HomeMy WebLinkAbout3612_DukeAllen_RABLF_Sept 2021 Leachate Report_FID1628556_20211230DUKE
ENERGY,
December 30, 2021
Ms. Sarah Moutos
North Carolina Department of Environmental Quality
Division of Waste Management
Solid Waste Section
1646 Mail Service Center
Raleigh, NC 27699-1646
526 South Church Street
Charlotte, NC 28202
Mailing Address:
PO Box 1006
Mail Code EC13K
Charlotte, NC 28201-1006
704 382 7171
Subject: Semi-annual Leachate Sampling Results — September 2021
Duke Energy Carolinas, LLC
Allen Steam Station
Retired Ash Basin Ash Landfill, Phase I, Cells 1 and 2, Permit #36-12
Dear Ms. Moutos:
In accordance with the current landfill Operations Plan, Duke Energy is providing the results of semi-
annual leachate sampling for the Allen Steam Station (Allen or Station) Retired Ash Basin (RAB) Ash
Landfill located in Gaston County, North Carolina.
On August 31, 2021, leachate samples were collected from the leachate collection system at sample
ports for Cell 1 and Cell 2 as depicted on Figure 1. The samples were collected by Duke Energy
personnel. A summary of sampling results can be found in Table 1. Laboratory analytical and field
forms are provided as Attachments 1 and 2, respectively. The parameters tested are not bound by state
groundwater or surface water standards.
The Allen RAB Ash Landfill leachate is sampled semi-annually during March and September. The next
landfill leachate sampling event will occur during March 2022 with documentation to follow.
If you have any questions or concerns, please contact me at 704-382-7171 or at
Courtney.Murphy(o-)duke-energy.com.
Sincerely,
dw�w- ff"
Courtney W. Murphy, P.G.
Environmental Services
Cc (via email): Mr. Jeff Flanagan — Allen Steam Station
Mr. Scott Harris —Allen Steam Station
Mr. Randy Gantt — Allen Steam Station
Ms. Erica Tuchbaum — Duke Energy Corporation
Ms. Kimberlee Witt — Duke Energy Corporation
Page 1 of 1
EN 09k 67NUT—� ❑Paper Report ❑Electronic Data - Email CD (data loaded: Yes I No) DoclEvent # NC DENR I Environmental Monitorin—
g
Division of Waste Management - Solid Waste Reporting Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1 As such, these documents are
available for inspection and examination by any person upon request (NC General Statute 132-6)
Instructions:
Prepare one form for each individually monitored unit.
• Please type or print legibly.
• Attach a notification table with values that attain or exceed NC 2L groundwater standards or NC 2B surface water standards. The notification
must include a preliminary analysis of the cause and significance of each value. (e g naturally occurring, off -site source, pre-existing
condition, etc.).
• Attach a notification table of any groundwater or surface water values that equal or exceed the reporting limits.
• Attach a notification table of any methane gas values that attain or exceed explosive gas levels This includes any structures on or nearby the
facility (NCAC 13B 1629 (4)(a)(i).
• Send the original signed and sealed form, any tables, and Electronic Data Deliverable to: Compliance Unit, NCDENR-DWM Solid Waste
Section, 1646 Mail Service Center, Raleigh, NC 27699-1646.
Solid Waste Monitoring Data Submittal Information
Name of entity submitting data (laboratory, consultant, facility owner):
Duke Energy Carolinas, LLC
Contact for questions about data formatting. Include data preparees name, telephone number and E-mail address:
Name: r niirtnPv W Miirnhv Pr; Phone: 17041'IA2-7171
E-mail: r.nurtnPv MnrnhvrAduka-anamv rnm
NC Landfill Rule: Actual sampling dates (e.g.,
Facility name: Facility Address: Facility Permit # (.0500 or .1600) October 20-24. 2006)
Retired Ash Basin (RAB) Ash
Landfill 253 Plant Allen Rd. 36-12 .0500 August 31, 2021
Duke Energy Belmont, NC 28012
Allen Steam Station
Environmental Status: (Check all that apply)
❑ Initial/Background Monitoring ❑x Detection Monitoring Assessment Monitoring ❑ Corrective Action
of data submitted: (Check all that apply)
Groundwater monitoring data from monitoring wells
Groundwater monitoring data from private water supply wells
Leachate monitoring data
Surface water monitoring data ❑
Methane gas monitoring data
Corrective action data (specify)
Other(specify)
Notification attached?
❑No. No groundwater or surface water standards were exceeded
Yes, a notification of values exceeding a groundwater or surface water standard is attached. It includes a list of groundwater and surface water
monitoring points, dates, analytical values, NC 2L groundwater standard, NC 2B surface water standard or NC Solid Waste GWPS and
preliminary analysis of the cause and significance of any concentration.
❑ Yes, a notification of values exceeding an explosive methane gas limit is attached. It includes the methane monitoring points, dates, sample
values and explosive methane gas limits.
Certification To the best of my know a ge, the information reported and statements made on this data submittal and attachments are true and correct.
Furthermore, I have attached complete notification of any sampling values meeting or exceeding groundwater standards or explosive gas
levels, and a preliminary analysis of the cause and significance of concentrations exceeding groundwater standards. I am aware that there
are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
Courtney W. Murphy, P.G. Senior Environmental Specialist (704) 382-7171
Facility Representative Name (Print) Title (Area Code) Telephoni- Numher
Digitally signed by Courtney W. Murphy, P G 12/30/2021 Affix NC Licens/eltlfbel ' al Geolo Est Seal
Courtney W. Murphy, P.G. Date 2021,12.3015:40:47.05'00 0%, �g
Signature Date ����••'� ilk
E S,RQ���,i(1
o
Duke Energy Corporation, Mail Code EC13K, P.O. Box 1006, Charlotte, NC 28201-1006 Z
Facility Representative Address
#F-0566
NC PE Firm License Number (if applicable effective May 1, 2009)
Revised 612009 °" ""�••••rr
/ II
/
I �I °\\\
o \ �\ \
\\\\\\\
\\ =1 J \ I I
I
\ I I I I
N 529,000
��
I 1 l
/ N 529,000
��\
01
((I � \�-- �� �
I \
I I
I 11 THE FOLLOWING FORCE MAIN PIPING
I I
00
,—
II
�_ _
-�� � J_
I
/ / \ v
=—=�, /l \\��� � ��/ I J )
1 ARE - - -
IONVIDWG.SALNOOACV-C SIA.ALO-CV
IIII
I
W
/�//
/Q�///
/
__=
//� �l_
\\ /� W
' I �\ \/ // `�
�r- --- �\ �� / WI
I I DWG. ALN00-PY-P-UP.00.PL-529 OF
ALLEN STEAM STATION'S WATER
1 IIII REDIRECTION PROGRAM. TO SEE THE
FORCE MAIN PIPES REACH THE COAL
YARD SUMP NORTH OF THE LANDFILL,
REFER TO DWG.
% I
00 \ \ J /
-� -�\
/�j
ALN00-PY-P-UP.00.PL-526 OF THE
STEAMALLEN REDI ECTIONPROGRAM. WATER
III
► I II / /,
\\\\\ \��
\ �
I
I
\\\\\\
L
NEW 6" DIA. SDR 11
PCOALFORCE A IN
1 I I I
I I I
\\ \ 1 \
If
f
YARD
TOSUMP
SEEDWG
I II ALN00-PY.P-UP.00.PL-529
I
I
/,
II IIII
III I
\ I IT I I
) I
/� ��\\ \\
\\\\
�.��_�—==
\ �_� _ _ = _ _ =
I
S 24' HAUL
� � ==RERE
0-_�—ROADrROD
III IIIII
N 528,500
N 528,500
IIIII
EXISTING
I II I
STRUCTURAL
FILLIII
III I III
IIII
II IIII
I I
IIII I
/ III
1 III I
�
�'
I
I
III
I Irl I
II IIII
/ I III
IIIII
/ IIIII
I
i
�
Ilo
2 LEACHATE FOICEIIAIN
I I D TRENCH (TYP.)
II I I IIIIII
I
IIII
I l
III
� IIII
I
I
�
�I
, II I III I\ I IIIII
III I
IIIIIIII
III Jill
I I I I
I II
IIII
II
1. IIIII
I w
I I
I I I
I III^N
x
I (I
I
S I
S11
I I I I IIIIII � I IIIII
I I II I NEW 6" DIAMETER
IIII II SDR 11 HDPE FORCE MAIN
I I I III III PER DWG ALN00-CV-C-51.AL-511
I11�
III;
s9
� III
III
1 II\
I I \
_
/J
\ I
\ Il z
I�
t ,,LC650 3
! I
i l IIIIII II
III I
III�II
IiI� IL
IIXI
III
II
CELL 4
(10.6 AC) / I
II
I IIIIIIIIIII
3 ERIMETI—IIII
M
528,000
IIII IIIIIIIIIII
ASE 2N
D1 N 528,000
— 640_ ] 2//
Y
I
I II I
I
E 2
A 1
OP EL
SS I
I I I HH�A
630--
0
,I►IIIIIIII
IIIIIIII
II I
III III
�
.
III
I I I II I
I
I
�
�,
III II II
�
II I
s9
IIIII
I I III II III I
III I I�
\ I
I
�
0
0
IIIII
IIIII II
II I IIIIII II I
�
I I
I I III II I III I
PERIMETER BERM
CASE 2
EL
(12.8 AC) o
,IIIII
it ll l IIII I II
IIII I II
�
I
CELL ,
I I I I I I I I
I IIIIII I II
\
� I
(10.7 AC)
I
IIIII I I
I I IIIII � IIIII
� I �
I
III IIIII IIIII
� I
' 10
III I
IIII IIIII I II II
I
IIIII III
N 527,500
I
I 11 I III N 527,500
_
II
I �a I �
JI
it
AJ,III
I
III III
III JIII
11 I III
I
II II I I I
i 1
I I I I I
II IIIII
__ I I
I
I
I
I I III
II II II
IIII III I II
I
I
\ I W
a
20 ��I
D5 HOUSE
I
IIIII I II I
<IIIII III
I IIIIII I I I►I
I I
I
I .I
IIII LEGEND
/
II I
EXISTING GRADE CONTOUR
IIII I
III
II/I►///
EXISTING
RISERS
630
_
I
U J/I/ J/
M EL 613'
II/II�//I/IPROPOSED GRADE CONTOUR
(SEE NOTE 1)CMP
PERIMETER BERM CONTOURSB
22 LEAHATE FORCEMAIN
D5 TRENCH (TYP.)
� TI
//)II
�I
(SEE DETAIL CASE 2)
LEACHATE FORCE MAIN
HOUSE
�
EXISTING 36' CMP
\ \ -�
N 527 000
0 RCP BARRELS
1. PROTECTIVE COVER CONTOURS REPRESENT TOP OF
\
EDGE OF EXISTING
/ / B�K
,.
__-
_ - 630 — — _�
RMtd— - -- --
=��
—_
FORCE MAI
III I ((( f
11
OUTLET \\ I IIII
/ PROTECTIVE COVER CONTOURS.
REFERENCE:
O
=
ABANDONED JANU
RY �9
I J
TOPOGRAPHIC MAP FROM AERIALPHOTOGRAPHY
PERFORMED ON APRIL 2, 2006. PROVIDED BY NOVAO
SURVEYING AND MAPPING, INC..O
O
cl�
Lo
^
PI S
,00 o So ,00 200
1-4
—
w
I
t
EXISTING A BASIN
W.E. V IESII
- I
III
\ — I I IIIIII III
I I ( IN FEET )
I
_
I I
r
O
LLI
0
U
U
z_
LLJ
u�
;x I
D
cn
m
Q
L
Z
O
�
w
w
tY
U
cn
w
0
w
J
J
w
0
z
Q
J
0
N
\
w
Q
Ln
a
o
LL
z
0
�
Q
� z
z c/-)
u J
_-:5
�
w Q
U
CD
m
Q
z =
LLJ
J ~
� z
z
I
o
(-D z
=
cn
Q
z O
LL
Lw J
w LIJ
m
Lr-
L_I _I
11-1
DRAWN BY:
CHECKED BY:
CLD
KRD
DESIGNED BY:
APPROVED BY:
CFS
PROJECT NUMBER
1356-06-825
SCALE:
DATE:
1" = 100'
3-12-08
DRAWING:
OF:
C14. 1
24
N
/
z
0
C)
U
In
O
Ld
0
a
i
J
3
z
z
Ir
Table 1
Notes:
Allen Steam Station
Retired Ash Basin (RAB) Ash Landfill (Permit No. 36-12)
Leachate Analytical Data
Constituent
Analytical Result
(µg/L unless otherwise noted)
August 31, 2021
Cell 1
Cell 2
Antimony
< 0.104
< 0.104
Arsenic
34.0
75.0
Barium
33
34
Beryllium
1.54
1.65
Boron
68,200
172,000
Cadmium
4.98
1.24
Chloride
110 mg/L
150 mg/L
Chromium
3 J
3 J
Cobalt
1,130
917
Copper
0.121 mg/L
0.030 mg/L
Fluoride
1 J mg/L
1.7 J mg/L
Iron
66
14
Lead
1.23
0.39 J
Manganese
14,700
15,900
Mercury
0.07
0.05 J
Nickel
529
76
Nitrate (as N)
54 mg-N/L
26 mg-N/L
pH
4.62 S.U.
4.53 S.U.
Selenium
31.2
138
Silver
0.05 J
0.054 J
Sulfate
4,000 mg/L
2,900 mg/L
Temperature (°C)
24.0 °C
23.0 °C
TDS
6,100 mg/L
5,080 mg/L
Thallium
10.6
2.25
Vanadium
0.843
0.374
Zinc
0.475 mg/L
0.118 mg/L
µg/L = micrograms per liter
mg/L = milligrams per liter
mg-N/L = milligrams of Nitrogen per liter
S.U. = standard units
.0 = degrees Celcius
Attachment 1
Allen Retired Ash Basin (RAB) Ash Landfill
Semi -Annual Monitoring Event
Leachate Analytical Results
DUE Analytical Laboratory
ENERGY
Y
13339 Hagers Ferry Road
Huntersville, NC 28078-7929
McGuire Nuclear Complex - MG03A2
Phone:980-875-5245 Fax:980-875-4349
Order Summary Report
Order Number: J21080226
Project Name: ALLEN - GW LEACHATE
Task Code: LCS
Customer Name(s): C Murphy, R Gantt,D O Brien, B Moeller, J Stowe
Customer Address: Allen Steam Station
253 Plant Allen Road
Belmont, NC 28012
Lab Contact: Peggy Kendall Phone: 980-875-5848
Report (Signature)
Authorized By: Pee, � pats; 9/16/2021
Si nature
Pe y dall
Program Comments:
QC Note:
Page 1 of 30
LCS_CELL-1 Hg MS/MSD recoveries fell below the QC limits. The blank and LCS were within the control limits. The sample
result should be considered an estimate.
Nitrate (0.28 mg/L) and boron (0.125 mg/L) were detected in the field blank.
Data Flags & Calculations:
Any analytical tests or individual analytes within a test flagged with a Qualifier indicate a deviation from the method quality
system or quality control requirement. The qualifier description is found at the end of the Certificate of Analysis (sample results)
under the qualifiers heading. All results are reported on a dry weight basis unless otherwise noted. Subcontracted data
included on the Duke Certificate of Analysis is to be used as information only. Certified vendor results can be found in the
subcontracted lab final report. Duke Energy Analytical Laboratory subcontracts analyses to other vendor laboratories that have
been qualified by Duke Energy to perform these analyses except where noted.
Data Package:
This data package includes analytical results that are applicable only to the samples described in this narrative. An estimation of
the uncertainty of measurement for the results in the report is available upon request. This report shall not be reproduced, except
in full, without the written consent of the Analytical Laboratory. Please contact the Analytical laboratory with any questions. The
order of individual sections within this report is as follows:
Job Summary Report, Sample Identification, Technical Validation of Data Package, Analytical Laboratory Certificate of Analysis,
Analytical Laboratory QC Reports, Sub -contracted Laboratory Results, Customer Specific Data Sheets, Reports &
Documentation, Customer Database Entries, Test Case Narratives, Chain of Custody (COC)
Certification:
The Analytical Laboratory holds the following State Certifications : North Carolina (DENR) Certificate #248, South Carolina
(DHEC) Laboratory ID # 99005. Contact the Analytical Laboratory for definitive information about the certification status of
specific methods.
Sample ID's & Descriptions:
Collection
Sample ID Plant/Station Date and Time Collected By
2021022099 ALLEN
31-Aug-21 3:16 PM
2021022100 ALLEN
31-Aug-21 3:21 PM
2021022101 ALLEN
31-Aug-21 3:25 PM
3 Total Samples
Page 2 of 30
Sample Description
Connor Zahora
ALN_LCS-CELL1
Connor Zahora
ALN_LCS-CELL2
Connor Zahora
ALN FB-20210831-1525
Page 3 of 30
Technical Validation Review
Checklist:
COC and .pdf report are in agreement with sample totals❑ Yes ❑ No
and analyses (compliance programs and procedures).
All Results are less than the laboratory reporting limits. ❑ Yes❑ No
All laboratory QA/QC requirements are acceptable. 0 Yes ❑ No
Report Sections Included:
d❑ Job Summary Report
❑ Sample Identification
❑ Technical Validation of Data Package
d❑ Analytical Laboratory Certificate of Analysis
❑ Analytical Laboratory QC Report
❑ Sub -contracted Laboratory Results
❑ Customer Specific Data Sheets, Reports, & Documentation
❑ Customer Database Entries
❑ Chain of Custody
❑ Electronic Data Deliverable (EDD) Sent Separately
Reviewed By: Peggy Kendall Date: 9/16/2021
Certificate of Laboratory Analysis Page 4 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Site: ALN LCS-CELL1
Sample #:
2021022099
Collection Date: 08/31/2021
03:16 PM
Loc code: ALN LCS-CELL1
Matrix:
GW RCRA
Analyte
Result
Units
Qualifiers RDL
MDL
DF
Method
Analysis Date/Time
Analyst
INORGANIC IONS BY IC - Q21090005
Chloride
110
mg/L
5
0.0154
50
EPA 9056A
09/01/2021 09:14
BGN9034
Fluoride
1 J
mg/L
5
0.0479
50
EPA 9056A
09/01/2021 09:14
BGN9034
Nitrate
240
mg/L
5
0.0209
50
EPA 9056A
09/01/2021 09:14
BGN9034
Nitrate as N
54
mg-N/L
1.15
0.002
50
EPA 9056A
09/01/2021 09:14
BGN9034
Sulfate
4000
mg/L
100
0.0428
1000
EPA 9056A
09/01/2021 09:14
BGN9034
MERCURY (COLD VAPOR) IN WATER - Q21090158
Mercury (Hg) 0.07 ug/L M 0.05
TOTAL RECOVERABLE METALS BY ICP - Q21090029
0.01 1 EPA 7470A 09/14/2021 09:20 JAA5429
Barium (Ba)
0.033
mg/L
0.005
0.002
Boron (B)
68.2
mg/L
2.5
0.005
Chromium (Cr)
0.003 J
mg/L
0.005
0.001
Copper (Cu)
0.121
mg/L
0.005
0.001
Iron (Fe)
0.066
mg/L
0.01
0.004
Manganese (Mn)
14.7
mg/L
0.005
0.001
Nickel (Ni)
0.529
mg/L
0.005
0.001
Zinc (Zn)
0.475
mg/L
0.005
0.004
TOTAL RECOVERABLE METALS BY ICP-MS - Q21090035
Antimony (Sb)
0.104 U
ug/L
1
Arsenic (As)
34.0
ug/L
1
Beryllium (Be)
1.54
ug/L
1
Cadmium (Cd)
4.98
ug/L
1
Cobalt (Co)
1130
ug/L
20
Lead (Pb)
1.23
ug/L
1
Selenium (Se)
31.2
ug/L
1
Silver (Ag)
0.05 J
ug/L
1
Thallium (TI) Low Level
10.6
ug/L
0.2
Vanadium (V) Low Level
0.843
ug/L
0.3
TOTAL DISSOLVED SOLIDS
- (Analvsis Performed by
Pace Laboratories)
1 SW 6010D
09/02/2021 17:44
DMFRANC
50 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
1 SW 6010D
09/02/2021 17:44
DMFRANC
0.104
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.111
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.249
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.032
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.077
20
SW 6020B
09/09/2021 01:19
CWSPEN3
0.037
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.193
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.035
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.041
1
SW 6020B
09/09/2021 01:19
CWSPEN3
0.114
1
SW 6020B
09/09/2021 01:19
CWSPEN3
Vendor Parameter Complete Vendor Method V_PACE
Certificate of Laboratory Analysis Page 5 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Site: ALN LCS-CELL2
Sample #:
2021022100
Collection Date: 08/31/2021
03:21 PM
Loc code: ALN LCS-CELL2
Matrix:
GW RCRA
Analyte
Result
Units
Qualifiers RDL
MDL
DF
Method
Analysis Date/Time
Analyst
INORGANIC IONS BY IC - Q21090005
Chloride
150
mg/L
5
0.0154
50
EPA 9056A
09/01/2021 09:29
BGN9034
Fluoride
1.7 J
mg/L
5
0.0479
50
EPA 9056A
09/01/2021 09:29
BGN9034
Nitrate
120
mg/L
5
0.0209
50
EPA 9056A
09/01/2021 09:29
BGN9034
Nitrate as N
26
mg-N/L
1.15
0.002
50
EPA 9056A
09/01/2021 09:29
BGN9034
Sulfate
2900
mg/L
100
0.0428
1000
EPA 9056A
09/01/2021 09:29
BGN9034
MERCURY (COLD VAPOR) IN WATER - Q21090158
Mercury (Hg) 0.05 J ug/L 0.05
TOTAL RECOVERABLE METALS BY ICP - Q21090029
0.01 1 EPA 7470A 09/14/2021 09:27 JAA5429
Barium (Ba)
0.034
mg/L
0.005
0.002
Boron (B)
172
mg/L
2.5
0.005
Chromium (Cr)
0.003 J
mg/L
0.005
0.001
Copper (Cu)
0.030
mg/L
0.005
0.001
Iron (Fe)
0.014
mg/L
0.01
0.004
Manganese (Mn)
15.9
mg/L
0.005
0.001
Nickel (Ni)
0.076
mg/L
0.005
0.001
Zinc (Zn)
0.118
mg/L
0.005
0.004
TOTAL RECOVERABLE METALS BY ICP-MS - Q21090035
Antimony (Sb)
0.104 U
ug/L
1
Arsenic (As)
75.0
ug/L
1
Beryllium (Be)
1.65
ug/L
1
Cadmium (Cd)
1.24
ug/L
1
Cobalt (Co)
917
ug/L
20
Lead (Pb)
0.39 J
ug/L
1
Selenium (Se)
138
ug/L
1
Silver (Ag)
0.054 J
ug/L
1
Thallium (TI) Low Level
2.25
ug/L
0.2
Vanadium (V) Low Level
0.374
ug/L
0.3
TOTAL DISSOLVED SOLIDS
- (Analvsis Performed by
Pace Laboratories)
1 SW 6010D
09/02/2021 17:48
DMFRANC
50 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
1 SW 6010D
09/02/2021 17:48
DMFRANC
0.104
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.111
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.249
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.032
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.077
20
SW 6020B
09/09/2021 01:28
CWSPEN3
0.037
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.193
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.035
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.041
1
SW 6020B
09/09/2021 01:28
CWSPEN3
0.114
1
SW 6020B
09/09/2021 01:28
CWSPEN3
Vendor Parameter Complete Vendor Method V_PACE
Certificate of Laboratory Analysis Page 6 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Site: ALN
FB-20210831-1525
Field Blank
Sample #:
2021022101
Collection Date:
08/31/2021 03:25 PM
Loc code: ALN
QA
Matrix:
GW RCRA
Analyte
Result
Units
Qualifiers RDL
MDL
DF
Method
Analysis Date/Time
Analyst
INORGANIC IONS BY IC - Q21090005
Chloride
0.03 J
mg/L
0.1
0.0154
1
EPA 9056A
09/01/2021 08:59
BGN9034
Fluoride
0.0479 U
mg/L
0.1
0.0479
1
EPA 9056A
09/01/2021 08:59
BGN9034
Nitrate
0.28
mg/L
0.1
0.0209
1
EPA 9056A
09/01/2021 08:59
BGN9034
Nitrate as N
0.06
mg-N/L
0.023
0.002
1
EPA 9056A
09/01/2021 08:59
BGN9034
Sulfate
0.0428 U
mg/L
0.1
0.0428
1
EPA 9056A
09/01/2021 08:59
BGN9034
MERCURY (COLD VAPOR) IN WATER - Q21090158
Mercury (Hg) 0.01 U ug/L 0.05
TOTAL RECOVERABLE METALS BY ICP - Q21090029
0.01 1 EPA 7470A 09/14/2021 09:29 JAA5429
Barium (Ba)
0.002 U
mg/L
0.005
0.002
Boron (B)
0.125
mg/L
0.05
0.005
Chromium (Cr)
0.001 U
mg/L
0.005
0.001
Copper (Cu)
0.001 U
mg/L
0.005
0.001
Iron (Fe)
0.004 U
mg/L
0.01
0.004
Manganese (Mn)
0.001 U
mg/L
0.005
0.001
Nickel (Ni)
0.001 U
mg/L
0.005
0.001
Zinc (Zn)
0.004 U
mg/L
0.005
0.004
TOTAL RECOVERABLE METALS BY ICP-MS - Q21090035
Antimony (Sb)
0.104 U
ug/L
1
Arsenic (As)
0.111 U
ug/L
1
Beryllium (Be)
0.249 U
ug/L
1
Cadmium (Cd)
0.032 U
ug/L
1
Cobalt (Co)
0.077 U
ug/L
1
Lead (Pb)
0.037 U
ug/L
1
Selenium (Se)
0.193 U
ug/L
1
Silver (Ag)
0.035 U
ug/L
1
Thallium (TI) Low Level
0.041 U
ug/L
0.2
Vanadium (V) Low Level
0.12 J
ug/L
0.3
TOTAL DISSOLVED SOLIDS
- (Analvsis Performed by
Pace Laboratories)
Vendor Parameter Complete
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
1 SW 6010D
09/02/2021 17:53
DMFRANC
0.104
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.111
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.249
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.032
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.077
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.037
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.193
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.035
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.041
1
SW 6020B
09/09/2021 13:47
CWSPEN3
0.114
1
SW 6020B
09/09/2021 13:47
CWSPEN3
Vendor Method
Qualifiers:
J Analyte detected above the MDL, but below the RL. Analyte concentration should be considered an estimate.
M Matrix Spike and/or Matrix Spike Duplicate recovery was outside of the control limits. The associated Laboratory Control
Spike (LCS) recovery was acceptable.
V_PACE
Certificate of Laboratory Analysis Page 7 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090005 Dionex INORGANIC IONS BY IC
Blank # 1
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Chloride
0
0
mg/L
1
0.0154
0.1
< MDL
Fluoride
0
0
mg/L
1
0.0479
0.1
< MDL
Nitrate
0
0
mg/L
1
0.0209
0.1
< MDL
Sulfate
0.002
0.002
mg/L
1
0.0428
0.1
< MDL
LCS # 1
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL
UCL
Qualifier
Chloride
1.95
1.95
mg/L
1
0.0154
2
97.6
90
110
Fluoride
1.99
1.99
mg/L
1
0.0479
2
99.4
90
110
Nitrate
2
2
mg/L
1
0.0209
2
99.8
90
110
Sulfate
1.86
1.86
mg/L
1
0.0428
2
93
90
110
MS # 1
Parent Sample:
J21070163 -- 2021018728
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery
LCL
UCL
Qualifier
Chloride
6.67
33.3
mg/L
5
0.0154
10
91.5
80
120
Fluoride
1.94
9.69
mg/L
5
0.0479
10
95.5
80
120
Nitrate
1.9
9.51
mg/L
5
0.0209
10
92.8
80
120
Sulfate
5.21
26
mg/L
5
0.0428
10
90.4
80
120
MSD # 1
Parent Sample:
J21070163 -- 2021018728
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery
LCL
UCL
RPD
Qualifier
Chloride
6.67
33.3
mg/L
5
0.0154
10
91.6
80
120
0.0983
Fluoride
1.94
9.72
mg/L
5
0.0479
10
95.8
80
120
0.356
Nitrate
1.91
9.55
mg/L
5
0.0209
10
93.3
80
120
0.462
Sulfate
5.2
26
mg/L
5
0.0428
10
90.4
80
120
0.0774
Certificate of Laboratory Analysis Page 8 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090158 HG 7470 MERCURY (COLD VAPOR) IN WATER
Blank # 1
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.018
0.018
ug/L
1
0.01
0.05
> MDL
Blank # 2
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.004
0.004
ug/L
1
0.01
0.05
< MDL
Blank # 3
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.003
0.003
ug/L
1
0.01
0.05
< MDL
Blank # 4
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.009
0.009
ug/L
1
0.01
0.05
< MDL
Blank # 5
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.002
0.002
ug/L
1
0.01
0.05
< MDL
Blank # 6
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.022
0.022
ug/L
1
0.01
0.05
> MDL
Blank # 7
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Qualifier
Mercury (Hg)
0.021
0.021
ug/L
1
0.01
0.05
> MDL
LCS # 1
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery LCL
UCL
Qualifier
Mercury (Hg)
1.84
1.84
ug/L
1
0.01
2
92.3 85
115
LCS # 2
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery LCL
UCL
Qualifier
Mercury (Hg)
1.92
1.92
ug/L
1
0.01
2
96 85
115
LCS # 3
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery LCL
UCL
Qualifier
Mercury (Hg)
1.95
1.95
ug/L
1
0.01
2
97.3 85
115
MS # 1
Parent Sample: J21080226 -- 2021022099
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery LCL
UCL
Qualifier
Mercury (Hg)
0.297
0.297
ug/L
1
0.01
1
22.8 75
125
M
Certificate of Laboratory Analysis Page 9 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090158 HG 7470 MERCURY (COLD VAPOR) IN WATER
MSD # 1
Parent Sample:
J21080226 -- 2021022099
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
0.298
0.298
ug/L
1
0.01
1
22.9
75 125 0.438
M
MS # 2
Parent Sample:
J21090002 -- 2021024366
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL
Qualifier
Mercury (Hg)
0.949
0.949
ug/L
1
0.01
1
93.5
75 125
MSD # 2
Parent Sample:
J21090002 -- 2021024366
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
0.947
0.947
ug/L
1
0.01
1
93.3
75 125 0.214
MS # 3
Parent Sample:
J21090027 -- 2021024515
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL
Qualifier
Mercury (Hg)
1.28
1.28
ug/L
1
0.01
1
102
75 125
MSD # 3
Parent Sample:
J21090027 -- 2021024515
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
1.32
1.32
ug/L
1
0.01
1
106
75 125 3.08
MS # 4
Parent Sample:
J21090027 -- 2021024525
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL
Qualifier
Mercury (Hg)
1
1
ug/L
1
0.01
1
97.5
75 125
MSD # 4
Parent Sample:
J21090027 -- 2021024525
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
1
1
ug/L
1
0.01
1
97.4
75 125 0.103
MS # 5
Parent Sample:
J21090027 -- 2021024535
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL
Qualifier
Mercury (Hg)
1.09
1.09
ug/L
1
0.01
1
108
75 125
MSD # 5
Parent Sample:
J21090027 -- 2021024535
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
1.3
1.3
ug/L
1
0.01
1
129
75 125 17.7
M
MS # 6
Parent Sample:
J21090027 -- 2021024545
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL
Qualifier
Mercury (Hg)
1.14
1.14
ug/L
1
0.01
1
113
75 125
MSD # 6
Parent Sample:
J21090027 -- 2021024545
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL UCL RPD
Qualifier
Mercury (Hg)
1.15
1.15
ug/L
1
0.01
1
114
75 125 0.885
Certificate of Laboratory Analysis Page 10 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090158 HG 7470 MERCURY (COLD VAPOR) IN WATER
Qualifiers:
M Matrix Spike and/or Matrix Spike Duplicate recovery was outside of the control limits. The associated
Laboratory Control Spike (LCS) recovery was acceptable.
Certificate of Laboratory Analysis
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090029 1CP_TRM TOTAL RECOVERABLE METALS BY ICP
Blank # 1
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Barium (Ba)
-0.000314
-0.000314
mg/L
1
0.002
0.005
< MDL
Boron (B)
0.0016
0.0016
mg/L
1
0.005
0.05
< MDL
Chromium (Cr)
0.000271
0.000271
mg/L
1
0.001
0.005
< MDL
Copper (Cu)
-0.00178
-0.00178
mg/L
1
0.001
0.005
< MDL
Iron (Fe)
0.0018
0.0018
mg/L
1
0.004
0.01
< MDL
Manganese (Mn)
-0.000094
-0.000094
mg/L
1
0.001
0.005
< MDL
Nickel (Ni)
-0.000715
-0.000715
mg/L
1
0.001
0.005
< MDL
Zinc (Zn)
-0.000677
-0.000677
mg/L
1
0.004
0.005
< MDL
LCS # 1
Page 11 of 30
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL
UCL
Barium (Ba)
5.02
5.02
mg/L
1
0.002
5
100
80
120
Boron (B)
4.9
4.9
mg/L
1
0.005
5
98
80
120
Chromium (Cr)
4.94
4.94
mg/L
1
0.001
5
98.9
80
120
Copper (Cu)
4.9
4.9
mg/L
1
0.001
5
97.9
80
120
Iron (Fe)
5
5
mg/L
1
0.004
5
99.9
80
120
Manganese (Mn)
4.99
4.99
mg/L
1
0.001
5
99.9
80
120
Nickel (Ni)
5.06
5.06
mg/L
1
0.001
5
101
80
120
Zinc (Zn)
5.08
5.08
mg/L
1
0.004
5
102
80
120
MS # 1
Parent Sample:
J21090002
-- 2021024358
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL
UCL
Barium (Ba)
5.22
5.22
mg/L
1
0.002
5
104
75
125
Boron (B)
5.13
5.13
mg/L
1
0.005
5
103
75
125
Chromium (Cr)
5.06
5.06
mg/L
1
0.001
5
101
75
125
Copper (Cu)
5.06
5.06
mg/L
1
0.001
5
101
75
125
Iron (Fe)
5.62
5.62
mg/L
1
0.004
5
103
75
125
Manganese (Mn)
15.4
15.4
mg/L
1
0.001
5
105
75
125
Nickel (Ni)
5.09
5.09
mg/L
1
0.001
5
102
75
125
Zinc (Zn)
5.09
5.09
mg/L
1
0.004
5
102
75
125
MSD # 1
Parent Sample:
J21090002
-- 2021024358
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery
LCL
UCL
RPD
Barium (Ba)
5.08
5.08
mg/L
1
0.002
5
101
75
125
2.68
Boron (B)
5.05
5.05
mg/L
1
0.005
5
101
75
125
1.65
Chromium (Cr)
4.95
4.95
mg/L
1
0.001
5
99
75
125
2.2
Copper (Cu)
4.94
4.94
mg/L
1
0.001
5
98.9
75
125
2.38
Iron (Fe)
5.5
5.5
mg/L
1
0.004
5
101
75
125
2.09
Manganese (Mn)
15.1
15.1
mg/L
1
0.001
5
99.2
75
125
1.96
Nickel (Ni)
4.99
4.99
mg/L
1
0.001
5
99.6
75
125
2.02
Qualifier
Qualifier
Qualifier
Qualifier
Certificate of Laboratory Analysis Page 12 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090029 ICP_TRM TOTAL RECOVERABLE METALS BY ICP
MSD # 1 Parent Sample: J21090002 -- 2021024358
Parameter Measured Final Units Dil MDL Spike % Recovery LCL UCL RPD Qualifier
Zinc (Zn) 5.01 5.01 mg/L 1 0.004 5 100 75 125 1.62
Certificate of Laboratory Analysis Page 13 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090035 IMS_TRM TOTAL RECOVERABLE METALS BY ICP-MS
Blank # 1
Parameter
Measured
Final
Units
Dil
MDL
RDL
Relative Concentration
Antimony (Sb)
-0.066
-0.066
ug/L
1
0.104
1
< MDL
Arsenic (As)
0.025
0.025
ug/L
1
0.111
1
< MDL
Beryllium (Be)
-0.03
-0.03
ug/L
1
0.249
1
< MDL
Cadmium (Cd)
0.001
0.001
ug/L
1
0.032
1
< MDL
Cobalt (Co)
0.004
0.004
ug/L
1
0.077
1
< MDL
Lead (Pb)
0.009
0.009
ug/L
1
0.037
1
< MDL
Selenium (Se)
0.013
0.013
ug/L
1
0.193
1
< MDL
Silver (Ag)
0.003
0.003
ug/L
1
0.035
1
< MDL
Thallium (TI) Low Level
0.025
0.025
ug/L
1
0.041
0.2
< MDL
Vanadium (V) Low Level
0.061
0.061
ug/L
1
0.114
0.3
< MDL
LCS # 1
Parameter
Measured
Final
Units
Dil
MDL
S ike
% Recovery
LCL
UCL
Antimony (Sb)
49.1
49.1
ug/L
1
0.104
50
98.2
80
120
Arsenic (As)
49.1
49.1
ug/L
1
0.111
50
98.1
80
120
Beryllium (Be)
49.6
49.6
ug/L
1
0.249
50
99.2
80
120
Cadmium (Cd)
49.1
49.1
ug/L
1
0.032
50
98.3
80
120
Cobalt (Co)
49.3
49.3
ug/L
1
0.077
50
98.7
80
120
Lead (Pb)
48.7
48.7
ug/L
1
0.037
50
97.3
80
120
Selenium (Se)
48.1
48.1
ug/L
1
0.193
50
96.2
80
120
Silver (Ag)
49.3
49.3
ug/L
1
0.035
50
98.6
80
120
Thallium (TI) Low Level
46.5
46.5
ug/L
1
0.041
50
93
80
120
Vanadium (V) Low Level
48.3
48.3
ug/L
1
0.114
50
96.7
80
120
MS # 1
Parent Sample:
J21090002 -- 2021024360
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL
UCL
Antimony (Sb)
49.6
49.6
ug/L
1
0.104
50
99.2
75
125
Arsenic (As)
50
50
ug/L
1
0.111
50
98.9
75
125
Beryllium (Be)
48.6
48.6
ug/L
1
0.249
50
95.7
75
125
Cadmium (Cd)
48.4
48.4
ug/L
1
0.032
50
96.2
75
125
Cobalt (Co)
61.9
61.9
ug/L
1
0.077
50
95.2
75
125
Lead (Pb)
48.5
48.5
ug/L
1
0.037
50
96.9
75
125
Selenium (Se)
47.5
47.5
ug/L
1
0.193
50
93.7
75
125
Silver (Ag)
47.9
47.9
ug/L
1
0.035
50
95.7
75
125
Thallium (TI) Low Level
44
44
ug/L
1
0.041
50
87.7
75
125
Vanadium (V) Low Level
49.4
49.4
ug/L
1
0.114
50
97.5
75
125
MSD # 1
Parent Sample:
J21090002 -- 2021024360
Parameter
Measured
Final
Units
Dil
MDL
Spike
% Recovery
LCL
UCL RPD
Antimony (Sb)
49.5
49.5
ug/L
1
0.104
50
98.9
75
125 0.309
Qualifier
Qualifier
Qualifier
Qualifier
Certificate of Laboratory Analysis Page 14 of 30
This report shall not be reproduced, except in full.
Order # J21080226
Level II QC Summary
Q21090035 IMS_TRM TOTAL RECOVERABLE METALS BY ICP-MS
MSD # 1
Parameter
Measured
Final
Units
Dil
MDL
Arsenic (As)
50.9
50.9
ug/L
1
0.111
Beryllium (Be)
48.8
48.8
ug/L
1
0.249
Cadmium (Cd)
48.9
48.9
ug/L
1
0.032
Cobalt (Co)
62.3
62.3
ug/L
1
0.077
Lead (Pb)
48.7
48.7
ug/L
1
0.037
Selenium (Se)
48.5
48.5
ug/L
1
0.193
Silver (Ag)
48.2
48.2
ug/L
1
0.035
Thallium (TI) Low Level
45.1
45.1
ug/L
1
0.041
Vanadium (V) Low Level
49.8
49.8
ug/L
1
0.114
Parent Sample:
J21090002 -- 2021024360
Spike
% Recovery
LCL
UCL
RPD
50
101
75
125
1.75
50
96.1
75
125
0.463
50
97.1
75
125
0.958
50
96.1
75
125
0.893
50
97.3
75
125
0.484
50
95.7
75
125
2.14
50
96.4
75
125
0.716
50
89.8
75
125
2.31
50
98.2
75
125
0.771
Qualifier
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
0g8pipocfrke. Suite 100
�J Huntersville, NC 28078
(704)875-9092
September 09, 2021
Program Manager
Duke Energy
13339 Hagers Ferry Road
Bldg.7405 MG30A2
Huntersville, NC 28078
RE: Project: J21080226 ALN LCS
Pace Project No.: 92558935
Dear Program Manager:
Enclosed are the analytical results for sample(s) received by the laboratory on September 01, 2021. The results relate only
to the samples included in this report. Results reported herein conform to the applicable TNI/NELAC Standards and the
laboratory's Quality Manual, where applicable, unless otherwise noted in the body of the report.
The test results provided in this final report were generated by each of the following laboratories within the Pace Network:
• Pace Analytical Services - Asheville
If you have any questions concerning this report, please feel free to contact me.
Sincerely,
%D'a6-
Nicole D'Oleo
nicole.d'oleo@pacelabs.com
(704)875-9092
Project Manager
Enclosures
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 1 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
0g8piecfrke. Suite 100
�J Huntersville, NC 28078
(704)875-9092
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Pace Analytical Services Asheville
2225 Riverside Drive, Asheville, NC 28804
Florida/NELAP Certification #: E87648
North Carolina Drinking Water Certification #: 37712
CERTIFICATIONS
North Carolina Wastewater Certification #: 40
South Carolina Certification #: 99030001
Virginia/VELAP Certification #: 460222
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC. Page 2 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
�O�K�ice. Suite 100
�J Huntersville, NC 28078
(704)875-9092
SAMPLE SUMMARY
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Lab ID
Sample ID
Matrix
Date Collected
Date Received
92558935001
LCS-CELL1
Water
08/31/2115:16
09/01/2113:30
92558935002
LCS-CELL2
Water
08/31/2115:21
09/01/2113:30
92558935003
ALN FB-20210831-1525
Water
08/31/21 15:25
09/01/21 13:30
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 3 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
0g8pigcfrke. Suite 100
�J Huntersville, NC 28078
(704)875-9092
SAMPLE ANALYTE COUNT
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Analytes
Lab ID Sample ID
Method
Analysts
Reported
Laboratory
92558935001 LCS-CELL1
SM 2540C-2011
ZMC
1
PASI-A
92558935002 LCS-CELL2
SM 2540C-2011
ZMC
1
PASI-A
92558935003 ALN FB-20210831-1525
SM 2540C-2011
ZMC
1
PASI-A
PASI-A = Pace Analytical Services -Asheville
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC. Page 4 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
0g8pi§cfrke. Suite 100
�J Huntersville, NC 28078
(704)875-9092
SUMMARY OF DETECTION
Project:
Pace Project No.:
J21080226 ALN LCS
92558935
Lab Sample ID
Client Sample ID
Method
Parameters Result Units Report Limit Analyzed Qualifiers
92558935001
LCS-CELL1
SM 2540C-2011
Total Dissolved Solids 6100 mg/L 500 09/02/21 17:13
92558935002
LCS-CELL2
SM 2540C-2011
Total Dissolved Solids 5080 mg/L 417 09/02/21 17:13
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC. Page 5 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
og8� '6fke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
PROJECT NARRATIVE
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Method: SM 2540C-2011
Description: 2540C Total Dissolved Solids
Client: Duke Energy
Date: September 09, 2021
General Information:
3 samples were analyzed for SM 2540C-2011 by Pace Analytical Services Asheville. All samples were received in acceptable condition
with any exceptions noted below or on the chain -of custody and/or the sample condition upon receipt form (SCUR) attached at the end
of this report.
Hold Time:
The samples were analyzed within the method required hold times with any exceptions noted below.
Method Blank:
All analytes were below the report limit in the method blank, where applicable, with any exceptions noted below.
Laboratory Control Spike:
All laboratory control spike compounds were within QC limits with any exceptions noted below.
Matrix Spikes:
All percent recoveries and relative percent differences (RPDs) were within acceptance criteria with any exceptions noted below.
Duplicate Sample:
All duplicate sample results were within method acceptance criteria with any exceptions noted below.
Additional Comments:
This data package has been reviewed for quality and completeness and is approved for release.
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC. Page 6 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� �nlc6rke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
ANALYTICAL RESULTS
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Sample: LCS-CELL1 Lab ID: 92558935001 Collected: 08/31/21 15:16 Received: 09/01/21 13:30 Matrix: Water
Report
Parameters Results Units Limit MDL DF Prepared Analyzed CAS No. Qual
2540C Total Dissolved Solids Analytical Method: SM 2540C-2011
Pace Analytical Services -Asheville
Total Dissolved Solids 6100 mg/L 500 500 1 09/02/21 17:13
Date: 09/09/2021 01:41 PM
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 7 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� Q'6fke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
ANALYTICAL RESULTS
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Sample: LCS-CELL2 Lab ID: 92558935002 Collected: 08/31/21 15:21 Received: 09/01/21 13:30 Matrix: Water
Report
Parameters Results Units Limit MDL DF Prepared Analyzed CAS No. Qual
2540C Total Dissolved Solids Analytical Method: SM 2540C-2011
Pace Analytical Services -Asheville
Total Dissolved Solids 5080 mg/L 417 417 1 09/02/21 17:13
Date: 09/09/2021 01:41 PM
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 8 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� S'6fke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
ANALYTICAL RESULTS
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Sample: ALN_FB-20210831-1525 Lab ID: 92558935003 Collected: 08/31/21 15:25 Received: 09/01/21 13:30 Matrix: Water
Report
Parameters Results Units Limit MDL DF Prepared Analyzed CAS No. Qual
2540C Total Dissolved Solids Analytical Method: SM 2540C-2011
Pace Analytical Services -Asheville
Total Dissolved Solids ND mg/L 25.0 25.0 1 09/02/21 17:13
Date: 09/09/2021 01:41 PM
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 9 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� ,6fke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
QUALITY CONTROL DATA
Project: J21080226 ALN LCS
Pace Project No.: 92558935
QC Batch: 644890 Analysis Method: SM 2540C-2011
QC Batch Method: SM 2540C-2011 Analysis Description: 2540C Total Dissolved Solids
Laboratory: Pace Analytical Services -Asheville
Associated Lab Samples: 92558935001, 92558935002, 92558935003
METHOD BLANK: 3383303
Matrix:
Water
Associated Lab Samples: 92558935001, 92558935002, 92558935003
Blank
Reporting
Parameter
Units
Result
Limit
Total Dissolved Solids
mg/L
ND
25.0
LABORATORY CONTROL SAMPLE:
3383304
Spike
LCS
Parameter
Units
Conc.
Result
Total Dissolved Solids
mg/L
250
248
SAMPLE DUPLICATE: 3383305
92558820003 Dup
Parameter Units Result Result
Total Dissolved Solids mg/L 22000 21400
MDL Analyzed Qualifiers
25.0 09/02/2117:10
LCS % Rec
% Rec Limits Qualifiers
99 90-110
Max
RPD RPD Qualifiers
3 25
SAMPLE DUPLICATE: 3383306
92558905009 Dup Max
Parameter Units Result Result RPD RPD Qualifiers
Total Dissolved Solids mg/L 1940 1890 3 25
Results presented on this page are in the units indicated by the "Units" column except where an alternate unit is presented to the right of the result.
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
Date: 09/09/2021 01:41 PM without the written consent of Pace Analytical Services, LLC. Page 10 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� �poc6rke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
QUALIFIERS
Project: J21080226 ALN LCS
Pace Project No.: 92558935
DEFINITIONS
DF - Dilution Factor, if reported, represents the factor applied to the reported data due to dilution of the sample aliquot.
ND - Not Detected at or above adjusted reporting limit.
TNTC - Too Numerous To Count
J - Estimated concentration above the adjusted method detection limit and below the adjusted reporting limit.
MDL -Adjusted Method Detection Limit.
PQL - Practical Quantitation Limit.
RL - Reporting Limit - The lowest concentration value that meets project requirements for quantitative data with known precision and
bias for a specific analyte in a specific matrix.
S - Surrogate
1,2-Diphenylhydrazine decomposes to and cannot be separated from Azobenzene using Method 8270. The result for each analyte is
a combined concentration.
Consistent with EPA guidelines, unrounded data are displayed and have been used to calculate % recovery and RPD values.
LCS(D) - Laboratory Control Sample (Duplicate)
MS(D) - Matrix Spike (Duplicate)
DUP - Sample Duplicate
RPD - Relative Percent Difference
NC - Not Calculable.
SG - Silica Gel - Clean -Up
U - Indicates the compound was analyzed for, but not detected.
Acid preservation may not be appropriate for 2 Chloroethylvinyl ether.
A separate vial preserved to a pH of 4-5 is recommended in SW846 Chapter 4 for the analysis of Acrolein and Acrylonitrile by EPA
Method 8260.
N-Nitrosodiphenylamine decomposes and cannot be separated from Diphenylamine using Method 8270. The result reported for
each analyte is a combined concentration.
Reported results are not rounded until the final step prior to reporting. Therefore, calculated parameters that are typically reported as
"Total" may vary slightly from the sum of the reported component parameters.
Pace Analytical is TNI accredited. Contact your Pace PM for the current list of accredited analytes.
TN -The NELAC Institute.
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
Date: 09/09/2021 01:41 PM without the written consent of Pace Analytical Services, LLC. Page 11 of 15
leAnalyiical
www.pacelabs.com
Pace Analytical Services, LLC
Og8� '6fke. Suite 100
��JJ Huntersville, NC 28078
(704)875-9092
QUALITY CONTROL DATA CROSS REFERENCE TABLE
Project: J21080226 ALN LCS
Pace Project No.: 92558935
Lab ID
92558935001
92558935002
92558935003
Sample ID
LCS-CELL1
LCS-CELL2
ALN_FB-20210831-1525
Date: 09/09/2021 01:41 PM
QC Batch Method
QC Batch
SM 2540C-2011
644890
SM 2540C-2011
644890
SM 2540C-2011
644890
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Analytical
Analytical Method Batch
Page 12 of 15
Document Name:
Document Revised: October 28, 20Rge
Analytical'
%�
Sample Condition Upon Recei t(SCUR)
Page 1 of 2
Document No.:
Issuing Authority:
l
F-CAR-CS-033-Rev.07
Pace Carolinas Quality Office
7 of 30
Laboratory receiving samples:
Asheville ❑ Eden❑ Greenwood ❑ Huntersville 0 Raleigh❑ Mechanicsville(] Atlanta❑ Kernersville❑
Sample condition Client Name: _ 1 WO# : 92558935
Upon Receipt � � Project it.,
Courier: ❑Fed Ex [_]UPS ❑U5P5 []client
❑ Commercial ®Page ❑other: 92558935
I
Custody Seal Present? ❑Yes CTNo Seals Intact? ❑Yes QNo
Dale/lnitlaisPerson Examining Contents:
Packing Material: ❑Bubble Wrap ❑Bubble Bags ❑t None ❑ Other BlologicaI Tissue Frozen?
Thermometer: ❑Yes ❑Na (! N/A
Wet []Blue ❑None
ype a ce:
-� Correction Factor:
Cooler Temp: J SJ Add/Subtract (°C) C- ' Temp should be above Freezing to VC
[]Samples out of temp criteria. Samples on ire, cooling process
Cooler Temp Corrected (`Q > ' 3 I has begun
USDA Regulated Soil ( N/A, water sample)
Did samples originate in a quarantine zone within the United States: CA, NY, or SC (check maps)? Did samples originate From a foreign source (Internationally,
nf7
Yes 1 IN❑ inriiuiina Hawafi and Puwrfn Rirnl? MY— riNn
Comments/Discrepancy:
Chain of Custody Present?
[)NO
[]NIA
1.
Samples Arrived within Mold Time?
��[/Y""es
i_]ves
No
[]N/A
2.
Short Hold Time Analysis <72 hr.}?
❑Yes
N6.
❑N/A
3.
Rush Turn Around Time Requested?
[--]Yes
No
❑N/A
4.
Sufficient Volume?
es
❑Na
] N/A
5,
Correct Containers Used?
-Pace Containers Used?
(Yes
❑Ye5
❑N❑
NNo
❑N/A
❑N/A
6.
Containers Intact?
[Yes
❑No
❑N/A
7.
Dissolved analysis: Samples Field Filtered?
[-]Yes
❑No
/A
a.
Sample Labels Match COC?
-Includes Date/Time/ID/Analysis Matrix:
. Yes
1'
❑No
❑N/A
9.
Headspace in VOA Vials (>S-6mm)?
[]Yes
❑No
/A
10.
Trip Blank Present?
Trip Blank Custody Seals Present?
❑Yes
OYes
[]NO
❑No
MN/A
0N/A
11.
COMMENTS/SAMPLE DISCREPANCY
Lot ID of split containers:
Field Dafa Required? Des [-]NO
CLIENT NOTIFICATION/RESOLUTION � if 5, f _ S,�K— ( � G f F� 6 `1 �� �— /
Project Manager SCURF Review:
Project Manager SRF Review:
Date:
Date:
Page 13 of 15
ace Analytical'
Document Name:
Sample Condition Upon Recelpt(SCUR)
Document Revised: October 28, 2c0
Page 2 of 2 age
Document No.:
Issuing Authority:
F-CAR-CS-0334Rev.07
Pace Carolinas Quality Office
*Check mark top half of box if pH and/or dechlorination is
verified and within the acceptance range for preservation
samples.
Exceptions: VOA, Coliform, TOC, Oil and Grease, DRD/8015 (water) OOC, LLHg
**Bottom half of box is to list number of bottles
8 of 30
Project t# W0# : 92558935
PM: NMG Due Dale: 09 90 // Y1
CLIENT: 92-Duke Ener
zz
Z
41
a
c
>
ca
z
v
Ai
al
c
>
u
2
a
M
v
c
M
u
z
Z
N
r
u
N
v
?
v
Q
M
=
u
v
n
m
z
4
0
Z
etl
N
d
Qu
N
N
u
A
C
r
z
0
m
2
u
4
!r
r
m
y
.p
is
N
m
n
c
7
v
2
a
u
S
z
m
°'
.�.
a
v
T-
CL
O
ry
L
v
a
c
0
N
x
a
z
a
n
E
a
Q
z
u
z
m
'n
Q
Z
a
c
?
Z
v
O
m
Z
Y
N
m
o
^
Y
r`^a
=
o
>
Z
«u.
2
a
a
y
ai
p
ry
_
�
2
N
:
a
`
2
N
c
n
o
�9
y
a
c
E
w
a
J
E
v
d
m
a
J
E
m
s
m
a
J
E
N
a
m
3
a
m
.3+
a
m
a
8
a
rl
m
a
E
m
a
m
a
E
rN-{
d.
m
a
E
e
a
m
E
a
E
Q
`a
N
7
•�
Lo
C
E
Q
`a
n
S
r+
0
Q
Q
E
N
7
m
l7
Q
E
Q
`m
r1
IA
H
l7
4
Q
E
CD
N
N
rn
t7
Q
n
m
Q
m
l7
4
b
E
q
S
l�
0
}
E
R
F1
a.
C�
S
E
7
m
0
7
c
1
a
A
�
C
N
°
Y
Q
O
]
N
`"
Y
t7
�
7
-J
E
.y
a
rn
`
N
N
d
in
J
E
N
Q
m
d
m
E
o
o
Q
4
E
N
W
•,
}
4
J
E
Q
3
am
�7
O
'N
I
`
z
N\J
4
5
6
7
\\�\N
N
a
9
10
11
12
1
N1
N�\N
�11
I
INN
-I
pH Adjustment Log for Preserved Samples
Sample 10
Type of Preservative
pH upon receipt
Date preservation adjusted
Time preservation
adjusted
Amount of Preservative
added
Lot p
Note:-Wheneverthere-i$-a-discrepan cy dffectln&North-C-a ro Jim a-compli a nce-s am ples,�-dopy-0a this4orm-will-t)&senttadhedVOFth-6arolln&&JbMNn-6Lrtiiiratiop-uffice-(i.a. -
Out of hold, Incorrect preservative, out of temp, incorrect containers.
Page 14 of 15
- - - - - -- - - ....... - - -r
CHAIN OF CUSTODY RECORD AND ANALYSIS REQUEST FORM
- - - - --- _._, _._._. _. _.__
DUKE
Duke Energy AnaIyncaI Laboratory
M.e CuW Muaraz feull�me tiasl
. - - --.-.-....-------•- - -------- -- ----- _ -..._-.-..._. - - -- - - _
, i
AnalyticalLaborator Use
_ _-_.--_,_._._._ _ - - - 29 of 30
Page
ENERGY
ea> oH.a......ryna
Hure«enll.,
i ;order #
i; �T 2/� �.�j Matrix WATER
NC x Page , , of —1 p
_ _ _ _
k c zaore
pwl.rs.uu
_ _ _ _ _ c+.,J�o�Leisso�e-
/] S f Anln B TI
L-sa.dey p J �
K%� 1
yr Pc LAR UTIONCOPY 17
tiAMPLE PRO I ORIGINAL IO LA6, COPY to CET
i
_._._._._.
Project Name PLANT ALQN SYSTEM
EM (PE Plum nu.
COLLECTION SYSTEM IPERMfT113&
!Vondor
'
" -
� 7
-GRAM
Ground Waal NPDES
Drinking Water UST
q
121
Cllenl COURTNEY MURPHY, RANDY GANTT, BRYAN
�Pa c
'ar�iy
- ----_.._.-Cnalar Tom
._.._,._.._.._., _,. , ,p,I_)._,._..
C
HCHA NIaste
_.._.. _.._.....
_
2
MOELLER. DEE OBRIEN. JOSH STOWE
_.._.._.__.._.,_,-_.._.._. ._.._,.-..».._.._.._.._.._
Operating Unit: AS00 Process�DENVws
A!�'
9 7 ' 2
i Filtration (0.45 um)
8 Unfiltered
ll
'
Account
Project: A.(-ty IDr Facility IO:ALN
-----_.. _ -
i"'
I Preservative
- -
ICE
ICE
Program 1 EOulS Task Cotle: ALN L.CS Sub-PrngremlTask Code
CqVOlume
SDo
300
SOD
HOPE
PET
PET
METALS - ICP TRIO
ISW6010D): Ba.B, Cr,
Cu. Fe. Mn. NI, 7n (8)
EPA
9056A-
--------- - -
Sample Description or ID
Customer fo com ate 411 a
W ppmprlare non•sRaded
4reas
SAMPLE ID
Hg(7470Af(1),IMS
TRM (SW6020B): 56.
CI,F,
NO3-N.
TDS
Collection Information
NUMBER
E ?
As. Be, Cd, Co, Pb, Se.
SO4
Date
rS,II-1A
Time Printed Name
ISiL &jAj/v mz ZAHoIRA
51 nature
x
Ag, TI(LL), VILL) (10)
ALN_LCS-CELL1
Z./O[I
ALN_LCS-CELL2
$.31-Ze
157.E CSvVJIln4 74HORA
r .�/ �
x
t
t
ofpJ!
ALN FB
-
15z5 (,crwajL. 2 140A
Cl
�-��
x
t
t
1
i
i
i
i
! I
I I
I
I j
1
I
F j
I
Accepted is
BY•/[�J}�f / Date Trm J Accepted 13y:
X
By DatefTime `Accepted By:
Daterrime SealedlLack Opened By
T OT�AL(J'f9 CONTAINERS
/I j) I D 0
Date/Time
/V�• _ t l 3
PantiTime
Daterrime
—Li- P--, c.-, + i
Use Indicated or comparable methods: NC SWS EDD format required. EQUIS EDD required.
0
3 3 3 0 0 n 0 0 0
r
Requested Turnaround
Total
c
„ V
J
21 Days
_
do
a
E c
14Days__ --
C9
n m
-7 Days
d
p
_
Other
}
• Add CORI Will Apply
U
DUKE e.yy Y...,O.u4,..u.y
WYfaa�GOW ]ar illIaWYMq 41157
ENERGY =4b.NC.yRu
49.>, Y, . =ran
pmt rrS37"
•_ _ _ _ _ _ _ _ _ _ _ ....... rt:--Xv iPlSofa...........
Project Name PLANT ALLEN-LEACHATE
COLLECTION SYSTEM (PERMITO 36
tz
Client COURTNEY MURPHY, RANDY GANTT, BRYAN
MOELLER. DEE OBRIEN, JOSH STOWE
OperatingUniv ASOO Process:BENVW5 Account:
Pro)ect: Activity ID: Facility ID:ALN
Program I EQuiS Talk Code: ALN LCS I Sub-Pmgromrrask Code,.
SAMPLE 10
NUMBER
Sample Description or ID
ELL2
fs/3,%t ?W
_ _ _ CHAIN OF CUSTODY RECORD AND ANALYSIS REQUEST FORM
•- -•-•- -•-•------•-•-•---•-•--•-'-•-• --- •---- i-�,i .-. --- --- ._._._._._._._.-.-.-.--.-._._.---.-.-.-.-.-----.-.-.-.-.--_._._._._ i Page 30 of 30
ytical
'Matrix WATER Nc x- Page_t_of 1
/�7r9 sc- r DISTRIBUTION
i
air
s n - - - i ORIGINAL to LAB. COPY to CLIENT
/ SAMPLE PROGRAM
1
Ground Water _X_. NPDES
d •7 Orinkmg Waterr _ LIST -_
Pace ... Waste
PO # 9172712 ! Filtration (0.45 um) b Unfiltered 8 Filtered
i
Preservative ICE ICE
Container Volume (MI-) Soo 300 500
—++
Container Type HOPE PET PET
- METALS - ICPTRM w
(5W60t0O): Ba.B.Cr. EPA
Customer to comprele afl appropriate non -shaded areas.
n '
d n
I p
x
Cu, Fe, Mn. NO, Zn (a)
NO (7470A) (t), IMS
TRM (SW6020B): 5b,
As. Be, Cd, Co. P0. Se,
Ag, TI(LLI. VILL) (SO)
T
t
r
IT
9056A:
Cl, F. TDS
NO3•N,
504
T T
T T
M
t T 1
e
a
U
Collection Information
Bale Time Printed Name Signature
15t6 &vwvc72 ZAHOU
$•3t-'L 15?a CollyMDR.1JlNOM -�~
$-3l�?d 15Z5 CwtiN/Tolt Z
x
x
3
By DalerTime Sealed4.ock Opened By
Use indic,iled or comparable methods, 9C SWS EDD formal required. EOUIS EDD required.
0
1 # 0
0
TOTAL M CONTAINERS TF
F77
-- -
Dalelnme
DatelTime
0
0
o
0
1 0
D
I o
I 0
i
m
Requested Turnaround Total E
t t
N c 21 Days
a
m o'
fl w
c 14 Days
c � -
t«
v
n '7 Days
E n
�v
m
c "Other
a "Add. COSI Will Apply
3
V
Attachment 2
Allen Retired Ash Basin (RAB) Ash Landfill
Semi -Annual Monitoring Event
Leachate Field Forms
F7 CAMA CCR ' rLandfill
NPDES DGW ASW LRB SPECIAL STUDY
FIELD SAMPLING LOG I; DUKE
4L, ENERGY
Site: UFCN WeII/SW ID: LGS - LEb -1 Date: 5-31-zc
El GROUNDWATER SAMPLE [:]SURFACE ❑ ❑ SURFACE WATER SAMPLE LEACHATE SAMPLE WLO WELL DEVELOPMENT
FIELD STAFF: LJL WEATHER: []SUNNY❑PARTLY CLOUDY ❑OVERCAST ❑RAIN ❑SNOW ASR TEMP: 8/0°F
COMPANY: Q DUKE ENERGY FIELD METER TYPE! SERIAL #: & ON
❑ OTHER: TURBIDIMETER TYPE/ SERIAL M .1321
START PURGE TIME: SAMPLE COLLECTION TIME: iS�G
PUMP/TUBING INTAKE DEPTH: (h) DEPTH TO WATER: (it) MOLT FACTOR': 0,163 (•(radius;12a2.3 14•7.48)
WELL DIAMETER: (in) HEIGHT OF WC: (it) WELL VOLUME: r (gal)
WELL DEPTH: (it) TOTAL VOLUME PURGED: (gal)
TYPE OF PUMP:
Bladder
Peristaltic
12 Volt
Grundfos
Other (
PURGE METHOD:
IF
SAMPLING METHOD:
PUMP SETTING:
p
tp,t 1"C) (—I Low Flow Sampling Stabilization Criteria
• pH ± 0 1 standard unit
• Speck Conductance = 5% in NS'cm
• DO t 0.2 mg1
• Turbidity less than 10 NTUs
TIME
WATER
LEVEL
FLOW
RATE
VOLUME
REMOVED
TEMPERATURE
DO
SPECIFIC
CONDUCTANCE
pH
ORP
TURBIDITY
(FT)
(x.xx)
(mUmin)
(x)
(gallons OR mL)
(x.xx)
(°C)
(x)
(mglL)
(x.xx)
(NSlcm)
((fix)
(su)
(x.xx)
(mV)
(�x)�/
(NTU)
(x.x)
ZI/'l
710L
US;
3✓O
2.7
�{
('90
qG2-
Kr
2.)
PLEASE REFER TO THE BACK OF THIS SHEET IF THE CHART ABOVE IS FULL
IS REDEVELOPMENT NEEDED (>10 NTUS)? ❑ YES NO WERE ALL SAMPLES ON ICE WITHIN 15 MINUTES?DYES [:]NO
IS A TURBIDITY METER DUPLICATE REQUIRED? DYES 8 NO IS THE LOCATION FIELD VEHICLE ACCESSIBLE? DYES ❑ NO
IS THE TURBIDITY METER DUPLICATE TAKEN, WITHIN 15%? ❑ YES ❑ NO DUPLICATE 1 (NTU) DUPLICATE 2 (NTU)
FINAL SAMPLE OBSERVATIONS:
DETECTED ODOR None H2S Petroleum Earthy Musty Undetermined
ODOR STRENGTH None Minor Strong
ADDITIONAL NOTES: APPEARANCE Clear Cloudy Turbid Redliron Film on Surface Sheen Fines Floc
WELL TAG
PROTECTIVE CASING
LOCK
DUST CAP
CONCRETE PAD
GOOD 11
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
Version 1.0 Revised 12/17/2018 RDP
❑ CAMA [—j CCR Landrill NPDES DGW ASW LRB SPECIAL STUDY,
FIELD SAMPLING LOG
Site: AUW Well/SW ID: LC5 - GEu. Z
Date: 9'a-74
DUKE
ENERGY
El GROUNDWATER SAMPLE [:]SURFACE WATER SAMPLE ❑❑LEACHATE SAMPLE WLO ❑ WELL DEVELOPMENT
pp
FIELD STAFF: L/51 WEATHER: ❑SUNNY []PARTLY CLOUDY ❑OVERCAST []RAIN []SNOW AIR TEMP: 89 -F
COMPANY: 0 DUKE ENERGY FIELD METER TYPE/ SERIAL #: 7135*1'!
❑ OTHER: TURBIDIMETER TYPE/ SERIAL #: 3321
START PURGE TIME: i• � SAMPLE COLLECTION TIME: 1521
PUMP/TUBING INTAKE DEPTH: r (n) DEPTH TO WATER: — 01) MULT FACTOR *• 0.163 ['(rad=us112)2'3 14.7.48)
WELL DIAMETER: (In) HEIGHT OF WC: v 00 WELL VOLUME: `~ (gal)
WELL DEPTH: (fl} TOTAL VOLUME PURGED: (gat)
TYPE OF PUMP:
Bladder
Peristaltic
12 Volt
Grundtos
Other { AQq )
PURGE METHOD:
SAMPLING METHOD:
PUMP SETTING:
P
H
p
Low Flow Sampling Stabilization Criteria
• pH t D.1 standard unit
Speck Conductance t 5% in NSfcm
• 00 f 0.2 mgq
• Turbidity less than 10 NTUs
TIME
WATER
LEVEL
FLOW
RATE
VOLUME
REMOVED
TEMPERATURE
DO
SPECIFIC
CONDUCTANCE
pH
ORP
TURBIDITY
(FT)
(x.xx)
(mUmin)
(x)
(gallons OR mL)
(x.xx)
VC)
(x)
(mg1L)
(x.xx)
(NSlcm)
(x)
(su)
(x.xx)
(mV)
(x)
(NTU)
(x.x)
1511
So t4m
M
It Z.77
s- 67
%5G
'to(
2*
Z. 19
K tiY
3. Y
PLEASE REFER TO THE BACK OF THIS SHEET IF THE CHART ABOVE IS FULL
IS REDEVELOPMENT NEEDED (>10 NTUS)? ❑ YES NO WERE ALL SAMPLES ON ICE WITHIN 15 MINUTES? YES NO
❑ IS A TURBIDITY METER DUPLICATE REQUIRED? YES ❑ A[]NONO IS THE LOCATION FIELD VEHICLE ACCESSIBLE? AYES ❑ NO
IS THE TURBIDITY METER DUPLICATE TAKEN, WITHIN 15%? ❑ YES ❑ NO DUPLICATE 1 (NTU) DUPLICATE 2 (NTU)
FINAL SAMPLE OBSERVATIONS:
DETECTED ODOR 610M H2S Petroleum Earthy Musty Undetermined
ODOR STRENGTH Ghe Minor Strong
ADDITIONAL NOTES: APPEARANCE Per Cloudy Turbid Red/iron Film on Surface Sheen Fines Floc
WELL TAG
PROTECTIVE CASING
LOCK
DUST CAP
CONCRETE PAD
GOOD
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
GOOD
BAD
NONE
z-
Version 1.0 Revised 12/17/2018 RDP