64 BQL41GW36
8/13/2014 BQL 0.7 1.54 BQL BQL41GW36
3/11/2015 0.86 1.44 BQL 5.1 BQL41GW36
8/26/2015 BQL BQL BQL BQL BQL41GW36
2/24/2016 1.26 1.06 BQL 7.58 BQL41GW36
5/4/2016 1.32 1.14 BQL 8.51 BQL41GW36
2/20/2017 BQL BQL BQL BQL BQL41GW36
2/21/2012 BQL BQL BQL BQL BQL41GW43
8/15/2012 BQL 1.4 BQL BQL BQL41GW43
2/20/2017 BQL BQL BQL BQL BQL41GW43
2/21/2012 BQL BQL BQL BQL BQL41GW44
8/14/2012 BQL BQL BQL BQL BQL41GW44
2/20/2017 BQL BQL BQL BQL BQL41GW44
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 4
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/14/2012 BQL BQL BQL BQL BQL41GW64
2/20/2013 BQL 2.9 BQL BQL BQL41GW64
8/13/2014 0.33 0.31 BQL BQL BQL41GW64
3/11/2015 BQL BQL BQL BQL BQL41GW64
8/26/2015 BQL BQL BQL BQL BQL41GW64
2/24/2016 BQL BQL BQL BQL BQL41GW64
5/4/2016 BQL BQL BQL BQL BQL41GW64
2/20/2017 BQL BQL BQL BQL BQL41GW64
2/21/2012 BQL BQL BQL BQL BQL41GW66
8/14/2012 BQL BQL BQL BQL BQL41GW104
2/21/2012 BQL BQL BQL BQL BQL41GW105
8/14/2012 BQL BQL BQL BQL BQL41GW105
3/11/2015 0.34 0.41 BQL 0.52 BQL41GW105
8/26/2015 BQL BQL BQL BQL BQL41GW105
2/20/2017 BQL BQL BQL BQL BQL41GW105
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 5
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
11/12/2013 2.45 8.7 BQL 68.7 BQL41GW106
8/13/2014 0.66 11.8 0.38 18.4 BQL41GW106
3/11/2015 0.71 9.03 BQL 19.2 BQL41GW106
8/26/2015 2.85 14.5 2.4 97.7 BQL41GW106
2/24/2016 BQL 10.1 BQL BQL BQL41GW106
5/4/2016 BQL 5.07 BQL 3.57 BQL41GW106
8/14/2012 BQL BQL BQL BQL BQL41GW107
2/20/2013 BQL BQL BQL BQL BQL41GW107
11/12/2013 BQL BQL BQL BQL BQL41GW107
8/13/2014 BQL BQL BQL BQL BQL41GW107
3/11/2015 BQL BQL BQL BQL BQL41GW107
8/26/2015 BQL BQL BQL BQL BQL41GW107
2/23/2016 BQL BQL BQL BQL BQL41GW107
5/3/2016 BQL BQL BQL BQL BQL41GW107
2/20/2017 BQL BQL BQL BQL BQL41GW107
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 6
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL BQL BQL41GW111
8/14/2012 BQL BQL BQL BQL BQL41GW111
2/20/2013 BQL BQL BQL BQL BQL41GW111
11/12/2013 BQL BQL BQL BQL BQL41GW111
8/13/2014 BQL BQL BQL BQL BQL41GW111
3/11/2015 BQL BQL BQL BQL BQL41GW111
2/23/2016 BQL BQL BQL BQL BQL41GW111
5/3/2016 BQL BQL BQL BQL BQL41GW111
2/20/2017 BQL BQL BQL BQL BQL41GW111
2/21/2012 BQL BQL BQL BQL BQL41GW112
8/14/2012 BQL BQL BQL BQL BQL41GW112
2/20/2013 BQL BQL BQL BQL BQL41GW112
11/12/2013 BQL BQL BQL BQL BQL41GW112
8/13/2014 BQL BQL BQL BQL BQL41GW112
3/11/2015 BQL BQL BQL BQL BQL41GW112
8/26/2015 BQL BQL BQL BQL BQL41GW112
2/23/2016 BQL BQL BQL BQL BQL41GW112
5/4/2016 BQL BQL BQL BQL BQL41GW112
2/20/2017 BQL BQL BQL BQL BQL41GW112
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 7
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL BQL BQL41GW113
8/15/2012 BQL BQL BQL BQL BQL41GW113
2/20/2013 BQL BQL BQL BQL BQL41GW113
11/13/2013 BQL BQL BQL 0.44 BQL41GW113
8/13/2014 BQL BQL BQL BQL BQL41GW113
3/11/2015 BQL BQL BQL BQL BQL41GW113
8/26/2015 BQL BQL BQL BQL BQL41GW113
2/23/2016 BQL BQL BQL BQL BQL41GW113
5/3/2016 BQL BQL BQL BQL BQL41GW113
2/20/2017 2.03 BQL 3.06 BQL BQL41GW113
2/21/2012 BQL BQL BQL BQL BQL41GW119
11/12/2013 BQL BQL BQL BQL BQL41PR67
8/13/2014 BQL BQL BQL BQL BQL41PR67
3/11/2015 BQL BQL BQL BQL BQL41PR67
8/26/2015 BQL BQL BQL BQL BQL41PR67
2/23/2016 BQL BQL BQL BQL BQL41PR67
5/3/2016 BQL BQL BQL BQL BQL41PR67
2/20/2017 BQL BQL BQL BQL BQL41PR67
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 8
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/15/2012 BQL 1.1 BQL BQL BQL41PR68
2/20/2013 BQL BQL BQL BQL BQL41PR68
8/13/2014 0.69 1.79 BQL 0.57 BQL41PR68
3/11/2015 BQL BQL 0.36 BQL BQL41PR68
8/26/2015 BQL BQL BQL BQL BQL41PR68
2/24/2016 BQL BQL BQL BQL BQL41PR68
5/4/2016 BQL BQL BQL BQL BQL41PR68
2/20/2017 BQL BQL BQL BQL BQL41PR68
2/21/2012 BQL BQL BQL BQL BQL41PR69
8/15/2012 BQL BQL BQL BQL BQL41PR69
2/20/2013 BQL BQL BQL BQL BQL41PR69
3/11/2015 BQL BQL BQL BQL BQL41PR69
8/26/2015 BQL BQL BQL BQL BQL41PR69
8/26/2015 BQL BQL BQL BQL BQL41PR69Dup
2/23/2016 BQL BQL BQL BQL BQL41PR69
5/3/2016 BQL BQL BQL BQL BQL41PR69
2/20/2017 BQL BQL BQL BQL BQL41PR69
2/21/2012 BQL BQL BQL BQL BQL41PR70
8/15/2012 BQL BQL BQL BQL BQL41PR70
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 9
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL BQL BQL41PR72
8/14/2012 BQL BQL BQL BQL BQL41PR72
2/20/2013 BQL BQL BQL BQL BQL41PR72
3/11/2015 BQL BQL BQL BQL BQL41PR72
8/26/2015 BQL BQL BQL BQL BQL41PR72
2/23/2016 BQL BQL BQL BQL BQL41PR72
5/3/2016 BQL BQL BQL BQL BQL41PR72
2/20/2017 BQL BQL BQL BQL BQL41PR72
2/21/2012 BQL BQL BQL BQL BQL41PR73
8/14/2012 BQL BQL BQL BQL BQL41PR73
3/11/2015 BQL BQL BQL BQL BQL41PR73
8/26/2015 BQL BQL BQL BQL BQL41PR73
2/23/2016 BQL BQL BQL BQL BQL41PR73
5/3/2016 BQL BQL BQL BQL BQL41PR73
2/20/2017 BQL BQL BQL BQL BQL41PR73
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 10
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/14/2012 BQL BQL BQL BQL BQL41PR74
2/20/2013 BQL BQL BQL BQL BQL41PR74
11/12/2013 BQL BQL BQL BQL BQL41PR74
8/13/2014 BQL BQL BQL BQL BQL41PR74
3/11/2015 BQL BQL BQL BQL BQL41PR74
8/26/2015 BQL BQL BQL BQL BQL41PR74
2/24/2016 BQL BQL BQL BQL BQL41PR74
5/3/2016 BQL BQL BQL BQL BQL41PR74
2/20/2017 BQL BQL BQL BQL BQL41PR74
2/21/2012 BQL 1.7 BQL BQL BQL41PR75
8/14/2012 BQL BQL BQL BQL BQL41PR75
2/20/2013 BQL BQL BQL BQL BQL41PR75
11/12/2013 BQL BQL BQL BQL BQL41PR75
8/13/2014 0.44 BQL BQL BQL BQL41PR75
3/11/2015 BQL BQL BQL BQL BQL41PR75
8/26/2015 BQL BQL BQL BQL BQL41PR75
2/23/2016 BQL BQL BQL BQL BQL41PR75
5/4/2016 BQL BQL BQL BQL BQL41PR75
2/20/2017 BQL BQL BQL BQL BQL41PR75
2/20/2017 BQL BQL BQL BQL BQL41PR76
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 11
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL 2.7 BQL BQL BQL41PR77
8/14/2012 BQL 2 BQL 2.9 BQL41PR77
2/20/2013 BQL BQL BQL BQL BQL41PR77
11/12/2013 BQL BQL BQL BQL BQL41PR77
8/13/2014 BQL 1.49 BQL BQL BQL41PR77
3/11/2015 BQL 1.76 BQL 0.52 BQL41PR77
8/26/2015 BQL BQL BQL BQL BQL41PR77
2/23/2016 BQL BQL BQL BQL BQL41PR77
5/3/2016 BQL BQL BQL BQL BQL41PR77
2/21/2012 BQL BQL BQL BQL BQL41PR78
8/14/2012 BQL 1.5 BQL 3.5 BQL41PR78
8/13/2014 BQL 2.35 BQL 4.96 BQL41PR78
3/11/2015 BQL 2.23 BQL 2.85 BQL41PR78
2/24/2016 BQL 1.13 BQL BQL BQL41PR78
2/20/2017 BQL BQL BQL BQL BQL41PR78
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 12
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
2/21/2012 BQL BQL BQL 2.4 BQL41PR79
8/15/2012 3.2 3.7 BQL 14.9 BQL41PR79
2/20/2013 1.3 3 BQL 7.7 BQL41PR79
11/12/2013 2.43 2.14 BQL 5.93 BQL41PR79
8/13/2014 BQL 3.25 BQL 2.44 BQL41PR79
3/11/2015 BQL 2.07 BQL 2.26 BQL41PR79
8/26/2015 2.61 2.81 BQL 13.6 BQL41PR79
2/24/2016 BQL 2.28 BQL 4.79 BQL41PR79
5/4/2016 2.17 3.23 BQL 3.33 BQL41PR79
2/20/2017 BQL BQL BQL BQL BQL41PR79
2/21/2012 BQL BQL BQL BQL BQL41PR80
8/15/2012 BQL BQL BQL BQL BQL41PR80
2/20/2013 BQL BQL BQL BQL BQL41PR80
11/12/2013 BQL BQL BQL 0.47 BQL41PR80
8/13/2014 BQL 0.35 BQL BQL BQL41PR80
3/11/2015 BQL 0.45 BQL BQL BQL41PR80
8/26/2015 BQL BQL BQL BQL BQL41PR80
2/24/2016 BQL BQL BQL BQL BQL41PR80
5/4/2016 BQL BQL BQL BQL BQL41PR80
2/20/2017 BQL BQL BQL BQL BQL41PR80
2/20/2017 BQL BQL BQL BQL BQL41PR81
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 13
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/15/2012 BQL BQL BQL BQL BQL41PR82
11/12/2013 0.46 0.35 BQL 0.73 BQL41PR82
2/23/2016 1.86 BQL BQL BQL BQL41PR82
5/3/2016 1.26 BQL BQL BQL BQL41PR82
8/15/2012 BQL 1 BQL BQL BQL41PR83
2/24/2016 BQL 3.05 BQL BQL BQL41PR83
5/4/2016 BQL 1.67 BQL BQL BQL41PR83
2/20/2017 BQL BQL BQL BQL BQL41PR83
2/20/2017 BQL BQL BQL BQL BQL41PR84
2/20/2017 BQL BQL BQL BQL BQL41PR85
8/14/2012 BQL BQL BQL BQL BQL41PR86
2/20/2013 BQL BQL BQL BQL BQL41PR86
11/12/2013 BQL BQL BQL BQL BQL41PR86
2/23/2016 BQL BQL BQL BQL BQL41PR86
5/3/2016 BQL BQL BQL BQL BQL41PR86
2/20/2017 BQL BQL BQL BQL BQL41PR86
3/11/2015 BQL BQL BQL BQL BQL41PR87
2/20/2017 BQL BQL BQL BQL BQL41PR87
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 14
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/15/2012 BQL 29.7 BQL BQL BQL41PR101
11/12/2013 2.12 4.5 BQL 3.19 BQL41PR101
8/13/2014 1.73 5.32 BQL 3.15 BQL41PR101
3/11/2015 BQL 0.57 BQL BQL BQL41PR101
8/26/2015 1.21 1.52 BQL BQL BQL41PR101
2/24/2016 BQL BQL BQL BQL BQL41PR101
5/4/2016 BQL BQL BQL BQL BQL41PR101
2/20/2017 BQL BQL BQL BQL BQL41PR101
8/14/2012 BQL 1.2 BQL 3.1 BQL41PR200
11/12/2013 1.99 0.81 BQL 2.04 BQL41PR200
2/24/2016 BQL 2.36 BQL 4.7 BQL41PR200
5/4/2016 BQL 2.25 1.84 BQL BQL41PR200
2/20/2017 BQL BQL BQL 3.22 BQL41PR200
11/12/2013 0.61 BQL BQL BQL BQL41PR203
8/13/2014 1.14 3.17 BQL 6.21 BQL41PR203
3/11/2015 1.12 3.69 BQL 15.4 BQL41PR203
8/26/2015 1.01 1.2 BQL BQL BQL41PR203
2/24/2016 1.04 3.4 BQL 12.9 BQL41PR203
5/4/2016 1.22 2.96 BQL 6.9 BQL41PR203
2/20/2017 BQL 1.99 BQL 5.5 BQL41PR203
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 15
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)BenzeneEthylbenzeneTolueneTotal XylenesAll Other AnalytesHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.2B
EPA METHOD 602 BY SM 6200B
DateSample ID
1 600 600 5002L GWQS
GCL 5000 84500 260000 85500
Contaminant of Concern
8/14/2012 1.2 1.2 BQL BQL BQL41PR212
11/12/2013 1.76 2.39 BQL 1.88 BQL41PR212
8/13/2014 1.37 2.03 BQL 1.28 BQL41PR212
3/11/2015 2.06 3.15 BQL 1.35 BQL41PR212
8/26/2015 BQL BQL BQL BQL BQL41PR212
2/23/2016 1.57 2.56 BQL BQL BQL41PR212
5/3/2016 BQL BQL BQL BQL BQL41PR212
8/14/2012 BQL 6.6 BQL 18.2 BQL41PR213
2/20/2017 BQL BQL BQL BQL BQL41PR213
11/12/2013 7.47 BQL BQL 12.4 BQL41PR220
2/23/2016 5.72 52.7 BQL 51.5 BQL41PR220
5/3/2016 8.45 50.2 BQL 51 BQL41PR220
8/15/2012 2.1 2.5 BQL BQL BQL41PR230
11/12/2013 4.37 BQL BQL 0.55 BQL41PR230
2/24/2016 3.9 4.26 BQL BQL BQL41PR230
5/4/2016 5.84 5.05 BQL 5.24 BQL41PR230
2/20/2017 4.42 3.98 BQL BQL BQL41PR230
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 16
9. Well nomenclature in RED indicates the well has been abandoned
PARAMETERUNITSGCL41GW105
41GW107
41GW112
41GW113
41GW25
41GW32
41GW32Dup
41GW36
41GW43
41GW44
41GW64
41PR101
41GW27
41PR200
41PR203
41PR213
41PR230
41PR68
41PR69
41PR72
41PR73
41PR74
41PR67
GROUNDWATER LABORATORY ANALYTICAL RESULTSSITE 1083TABLE 5.3ADate Sampled:2/20/2017EPA METHOD 610 BY EPA METHOD 62541GW111
2L GWQS41PR75
41PR76
41PR78
41PR79
41PR80
41PR8141PR8341PR8441PR8541PR8641PR87
ug/L2-Methylnaphthalene12,500.000030.00000.0 0.00.0 9.28 23 0.0 0.0 0.0 203 13.3 0.0 69.4 0.0 22.6 5.93 1.46 24.5 0.0 0.0 1.41.95 0.00.02.24 35.1 1.95 3.24 0.0 0.0 0.0 0.0 0.0 0.963 0.04.48ug/LAcenaphthene2,120.000080.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.99 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 2.22 0.0 0.0 0.0 0.0 0.00.0ug/LAcenaphthylene1,965.0000200.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LAnthracene2,000.00002,000.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzo(a)anthracene4.70000.05000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzo(a)pyrene0.81000.00500.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzo(b)fluoranthene0.75000.05000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzo(g,h,i)perylene200.0000200.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LBenzo(k)fluoranthene0.50000.50000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LChrysene5.00005.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LDibenzo(a,h)anthracene1.20000.00500.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LFluoranthene300.0000300.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 1 0.0 0.0 0.0 0.0 0.00.0ug/LFluorene990.0000300.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 1.12 0.0 0.0 0.0 0.0 0.00.0ug/LIndeno(1,2,3-c,d)pyrene0.05000.05000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LNaphthalene6,000.00006.00000.0 0.00.0 0.0 56.3 0.0 0.0 0.0 142 7.75 0.0 145 0.0 34.5 28 2.37 98.6 0.0 0.0 0.08.1 0.00.05.6 6.51 2.95 3.73 0.0 0.0 2.74 0.0 1.83 1.03 0.010.6ug/LPhenanthrene410.0000200.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0ug/LPyrene200.0000200.00000.0 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.00.0 0.00.00.0 0.0 0.0 0.0 0.0 1.11 0.0 0.0 0.0 0.0 0.00.0Totals:0.000.000.000.009.2879.30.000.000.0034521.050.00214.40.0057.133.934.82123.10.000.001.415.0810.050.007.8441.614.96.970.005.452.740.001.831.9930.00Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202 2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2088 Version, Change 3 effective December 1, 2013 3. ug/L = Micrograms per Liter 4. A zero ("0.0") in the results column indicates concentration is either below detection limit or below quantitation limit 5. A zero ("0.0000") in the 2L GWQS column indicates the 2L standard is equal to the laboratory detection limit 6. A zero ("0.0000") in the GCL column indicates a GCL has not been establishedPage 1
CEquip_ Rinsate
GROUNDWATER LABORATORY ANALYTICAL RESULTSSITE 1083TABLE 5.3A (Continued)2/21/2017Date Sampled:EPA METHOD 610 BY EPA METHOD 6252L GWQSUNITSPARAMETERGCL2-Methylnaphthalene12,500.000030.00000.00ug/LAcenaphthene2,120.000080.00000.00ug/LAcenaphthylene1,965.0000200.00000.00ug/LAnthracene2,000.00002,000.00000.00ug/LBenzo(a)anthracene4.70000.05000.00ug/LBenzo(a)pyrene0.81000.00500.00ug/LBenzo(b)fluoranthene0.75000.05000.00ug/LBenzo(g,h,i)perylene200.0000200.00000.00ug/LBenzo(k)fluoranthene0.50000.50000.00ug/LChrysene5.00005.00000.00ug/LDibenzo(a,h)anthracene1.20000.00500.00ug/LFluoranthene300.0000300.00000.00ug/LFluorene990.0000300.00000.00ug/LIndeno(1,2,3-c,d)pyrene0.05000.05000.00ug/LNaphthalene6,000.00006.00000.00ug/LPhenanthrene410.0000200.00000.00ug/LPyrene200.0000200.00000.00ug/LTotals:0.00Page 2Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202 2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013 3. ug/L = Micrograms per Liter 4. A zero ("0.00") in the results column indicates concentration is either below detection limit or below quantitation limit 5. A zero ("0.0000") in the 2L GWQS column indicates the 2L standard is equal to the laboratory detection limit 6. A zero ("0.0000") in the GCL column indicates a GCL has not been established
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/14/2012 391 BQL BQL BQL 191 BQL BQL BQL41GW02
11/12/2013 475 BQL BQL BQL 304 BQL BQL BQL41GW02
2/23/2016 26 BQL BQL BQL 42.9 BQL BQL BQL41GW02R
5/3/2016 35.4 BQL BQL BQL 73.6 BQL BQL BQL41GW02R
8/30/2016 NA NA NA NA 148 NA NA BQL41GW02R
8/15/2012 36.1 BQL BQL BQL 49.2 BQL BQL BQL41GW03
2/23/2016 75.3 BQL BQL BQL 105 BQL BQL BQL41GW03R
5/3/2016 29.9 BQL BQL BQL 48.1 BQL BQL BQL41GW03R
8/30/2016 NA NA NA NA 126 NA NA BQL41GW03R
8/30/2016 NA NA NA NA BQL NA NA BQL41GW05
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW06
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW06
8/13/2014 8.89 BQL BQL BQL 21.2 BQL BQL BQL41GW06
3/11/2015 8.21 BQL BQL BQL 13.3 BQL BQL BQL41GW06
8/26/2015 2.25 BQL BQL BQL 6.25 BQL BQL BQL41GW06
2/24/2016 4.97 BQL BQL BQL 4.07 BQL BQL BQL41GW06
5/4/2016 1.86 BQL BQL BQL 8.94 BQL BQL BQL41GW06
8/30/2016 NA NA NA NA 44.1 NA NA BQL41GW06
8/30/2016 NA NA NA NA BQL NA NA BQL41GW21
8/30/2016 NA NA NA NA BQL NA NA BQL41GW22
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 1
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
8/13/2014 BQL 0.49 BQL 0.373 0.755 BQL BQL BQL41GW23
3/11/2015 BQL 0.34 BQL 0.406 0.811 BQL BQL BQL41GW23
3/11/2015 BQL 0.34 BQL 0.34 0.623 BQL BQL BQL41GW23Dup
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW23
5/4/2016 BQL BQL BQL BQL 1.04 BQL BQL BQL41GW23
8/30/2016 NA NA NA NA BQL NA NA BQL41GW23
8/30/2016 NA NA NA NA BQL NA NA BQL41GW24
8/13/2014 43.2 0.3 BQL 0.52 65.7 BQL BQL BQL41GW25
3/11/2015 20.8 BQL BQL BQL 162 BQL BQL BQL41GW25
8/26/2015 38.3 BQL BQL BQL 159 BQL BQL BQL41GW25
2/24/2016 25.7 BQL BQL BQL 132 BQL BQL BQL41GW25
5/4/2016 39.6 BQL BQL BQL 157 BQL BQL BQL41GW25
8/30/2016 NA NA NA NA 142 NA NA BQL41GW25
2/20/2017 23 BQL BQL BQL 56.3 BQL BQL BQL41GW25
8/30/2016 NA NA NA NA 1.12 NA NA BQL41GW26
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 2
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW27
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW27
8/30/2016 NA NA NA NA BQL NA NA BQL41GW27
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW27
8/30/2016 NA NA NA NA BQL NA NA BQL41GW28
8/30/2016 NA NA NA NA 3.37 NA NA BQL41GW29
8/30/2016 NA NA NA NA BQL NA NA BQL41GW30
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW31
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW31
8/30/2016 NA NA NA NA BQL NA NA BQL41GW31
8/30/2016 NA NA NA NA 11.1 NA NA BQL41GW32
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW32
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW32Dup
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 3
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW33
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW33Dup
8/30/2016 NA NA NA NA BQL NA NA BQL41GW33
8/30/2016 NA NA NA NA BQL NA NA BQL41GW33Dup
8/30/2016 NA NA NA NA BQL NA NA BQL41GW34
8/30/2016 NA NA NA NA BQL NA NA BQL41GW35
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 4
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW36
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW36
2/20/2013 26.2 BQL BQL BQL 13.2 BQL BQL BQL41GW36
11/12/2013 20.3 BQL BQL BQL 12.4 BQL BQL BQL41GW36
8/13/2014 26.9 BQL BQL 0.618 12.2 BQL BQL BQL41GW36
3/11/2015 65.1 0.83 BQL 0.651 38.9 0.358 BQL BQL41GW36
8/26/2015 539 BQL BQL BQL 152 BQL BQL BQL41GW36
2/24/2016 105 BQL BQL BQL 95 BQL BQL BQL41GW36
5/4/2016 110 BQL BQL BQL 86.1 BQL BQL BQL41GW36
8/30/2016 NA NA NA NA 178 NA NA BQL41GW36
2/20/2017 203 BQL BQL BQL 142 BQL BQL BQL41GW36
8/30/2016 NA NA NA NA BQL NA NA BQL41GW37
8/30/2016 NA NA NA NA BQL NA NA BQL41GW38
8/30/2016 NA NA NA NA BQL NA NA BQL41GW39
8/30/2016 NA NA NA NA BQL NA NA BQL41GW40
8/30/2016 NA NA NA NA BQL NA NA BQL41GW41
8/30/2016 NA NA NA NA BQL NA NA BQL41GW42
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 5
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 407 BQL BQL BQL 87.1 BQL BQL BQL41GW43
8/15/2012 35.3 BQL BQL BQL 14.5 BQL BQL BQL41GW43
8/30/2016 NA NA NA NA BQL NA NA BQL41GW43
2/20/2017 13.3 BQL BQL BQL 7.75 BQL BQL BQL41GW43
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW44
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW44
8/30/2016 NA NA NA NA BQL NA NA BQL41GW44
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW44
8/30/2016 NA NA NA NA BQL NA NA BQL41GW45
8/30/2016 NA NA NA NA BQL NA NA BQL41GW46
8/30/2016 NA NA NA NA BQL NA NA BQL41GW62
8/30/2016 NA NA NA NA BQL NA NA BQL41GW63
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 6
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/14/2012 16.1 BQL BQL BQL 33.1 BQL BQL BQL41GW64
2/20/2013 32.4 BQL BQL BQL 71.2 BQL BQL BQL41GW64
8/13/2014 41.1 BQL BQL 0.743 67.8 BQL BQL BQL41GW64
3/11/2015 27.3 0.311 BQL 0.453 55.9 BQL BQL BQL41GW64
8/26/2015 41.2 BQL BQL BQL 48.5 BQL BQL BQL41GW64
2/24/2016 32.6 BQL BQL BQL 44.9 BQL BQL BQL41GW64
5/4/2016 30.5 BQL BQL BQL 39.9 BQL BQL BQL41GW64
8/30/2016 NA NA NA NA 428 NA NA BQL41GW64
2/20/2017 69.4 BQL BQL BQL 145 BQL BQL BQL41GW64
8/30/2016 NA NA NA NA BQL NA NA BQL41GW65
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW66
8/30/2016 NA NA NA NA BQL NA NA BQL41GW66
8/30/2016 NA NA NA NA BQL NA NA BQL41GW102
8/30/2016 NA NA NA NA BQL NA NA BQL41GW103
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW104
8/30/2016 NA NA NA NA BQL NA NA BQL41GW104
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 7
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW105
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW105
3/11/2015 1.13 BQL BQL BQL 2.71 BQL BQL BQL41GW105
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW105
8/30/2016 NA NA NA NA BQL NA NA BQL41GW105
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW105
11/12/2013 31.1 BQL BQL BQL 40.7 BQL BQL BQL41GW106
8/13/2014 84.5 BQL BQL 0.477 92.8 BQL BQL BQL41GW106
3/11/2015 78.2 0.434 BQL 0.349 87.2 BQL BQL BQL41GW106
8/26/2015 52.3 BQL BQL BQL 88.2 BQL BQL BQL41GW106
2/24/2016 176 BQL BQL BQL 203 BQL BQL BQL41GW106
5/4/2016 66 BQL BQL BQL 65.2 BQL BQL BQL41GW106
8/30/2016 NA NA NA NA 130 NA NA BQL41GW106
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 8
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
11/12/2013 BQL 0.295 BQL BQL BQL BQL BQL BQL41GW107
8/13/2014 BQL BQL BQL BQL 0.83 BQL BQL BQL41GW107
3/11/2015 BQL BQL BQL BQL 0.443 BQL BQL BQL41GW107
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
8/30/2016 NA NA NA NA BQL NA NA BQL41GW107
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW107
8/30/2016 NA NA NA NA BQL NA NA BQL41GW108
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
8/30/2016 NA NA NA NA BQL NA NA BQL41GW111
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW111
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 9
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
5/4/2016 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
8/30/2016 NA NA NA NA 1.14 NA NA BQL41GW112
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41GW112
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 10
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW113
8/15/2012 8.3 BQL BQL BQL BQL BQL BQL BQL41GW113
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41GW113
11/13/2013 8.78 BQL BQL 0.413 BQL BQL BQL BQL41GW113
8/13/2014 16.9 0.42 BQL 0.59 1.19 BQL BQL BQL41GW113
3/11/2015 1.68 BQL BQL 0.321 0.368 BQL BQL BQL41GW113
8/26/2015 20.5 BQL BQL BQL BQL BQL BQL BQL41GW113
2/23/2016 12.7 BQL BQL BQL 1.82 BQL BQL BQL41GW113
5/3/2016 26 BQL BQL BQL BQL BQL BQL BQL41GW113
8/30/2016 NA NA NA NA BQL NA NA BQL41GW113
2/20/2017 9.28 BQL BQL BQL BQL BQL BQL BQL41GW113
8/30/2016 NA NA NA NA BQL NA NA BQL41GW114
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41GW119
8/30/2016 NA NA NA NA BQL NA NA BQL41GW119
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 11
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
3/11/2015 0.283 BQL BQL BQL 1.05 BQL BQL BQL41PR67
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
8/30/2016 NA NA NA NA BQL NA NA BQL41PR67
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR67
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR68
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR68
8/13/2014 18 BQL BQL BQL 30.3 BQL BQL BQL41PR68
3/11/2015 2.42 BQL BQL BQL 6.3 BQL BQL BQL41PR68
8/26/2015 12.8 BQL BQL BQL 21.1 BQL BQL BQL41PR68
2/24/2016 11.2 BQL BQL BQL 8.16 BQL BQL BQL41PR68
5/4/2016 19 BQL BQL BQL 17.1 BQL BQL BQL41PR68
8/30/2016 NA NA NA NA 4.89 NA NA BQL41PR68
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR68
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 12
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 10.8 BQL BQL BQL 14.6 BQL BQL BQL41PR69
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR69
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR69
3/11/2015 2.85 BQL BQL BQL 1.15 BQL BQL BQL41PR69
8/26/2015 2.71 BQL BQL BQL BQL BQL BQL BQL41PR69
8/26/2015 3 BQL BQL BQL 0.943 BQL BQL BQL41PR69Dup
2/23/2016 1.09 BQL BQL BQL BQL BQL BQL BQL41PR69
5/3/2016 1.85 BQL BQL BQL BQL BQL BQL BQL41PR69
8/30/2016 NA NA NA NA BQL NA NA BQL41PR69
2/20/2017 1.4 BQL BQL BQL BQL BQL BQL BQL41PR69
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR70
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR70
8/30/2016 NA NA NA NA 2.8 NA NA BQL41PR70
8/30/2016 NA NA NA NA BQL NA NA BQL41PR71
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 13
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
8/26/2015 BQL BQL BQL BQL 2.67 BQL BQL BQL41PR72
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR72
8/30/2016 NA NA NA NA BQL NA NA BQL41PR72
2/20/2017 4.48 BQL BQL BQL 10.6 BQL BQL BQL41PR72
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR73
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR73
3/11/2015 1.7 BQL BQL BQL 0.61 BQL BQL BQL41PR73
8/26/2015 1.77 BQL BQL BQL BQL BQL BQL BQL41PR73
2/23/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR73
5/3/2016 BQL BQL BQL BQL 1.66 BQL BQL BQL41PR73
8/30/2016 NA NA NA NA 1.57 NA NA BQL41PR73
2/20/2017 1.95 BQL BQL BQL 8.1 BQL BQL BQL41PR73
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 14
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
8/13/2014 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
8/26/2015 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
2/24/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
5/3/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
8/30/2016 NA NA NA NA 1.87 NA NA BQL41PR74
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR74
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR75
8/14/2012 10.7 BQL BQL BQL 15.9 BQL BQL BQL41PR75
2/20/2013 9.7 BQL BQL BQL 21.7 BQL BQL BQL41PR75
11/12/2013 1.68 BQL BQL BQL 5.86 BQL BQL BQL41PR75
8/13/2014 6.74 BQL BQL BQL 17.8 BQL BQL BQL41PR75
3/11/2015 0.868 BQL BQL BQL 2.6 BQL BQL BQL41PR75
8/26/2015 BQL BQL BQL BQL 1.2 BQL BQL BQL41PR75
2/23/2016 1.02 BQL BQL BQL 1.72 BQL BQL BQL41PR75
5/4/2016 BQL BQL BQL BQL BQL BQL BQL BQL41PR75
8/30/2016 NA NA NA NA 1.22 NA NA BQL41PR75
2/20/2017 2.24 BQL BQL BQL 5.6 BQL BQL BQL41PR75
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 15
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/30/2016 NA NA NA NA 107 NA NA BQL41PR76
2/20/2017 35.1 BQL BQL BQL 6.51 BQL BQL BQL41PR76
2/21/2012 BQL BQL BQL BQL 7 BQL BQL BQL41PR77
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR77
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR77
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR77
8/13/2014 1.13 0.308 BQL BQL 3.49 BQL BQL BQL41PR77
3/11/2015 11.1 0.292 BQL BQL 12.4 BQL BQL BQL41PR77
8/26/2015 BQL BQL BQL BQL 1.04 BQL BQL BQL41PR77
2/23/2016 2.75 BQL BQL BQL 2.92 BQL BQL BQL41PR77
5/3/2016 1.39 BQL BQL BQL 7.18 BQL BQL BQL41PR77
8/30/2016 NA NA NA NA 1.3 NA NA BQL41PR77
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR78
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR78
8/13/2014 12 0.34 BQL 0.396 10.9 BQL BQL BQL41PR78
3/11/2015 25.9 0.472 BQL BQL 23.5 BQL BQL BQL41PR78
2/24/2016 17.8 BQL BQL BQL 13.3 BQL BQL BQL41PR78
2/20/2017 1.95 BQL BQL BQL 2.95 BQL BQL BQL41PR78
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 16
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL 6.4 BQL BQL BQL41PR79
8/15/2012 5.9 BQL BQL BQL BQL BQL BQL BQL41PR79
2/20/2013 18.8 BQL BQL BQL 14.7 BQL BQL BQL41PR79
11/12/2013 21.9 BQL BQL BQL 50.3 BQL BQL BQL41PR79
8/13/2014 12.3 BQL BQL 0.377 27 BQL BQL BQL41PR79
3/11/2015 9.29 BQL BQL BQL 12.2 BQL BQL BQL41PR79
8/26/2015 34.1 BQL BQL BQL 75.5 BQL BQL BQL41PR79
2/24/2016 34.3 BQL BQL BQL 32.6 BQL BQL BQL41PR79
5/4/2016 55.4 BQL BQL BQL 56.1 BQL BQL BQL41PR79
8/30/2016 NA NA NA NA 74 NA NA BQL41PR79
2/20/2017 3.24 BQL BQL BQL 3.73 BQL BQL BQL41PR79
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 17
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
2/21/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR80
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR80
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR80
11/12/2013 BQL BQL BQL 0.295 4.93 BQL BQL BQL41PR80
8/13/2014 0.962 0.457 BQL 0.314 1.5 BQL BQL BQL41PR80
3/11/2015 0.736 0.321 BQL BQL 1.77 BQL BQL BQL41PR80
8/26/2015 0.953 BQL BQL BQL 9.91 BQL BQL BQL41PR80
2/24/2016 1.44 BQL BQL BQL 1.89 BQL BQL BQL41PR80
5/4/2016 BQL BQL BQL BQL 1.25 BQL BQL BQL41PR80
8/30/2016 NA NA NA NA BQL NA NA BQL41PR80
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR80
8/30/2016 NA NA NA NA 8.88 NA NA BQL41PR81
2/20/2017 BQL 2.22 1 1.12 BQL BQL 1.11 BQL41PR81
8/15/2012 12.8 BQL BQL BQL BQL BQL BQL BQL41PR82
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR82
2/23/2016 27.8 BQL BQL BQL 41 BQL BQL BQL41PR82
5/3/2016 2.44 BQL BQL BQL 7.9 BQL BQL BQL41PR82
8/30/2016 NA NA NA NA 32.4 NA NA BQL41PR82
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 18
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/15/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR83
2/24/2016 15.9 BQL BQL BQL 29.7 BQL BQL BQL41PR83
5/4/2016 8.15 BQL BQL BQL 3.78 BQL BQL BQL41PR83
2/20/2017 BQL BQL BQL BQL 2.74 BQL BQL BQL41PR83
8/30/2016 NA NA NA NA BQL NA NA BQL41PR84
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR84
8/30/2016 NA NA NA NA BQL NA NA BQL41PR85
2/20/2017 BQL BQL BQL BQL 1.83 BQL BQL BQL41PR85
8/14/2012 BQL BQL BQL BQL BQL BQL BQL BQL41PR86
2/20/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR86
11/12/2013 BQL BQL BQL BQL BQL BQL BQL BQL41PR86
2/23/2016 BQL BQL BQL BQL 2.62 BQL BQL BQL41PR86
5/3/2016 0.991 BQL BQL BQL 6.06 BQL BQL BQL41PR86
8/30/2016 NA NA NA NA 1.41 NA NA BQL41PR86
2/20/2017 0.963 BQL BQL BQL 1.03 BQL BQL BQL41PR86
3/11/2015 BQL BQL BQL BQL BQL BQL BQL BQL41PR87
8/30/2016 NA NA NA NA BQL NA NA BQL41PR87
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR87
8/30/2016 NA NA NA NA BQL NA NA BQL41PR88
8/30/2016 NA NA NA NA BQL NA NA BQL41PR89
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 19
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/30/2016 NA NA NA NA 1.7 NA NA BQL41PR90
8/30/2016 NA NA NA NA 5.97 NA NA BQL41PR91
8/30/2016 NA NA NA NA BQL NA NA BQL41PR92
8/30/2016 NA NA NA NA BQL NA NA BQL41PR93
8/30/2016 NA NA NA NA BQL NA NA BQL41PR94
8/30/2016 NA NA NA NA BQL NA NA BQL41PR95
8/30/2016 NA NA NA NA BQL NA NA BQL41PR96
8/30/2016 NA NA NA NA BQL NA NA BQL41PR97
8/30/2016 NA NA NA NA 1.33 NA NA BQL41PR98
8/30/2016 NA NA NA NA BQL NA NA BQL41PR99
8/30/2016 NA NA NA NA BQL NA NA BQL41PR100
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 20
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/15/2012 100 BQL BQL BQL 81.4 BQL BQL BQL41PR101
11/12/2013 10.1 BQL BQL BQL 14.2 BQL BQL BQL41PR101
8/13/2014 60.1 BQL BQL 0.434 52.5 BQL BQL BQL41PR101
3/11/2015 0.915 BQL BQL BQL 1.85 BQL BQL BQL41PR101
8/26/2015 10.2 BQL BQL BQL 9.18 BQL BQL BQL41PR101
2/24/2016 5.39 BQL BQL BQL 4.03 BQL BQL BQL41PR101
5/4/2016 9.8 BQL BQL BQL 4.48 BQL BQL BQL41PR101
8/30/2016 NA NA NA NA 3.5 NA NA BQL41PR101
2/20/2017 BQL BQL BQL BQL BQL BQL BQL BQL41PR101
8/14/2012 6.8 BQL BQL BQL 14.2 BQL BQL BQL41PR200
11/12/2013 20.8 BQL BQL BQL 26.5 BQL BQL BQL41PR200
2/24/2016 28.1 BQL BQL BQL 28.3 BQL BQL BQL41PR200
5/4/2016 25.1 BQL BQL BQL 17.5 BQL BQL BQL41PR200
8/30/2016 NA NA NA NA 73.4 NA NA BQL41PR200
2/20/2017 22.6 BQL BQL BQL 34.5 BQL BQL BQL41PR200
8/30/2016 NA NA NA NA 165 NA NA BQL41PR201
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 21
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
11/12/2013 BQL BQL BQL BQL 1.26 BQL BQL BQL41PR203
8/13/2014 7.39 0.648 BQL 0.505 12.9 BQL BQL BQL41PR203
3/11/2015 17.1 0.396 BQL 0.34 32.5 BQL BQL BQL41PR203
8/26/2015 1.07 BQL BQL BQL 4.44 BQL BQL BQL41PR203
2/24/2016 15.8 BQL BQL BQL 37.3 BQL BQL BQL41PR203
5/4/2016 4.58 BQL BQL BQL 1.72 BQL BQL BQL41PR203
8/30/2016 NA NA NA NA 31.6 NA NA BQL41PR203
2/20/2017 5.93 BQL BQL BQL 28 BQL BQL BQL41PR203
8/30/2016 NA NA NA NA 35.9 NA NA BQL41PR210
8/30/2016 NA NA NA NA 16.6 NA NA BQL41PR211
8/14/2012 BQL BQL BQL BQL 9.2 BQL BQL BQL41PR212
11/12/2013 7.66 BQL BQL BQL 23 BQL BQL BQL41PR212
8/13/2014 8.39 BQL BQL 0.41 10.4 BQL BQL BQL41PR212
3/11/2015 2.49 0.5 BQL 0.314 11.7 BQL BQL BQL41PR212
8/26/2015 12.8 BQL BQL BQL 5.03 BQL BQL BQL41PR212
2/23/2016 6.04 BQL BQL BQL 8.24 BQL BQL BQL41PR212
5/3/2016 18.8 BQL BQL BQL 3.48 BQL BQL BQL41PR212
8/30/2016 NA NA NA NA 27.8 NA NA BQL41PR212
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 22
9. Well nomenclature in RED indicates the well has been abandoned
GW Standard Revised/Estab.
(See Table III)2-MethylnaphthaleneAcenaphtheneFluorantheneFluoreneNaphthalenePyreneHISTORICAL GROUNDWATER LABORATORY ANALYTICAL RESULTS
SITE 1083
TABLE 5.3B
Date PhenanthreneSample ID All Other Analytes30 80 300 300 6 200 2002L GWQS
GCL 12500 2120 300 990 6000 410 200
Contaminant of Concern
EPA 610 BY EPA METHOD 625 AND EPA METHOD 8260B (NAPHTHALENE ONLY)
8/14/2012 17.8 BQL BQL BQL 8.8 BQL BQL BQL41PR213
8/30/2016 NA NA NA NA 7.31 NA NA BQL41PR213
2/20/2017 1.46 0.99 BQL BQL 2.37 BQL BQL BQL41PR213
8/30/2016 NA NA NA NA 290 NA NA BQL41PR214
8/30/2016 NA NA NA NA 280 NA NA BQL41PR215
11/12/2013 24.9 BQL BQL BQL 35.5 BQL BQL BQL41PR220
2/23/2016 179 BQL BQL BQL 307 BQL BQL BQL41PR220
5/3/2016 82 BQL BQL BQL 113 BQL BQL BQL41PR220
8/30/2016 NA NA NA NA 323 NA NA BQL41PR220
8/30/2016 NA NA NA NA 318 NA NA BQL41PR221
8/15/2012 7.4 BQL BQL BQL 13.8 BQL BQL BQL41PR230
11/12/2013 1.83 BQL BQL BQL 4.68 BQL BQL BQL41PR230
2/24/2016 20.7 BQL BQL BQL 99.7 BQL BQL BQL41PR230
5/4/2016 29.5 BQL BQL BQL 122 BQL BQL BQL41PR230
8/30/2016 NA NA NA NA 153 NA NA BQL41PR230
2/20/2017 24.5 BQL BQL BQL 98.6 BQL BQL BQL41PR230
Notes: 1. 2L GWQS = North Carolina Groundwater Quality Standard 15A NCAC 2L .0202
2. GCL = Gross Contamination Levels for groundwater as defined in "Guidelines for Assessment and
Corrective Action for UST Releases" July 15, 2008 Version, Change 3 Effective December 1, 2013
3. All units are in ug/L (Micrograms per Liter)
4. BQL = Below Quantitation Limits
5. NA = Not Analyzed
6. A zero in the 2L GWQS column indicates the 2L Standard is equal to the laboratory detection limit
7. A zero in the GCL column indicates a GCL has not been established
8. Shaded concentrations indicate exceedance of the 2L GWQS
Page 23
9. Well nomenclature in RED indicates the well has been abandoned
41PR77
41PR74
41PR79
41PR75
41PR80
41PR82
41PR83
41PR85
41PR86
41PR67
41PR101
41PR68
41GW25
41GW37
41GW36
41GW43
41PR203
41PR204
41PR202
41GW106
41PR20141PR200
41GW05
41PR216
41PR217
41PR221
41PR22041PR219
41GW02R
41PR218
41GW03R
41PR215
41PR210
41PR211
41PR21241GW06
41PR213
41PR214
41GW64
LI
N
C
O
L
N
P
L
A
C
EROOSEVELT BLVDTRUMAN
R
OA
D
POLK PLACE41PR230
ARTHUR
D
RI
V
E
WILSON DRIVETAFT COURTB
U
C
H
A
N
A
N
D
R
I
V
E
Monitoring Wells 41GW39 & 41GW40located approximately 250 feet northeast and 300 feet southeast of 41GW24
Monitoring Well 41GW45 located approximately 180 feet south of 41GW119
41GW34
41GW30
41GW103
41GW102
41GW6241GW32
41PR7141GW42
41PR100
41PR72
41PR73
41GW104
41PR70
41PR69
41PR78
41GW22
41GW41
41GW111 41GW112
41GW107
41GW21
41PR81
41PR84
41GW23
41PR88
41GW66
41PR98
41GW29
41GW26
41PR95
41PR89
41PR90
41GW31
41GW33
41PR91
41PR87
41PR94
41PR96
41PR76
41GW108
41GW27
41GW114
41GW113
41GW65
41GW28
41PR97
41PR99
41GW46
41GW105
41GW63
41GW44
41GW119
41GW38
41PR92 41GW24
41PR93
41GW35
Scale:AS SHOWN
SITE 1083FREE PRODUCT PLUME MAP AS OF FEBRUARY 2017
NOTES
Job No.:217001 Date Drawn:Drawn By:THW Checked By:SAC
FIGURE
5.1
LEGEND
No Measurable Thickness
Product Detected
Free Product Plume
Free ProductWell by Type
Groundwater Flow Direction
Known Point of Release
JUNE 2017
This document is "FOR OFFICIAL USE ONLY" and it contains info that may be exempt from public release under theFOI Act (5 U.S.C. 552). It is to be handled IAW DoD policy and is not to be released to the public or personnel who do not have a valid "need-to-know" without prior approval of an authorized DoD official.
WARNING:
RW
Surface Water
T-I
T-II
T-III
Unknown
Well
MCAS CHERRY POINTPERIODIC MONITORINGREPORT
100 0 10050FeetSCALE
Fuel Line
Well Number Well Type Date Product Thickness (ft.)41GW05 T-II 2/20/2017 0.0241PR202 RW 2/20/2017 0.0141PR216 RW 2/20/2017 0.0241PR217 RW 2/20/2017 0.0241PR218 RW 2/20/2017 0.0241PR220 RW 2/20/2017 0.05
LI
N
C
O
L
N
P
L
A
C
EROOSEVELT BLVDTRUMAN ROAD
POLK PLACEARTHUR
D
RI
V
E
WILSON DRIVETAFT COURTB
U
C
H
A
N
A
N
D
R
I
V
E
41GW46
41GW28
41PR97
41PR99
41GW38
41PR98
41GW29
41PR9641PR94
41PR91
41GW108
41GW114
41PR95 41GW26
41PR93
41PR90
41GW65
41GW113
41GW63
41PR9241PR92
41GW66
41PR88
41GW21
41GW24
41PR89
41GW107
41GW05
41PR214
41PR21841PR21941PR221
41PR21741PR216
41PR21041PR21541PR211
41GW112
41PR20141PR202
41PR204
41GW41
41GW22
41GW62
41GW10641GW4241PR71
41PR100
41PR7041GW102
41GW103
41GW34
41GW30
41GW37
41GW35
41GW31
41GW104
41GW25
41PR101
41PR75
41PR80
41PR79
41GW36
41GW32
41PR203
41PR74
41PR67
41PR68
41GW64
41PR73
41PR72
41PR69
41PR83
Monitoring Wells 41GW39 & 41GW40located approximately 250 feet northeast and 300 feet southeast of 41GW24
Monitoring Well 41GW45 located approximately 180 feet south of 41GW119
41PR78
41PR86
41PR200
41GW111
41PR230
41GW44
41GW105
41GW27
41PR87
41GW33
41GW23
41PR212
41PR85
41GW03R
41PR81
41PR84
41PR213
41GW06
41GW02R41PR220
41PR82
41PR76
41GW119
41GW43
41PR77
This document is "FOR OFFICIAL USE ONLY" and it contains info that may be exempt from public release under theFOI Act (5 U.S.C. 552). It is to be handled IAW DoD policy and is not to be released to the public or personnel who do not have a valid "need-to-know" without prior approval of an authorized DoD official.
WARNING:
NOTES
LEGENDWell by Type
Fuel Line
Groundwater FlowDirection
Known Point of Release
Free Product Detected
EPA 602 by SM 6200B2L Compliant
EPA 602 by SM 6200BPlume in Excess of 2L
EPA 602 by SM 6200B2L Non-CompliantRW
Surface Water
T-I
T-II
T-III
Unknown
Well
Scale:AS SHOWN
SITE 1083EPA METHOD 602 BY SM 6200B COLORIMETRY AND PLUME IN EXCESS OF 2L AS OF FEBRUARY 2017
Job No.:217001 Date Drawn:AUG 2017 Drawn By:THW Checked By:SAC
FIGURE
5.2
1. The sampling frequency for this site is Semi-Annual and the next sampling event is scheduled for August 2017.
2. 2L Standard refers to North Carolina Groundwater Quality Standard 15A NCAC 2L.0202.
3. GCL refers to Gross Contaminant Level as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2008 Version, change 3 Effective December 1, 2013.
4. A 2L Standard of "0.00" implies a standard has not yet been established. According to NCAC T15:02L, any compound found above laboratory detection limits is considered non-compliant unless otherwise specified by the NCDEQ.
MCAS CHERRY POINTPERIODIC MONITORINGREPORT
SCALE
100 0 10050Feet
Sample ID Well Type Well Depth Date Parameter Results Units 2L Standard GCL41GW25T-II 18.50 2/20/2017 Benzene 3.47000 ug/L 1.00000 5000.0000041GW113T-II 25.00 2/20/2017 Benzene 2.03000 ug/L 1.00000 5000.0000041PR230RW 25.00 2/20/2017 Benzene 4.42000 ug/L 1.00000 5000.00000
LI
N
C
O
L
N
P
L
A
C
EROOSEVELT BLVDTRUMAN
R
OA
D
POLK PLACEARTHUR
D
RI
V
E
WILSON DRIVETAFT COURTB
U
C
H
A
N
A
N
D
R
I
V
E
41GW46
41GW28
41PR97
41PR99
41GW38
41PR98
41GW29
41PR9641PR94
41PR91
41GW108
41GW114
41GW119
41PR95
41GW26
41PR93
41PR90
41GW65
41GW31
41GW113
41GW63
41PR9241PR92
41GW66
41PR88
41GW21
41GW24
41PR89
41GW10741PR77
41GW05
41PR214
41PR21841PR219
41PR221
41PR217
41PR216
41PR21041PR21541PR211
41GW112
41PR201
41PR202
41GW22
41GW62
41GW42 41PR71
41PR100
41GW102
41GW103
41GW34
41GW30
41GW37
41GW35
41PR70
41PR212
41GW104
41GW106
41PR101
41PR74
41PR79
41GW25
41PR75
41PR203
41GW27
41GW36
41PR80
41PR213
41PR67
41PR81
41PR204
41PR68
41GW64
41PR69
41PR73
41PR72
Monitoring Wells 41GW39 & 41GW40located approximately 250 feet northeast and 300 feet southeast of 41GW24
Monitoring Well 41GW45 located approximately 210 feet south of 41GW114
41GW111
41PR78
41PR83
41PR86
41GW230
41PR200
41PR84
41PR85
41GW33
41GW03R41GW02R
41GW06
41PR220
41PR82
41PR87
41PR76
41GW105
41GW44
41GW23
41GW32
41GW43
This document is "FOR OFFICIAL USE ONLY" and it contains info that may be exempt from public release under theFOI Act (5 U.S.C. 552). It is to be handled IAW DoD policy and is not to be released to the public or personnel who do not have a valid "need-to-know" without prior approval of an authorized DoD official.
WARNING:
NOTES
LEGENDWell by Type
Groundwater FlowDirection
Known Point of Release
Free Product Detected
EPA 610 by EPA 6252L Compliant
EPA 610 by EPA 625Plume in Excess of 2L
EPA 610 by EPA 6252L Non-CompliantRW
Surface Water
T-I
T-II
T-III
Unknown
Well
Scale:AS SHOWN
SITE 1083EPA METHOD 610 BY EPA METHOD 625 COLORIMETRY AND PLUME IN EXCESS OF 2LAS OF FEBRUARY 2017
Job No.:217001 Date Drawn:JUNE 2017 Drawn By:THW Checked By:SAC
FIGURE
5.3
1. The sampling frequency for this site is Semi-Annual and the next sampling event is scheduled for August 2017.
2. 2L Standard refers to North Carolina Groundwater Quality Standard 15A NCAC 2L.0202.
3. GCL refers to Gross Contaminant Level as defined in "Guidelines for Assessment and Corrective Action for UST Releases" July 15, 2008 Version, change 3 Effective December 1, 2013.
4. A 2L Standard of "0.00" implies a standard has not yet been established. According to NCAC T15:02L, any compound found above laboratory detection limits is considered non-compliant unless otherwise specified by the NCDEQ.
MCAS CHERRY POINTPERIODIC MONITORINGREPORT
SCALE
100 0 10050Feet
Sample ID Well Type Well Depth Date Parameter Results Units 2L Standard GCL41GW25 T-II 18.50 2/20/17 Naphthalene 56.30000 ug/L 6.00000 6000.0000041GW36 RW 20.00 2/20/17 2-Methylnaphthalene 203.00000 ug/L 30.00000 12500.0000041GW36 RW 20.00 2/20/17 Naphthalene 142.00000 ug/L 6.00000 6000.0000041GW43 RW 20.00 2/20/17 Naphthalene 7.75000 ug/L 6.00000 6000.0000041GW64 T-II 18.00 2/20/17 2-Methylnaphthalene 69.40000 ug/L 30.00000 12500.0000041GW64 T-II 18.00 2/20/17 Naphthalene 145.00000 ug/L 6.00000 6000.0000041PR72 RW 30.00 2/20/17 Naphthalene 10.60000 ug/L 6.00000 6000.0000041PR73 RW 30.50 2/20/17 Naphthalene 8.10000 ug/L 6.00000 6000.0000041PR76 RW 30.50 2/20/17 2-Methylnaphthalene 35.10000 ug/L 30.00000 12500.0000041PR76 RW 30.50 2/20/17 Naphthalene 6.51000 ug/L 6.00000 6000.0000041PR200 RW 25.00 2/20/17 Naphthalene 34.50000 ug/L 6.00000 6000.0000041PR203 RW 25.00 2/20/17 Naphthalene 28.00000 ug/L 6.00000 6000.0000041PR230 RW 25.00 2/20/17 Naphthalene 98.60000 ug/L 6.00000 6000.00000
Fuel Line