HomeMy WebLinkAbout16028_Kale Bindex_SIR_2021.18.11
DWM Brownfields Inspection Report
Submitted By: jkslaughter_ncdenr
Submitted Time: 11/19/2021 10:02 AM
I. Inspection Information
Date & Time: 11/18/2021 11:49 AM Inspection Type: Meeting
Brownfields Staff:
Kevin Slaughter
Other Personnel:
Alexis McKenzie - H&H
Location:
Lat: 35.2117554, Long: -80.8627538,
Brownfields Inspection Report: Kale-Bindex (2000 Hawkins Street), 16028-12-060
11/18/2021 11:49 AM
Page 2 of 6
II. Project Information
Number: 16028-12-060 Name: Kale-Bindex (2000 Hawkins Street)
Address: 2000 Hawkins Street
City: Charlotte
County: Mecklenburg
III. Environmental
Current Use of Property: Residential
Structures on Property: Existing Structures Violation: No
Vapor Mitigation Systems: Observed Vapor Mitigation Violation: No
Use of Surface Water or Groundwater: Not Observed Water Use Violation: No
Exposed Soils: Not Observed Exposed Soils Violation: No
Summary: Onsite during installation of active VIMS within first floor garage of each
townhome within Buildings 4 and 5. These building have a previously installed sub-slab
VIMS barriers which is below the concrete slab.
Observed the completed interior suction piping within at least one unit within Building 4
(two suction points) and Building 5 (single suction point) during the Site Inspection
(Photos 1 and 2). Garage suction piping that has been completed is stubbed up in the
backyard of the respective townhome (Photo 4). Active fans, low vacuum alarms, and
PVC vertical exhaust risers have not been installed yet.
Summary: N/A
Summary: High density 3-story townhomes. First floor of each residence consists of a
garage with soil contact along rear masonry walls. In addition, the exterior wall of each
building end unit also has soil contact.
Summary: N/A
Brownfields Inspection Report: Kale-Bindex (2000 Hawkins Street), 16028-12-060
11/18/2021 11:49 AM
Page 3 of 6
Use of Basements: Observed Basement Violation: No
Storage of Chemicals: Not Observed Chemical Violation: No
Groundwater Monitoring Wells: Not Observed Monitoring Well Violation: No
Current Exposure to Public/Public Risk:
Summary: First floor garages have soil contact along rear masonry wall, and partial side
wall soil contact on end units of each building.
Summary: N/A
Condition:
Summary: N/A
TCE has been detected within a townhome during a prior sampling event at levels up to
4.8 ug/m3. The active VIMS is being installed to reduce indoor air TCE to below
residential risk standards.
Brownfields Inspection Report: Kale-Bindex (2000 Hawkins Street), 16028-12-060
11/18/2021 11:49 AM
Page 4 of 6
IV. Inspector Comments
V. PHOTOGRAPHS
Photo 1: Two VIMS suction point installed along left wall of garage in photo (Building 4).
Site visit performed to inspect progress of active VIMS installation on Building 4 and 5
townhomes. Was only able to access a couple of the garage areas where VIMS suction
piping had been installed during the site visit since many units had not been started or
the homeowners were not home to grant access. As stated previously, suction piping
within the units completed is routed to their respective backyards (Photo 4). Installation
of the VIMS fans, low vacuum alarms and PVC risers on the suction piping had not been
started at the time of the Site Inspection.
Brownfields Inspection Report: Kale-Bindex (2000 Hawkins Street), 16028-12-060
11/18/2021 11:49 AM
Page 5 of 6
Photo 2: Single suction point active VIMS installed along wall in photo (Building 5). Masonry
wall on the right of photo is in contact with soil to the top of the wall.
Photo 3: Typical Sch. 40 PVC suction point penetration through basement floor. Suction point
will extract air from a sub-slab, gravel filled suction pit using an active fan.
Brownfields Inspection Report: Kale-Bindex (2000 Hawkins Street), 16028-12-060
11/18/2021 11:49 AM
Page 6 of 6
Photo 4: PVC suction point piping extended from garage/basement level into back yard
adjacent to wood fence. Active VIMS fan and low vacuum alarm to be installed, then PVC VIMS
exhaust riser will be extended above townhome roofline.
Photo 5: Backyards of Building 5 townhomes. VIMS exhaust risers and fans on Building 4 and 5
had not been started at the time of the inspection.