DWM Brownfields Inspection Report
Submitted By: jkslaughter_ncdenr
Submitted Time: 03/22/2022 11:05 AM
I. Inspection Information
Date & Time: 03/17/2022 1:15 PM Inspection Type: Meeting
Brownfields Staff:
Kelly Johnson, Kevin Slaughter
Other Personnel:
Al Quarles- ATC, Scott Kurz - Vice President
Lincoln Harris
Location:
Lat: 35.2249705, Long: -80.850664,
Brownfields Inspection Report: West Stonewall Street (RN), 19084-15-060
03/17/2022 1:15 PM
Page 2 of 5
II. Project Information
Number: 19084-15-060 Name: West Stonewall Street (RN)
Address: 600 S Tryon St
City: Charlotte
County: Mecklenburg
III. Environmental
Current Use of Property: Commercial/Retail
Structures on Property: Existing Structures Violation: No
Vapor Mitigation Systems: Observed Vapor Mitigation Violation: Yes
Use of Surface Water or Groundwater: Not Observed Water Use Violation: No
Exposed Soils: Not Observed Exposed Soils Violation: No
Summary: Although the entire VIMS was observed, spent majority of the time at the
property evaluating VIMS riser discharge relocation options. Currently the VIMS
discharge is too close to the garage entrance, and the stairwell air intake located on
either side of the riser exhaust (Photo 1)
Summary: N/A
Summary: 22 story structure with ground floor office and retail space, 12 parking deck
levels, with 10 stories of office space located above the parking deck.
Summary: N/A
Brownfields Inspection Report: West Stonewall Street (RN), 19084-15-060
03/17/2022 1:15 PM
Page 3 of 5
Use of Basements: Not Observed Basement Violation: No
Storage of Chemicals: Not Observed Chemical Violation: No
Groundwater Monitoring Wells: Not Observed Monitoring Well Violation: No
Current Exposure to Public/Public Risk:
Summary: N/A
Summary: N/A
Condition:
Summary: N/A
Evaluation continuing regarding relocation of VIMS exhaust discharge to meet set-back
requirements. See Inspector Comments.
Brownfields Inspection Report: West Stonewall Street (RN), 19084-15-060
03/17/2022 1:15 PM
Page 4 of 5
IV. Inspector Comments
V. PHOTOGRAPHS
Photo 1: Current 8” dia. cast iron VIMS discharge with rain cap in center of photograph.
Entrance to upper garage level visible on right side of photo, while stairwell with its own roof
mounted air intake is visible on the right side of the photograph.
DEQ met with ATC and Lincoln Harris to determine how current VIMS exhaust riser
(Photo 1) could be rerouted to meet acceptable standards. After discussing options that
involved installing a portion of the riser on one of the two upper floors of the parking
deck, and discharging outside of parking deck, a couple of options were evaluated on the
first floor of the building where the riser could exit the side of the building, and extend up
exterior of building the appropriate distance to meet AARST guidelines regarding building
openings, etc. (Photos 2 and 3). ATC to evaluate possibilities discussed and provide an
alternate path for the VIMS exhaust stack to DEQ for approval.
Brownfields Inspection Report: West Stonewall Street (RN), 19084-15-060
03/17/2022 1:15 PM
Page 5 of 5
Photo 2: Cast iron VIMS exhaust riser visible in center of photograph turning 90 degrees vertical
to top of parking garage level and terminating at Photo 1. Currently evaluating the elimination
of vertical portion of riser and exiting building at this location.
Photo 3: Discussed extending riser horizontally out narrower opening to the right of the garage
entrance and extending it up the center of the brick wall to the appropriate height. Other
relocation methods on the upper two parking garage levels are also being considered.