HomeMy WebLinkAbout0601_ROSCANS_2010RiCHARID7SON SMITH GARDNER _
1_,�6,l'tE:l.li1M� `tTf,C)L.C?t.;l(f.tL
Febrl
Ms. Heather Dawes
EnergyXchange
66 EnergyXchange Dr.
Burnsville, NC 28714
RE: Project No. Xchange 10-1
Operations, Monitoring, and Maintenance Report - January 2010
Landfill Gas Management System at the closed Avery County MSW Landfill
Dear Heather:
This report provides information concerning the operation and monitoring (O&M) of the closed
Avery County MSW Landfill landfill gas (LFG) management system. This report covers the
first of three (3) required monitoring events before system termination, anticipated in June 2010.
Mr. Don Misenheimer (RSG) performed the January site visit on January 26, 2010. Action items
- - --take-n-during-theinspection- are -provided below and the monitoring results -are attached.
Decommissioned Wells: Two (2) of the four decommissioned wells (wells taken
off-line with well heads removed and capped) were not sealed. RSG re -sealed
The next routine monitoring event is tentatively scheduled for the first week of March 2010.
Please feel free to contact us with any questions at (919) 828-0577 or by email below
Cordially,
Richardson Smith Gardner and Associates, Inc.
ti
Don Mi nheimer tacey S ith, ,.E.
Projec Scientist, ext. 224 oject an. er, t.
don@rsgeng:ineers.cotn star rs en u rs.
DMM/sas
Att.
cc: Mr. Henry "Buddy" Norris, Avery County Solid Waste Department
Mr. Bill Wagner, NCDENR
File
127
HAProjects\Avery County (NC)\Landfill Gas (Energy Exchange)\letter_report_Avery_MSW_012910.wpd
14 N. BOYLAN AVENUE 9 RALEIGH, NORTH CAROLINA 27603 • TEL. 919-828-0577 • VNM/.RSGENGINEERS.COM
EVENT DATE: 1/26/2010
RSG PERSONNEL: Don Misenheimer
Avery County MSW Landfill LFG Collection System January 26, 2010
UNIT USED: GEM 2000 (Calibmlion Attaclxd)
-RSG PERSONNEL:_ Don Miwalidmcr
Xchange ID
RSG Map ID
Date/Time
mm/dd/yyyy
CH4
%
CO2
%
02
%
Balance
%
Adj,
Temperature
T
Init.
Temperature
T
Adj. Static
Pressure
in H2O
Init. Static
Pressure
in H2O
Baro
in Hg
Adj.
Flow
Scfm
Init. Flow
Scfm
Adj. Diff.
Pressure
in H2O
ACLFEW10
W1
1/26/201012:22
67.6
32.3
0
0.1
40
40
-21.6
-21.6
26.97
3
<o>
0.003
ACLFEW 12
W2
1/26/2010 12:44
68.7
31.2
0
0.1
42
42
-21.3
-21.3
26.97
8
<o>
0.013
ACLFEW 14
W3
1/26/2010 12:56
66.7
33.1
0
0.2
38
38
-21.1
-21.1
26.96
9
<o>
0.019
ACLFFW16
W4
1/26/201013:04
70.7
29.2
0
0.1
37
37
-21.1
-21.1
26.99
7
<o>
0
ACLFEW18
W5�
---
---
---
•--
---
---
•--
---
---
---
•--
---
---
ACLFEW20
WG
---
---
--•
---
--
---
•--
--
•-
•--
-••
---
---
ACLFEW22
W7`,
---
•--
-•-
--
--•
--
•--
---
---
-•
---
•--
---
ACLFEW24
W81
---
---
---
•-•
---
---
---
--
---
---
•-•
---
---
Blower Inlet
1/261201013: 17
67.9
31.5
0.2
0.2
<o>
70
-21.7
-21.7
29.74
<o>
<o>
<o>
BFS Outlet
1/26/2010 13:25
54.9
26.6
3.4
15.1
<o>
78
0.1
0.1
29.77
<o>
<o>
<o>
Notes:
RSG ID's W5-W8 have been previously decomissioned. _
The differential pressure measurement should be positive. A negative differential pressure indicates no gas flow. Negative differential pressure
may be he result of dirt or water obstructing the pitot tube perforations. Overpulling by adjacent extractions wells may also result in negative
pressure being displayed.
Page 1 of 1
Pine Environmental Services, Inc
84-1-11 Garvey Suite_1_l_3, Raleigh, NC 27616
866-646-7463(Toll-Free)
919-713-0008(Phone)
919-878-1122(Fax)
pine-nc@pine-environmental. c_om
Certificate of GEM 2000 Calibration
GEM 2000 Serial Number gm05593 was calibrated to the manufacturer's specifications with NIST
standards.
Model: 2000
Pine No: 2571
Serial No: gm05593
lot Number:Lot 7968 (GEM Gas) Exp: 8-2-2011
bration Standard
Instrument
Output
Allowable Range
o
/o Difference
FCarbonDioxide: 15%
15%
14.25-15.75 %
0%
hane: 15%
15%
14.25-15.75 %
0%
lat Numher- Lot 10079 (4 GAS) Exp: 6-29-2010
ECafibra.tionStandard
Instrument
llowable Range
% Difference
9%
20.9%
19.86-21.94 %
0%
Environmental Conditions of Test Area:
Temperature Degree 68 4 %Relative Humidity 60
F:
Calibrated By: John Paul Keon Date: 1/25/2010 9:23:00 AM
All instruments are calibrated by Pine Environmental Services, Inc. according to the manufacturer's
specifications, but it is the customer's responsibility to calibrate and maintain this unit in
accordance with the manufacturer's specifications and/or the customer's own specific needs.
Notify Pine Environmental Services, Inc. of any defect within 24 hours of receipt of equipment
Please call 866-646-7463 for Technical Assistance
See attached packing list
httt)://Vinewebapps/Calibrepair/calibreport.aspx?pinenum=2571 &calibtype=0 2/1 /2010
>,, RICHARDSON SMITH GARDNER & ASSOCIATES
• —— e e —e ee
April 26, 2010
Mr. Bill Wagner
Division of Waste Management — NCDENR
2090 US Highway 70
Swannanoa, North Carolina 28778
RE: Methane Monitoring Well Installation
Avery County MSW Landfill
NC Solid Waste Permit No. 06-01
Spruce Pine, North Carolina
Dear Bill:
On behalf of Avery County, Richardson Smith Gardner & Associates (RSG) is hereby providing
an update to the implementation of the Landfill Gas Monitoring Plan', approved on February 16,
2010. To date, six (6) of the eight (8) planned monitoring probes have been installed. Due to
surveying work is required to install the remaining two (2) gas probes. RSG is notifying the
Division that these remaining probes will be installed within the next 30 days, or we will provide
an
We appreciate your attention and we are prepared to respond immediately to any questions or
concerns. Please feel free to contact us by phone at (919) 828-0577 or by email below.
Sincerely,
Richardson S th Gardner & Associates, Inc.
s
---
Don Mifnheimer
Project Scientist, ext. 224
don@rsgengineers.com
Cc:
Stakyy A S' _, ith; P.E.
Projec gnager, ext. 127
Stacey2rsg eng;ineers.com
Mr. Henry "Buddy" Norris, Avery County Solid Waste Department
Mr. Allen Gaither, NCDENR
File
HAProjectstAvery-County (NC)Wvery-09-8-(LandfiltCm Management -Plan)Vetter_04261
Landfill Gas Monitoring Plan, Averyy County MSW Landfill, Richardson Smith Gardner and Associates, Inc., January
2010.
14 N. BOYLAN AVENUE 9 RALEIGH, NORTH CAROLINA 27603 e TEL. 919-828-0577 • WWW.RSGENGINEERS.COM