DWM Brownfields Inspection Report
Submitted By: jkslaughter_ncdenr
Submitted Time: 08/18/2022 7:48 AM
I. Inspection Information
Date & Time: 08/17/2022 12:38 PM Inspection Type: Meeting
Brownfields Staff:
Kevin Slaughter
Other Personnel
AECOM - John Moran, Jordan Harrell and Jim
Dimitroff. First Choice Radon - Alton Berry
Location:
Lat: 36.06663958, Long: -80.23139535
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 2 of 7
II. Project Information
Number: 18032-14-034 Name: Carter G. Woodson Charter School
Address: 420, 437 Goldfloss St
City: Winston Salem
County: Forsyth
III. Environmental
Current Use of Property: Institutional
Structures on Property: Existing Structures Violation: No
Vapor Mitigation Systems: Observed Vapor Mitigation Violation: No
Use of Surface Water or Groundwater: Not Observed Water Use Violation: No
Exposed Soils: Not Observed Exposed Soils Violation: No
Summary: Observed smoke testing of Active VIMS to verify presence of suspected
preferential pathway identified during previous site inspection and determine if
additional preferential pathways were present within the building. Based on visible
smoke, and ppbRAE readings, several preferential pathways were located (Photos 1-7)
Summary: N/A
Summary: One story, primarily CMU block, middle school building. School building not in
use at the time of the Site Inspection/smoke test.
Summary: N/A
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 3 of 7
Use of Basements: Not Observed Basement Violation: No
Storage of Chemicals: Not Observed Chemical Violation: No
Groundwater Monitoring Wells: Not Observed Monitoring Well Violation: No
Current Exposure to Public/Public Risk:
Summary: N/A
Summary: N/A
Condition:
Summary: N/A
The school building is not currently in-use, and as a result, no risk to the public was
observed at the time of the Site Inspection. In addition, the active VIMS is in operation,
which should significantly reduce/eliminate VI into the building if the system is in
operation.
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 4 of 7
IV. Inspector Comments
V. PHOTOGRAPHS
Photo 1: Smoke generating equipment and duct work attached to one of the three VIMS
exhaust risers on the western end of the building.
The smoke test was begun prior to DEQ personnel arriving onsite to observe the testing.
No visible smoke from below the concrete slab was observed while DEQ personnel was
onsite, although photos and videos taken by AECOM earlier in the day showed significant
smoke from below the slab in the area where air movement was detected during a
previous Site Inspection (Photo 7).
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 5 of 7
Photo 2: Smoke observed at test equipment during start of typical smoke test.
Photo 3: Checking VIMS riser port for presence of smoke. There was a significant delay from
the start of the test, until smoke was observed at riser port prior to being injected below slab.
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 6 of 7
Photo 4: A ppbRAE being used to check for the presence of smoke around a VIMS suction point.
Photo 5: Checking bathroom vapor pin for the presence of smoke during testing.
Brownfields Inspection Report: Carter G. Woodson Charter School, 18032-14-034
08/17/2022 12:38 PM
Page 7 of 7
Photo 6: Using ppbRAE to check utility penetrations within restroom during testing.
Photo 7: Photograph of suction point within classroom where smoke was observed exiting both
sides of interior wall during testing performed prior to DEQ arrival.