HomeMy WebLinkAbout2021.11.03_CCO.p18-19-24_DEQNoticeChemoursAboutDownstreamCounties
November 3, 2021
CERTIFIED MAIL / RETURN RECEIPT REQUESTED
Ms. Dawn Hughes
Plant Manager
Chemours Fayetteville Works
22828 NC Highway 87 W
Fayetteville NC 28306
RE: Notice Regarding Chemours’ Obligations Under Consent Order and 15A NCAC
02L .0106 - Offsite Groundwater Assessment and Provision of Replacement Drinking
Water Supplies.
Dear Ms. Hughes:
The North Carolina Department of Environmental Quality (DEQ) has determined that
Chemours is responsible for contamination of groundwater monitoring wells and water supply
wells in New Hanover County and potentially other downstream counties affected by PFAS
contamination in the Cape Fear River. Pursuant to 15A NCAC 2L .0101 et seq. and paragraph
18 of the Consent Order entered by Bladen County Superior Court on February 25, 2019
(Consent Order), Chemours must conduct a comprehensive assessment of this contamination and
ultimately prepare an appropriate corrective action plan to address it. Pursuant to paragraphs 19-
24 of the Consent Order, Chemours must also provide replacement drinking water supplies for
affected parties.
Duty to Conduct Assessment of Contamination
Since early 2019, DEQ has been sampling groundwater monitoring wells and water
supply wells in New Hanover County in part to determine whether activities at the Chemours
Fayetteville Works facility (Facility) have caused contamination of groundwater in this region.
The results of this sampling have established that multiple wells in New Hanover County are
contaminated with PFAS compounds that originated at the Facility. This data constitutes
additional information that was not in DEQ’s possession at the time that the Consent Order was
lodged with the Court in November of 2018.
Chemours’ prior submissions to DEQ, including its September 30, 2019 On and Offsite
Assessment, have failed to include any assessment or proposal to assess groundwater
contamination in New Hanover, Pender, Columbus or Brunswick Counties. As the party
responsible for this contamination, Chemours must comply with the requirements of 15A NCAC
2L .0101 et seq. as well as paragraph 18 of the Consent Order by conducting a comprehensive
assessment of this contamination. Specifically, 15A NCAC 2L .0106(g) and paragraph 18 of the
Consent Order require Chemours to assess (1) the source and cause of the contamination; (2) any
imminent hazards to public health and safety; (3) all receptors and significant exposure
pathways; (4) the horizontal and vertical extent of the soil and groundwater contamination, and
all significant factors affecting contaminant transport and (5) geological and hydrogeological
features influencing the movement, chemical, and physical character of the contaminants.
Therefore, DEQ directs Chemours to submit, within 90 days of receipt of this Notice, a
plan for DEQ review and approval to conduct a comprehensive assessment of the groundwater
contamination in New Hanover County and other affected counties that meets the requirements
of 15A NCAC 2L .0106(g) and paragraph 18 of the Consent Order.1
Duty to Provide Replacement Drinking Water to Affected Parties
DEQ’s investigation has revealed that groundwater contamination in New Hanover
County has reached private drinking water supply wells. Chemours’ prior submissions to DEQ,
including its April 26, 2019 Drinking Water Compliance Plan as updated and amended, have
failed to indicate any intention to conduct sampling of private drinking water wells in
downstream counties or to provide replacement drinking water supplies to affected parties in
these areas.
Pursuant to paragraphs 19 and 20, Chemours is responsible for providing replacement
water supplies for “any party with a private drinking water supply well” contaminated by PFAS
at or above levels specified in the Consent Order. Pursuant to paragraph 21, Chemours is
required to conduct sampling of drinking water wells to determine whether parties are eligible
for replacement drinking water supplies.
Therefore, DEQ directs Chemours to submit, within 90 days of receipt of this Notice, an
updated Drinking Water Compliance Plan pursuant to paragraph 24 of the Consent Order. The
updated plan shall provide for sampling of drinking water wells in downstream counties to
identify affected parties entitled to provision of replacement water supplies.
Failure to comply with the State’s rules and the Consent Order in the manner and time
specified may result in enforcement action by DEQ.
1 DEQ notes that on April 7, 2020 DEQ determined that Chemours’ Corrective Action Plan was insufficient and would require
significant revisions. DEQ has since deferred review of the Corrective Action Plan until further progress has been made in the fulfillment of Chemours obligations to assess on and offsite contamination. Ultimately, however, any approvable corrective action
plan must address the results of the assessment described in this Notice.
We appreciate your attention and prompt response in this matter. If you have any
questions, please feel free to contact me at (919) 707-8700.
Sincerely,
Sushma Masemore, P.E.
Assistant Secretary for the Environment, NCDEQ