Loading...
HomeMy WebLinkAbout20050 Rite Aid VIMS Bdg 3 and Approval 2021.08.11 August 12, 2021 Sent Via E-Mail Trinh DeSa Hart &Hickman, PC 2923 South Tryon Street, Suite 100 Charlotte, NC 28203 TDeSa@harthickman.com Subject: Work Plan Approval-Additional Vapor Assessment Building 3 Rite Aid Brownfields Site Charlotte, Mecklenburg County Brownfields Project No. 20050-16-060 Dear Mr. DeSa, The Department of Environmental Quality (DEQ) Brownfields Program received your Work Plan Additional Vapor Assessment Revision 1 Building 3 dated August 11, 2021 for the above referenced Brownfields Property. DEQ Brownfields reviewed this document, and determined that comments made by DEQ Brownfields to the previous version of this work plan (dated July 12, 2021) have been incorporated as requested. Therefore, DEQ Brownfields approves the current work plan. Please be advised that this approval from DEQ Brownfields does not waive any applicable requirement to obtain any necessary permits, licenses or certifications which may be required from other state or local entities. If you have questions about this correspondence or require additional information, please feel free to contact me by phone at 704/661-0330 or by email at carolyn.minnich@ncdenr.gov Sincerely, Carolyn Mininch Brownfields Project Manager ec: Kelly Johnson, DEQ Vapor Intrusion Mitigation Plan Camp North End Building 2 - North Brownfields Project No. 20050-16-060 Rite Aid Facility 1776 Statesville Ave Charlotte, North Carolina July 16, 2020 H&H Job No. ATL-001 #1269 Engineering #C-245 Geology S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx Vapor Intrusion Mitigation Plan Building 2 - North Rite Aid Facility 1776 Statesville Ave Charlotte, North Carolina Brownfields Project No. 20050-16-060 H&H Job No. ATL-001 Table of Contents 1.0 Introduction ................................................................................................................ 1 2.0 Summary of Previous Vapor Intrusion Assessment ............................................... 2 3.0 Design Basis ................................................................................................................ 4 4.0 Quality Assurance / Quality Control ........................................................................ 8 5.0 Post-Construction and Pre-Occupancy System Effectiveness Testing ................. 8 6.0 Post-Occupancy Testing .......................................................................................... 11 7.0 Future Tenants & Building Uses ............................................................................ 12 8.0 Reporting .................................................................................................................. 12 Attachments Figure 1 Site Plan Attachment A Excerpts from Previous Sub-Slab Soil Vapor and Indoor Air Assessments Attachment B Vapor Intrusion Mitigation System Venting Drawings Sheets VM-1, VM-2, and VM-3 Attachment C Cupolex® Specification Sheets and Structural Slab Design Sheets Attachment D Vapor Intrusion Mitigation System Product Specification Sheets Attachment E Vapor Pin® Standard Operating Procedures Documents 1 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx Vapor Intrusion Mitigation Plan Building 2 - North Rite Aid Facility 1776 Statesville Ave Charlotte, North Carolina Brownfields Project No. 20050-16-060 H&H Job No. ATL-001 1.0 Introduction Hart & Hickman, PC (H&H) has prepared this Vapor Intrusion Mitigation Plan (VIMP) for installation of a vapor intrusion mitigation system (VIMS) within the northern portion of Building 2 on the Rite Facility Brownfields Property located at 1776 Statesville Avenue, in Charlotte, Mecklenburg County (Site). The Brownfields Site is approximately 47.87 acres and is comprised of three contiguous parcels of land (Mecklenburg PIN #s 07903102, 07903105, and 07903103). The Site entered into a Brownfields Agreement with the North Carolina Department of Environmental Quality Brownfields (DEQ Brownfields) Program on November 2, 2010 (Brownfields Project No. 20050-16-060) dated October 2017. Soil and groundwater are contaminated at the Brownfields Site due to historical operations and activities. The US Army Corps of Engineers (Corps), on behalf of the US Department of Defense (DOD) is working with DEQ to address impacts release to historical operations conducted at the Site including manufacturing of Model T Ford automobiles, a storage depot for the US Government, and for production of Hercules missiles for the military. The Protective Developer (PD) is Camp Landowner, LP, and the development is known as Camp North End. The Camp North End Building 2 project address is listed as 201 Camp Road and 701 Keswick Avenue. Building 2 (previously referred to as Building 1 during Brownfields activities, and Corps Building 5) is located in the eastern-central portion of the Site as depicted on Figure 1 and is currently unoccupied. The Building 2 designation for this building is used throughout this VIMP. 2 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx The building is comprised of a warehouse style structure with an existing concrete slab and brick walls. Building 2 is proposed to be retrofitted for commercial and retail use, and is not proposed to contain residential units. This VIMP document includes the following sections: • a brief summary of previous vapor intrusion assessment activities completed at the Site (Section 2.0), • a description of the proposed VIMS (Section 3.0), • quality assurance/quality control (QA/QC) procedures that will be implemented during installation of the VIMS (Section 4.0), • post-installation/pre-occupancy testing that will be conducted to confirm the effectiveness of the VIMS (Sections 5.0 and 6.0), • a discussion about future tenant uses (Section 7.0), and • reporting activities (Section 8.0). This VIMP was prepared in accordance with the DEQ Division of Waste Management (DWM) Vapor Intrusion Guidance (VI Guidance) dated March 2018 and the Brownfields Program Vapor Intrusion Mitigation System Design Submittal New Construction Minimum Requirements Checklist which is included as Appendix H in the VI Guidance. 2.0 Summary of Previous Vapor Intrusion Assessment H&H completed sub-slab soil vapor (SSV) and indoor air (IA) sampling activities at the Site in 2016. The SSV sampling results are summarized in the H&H Phase I and II Environmental Site Assessment report dated August 16, 2016, and the indoor air sampling results are summarized in the H&H Indoor Air Assessment report dated, November 9, 2016. A brief summary of the SSV and IA sampling results for Building 2 (formerly identified as Building 1 during the assessment activities) is described below. 3 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx In April 2016, H&H installed three soil-gas monitoring points (SGMPs), SSV-4 through SSV-6, in Building 2. Analytical results indicated that trichloroethylene (TCE) was detected above the NC DEQ Non-Residential Sub-Slab Soil Gas Screening Levels (SGSLs) in SSV-4 (34,000 µg/m3) and SSV-5 (3,000,000 µg/m3) collected in the northern portion of Building 2. In addition, tetrachloroethylene (PCE) was detected above its residential SGSLs and chloroform was detected above its non-residential SGSLs in sample SSV-5. Based on the results of the SSV sampling, H&H conducted IA sampling activities in Building 2 in June 2016. H&H collected a total of six indoor air samples (IAS-1 through IAS-6) in the northern portion of Building 2. The indoor air samples were analyzed for PCE, TCE, and their degradation products, and chloroform. Note, acrolein was also included as an analyte for the IA samples because previous IA sampling conducted by Hoffman Engineering, Inc. (on behalf of Rite Aid in 2008) reported acrolein at concentrations above the DWM Indoor Air Screening Levels (IASLs). In September 2016, additional IA samples (IAS-22 and IAS-23) were collected from the southern portion of Building 2 after a temporary vapor wall barrier (comprised of plastic sheeting and drywall) was installed between the northern side and southern side of Building 2. The purpose of the temporary vapor wall barrier was to prevent air exchange between the northern and southern portions of Building 2, and thus isolate each area prior to and during the sampling event. The analytical data from the IA samples indicated that TCE was detected above the Non- Residential IASL in samples IAS-2 through IAS-5 located in the northern portion of Building 2. TCE was detected above its Residential IASL in sample IAS-1, collected from the northernmost section of Building 2, and IAS-6, collected from the southern portion of Building 2. However, TCE was not detected above the Residential IASL in samples IAS-22 and IAS-23, collected from the southern portion of Building 2 after installation of the temporary vapor wall barrier. Acrolein was detected above its Non-Residential IASL in each sample, but was also detected in the background samples. In addition, acrolein was not detected in the previous SSV samples from Building 2 and is also a common by-product of petroleum and tobacco combustion. Therefore, it is unlikely that acrolein was a result of vapor intrusion from the sub-surface. DEQ issued a project memorandum noting that acrolein was not considered an environmental impact from historical 4 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx operations at the Site. Excerpts included analytical data tables and sample location maps from the previous assessment activities are included as Attachment A. Based on the TCE detections in indoor air within the northern portion of Building 2, DEQ determined that vapor intrusion mitigation controls are warranted for the northern area of Building 2. Based on the results of the indoor air sampling data, DEQ determined that vapor mitigation controls are not warranted for the southern portion of the Building 2, located south of the previous temporary vapor wall barrier. The VIMS proposed in the northern portion of the Building 2 is described in the following sections of this VIMP. Note, as part of the proposed construction plans for Building 2, a road extension, identified as the Keswick Avenue extension (a.k.a. the “Keswick Cut”), will be constructed as an open-air area through the central portion of Building 2 at a location immediately south of the of the temporary vapor wall barrier. The section of Building 2 located north of the proposed Keswick Avenue extension is referred to as Building 2 – North, and the area south of the road extension is referred to as Building 2 – South. During construction of the Keswick Avenue extension, the existing concrete slab in this area will be removed and new exterior walls along the street extension will be constructed. Thus, the VIMS described in the following sections of this VIMP will be installed in Building 2 – North and will terminate at the exterior wall along the road extension. 3.0 Design Basis This VIMP consists of installation of an active VIMS at Building 2 – North to mitigate potential vapor intrusion concerns from the sub-surface for non-residential use scenarios. The VIMP is included as Sheets VM-1, VM-2, and VM-3 in Attachment B and will be used to guide construction of the VIMS. Please note that H&H is providing the venting design on Sheets VM-1, VM-2, and VM-3 in Attachment B, and Pontarolo Engineering, Inc. (Pontarolo), the design engineer for the Cupolex® line of products, is providing the structural drawings for the contractor for the concrete slab which is presented on Sheets C1, C2, and C3 in Attachment C. Prior to construction, Pontarolo will provide final structural drawings to the construction contractor. 5 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx The proposed plans for Building 2 – North contain open-air pavilions and porches located outside of the exterior building walls. These areas may contain a roof or cover, but will not be closed-in, nor will they contain heating, ventilation, and air condition (HVAC) units or controls. The locations of these open-air porches and pavilions are depicted on Sheet VM-1. Installation of VIMS The approximate area of Building 2 – North covered by the VIMS is approximately 101,000 square feet (sq ft). The VIMS includes installation of a Cupolex® Windi H.5 (5cm) ventilated floor system installed atop the existing concrete slab in Building 2. The Cupolex Windi system consists of polypropylene Cupolex plastic dome-shaped concrete forms interlocking in a grid pattern with a height of 5 cm, or approximately 2-inches. A 4-inch thick concrete slab will be poured above the Cupolex system to create a floating slab-on-grade concrete floor system with an under-slab void. Manufacturer specification sheets for the Cupolex system components are included in Attachment C. The Cupolex system will be installed by the redevelopment contractor at the direction of Cupolex Building Systems, a division of Pontarolo who will provide training for the installation contractor and will perform limited inspections of the ventilated floor installation. H&H will perform additional inspections of the VIMS during installation activities as discussed further in Section 4.0. As sections of the concrete slab are poured, penetrations (including, but not limited to expansion joints, control joints, construction joints, isolation joints, open cracks in the Cupolex concrete floor slab, plumbing and electrical conduits, venting system pipes, etc.) to the floor will be sealed using a urethane caulk or grout per manufacturer installation recommendations to prevent movement of air along the annulus between pipes, conduits, utility banks, or similar features. Details showing typical sealing of vertical penetrations through the slab and Cupolex floor are included on Sheet VM-2 in Attachment B. Please note that there are no elevator shafts or slab-steps (slab elevation changes) proposed in Building 2 – North. Also, please note that exterior doorways and openings are proposed to be retrofitted to account for the approximate 6-inch combined height of the Cupolex and concrete floor. However, if a doorway is unable to be retrofitted due to structural or architectural reasons, then a ramp at the doorway to the top of the new concrete floor slab may be constructed per Detail 13 on Sheet VM-2. 6 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx Sealing Agents The polyurethane caulk or grout used to seal the concrete floor slab penetrations shall be a low- VOC containing product and will not contain TCE or PCE. The vapor barrier material for sealing around ramps (if needed) or repairs in the Cupolex system will be Raven Industries 20-mil VaporBlock Plus, or an equivalent product approved by the VIMP design engineer and DEQ Brownfields. The appropriate vapor barrier sealing products (mastic/epoxy, tapes, etc.) associated with the selected vapor barrier shall be used and installed per manufacturer recommendations. Products used in the VIMS must be approved by the VIMS design engineer certifying the VIMP. The Raven VaporBlock Plus specifications are included in Attachment D. Tenant Walls Note, Building 2 – North will contain multiple commercial tenants after construction. The tenants may install stud walls located on the new concrete floor installed above the Cupolex system. The stud walls are not proposed to extend through the concrete floor slab. In the event walls or utilities are constructed through the new concrete floor slab and penetrate the Cupolex system, the penetrations will be sealed and repaired per the details in Sheets VM-1 to VM-3. Repairs or modifications that extend through the concrete floor and to the Cupolex system will be inspected by a North Carolina (NC) Professional Engineer (PE) prior to completion. In addition, a report documenting the repairs and modifications will be submitted to DEQ Brownfields upon completion of the activities. To the extent practical, attempts will be made to avoid the use of the primary contaminants of concern in the building construction materials. At a minimum, the construction materials will not contain PCE or TCE. Vent Piping and Motorized-Fans The VIMS will be installed as an active system designed to prevent potential vapors from migrating into the building by sub-slab depressurization within the under-slab voids within the Cupolex system. Vapors will be extracted from the sub-slab using 4-inch diameter polyvinyl chloride (PVC) or 4-inch diameter cast-iron vent piping that will penetrate the concrete floor slab and Cupolex and extend above the building’s roofline along existing interior columns or within 7 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx proposed stud walls. The riser pipes will be connected to an in-line electrical-powered extraction fan installed on the building’s roof. H&H has proposed installation of Festa AMG Legend fans; however, the fan type and size may be modified based on the results of the influence testing (Section 5.0) to provide adequate sub-slab depressurization within the building. Alternative electric fans must be approved by the design engineer certifying the VIMS, and DEQ Brownfields will be notified of the change. The proposed locations of the vent riser pipes and details are included on Sheets VM-1 and VM-2 in Attachment B. The exhaust point of the vent pipe and fan will be located at least 3 ft above the building’s roofline, and least 15 ft horizontally from HVAC intakes, areas where people congregate or traverse, and other operable openings into the building. Additionally, the exposed vent piping will be labeled with “Vapor Mitigation – Contact Maintenance Department” (or similar language) at intervals no greater than 10-linear ft. along spans of the vent pipes. A label will also be affixed on or near the fans with a unique fan identification number and with information similar to that on the pipe labels as indicated above. VIMS Alarm System In accordance with the DWM VI Guidance, an alarm system is required for active VIMS to alert the building maintenance staff should the extraction fan fail to operate as designed. An alarm system will be installed that will consist of a telemetric monitoring system that will alert building maintenance staff with email, text, and/or phone notifications if the fans fail to operate correctly. The alarm system will contain a Sensaphone differential pressure sensor on each riser that will communicate with a centralized computer that will be enabled with cellular or internet connection. Specifications for the proposed alarm system, the Sensaphone Sentinel Monitoring System, are included on Sheet VM-2 and specification sheets are included in Attachment D. The location to house the Sensaphone Sentinel unit will be chosen by the architect/owner. Similar alternative devices for the alarm system may be installed by the owner/installation contractor with the approval of the VIMS design engineer certifying the VIMS. The final product specifications and alarm system design details will be included in the as-built drawings and submitted to DEQ Brownfields with the VIMS Installation Report. 8 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx 4.0 Quality Assurance / Quality Control For quality assurance and quality control (QA/QC) purposes, inspections will be conducted during various phases of VIMS installation activities. Inspections will be performed as follows: • prior to installation of the Cupolex forms to observe installation activities associated with utility trenches and penetrations, • during installation of the Cupolex system, prior to slab-pours, and • during installation of the exhaust vent piping and extraction fans. Each inspection will be performed by, or under the direction of, the VIMS design engineer (NC PE) certifying the VIMP. In addition, Cupolex Building Services will provide limited inspections and site-specific training during installation of the Cupolex system for the installation contractor. The inspections will include field logs and photographs for each portion of the VIMS. The engineer certifying the report, or designee, will provide DEQ Brownfields with at least a 48-hour notice prior to conducting inspections. 5.0 Post-Construction and Pre-Occupancy System Effectiveness Testing Following installation of the Cupolex system and completion of the concrete floor slab, but prior to building occupancy, influence pilot testing will be conducted to measure VIMS vacuum communication below the slab. To conduct the proposed influence testing, variable speed vapor extraction fans similar to the proposed electric fans (AMG Legend) will be attached to the exhaust end of the sub-slab vent piping system. Vacuum and air flow will be measured at varying speeds with measurements recorded at the extraction fan location to evaluate pressure differential between indoor air and the Cupolex sub-slab void space. The proposed vacuum monitoring points are shown on Sheet VM-1 and will consist of Vapor Pin® devices with secured covers that will be installed after the new concrete slab is poured and set flush with the finished concrete floor surface. Specification sheets and installation instructions for the Vapor Pin devices are provided in Attachment E. Due to the interconnectedness and limited air resistance of the void space within the Cupolex system, vacuum across the entire void space throughout the building are expected to 9 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx be similar. Therefore, the proposed monitoring points should be sufficient to provide representative data of sub-slab vacuum measurements across the building. Depressurization is considered sufficient if vacuum measurements meet or exceed 4 pascals (approximately 0.016 inches of water column, inWC) at remote extents of the VIMS treatment area per DEQ Brownfields requirements. Based on post-construction effectiveness testing, an alternative fan (other than the proposed AMG Legend) may be selected by the design engineer to meet the 4 pascals vacuum levels. If an alternative fan is selected, DEQ Brownfields will be notified and the fan specifications will be included in the VIMS Installation Report. Upon completion of the VIMS installation activities including activation of the permanent extraction fans and when the condition of the building is similar to that of occupancy, vacuum effectiveness testing will be performed by collecting pressure differential measurements at the vacuum monitoring points described above to confirm that the permanent extraction fan effectively depressurizes the sub-slab voids in the Cupolex system. Vacuum and air flow measurements will also be measured at the extraction fan locations. Based on the layout of future commercial tenants, some of the vacuum monitoring points may be inaccessible after future upfit activities. In these cases, the specified monitoring points will be abandoned with an air-tight sealant and concrete and new monitoring points will be installed in accessible areas within the building. DEQ Brownfields will be notified of modifications to the monitoring point locations for review and approval prior to performing the modifications. As shown on VM-1, the VIMS has been designed to prevent potential vapor intrusion into the proposed Site building using one interconnected Cupolex void space across the entire building footprint. Due to the ability to maintain a high vacuum within the Cupolex void space, consistent vacuum measurements of 4 pascals or greater is expected to provide an adequate measure of sub- slab depressurization to prevent vapor intrusion into the building. Indoor air analytical sampling will also be conducted to verify the VIMS effectiveness. Upon completion of successful pilot testing and prior to occupancy of the building, an initial indoor air sampling event (IAS Event No. 1) will be conducted. In addition, a confirmation indoor air 10 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx sampling event (IAS Event No. 2) will be completed approximately one year following IAS Event No. 1. Based on results of IAS Event No. 1 and IAS Event No. 2, H&H will request DEQ Brownfields provide written approval to discontinue confirmation indoor air sampling events. After construction of the VIMS, only limited walls are anticipated to be installed within the building space. Therefore, the majority of the building space will be interconnected the IAS Events. A total of five indoor air samples are proposed to be collected during each event along with one indoor air duplicate sample and one background air sample. The locations of the proposed indoor air parent samples are depicted on Sheet VM-1. The background and indoor air samples will be collected using individually-certified 6-liter stainless steel Summa sample canisters connected to in-line flow controllers with a vacuum gauge. The flow controllers will be set by the laboratory to allow the samples to be collected over an approximately 8-hour period (commercial use scenario). A 3-foot long sampling cane will be connected to the flow controller so that the sample intake point is positioned approximately 5 ft above grade (typical breathing zone height) when the sample canister is set on its base. Prior to and after the indoor and background air samples are collected, vacuum in the canisters will be measured using a laboratory-supplied vacuum gauge and recorded by sampling personnel. A vacuum will be maintained within each canister at the conclusion of the sampling event. The starting and ending vacuum in each canister will be recorded on the sample chain-of-custody form. In addition, vacuum measurements taken by the laboratory at the time of sample receipt will be provided in the final laboratory report. Following sample collection, the Summa canisters will be labeled and shipped under standard chain-of-custody procedures to a qualified laboratory for analysis of select VOCs by EPA Method TO-15. The laboratory will be instructed to analyze for only those compounds detected above the laboratory method detection limit in the previous indoor air samples from the 2016 assessment, with the exception of acrolein which was determined to not likely be a result of vapor intrusion (Section 2.0). The laboratory will be requested to use reporting limits that are below DEQ DWM Non-Residential Vapor Intrusion Indoor Air Screening Levels (IASLs). In addition, the laboratory will be requested to report compound concentrations above the laboratory method detection limits, but below the laboratory reporting limits (i.e., J-Flags). 11 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx The analytical data will be compared to the DEQ DWM Non-Residential IASLs and entered in the DEQ Risk Calculators. Reports documenting indoor air sampling activities will be submitted to DEQ Brownfields within four to six weeks of completion of each sampling event. The analytical data will be provided to DEQ Brownfields within two weeks of receipt and validation of the data. Based upon the sampling results, H&H will make recommendations in accordance with the DWM VI Guidance. It is anticipated that the recommendations will consist of one of the following: • The VIMS is effective, and no further sampling of indoor air is warranted (per the DWM VI Guidance, in the case where calculated cumulative risks are below 1x10-4 for potential carcinogenic risks and below a hazard index of 1 for potential non-carcinogenic risks). • Additional indoor air sampling is warranted to confirm that the VIMS is effective (per the DWM VI Guidance, in the case where calculated cumulative risks are greater than 1x10-4 for potential carcinogenic risks or above a hazard index of 1 for potential non-carcinogenic risks). Modifications to the active fans or other VIMS components may be conducted, if required, and follow-up sampling will be performed after modification to the fans or VIMS. 6.0 Post-Occupancy Testing Post-occupancy vacuum testing will be conducted to verify the VIMS is operating and continues to effectively depressurize the sub-slab voids in the Cupolex system. For the first year of post- occupancy operation, vacuum testing will be conducted on a quarterly basis and will be reported to DEQ Brownfields on a quarterly basis. Post-occupancy vacuum measurement events will be conducted using the Vapor Pin® devices similar to the pre-occupancy testing described above. The VIMS will include a vacuum alarm system with telemetric alarm notifications that will immediately notify the building maintenance department of loss of power or vacuum at the fans and risers. Therefore, repairs or modifications to the system shall occur promptly to ensure proper operation of the VIMS. 12 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx After the first year of post-occupancy operation, H&H will evaluate the quarterly vacuum testing data collected over the first year with DEQ Brownfields to determine the frequency and reporting requirements for future monitoring events. Modifications to the frequency of the vacuum monitoring events will be submitted to DEQ Brownfields for approval prior to making changes to the schedule or reporting requirements. If vacuum measurements during testing do not meet or exceed 4 pascals (approximately 0.016- inWC), H&H will evaluate the VIMS to determine the cause and identify potential repairs or modifications to obtain the desired vacuum. Alteration or repair to the VIMS will be reported to DEQ Brownfields. 7.0 Future Tenants & Building Uses The building will be operated by a property management company with a maintenance staff that will notify H&H (or another NC PE firm), of any potential exposure, damage, alteration, or repairs to the VIMS. As previously discussed, the commercial retail spaces may not all be initially occupied but the VIMS will be installed throughout the building prior to occupancy. The property manager will inform future retail space tenants of the presence of the VIMS and request that they notify them of any damage to the system during potential future renovation or upfit activities. H&H (or another NC PE firm) will provide oversight and inspection of any work that may potentially impact the VIMS and submit documentation of these activities to DEQ Brownfields. 8.0 Reporting Following successful post-construction effectiveness testing, a NC PE-certified report documenting installation of the VIMS (VIMS Installation Report) will be submitted to DEQ Brownfields for review and compliance approval. The report will summarize VIMS installation activities, QA/QC measures, post-construction and pre-occupancy system effectiveness testing activities, and an opinion as to whether the VIMS was installed consistent with the design and objective of the DEQ-approved VIMP. The report will include as-built construction figures, SDS 13 S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Camp North End_Building 2 North_VIMP_071620.docx sheets for products used in the VIMS and by the general contractor in the building, and inspection reports from H&H and Pontarolo that include photographs and field logs. Quarterly reports will be provided to DEQ Brownfields to document quarterly vacuum monitoring for the first year following building occupancy. First year post-occupancy monitoring data will be evaluated to determine appropriate frequency and reporting requirements for future vacuum monitoring events. A request to reduce the number of future vacuum monitoring points must be submitted to DEQ Brownfields for approval. In addition, a post-occupancy indoor air analytical sampling will be conducted approximately one year after occupancy and reported to DEQ Brownfields under separate cover. Reporting for vacuum monitoring events will be conducted and reported under a licensed NC PE or NC Professional Geologist (PG) seal. If VIMS modifications or repairs are needed or conducted, the NC PE will notify DEQ Brownfields and provide documentation of activities conducted for DEQ Brownfields record. FORMERLY KNOWN AS BUILDING #2 FORMER BOILER HOUSE BUILDING #48 FORMERLY KNOWN AS BUILDING #3 BUILDING T-26EXECUTIVE OFFICE REGIONAL TRAINING OFFICE (FORMER CAFETERIA) BUILDING #50 BUILDING 2 - NORTH (FORMER BUILDING 1) BUILDING 2 - SOUTH (FORMER BUILDING 1) FORMER OFFICES KESWICK AVENUE EXTENSION (KESWICK CUT)STATESVILLE AVENUECAMP ROAD W O L F B E R R Y S T R E E T KE S W I C K A V E N U E NORTH GRAHAM STREETPROPOSED OPEN-AIR COVERED PORCH PROPOSED OPEN-AIR COVERED PORCH MV GRAHAM PROPERTY JOB NO. ATL-001 REVISION NO. 0DATE: 07-13-20 FIGURE NO. 1 CAMP NORTH END / RITE AID FACILITY BROWNFIELDS PROJECT NO. 20050-16-060 1776 STATESVILLE AVENUE CHARLOTTE, NORTH CAROLINA SITE MAP 2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f)License # C-1269 / #C-245 Geology LEGEND SITE PROPERTY BOUNDARY TEMPORARY WALL SEAL LOCATION (INSTALLED FOR THE SEPTEMBER 2016 INDOOR AIR SAMPLING EVENT) PROPOSED AREA FOR VAPOR INTUSION MITIGATION SYSTEM (APPROXIMATELY 101,000 SQ FT) PROPOSED KESWICK EXTENSION (KESWICK CUT) OPEN-AIR STREET NOTES: 1. VAPOR INTRUSION MITIGATION SYSTEM (VIMS) IS PROPOSED FOR BUILDING 2 - NORTH. 2. BUILDING 2 WAS FORMERLY REFERRED TO AS BUILDING 1 DURING PREVIOUS ASSESSMENT ACTIVITIES. 3. REFER TO SHEETS VM-1, VM-2, AND VM-2 FOR THE VIMS DETAILS.S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Figures\SITE MAP.dwg, 7/16/2020 4:34:49 PM, DWG To PDF.pc3 Attachment A Excerpts from Previous Sub-Slab Soil Vapor and Indoor Air Assessments Table 1 Summary of Sub-Slab Soil Gas Analytical Results Rite Aid Facility Charlotte, North Carolina H&H Job No. ATL-001Soil Gas ID SSV-1 SSV-2 SSV-3 SSV-4 SSV-5 SSV-6 SSV-7 SSV-8 SSV-9 SSV-10 SSV-11 SSV-12Date 4/22/2016 4/22/2016 4/22/2016 4/25/2016 4/25/2016 4/25/2016 4/25/2016 4/25/2016 4/22/2016 4/22/2016 4/25/2016 4/25/2016Location Building #48 Building #48 Building #50 Building #1 Building #1 Building #1 Building #3 Building #3 Building T-26 Executive Office Building #2 Building #2Residential Non-ResidentialAcetone 19 27 <19 67 J <190 23 18 J 110 62 32 58 61216,000 2,720,000Acrolein <2.8 <2.8 <2.8 <28 <28 <2.8 <2.8 <2.8 <2.8 <2.8 <2.8 <2.80.139 1.75Benzene 1.4 <0.64 <0.64 <6.4 15 0.65 1.3 0.37 J <0.64 1.1 1.0 <0.45 J120 1,5702-Butanone (MEK) 5.0 J 3.7 J 0.86 J <240 4.6 J 5.4 J 4.4 J 6.7 J 5.4 J 3.1 J 1.9 J 4.0 J34,800 438,000Carbon disulfide 4.4 J 0.98 J 0.85 J <62 <62 0.56 J 0.56 J <6.2 0.85 J 2.6 J 0.57 J 0.62 J4,870 61,300Carbon Tetrachloride 0.60 J 0.63 J 0.53 J <13 10 J <1.3 <1.3 0.35 J 0.45 J <1.3 12 <1.3156 2,040Chloroform 1.3 <0.98 <0.98 301,300<0.98 1.8 0.47 J <0.98 <0.98 5.8 <0.9840.7 533Chloromethane 0.45 J 0.56 J <0.83 <8.3 <8.3 0.40 J <0.83 0.25 J 0.45 J 0.52 J 0.38 J 0.40 J626 7,8801,3-Dichlorobenzene<1.2 <1.2 0.34 J <12 <12 0.41 J <1.2 <1.2 0.43 J <1.2 0.55 J 0.55 JNE NEDichlorodifluoromethane (Freon 12) 2.7 2.8 2.7 <9.9 <9.9 2.8 2.7 3.1 2.8 2.9 2.7 2.8695 8,7601,2-Dichloroethane 0.29 J <0.81 <0.81 <8.1 <8.1 <0.81 <0.81 <1.2 <0.81 <0.81 <0.81 <0.8136 472cis-1,2-Dichloroethylene<0.79 <0.79 <0.79 <7.9 20 <0.79 0.33 J <0.79 <0.79 <0.79 <0.79 <0.79NE NEtrans-1,2-Dichloroethylene0.38 J <0.79 <0.79 <7.9 33 <0.79 <0.79 <0.79 <0.79 <0.79 <0.79 <0.79NE NEEthanol 44 380 140 690 610 460 110 1,100 310 450 1400 130NE NEEthyl acetate 5.0 1.2 2.1 <7.2 <7.2 <0.72 1.2 <0.72 1.0 3.6 <0.72 23487 6,130Ethylbenzene11 0.38 J 0.56 J <8.7 <8.7 <0.87 <0.87 <0.87 0.97 3.1 <0.87 0.36 J374 4,9104-Ethyltoluene0.31 J <0.98 <0.98 <9.8 <9.8 <0.98 <0.98 <0.98 <0.98 <0.98 <0.98 0.88 JNE NEHeptane 0.51 J <0.82 <0.82 <8.2 <8.2 <0.82 0.33 J, V-06 <0.82 <0.82 0.30 J, V-06 <0.82 0.57 J, V-06NE NEHexane <28 <28 <28 <280 <280 <28 <28 <28 <28 1.7 J, L-03, V-05 <28 <284,870 61,3002-Hexanone (MBK) 0.70 J 0.51 J <0.82 <8.2 <8.2 0.82 0.84 0.41 J 0.79 J <0.82 0.31 J <0.82209 2,360Isopropanol 4.2 J 6.2 J 2.0 J 7.3 J, L-03 9.0 J, L-03 5.4 J 2.7 J 14 J 8.2 J 8.3 J 24 7.3 J1,390 17,500Methyl tert-Butyl Ether<0.72 <0.72 <0.72 <7.2 <0.72 0.32 J, L-03 <0.72 1.0 L-03 <0.72 <0.72 L-03 0.40 J, L-03 <0.72 L-033,600 47,200Methylene Chloride2.2 J 2.5 J 2.6 J <69 <69 1.5 J 1.5 J 3.2 J 4.0 J 8.4 2.6 J 4.0 J4,170 52,6004-Methyl-2-pentanone (MIBK) 0.82 <0.82 <0.82 <8.2 <8.2 0.34 J 0.38 J 1.0 0.61 J 0.29 J 0.28 J 0.44 J20,900 263,000Naphthalene<1.0 <1.0 <1.0 <10 <10 <1.0 <1.0 <1.0 <1.0 <1.0 <1.0 5.520.9 263Propene 2.7 J 3.3 J <14 <140 19 J 1.8 J 1.8 J <14 <14 1.2 J 1.1 J 1.4 J20,900 263,000Styrene 0.39 J <0.85 <0.85 <8.5 <8.5 <0.85 <0.85 <0.85 <0.85 <0.85 <0.85 <0.856,950 87,600Tetrachloroethene 98 1.2 J 0.81 J 1109903.3 36 33 <1.4 0.43 J 9.0 1.0 J278 3,500Tetrahydrofuran <0.59 <0.59 <0.59 <5.9 <5.9 <0.59 <0.59 0.27 J 0.40 J <0.59 0.48 J <0.5913,900 175,000Toluene 120 4.0 7.0 <7.5 <7.5 0.51 J 1.1 0.74 J 10 44 1.4 1134,800 438,000Trichloroethene200.80 J 0.45 J34,0003,000,00013 2.1 <1.4 1.6 1.57300.86 J13.9 175Trichlorofluoromethane (Freon 11) 1.6 J 2.0 J 1.4 J 36 J <45 1.8 J 1.6 J 3.5 J 2.0 J 110 4.9 2.1 JNE NE1,1,2-Trichloro-1,2,2-trifluoroethane (Freon 113) 0.77 J 0.61 J 0.80 J <61 <61 0.71 J 6.4 750 0.58 J 0.64 J 1.6 J 0.83 J209,000 2,630,0001,2,4-Trimethylbenzene 2.1 0.59 J 0.51 J <9.8 <9.8 0.71 J 0.92 J 0.94 J 0.90 J 0.59 J 0.94 J 1248.7 6131,3,5-Trimethylbenzene 0.31 J <0.98 <0.98 <9.8 <9.8 <0.98 <0.98 <0.98 <0.98 <0.98 <0.98 4.9NE NEm&p-Xylene41 V-06 1.5 J, V-06 2.2 V-06 <17 <17 <1.7 0.47 J, V-06 <1.7 4.6 V-06 13 V-06 0.76 J, V-06 2.7 V-06695 8,760o-Xylene8.1 0.49 J 0.69 J <8.7 <8.7 <0.87 <0.87 0.30 J 1.5 2.3 0.38 J 0.71 J695 8,760Notes:1. Screening critera based on the NC Division of Waste Management Vapor Intrusion Screening Levels (DWM VISL - March 2016)2. Acrolein non-detect concentrations reported to the laboratory method detection limit (MDL)Bold indicates exceedance of the Residential VISLUnderline indicates exceedance of the Non-Residential VISLµg/m3 = micrograms per cubic meterNE = Not EstablishedSamples were collected into 3-L Summa cannisters and analyzed by EPA Method TO-15 over a 15 minute intervalSSV = Sub Slab Soil GasVOCs = Volatile Organic CompoundsJ = Indicates concentration detected above the laboratory MDL, but below the laboratory reporting limit, therefore it is an estimated concentrationL-03 = Indicates laboratory fortified blank/laboratory control sample recovery is outside of control limits. Reported value for this compound is likely to be biased on the low sideV-06 = Indicates continuing calibration did not meet method specifications and was biased on the high side for this compoundScreening Criteria1 (µg/m3)DWM VISLsVOCs TO-15 (µg/m3)S:\AAA-Master Projects\ATCO LLC - ATC\Task-010 Indoor Air\Tables\Soil gas table.xlsSSVDate: 10/11/2016Table 1Hart & Hickman, PC Table 2 Summary of Outdoor and Indoor Air Monitoring Field DataRite Aid FacilityCharlotte, North CarolinaH&H Job No. ATL-001Sample Date TimeTemperature(oF) Sample LocationPrecipitation (inches)Barometric Pressure(in. Hg) Wind DirectionWind Speed (mph)Beginning77 0.00 29.92 S 4Middle 93 0.00 29.90 S 5End 96 0.00 29.92 S 7Beginning 70 0.00 30.19 N - NE 2 - 4Middle 81 0.00 30.17 N - NE 4 - 6End 89 0.00 30.08 N - NW 4 - 5Sample Date TimeTemperature(oF)Sample IDDifferential Pressure (inches of water)Beginning 78NAMiddle 92NAEnd 96NABeginning 820.007Middle 860.006End 890.008Beginning 830.008Middle 850.009End 880.008Beginning 830.009Middle 860.010End 890.009Beginning840.003Middle 840.003End 850.005Beginning830.006Middle 860.006End 880.007Beginning 830.015Middle 840.016End 880.009Beginning840.021Middle 850.017End 920.017Beginning 840.011Middle 860.013End 910.017Beginning 850.005Middle 910.009End 910.006Beginning870.004Middle 910.007End 920.006Beginning 800.022Middle 820.029End 920.027Beginning82IAS-18 0.001Middle 90IAS-19 / DUP 0.003End 92IAS-20 0.004Beginning800.000Middle 920.000End 910.000Beginning 820.008 (-0.006)Middle 840.007 (0.005)End 860.006 (0.008)Notes:Information from on-site weather station set up by H&H on June 4, 2016 and September 17, 2016.Indoor air differential pressure measured between buildings and outside air. Positive value indicates that the pressure in the building was higher than the outside pressure. Parentheses indicate the differential pressure measured between the active and sampling sides of Building 1. Positive value indicates a postive pressure on the sampling side. Wind direction indicated source direction, i.e. south wind is blowing from south to north.Beginning refers to times of approximately 0800 to 0900 at start of samplingMid refers to times of approximately 1200 to 1300 at midpoint of samplingEnd refers times of approximately 1600 to 1700 at endpoint of samplingNA = Not Applicable; -- = Not MeasuredBuilding #1 Southern Warehouse AreaBuilding #1 Central Warehouse AreaBuilding #1 Employee OfficeBuilding #1 Southern Warehouse AreaBuilding #2 Central Warehouse AreaBuilding #2 Eastern Warehouse AreaBuilding #1 Shipping OfficeBuilding #1 Northern Warehouse AreaBuilding #48 Central Storage RoomBuilding # 1 Maintenance OfficeBuilding #48 West/Central Storage RoomIAS-21Building #2 - Central and Eastern Warehouse AreaBuilding #48 - Entire BuildingBuilding #50 - Former Boiler House6/4/20169/17/20169/17/20169/17/20169/17/20166/4/20166/4/20166/4/20166/4/2016Outdoor MeasurementsIndoor Measurements6/4/20169/17/20166/4/20166/4/2016Southern side of Buirling #1Between Buildings #1 and #2Sample LocationExterior - On south side of Building #1 (upwind of each building)IAS-66/4/20166/4/20166/4/20166/4/2016IAS-7IAS-8IAS-9IAS-10IAS-22 IAS-23BASIAS-1IAS-2IAS-3IAS-4IAS-11, IAS-12, IAS-13, IAS-14, IAS-15, IAS-16, IAS-17IAS-5File: S:\AAA-Master Projects\ATCO LLC - ATC\Task-010 Indoor Air\Tables\Indoor Air Table - revised Sept 2016.xlsTable 2 Monitoring dataDate: 10/7/2016Table 2Hart & Hickman, PC Table 3 Summary of Indoor Air Analytical Results Rite Aid Facility Charlotte, North Carolina H&H Job No. ATL-001 File: S:\AAA-Master Projects\ATCO LLC - ATC\Task-010 Indoor Air\Tables\Indoor Air Table - revised Sept 2016Table 3 - IA AnalyticalDate: 11/9/2016 Table 3 Hart & Hickman, PC Indoor Air Sample ID IAS-1 IAS-2 IAS-3 IAS-4 IAS-5 IAS-6 IAS-7 IAS-8 IAS-9 IAS-10 BAS-1 Date 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 6/4/2016 Sampling Height 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft Location Building #1 Shipping Office Building #1 Northern Warehouse Area Building # 1 Maintenance Office Building #1 Central Warehouse Area Building #1 Employee Office Building #1 Southern Warehouse Area Building #2 Central Warehouse Area Building #2 Eastern Warehouse Area Building #48 West/Central Storage Room Building #48 Central Storage Room Background Sample South of Building #1 VOCs (TO-15)Residential Non-Residential ` Acrolein 4.5 3.3 5.0 3.5 5.5 1.9 1.7 2.5 2.3 2.7 2.4 0.00417 0.0175 Chloroform 0.22 0.29 0.25 0.28 0.26 0.22 <0.17 <0.17 <0.17 <0.17 <0.17 1.22 5.33 1,1-Dichloroethylene <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 41.7 175 cis-1,2-Dichloroethylene <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 NS NS trans-1,2-Dichloroethylene <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 NS NS Tetrachloroethene <0.24 0.73 0.33 0.36 0.36 <0.24 0.27 0.33 0.49 5.0 <0.24 8.34 35 Trichloroethylene 1.6 54 24 19 27 1.0 <0.19 <0.19 <0.19 0.31 <0.19 0.417 1.75 Vinyl Chloride <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 2.30 27.9 Indoor Air Sample ID IAS-11 IAS-12 IAS-13 IAS-14 IAS-15 IAS-16 IAS-17 IAS-18 IAS-20 IAS-21 IAS-22 IAS-23 BAS-2 BAS-3 Date 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 9/17/2016 Sampling Height 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft 5-ft Location Building #2 Northeastern Warehouse Area Building #2 Eastern Warehouse Area Building #2 Southeastern Warehouse Area Building #2 East/Central Warehouse Area Building #2 East/Central Warehouse Area Building #2 North/Central Warehouse Area Building #2 South/Central Warehouse Area Building #48 Eastern Storage Room Building #48 East/Central Storage Room Building #48 East/Central Storage Room Building #48 Western Storage Room Former Boiler House Building #1 Southern Warehouse Area Building #1 Southern Warehouse Area Background Sample Northeast of Building #1 Background Sample Northwest of Building #2 VOCs (TO-15)Residential Non-Residential Acrolein 1.2 J <1.6 0.75 J <1.6 3.6 4.0 4.3 2.8 1.2 J 1.5 J 0.7 J <1.6 1.4 J 4.8 0.90 J 0.50 J 0.00417 0.0175 Chloroform 0.082 J 0.20 0.072 J 0.072 J 0.082 J 0.086 J 0.089 J 0.072 J 0.088 J 0.073 J 0.082 J 0.086 J 0.082 J 0.079 J 0.086 J 0.082 J 1.22 5.33 1,1-Dichloroethylene <0.14 0.12 J <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.20 <0.20 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 41.7 175 cis-1,2-Dichloroethylene <0.14 0.11 J <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.20 <0.20 <0.14 <0.14 <0.14 <0.14 <0.14 0.083 J NS NS trans-1,2-Dichloroethylene <0.14 0.10 J <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 <0.20 <0.20 <0.14 <0.14 <0.14 <0.14 <0.14 <0.14 NS NS Tetrachloroethene 0.11 J 0.31 0.13 J 0.071 J 0.090 J 0.116 J 0.090 J 0.081 J <0.34 <0.34 0.071 J 0.076 J 0.086 J 0.086 J 0.095 J 0.100 J 8.34 35 Trichloroethylene 0.21 0.34 0.17 J 0.12 J 0.21 0.11 J 0.15 J <0.19 0.24 J 0.23 J 0.11 J <0.19 0.37 0.30 J <0.19 <0.19 0.417 1.75 Vinyl Chloride <0.090 0.072 J <0.090 <0.090 <0.090 <00090 <0.090 <0.090 <0.13 <0.13 <0.090 <0.090 <0.090 <0.090 <0.090 <0.090 2.30 27.9 Notes: 1. Screening critera based on the NC Division of Waste Management Vapor Intrusion Screening Levels (DWM VISL - March 2016) (TCR = 1 x 10-5, THQ = 0.2) Bold indicates exceedance of the Residential IASLUnderline indicates exceedance of the Non-Residential IASL Gray indicates compound not detected above the indicated detection limitTCR = Target Cancer Risk; THQ = Target Hazard Quotient µg/m3 = micrograms per cubic meter; IASL=Indoor Air Screening Level NS = Not Specified; Not ApplicableSamples were collected into 6-L Summa cannisters and analyzed by EPA Method TO-15 over an 8 hour interval IAS = Indoor Air SampleVOCs = Volatile Organic Compounds J flag indicates an estimated concentration above the method detection limit, but below the reporting limit Indoor Air Screening Levels (1) (µg/m3) Indoor Air Screening Levels (1) (µg/m3) IAS-19 / DUP-9-17-16 TITLE PROJECT SITE LOCATION MAP RITE AIDCHARLOTTE, NORTH CAROLINA DATE: JOB NO: REVISION NO: FIGURE NO: 5-2-16 0 1ATL-001 0 2000 4000 APPROXIMATE SCALE IN FEETN U.S.G.S. QUADRANGLE MAP QUADRANGLE 7.5 MINUTE SERIES (TOPOGRAPHIC) CHARLOTTE EAST, NC 1967REVISED/INSPECTED 1988ANDDERITA, NC 1993 SITE BUILDING #2 FORMER BOILER HOUSE BUILDING #48 BUILDING #1 BUILDING #3 BUILDING T-26EXECUTIVE OFFICE REGIONAL TRAINING OFFICE (FORMER CAFETERIA) ? ? SSV-4 SSV-6 SSV-5 SSV-8 SSV-12 SSV-10 SSV-11 SSV-9 BUILDING #50 SSV-7 SSV-3 SHIPPING OFFICE BREAKROOM/ RESTROOMS MAINTENANCE OFFICE OFFICES IAS-2 IAS-1 IAS-4 IAS-3 IAS-5 IAS-7 IAS-8 IAS-10 IAS-6 SSV-1 SSV-2 IAS-9 3 4 9 5 10 8 2 1 6 BAS-1 IAS-23 IAS-22 IAS-13 IAS-12 IAS-15 IAS-17 IAS-14 IAS-11 IAS-16 IAS-21 IAS-20 IAS-19/DUP IAS-18 BAS-3 BAS-2 JOB NO. ATL-001 REVISION NO. 0DATE: 9-26-16 FIGURE NO. 2 RITE AID FACILITY 1776 STATESVILLE AVENUE CHARLOTTE, NORTH CAROLINA INDOOR AIR SAMPLE LOCATION MAP 2923 South Tryon Street-Suite 100 Charlotte, North Carolina 28203 704-586-0007(p) 704-586-0373(f) License # C-1269 / #C-245 Geology LEGEND SITE PROPERTY BOUNDARY ESTIMATED SOLVENT PLUME OFFICE AREAS INDOOR AIR SAMPLE LOCATION (HOFFMAN ENGINEERING INC; 2008) BACKGROUND AIR SAMPLE LOCATION SUB-SLAB SOIL VAPOR SAMPLE LOCATION INDOOR AIR SAMPLE LOCATION BACKGROUND AIR SAMPLE LOCATION TEMPORARY WALL SEAL LOCATION (INSTALLED FOR THE SEPTEMBER 2016 INDOOR AIR SAMPLING EVENT) NOTES: 1.SUB-SLAB VAPOR SAMPLE LOCATIONS SAMPLED IN APRIL 2016. 2.INDOOR AIR SAMPLES (IAS-1 THROUGH IAS-10) AND BACKGROUND AIR SAMPLE (BAS-1) SAMPLED IN JUNE 2016. 3.INDOOR AIR SAMPLES (IAS-11 THROUGH IAS-23) AND BACKGROUND AIR SAMPLES (BAS-2 AND BAS-3) SAMPLED IN SEPTEMBER 2016. 4.DURING JUNE 2016 INDOOR AIR SAMPLING EVENT, THE WIND DIRECTION WAS FROM THE SOUTH. 5.DURING SEPTEMBER 2016 INDOOR AIR SAMPLING EVENT, THE WIND DIRECTION WAS FROM THE NORTH.S:\AAA-Master Projects\ATCO LLC - ATC\Task-010 Indoor Air\Figures\Indoor Air Sample Location Map.dwg, FIG 2, 10/7/2016 11:20:16 AM, tdesa Attachment B Vapor Intrusion Mitigation System Venting Drawings Sheets VM-1, VM-2, and VM-3 751748748a/cLINE OF CLERESTORYABOVELINE OF CLERESTORYABOVELINE OF CLERESTORYABOVELINE OF CLERESTORYABOVENEW STOREFRONT BYRESTAURANT TENANTNEW STOREFRONT BYRESTAURANT TENANTNEWSTOREFRONTBY TENANTNEWSTOREFRONT BYRESTAURANTTENANT, TYP.NORTH PORCHALIGNNEW WALLINFILL INEXISTINGOPENINGCOVERED PORCHSUITE 105SUITE 104NEW STOREFRONTIN NEW OPENINGPOTENTIAL FUTUREKITCHEN LOCATIONNEW UTILITY TRENCHINSTALLED PRIOR TOCUPOLEXW2 W1W3aW3a W3a W1W1 W1 W1W1 W3aW3W3 W3 W3W1W1W3aW3a W2 W2 W1 W1 W1 W1W1 W1 W1 EXISTING RAMP TO REMAINW3W3 NEW STEEL PAN, STEELFRAMED STAIR ANDLANDINGRISERW3W3 W3FREE STANDING PLANTERS (FFE),FEATHER CONCRETE ATTOP OF EXISTING RAMPTO MEET NEW SLABELEVATIONNEW RELOCATEDRISER ROOMLINE OF CLERESTORYABOVENEW STREET SURFACE BELOW,SEE CIVILSTOREFRONTIN EXISTINGOPENINGNEWSTOREFRONTIN OPENINGNEWSTOREFRONTIN EXISTINGOPENINGNEW STOREFRONT INEXISTING OPENINGNEW WALL INFILL INEXISTING OPENINGNEW STOREFRONTIN EXISTINGOPENINGNEW WINDOWSSUITE 101SOUTHPORCHNEWSTOREFRONTSTOREFRONTIN EXISTINGOPENINGNEW STOREFRONTIN NEW OPENINGW1W3NEW UTILITY TRENCHINSTALLED PRIOR TOCUPOLEXW3W1W1W1 W1W1W1W1 F-2F-1F-3F-4SERVICE CORRIDORLEGENDEXISTING I-BEAM COLUMNEXTENT OF CUPOLEX®WINDI H.5 VENTILATED FLOOR AND NEW 4-INCH CONCRETESLAB (5 CM / 2-INCH HEIGHT)4-INCH DIA SCH 40 SOLID PVC OR CAST IRON VERTICAL RISER LOCATION WITH FANNUMBER (SEE DETAILS 8, 9, & 10 ON SHEET VM-2)PROPOSED UTILITY TRENCH(INSTALLED PRIOR TO CUPOLEX AND NEW CONCRETE SLAB)2-INCH DIA SOLID PVC TRANSFER PIPEDIFFERENTIAL PRESSURE SENSOR/ALARM (SEE DETAIL 11 ON SHEET VM-2)MONITORING POINT (SEE DETAIL 6 ON SHEET VM-2PROPOSED STUD WALL (INSTALLED ATOP NEW CONCRETE SLAB)EXISTING WALL TO REMAINPROPOSED LOCATION FOR POST-CONSTRUCTION INDOOR AIR SAMPLENOTES:1.REFER TO SHEET VM-2 FOR VIMS VENTING DETAILS AND SHEET VM-3 FOR VIMSVENTING SPECIFICATIONS.2.REFER TO DETAIL 12 FOR SLAB REPAIR DETAILS AFTER INSTALLATION OFCUPOLEX.3.REFER TO DETAIL 13 FOR RAMPS ARE EXISTING DOORWAYS ARE INSTALLED.4.EXISTING BUILDING CONTAINS AN APPROXIMATE 6" CONCRETE SLAB.5.THE PROPOSED AREA FOR THE CUPOLEX WINDI VENTILATED FLOOR AREA ISAPPROXIMATELY 102,000 SQ FT.6.DIA = DIAMETERSCH = SCHEDULETYP. = TYPICALVIMS = VAPOR INTRUSION MITIGATION SYSTEMH&H NO. ATL.001VAPOR INTRUSIONMITIGATION SYSTEMVENTING LAYOUTREVISION 0JULY 13, 2020VM-1VAPOR MITIGATION PLAN PREPARED BY:2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f)License # C-1269 / #C-245 GeologyPROFESSIONALAPPROVAL07/13/20ISSUED FOR DEQ SUBMITTALBUILDING 2 -NORTH2" SCH 40 PVC TRANSFER PIPES (3 TOTAL)CONNECTING CUPOLEX VOID SPACE(INSTALL THROUGH EXISTING OPENINGS IFPRESENT, TYP)INSTALL RISER WITHINNEW 8" STUD WALLOPEN AIRPORCHOPEN AIRPORCHOPEN AIRPAVILIONOPEN AIRPORCHPROPOSED KESWICKAVENUE EXTENSION(OPEN AIR STREET)OPEN AIR PAVILION2" SCH 40 PVC TRANSFER PIPES (4 TOTAL)CONNECTING CUPOLEX VOID SPACE(INSTALL THROUGH EXISTING OPENINGSIF PRESENT, TYP)EXISTING OPENING IN WALLEXISTING OPENING IN WALLF-1PROPOSED STUD WALL INSTALLEDATOP NEW CONCRETE SLABPROPOSED UTILITY TRENCH FINISHED WITHCOMPACTED GRAVEL OR SOIL, OR CONCRETEPRIOR TO CUPOLEX INSTALLATION PERAPPROVAL OF THE STRUCTURAL ENGINEER.BUILDING 2 - NORTH - VIMS VENTING LAYOUT1" = 40'VM-111VM21VM22VM22VM22VM22VM23VM23VM24VM24VM25VM25VM26VM26VM2REFER TO DETAIL 7 ON SHEET VM-2 FORPENETRATION DETAILS, SUCH ASBATHROOM PLUMBING, TYP.8&10VM28&10VM28&10VM29&10VM26VM21VM24VM22VM2CAMP NORTH END 201 CAMP RD AND 701 KESWICK AVE BROWNFIELDS PROJECT #20050-16-060 CHARLOTTE, NORTH CAROLINAPROPOSED UTILITY TRENCH FINISHED WITHCOMPACTED GRAVEL OR SOIL, OR CONCRETEPRIOR TO CUPOLEX INSTALLATION PERAPPROVAL OF THE STRUCTURAL ENGINEER.S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Figures\VIMP_VENT DRAWINGS.dwg, 7/16/2020 3:18:39 PM, DWG To PDF.pc3 CUPOLEX SECTION AT EXTERIOR WALLNTSVM-21CUPOLEX SECTION AT EXISTING INTERIOR WALLNTSVM-24CUPOLEX SECTION AT PROPOSED INTERIOR STUD WALLNTSVM-22CUPOLEX SECTION AT EXISTING INTERIOR COLUMNNTSVM-23TYPICAL PENETRATION THROUGH CUPOLEXNTSVM-27TYPICAL MONITORING POINT DETAILNTSVM-26TYPICAL SLAB REPAIR SECTIONNTSVM-212TYPICAL RAMP AT DOORWAY (IF INSTALLED)NTSVM-213TYPICAL TRANSFER PIPE SECTIONNTSVM-25TYPICAL RISER PIPE CONNECTION TO CUPOLEX AT INTERIOR COLUMNNTSVM-28 RISER PIPE CONNECTION TO CUPOLEX AT INTERIOR PROPOSED WALLNTSVM-29TYPICAL RISER PIPE AND FAN AT ROOFTOPNTSVM-210 TYPICAL VACUUM ALARM SET-UPNTSVM-211H&H NO. ATL.001VAPOR INTRUSIONMITIGATION SYSTEMVENTING DETAILSREVISION 0JULY 13, 2020VM-2VAPOR MITIGATION PLAN PREPARED BY:2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f)License # C-1269 / #C-245 GeologyPROFESSIONALAPPROVALISSUED FOR DEQ SUBMITTALBUILDING 2 -NORTHASSISTED BY:CAMP NORTH END 201 CAMP RD AND 701 KESWICK AVE BROWNFIELDS PROJECT #20050-16-060 CHARLOTTE, NORTH CAROLINACONDITIONS:1. DRAWINGS AND DESIGNS ARE BASED ON DRAWINGS AND DESIGNS PROVIDED BY PONTAROLOENGINEERING INC. AND ARE BEING USED WITH THEIR CONSENT.2. ANY SUBSTITUTION OF MATERIAL IS STRICTLY PROHIBITED AND DOES NOT COMPLY WITH THEDESIGN PROVIDED.3. THE DOCUMENTS DEFINE THE EXTENT AND SCOPE OF THE WORK BUT DO NOT DELEGATEFUNCTIONS OR WORK TO ANY SPECIFIC TRADE.4. THESE DRAWINGS INDICATE PERFORMANCE AND GENERAL ARRANGEMENT OF WORK. THEYARE DIAGRAMIC EXCEPT WHERE SPECIFIC DETAILS ARE GIVEN. THEY MUST BE READ INCONJUNCTION WITH OTHER DESIGN CONSULTANT'S, ARCHITECTURAL, SITE SERVICES,STRUCTURAL, ELECTRICAL, MECHANICAL, LANDSCAPING AND ALL OTHER DIVISION DRAWINGS.5. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. DO NOT SCALE THESE DRAWINGS.6. THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS BEFORE PROCEEDINGWITH THE WORK. ANY DISCREPANCIES SHALL BE REPORTED TO THE DESIGNER IMMEDIATELY.NOTE:1.REFER TO SHEET VM-1 FOR VIMS VENTING LAYOUT AND SHEET VM-3 FOR VIMSVENTING SPECIFICATIONS.07/13/20S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Figures\VIMP_VENT DRAWINGS.dwg, 7/16/2020 3:19:30 PM, DWG To PDF.pc3 H&H NO. ATL.001VAPOR INTRUSIONMITIGATION SYSTEMVENTINGSPECIFICATIONSREVISION 0JULY 13, 2020VM-3VAPOR MITIGATION PLAN PREPARED BY:2923 South Tryon Street-Suite 100Charlotte, North Carolina 28203704-586-0007(p) 704-586-0373(f)License # C-1269 / #C-245 GeologyPROFESSIONALAPPROVALISSUED FOR DEQ SUBMITTALBUILDING 2 -NORTHASSISTED BY:A. GENERALB. INTENT AND BASIS - ACTIVE VENTING DESIGNC. VENTING SYSTEM RISER PIPESH. SPECIAL INSPECTIONS AND TESTSI. SUBMITTALSJ. VENTING SYSTEM INSPECTION AND MAINTENANCE1. THE PLACEMENT OF THE CUPOLEX® FORMS, RISER PIPE STUBS, INLET PIPE STUBS, UTILITYPENETRATION BOOTS, AND INTERNAL WALL FOOTING AIR TRANSFER PIPES SHALL BE INSPECTEDBY THE DESIGN ENGINEER PRIOR TO POURING OF CONCRETE. THE RISER PIPES, FANINSTALLATION, AND ALARM INSTALLATION SHALL BE INSPECTED BY THE DESIGN ENGINEER PRIORTO OPERATION.2.THE CONTRACTOR SHALL PROVIDE THE DESIGNER OR THE APPROVED CONTRACTOR AT LEAST 48HOURS NOTICE BEFORE REQUESTED INSPECTION TIMES IN ORDER FOR THE INSPECTOR TONOTIFY NC DEQ OF THE UPCOMING INSPECTION.3. THE CONTRACTOR SHALL ARRANGE FOR THE DESIGNER OR APPROVED CONTRACTOR TOPERFORM A VACUUM TEST ON THE COMPLETED CUPOLEX® FLOOR SLAB AFTER ALL JOINT,PENETRATION, CONDUIT, AND OTHER SEALING REQUIRED BY THESE DESIGNS HAS BEENCOMPLETED, AND BEFORE FLOOR COVERINGS ARE PLACED. THE CONTRACTOR SHALL PROMPTLYSEAL ANY LEAKS IN THE FLOOR SLAB IDENTIFIED BY THE VACUUM TEST. THE RESULTS OF THEVACUUM TEST WILL ALSO BE USED BY THE DESIGN ENGINEER TO VERIFY THE FAN OR BLOWER TOBE INSTALLED ON THE VERTICAL RISER PIPE SHOWN IN THESE DRAWINGS IS ADEQUATE, OR TORECOMMEND A DIFFERENT TYPE OF FAN BLOWER TO INSTALL, PER APPROVAL OF NC DEQ.4. THE CONTRACTOR SHALL ARRANGE FOR THE DESIGNER OR APPROVED CONTRACTOR TO CHECKTHE OPERATION OF ALL VENTING SYSTEM ALARMS AND FAN OPERATION, BEFORE THE BUILDING ISOCCUPIED.1. SHOP DRAWINGS, MATERIAL SPECIFICATIONS, INSTALLATION INSTRUCTIONS, OPERATION ANDMAINTENANCE INFORMATION, AND WARRANTIES SHALL BE SUBMITTED TO THE DESIGNER ORAPPROVED CONTRACTOR PRIOR TO FABRICATION, CONSTRUCTION, AND/OR INSTALLATION, ASAPPLICABLE:a.RISER PIPE SPECIFICATIONS AND LOCATIONS (INCLUDING ACTIVE FAN LOCATION)b.VAPORBLOCK PLUS VAPOR BARRIER (VBP20) AND TAPES (OR APPROVED EQUIVALENT)c.VACUUM MONITORS/ALARMS AND LOCATIONS2. SHOP DRAWINGS AND OTHER SUBMITTALS ARE REVIEWED BY THE DESIGNER OR APPROVEDCONTRACTOR ONLY FOR GENERAL COMPLIANCE WITH THESE VENTING DRAWINGS.RESPONSIBILITY FOR CORRECTNESS SHALL REST WITH THE CONTRACTOR. IF THERE ISCONFLICT BETWEEN SHOP AND THESE DRAWINGS OR SPECIFICATIONS THESE DRAWINGSAND/OR SPECIFICATIONS SHALL TAKE PRECEDENCE. REQUESTS TO PERFORM MODIFICATIONSSHALL BE SUBMITTED SEPARATELY FOR THE DESIGNER'S REVIEW.1. THE OWNER SHALL BE RESPONSIBLE FOR THE ROUTINE OPERATION, INSPECTION,CALIBRATION, AND MONITORING OF THE VENTING SYSTEM ACCORDING TO MANUFACTURERRECOMMENDATIONS, AS APPLICABLE, INCLUDING:a.INSPECTION AND REPAIR OF SEALS IN THE SLAB, AND SEALING OF ANY NEW CRACKS OROPENINGS IN THE SLAB THAT OCCUR FOR ANY REASON; ANDb.IF THE SYSTEM MONITOR (SENSAPHONE SENTINEL) ALARM SOUNDS DURING ACTIVEOPERATION, THE CAUSE OF THE ALARM SHALL BE DETERMINED AND CORRECTED.2. THE OWNER SHALL DESIGNATE A PERSON OR DEPARTMENT RESPONSIBLE FOR THEOPERATION, INSPECTION, MONITORING, AND AS NECESSARY, REPAIR OF THE VENTING SYSTEMDESCRIBED IN THESE DRAWINGS AND ASSOCIATED VAPOR INTRUSION MITIGATION PLAN. THISPERSON SHALL BE FAMILIAR WITH THESE DRAWINGS AND THE OPERATION OF THE FANS ANDMONITORING EQUIPMENT.1. THE VENT RISER PIPE SHALL PENETRATE THE CUPOLEX FLOOR SLAB AT THE LOCATION SHOWNON DRAWING VM-1 AND RISE VERTICALLY AND EXIT THE BUILDING AS SHOWN ON DRAWING VM-2.2. THE RISER PIPE SHALL BE SCHEDULE 40 PVC WITH CLASS A FIRE RATING AND FLAME/SMOKE INDEXOF AT MOST 25/50 BY ASTM METHOD E84 OR CAST IRON MAY BE USED INSTEAD OF PVC. CAST IRONPIPE (CIP) SHALL BE HUBLESS (NO HUB).3. ALL PVC PIPING CONNECTIONS SHALL BE SOLVENT CEMENTED AND PERMANENTLY SEALED USINGA PRIMER MEETING THE REQUIREMENTS OF ASTM F656 AND A SOLVENT MEETING THEREQUIREMENTS OF ASTM D2564. THE SOLVENT SHALL BE LOW VOC AND CONTAIN NOTETRACHLOROETHENE (PCE) OR TRICHLOROETHENE (TCE). JOINTS SHALL BE MADE WHILE THESOLVENT IS WET AND SHALL BE IN ACCORDANCE WITH ASTM D2855 AND ASTM F402. ALL HUBLESSCAST IRON CONNECTIONS SHALL BE MADE WITH SHIELDED HUBLESS COUPLINGS MANUFACTURED INACCORDANCE WITH CISPI 310 OR ASTM C 1277 AND CERTIFIED BY NSF® INTERNATIONAL.4. THE RISER PIPE SHALL BE INSTALLED IN A SECURE AND PLUMB MANNER IN THE CUPOLEX® FORMSPRIOR TO POURING OF THE CONCRETE FLOOR SLAB. THE RISER PIPE STUB MUST BE MARKED ORLABELED ABOVE THE FLOOR.5. THE RISER PIPE SHALL BE INSTALLED IN COMPLIANCE WITH THE MECHANICAL AND PLUMBINGDRAWINGS FOR THIS PROJECT INCLUDING, BUT NOT LIMITED TO, ANY PIPE WRAP AND FIRE STOPREQUIREMENTS, ALL APPLICABLE BUILDING AND FIRE CODES, AND SHALL BE TIED-OFF (I.E.,VERTICALLY SUPPORTED) AT EACH FLOOR.6. ALL VERTICAL PIPE RUNS SHALL BE SUPPORTED AT LEAST EVERY 10 FEET AND AT EVERYPENETRATION THROUGH SLABS, CEILINGS, OR ROOF DECKS.7. HORIZONTAL RUNS SHALL BE SUPPORTED AT LEAST EVERY 6 FEET WITH CODE APPROVEDHANGERS. ALL HORIZONTAL RUNS SHALL BE SUPPORTED WITHIN TWO FEET OF EACH FITTING.8. HORIZONTAL PIPE RUNS SHALL SLOPE A MINIMUM OF 1/8" PER FOOT (1%) RUN TO ENSURE THATANY CONDENSATION OR MOISTURE IN THE PIPE WILL DRAIN TOWARD THE VERTICAL RISER ANDFLOOR PENETRATION.9. THE TOTAL LENGTH OF PIPE AND NUMBER OF FITTINGS BETWEEN THE FLOOR PENETRATION POINTAND THE EXHAUST POINT SHALL BE MINIMIZED TO THE EXTENT PRACTICAL TO REDUCE FRICTIONLOSSES IN THE PIPE.10. EACH VERTICAL AND HORIZONTAL RUN OF ACCESSIBLE RISER SHALL BE CLEARLY ANDPERMANENTLY LABELED AT LEAST EVERY TEN (10) FEET WITH "VAPOR MITIGATION SYSTEM -CONTACT MAINTENANCE". A LABEL SHALL BE AFFIXED NEAR THE VACUUM ALARMS WITH "VAPORMITIGATION SYSTEM - CONTACT MAINTENANCE IF ALARM IS ACTIVATED". OTHER SIMILAR LANGUAGEMAY BE USED FOR THE LABELS PER APPROVAL OF THE ENGINEER.11. VAPOR BARRIER USED FOR SLAB REPAIRS OR UNDER RAMPS AT DOORWAYS SHALL BE RAVENINDUSTRIES 20-MIL VAPOR BLOCK PLUS, OR EQUIVALENT VAPOR BARRIER APPROVED BY THEDESIGN ENGINEER AND NC DEQ.1. THE INTENT OF THIS DESIGN IS TO USE CUPOLEX® WINDI H.5 CONCRETE FORMING SYSTEMS TOVENT THE VOID SPACE (BELOW THE FLOOR SLAB) AT A RATE SUFFICIENT TO PREVENT VOLATILEORGANIC COMPOUNDS (VOCS) FROM INTRUDING INTO THE BUILDING.2. VENTING OF THE CUPOLEX® VOID SPACE WILL BE PERFORMED BY ACTIVE VENTING USING FOUR(4) RISER PIPES WITH ELECTRIC AMG LEGEND BLOWER FANS TO VENT THE RISER PIPES (AS SHOWNON DRAWING VM-2) SUCH THAT THE FAN OR BLOWER WILL PULL AIR FROM THE SUB-SLAB VOIDSPACE THROUGH ITS VERTICAL RISER PIPE AND CREATE A RELATIVE VACUUM IN THE SUB-SLAB VOIDSPACE COMPARED TO INDOOR AIR. A MINIMUM DIFFERENTIAL PRESSURE OF 4 PASCALS, ASREQUIRED BY THE NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY (NC DEQ)BROWNFIELDS PROGRAM, SHALL BE ACHIEVED ACROSS THE SLAB. BASED ON THE INFLUENCETESTING RESULTS, AN ALTERNATIVE FAN MAY BE SELECTED UPON APPROVAL OF THE ENGINEERAND NC DEQ.3. A LOW AIR PERMEABILITY FLOOR WILL BE ACCOMPLISHED BY THE INTERLOCKING CUPOLEX FORMSAND THE CONCRETE SLAB, SEALS PLACED AROUND PIPE PENETRATIONS OF THE CUPOLEX FORMSAND SLAB, AND BY PROPERLY SEALING JOINTS, PENETRATIONS, AND OTHER POTENTIAL AIR FLOWPATHWAYS IN THE SLAB.4. PROPOSED UTILITY TRENCHES INSTALLED WITHIN EXISTING CONCRETE SLAB SHALL BE FINISHEDWITH COMPACTED GRAVEL, COMPACTED SOILS, CONCRETE, OR SIMILAR, AND SET FLUSH WITHSURROUNDING FLOOR SERVICE PRIOR TO INSTALLATION OF THE CUPOLEX FORMS. THE UTILITYTRENCH INSTALLATIONS AND BACKFILL SHALL BE APPROVED BY THE STRUCTURAL ENGINEER PRIORTO INSTALLATION THE CUPOLEX FORMS.1. THE WORK DEPICTED ON THESE DRAWINGS SHALL BE PERFORMED BY AN EXPERIENCEDCONTRACTOR WHO HAS A WORKING KNOWLEDGE OF APPLICABLE CODE STANDARDS AND INDUSTRYACCEPTED STANDARD GOOD PRACTICE. NOT EVERY CONDITION OR ELEMENT IS OR CAN BEEXPLICITLY SHOWN ON THESE DRAWINGS; THEREFORE, THE CONTRACTOR SHALL USE INDUSTRYACCEPTED STANDARD GOOD PRACTICE FOR MISCELLANEOUS WORK NOT EXPLICITLY SHOWN.2. ALL WORK SHALL BE IN COMPLIANCE WITH FEDERAL, STATE, AND LOCAL BUILDING, FIRE, ANDELECTRICAL CODES.3. THE CONTRACTOR SHALL CONFER WITH AND SEEK THE APPROVAL OF THE ARCHITECT FOR THEFINAL LOCATIONS OF VENTING SYSTEM COMPONENTS.4. SEE STRUCTURAL PLANS FOR ALL STRUCTURAL CONCRETE DIMENSIONS AND DETAILS. SEEARCHITECTURAL PLANS FOR ALL WALL, CEILING, AND ROOF DIMENSION DETAILS.5. ALL INSPECTIONS REQUIRED BY BUILDING CODES AND/OR THESE DRAWINGS SHALL BE PROVIDEDBY DESIGNER AND/OR THE BUILDING DEPARTMENT AS APPLICABLE.1. THE IN-LINE FAN ON THE RISER PIPE SHALL BE INSTALLED AS CLOSE AS PRACTICABLE TO THEPOINT OF EXIT FROM THE BUILDING. SEE SHEET VM-1 FOR RISER PIPE LOCATION AND SHEET VM-2FOR VENT RISER PIPE SECTION. THE FAN AREA MUST BE ACCESSIBLE FOR FUTURE FANMAINTENANCE AND/OR REPLACEMENT AS REQUIRED.D. VENTING SYSTEM AIR TRANSFER PIPESE. ACTIVE VENTING SYSTEM FANS OR BLOWERSF. ACTIVE VENTING SYSTEM MONITORS AND ALARMSG. SEALING OF JOINTS, CRACKS, AND OPENINGS IN THE SLAB2. PROVIDE 120 VOLT ELECTRIC SERVICE WITH A DEDICATED CIRCUIT BREAKER WITHIN FIVE (5) FEETOF THE FAN LOCATION.3. THE EXHAUST POINT SHALL BE AT LEAST 15 FEET HORIZONTALLY FROM ANY HVAC AIR INTAKES OROTHER OPENINGS INTO THE BUILDING. THE RISER EXHAUST POINT SHALL BE AT LEAST 3 FEETABOVE THE BUILDING ROOF LINE.1. A SENSAPHONE DIFFERENTIAL PRESSURE SENSOR SHALL BE INSTALLED AT EACH RISER PIPE ANDCONNECTED TO A CENTRALIZED SENSAPHONE SENTINEL REMOTE MONITORING DEVICE, OR SIMILARALARM SYSTEM APPROVED BY THE ENGINEER, AS SHOWN ON SHEETS VM-1 AND VM-2. THECENTRALIZED SENSAPHONE SENTINEL DEVICE SHALL BE INSTALLED IN A SUITABLE MONITOREDLOCATION TO BE IDENTIFIED BY THE OWNER OR ARCHITECT. THE SENSAPHONE SENTINEL SHALL BENO MORE THAN 700 FT FROM EACH DIFFERENTIAL PRESSURE SENSOR.2. PROVIDE 120 VOLT ELECTRIC SERVICE AT AN ELECTRICAL JUNCTION BOX WITHIN FIVE (5) FEET OFTHE DIFFERENTIAL PRESSURE SENSOR. A 24 V DC POWER SUPPLY ACCESSORY SHALL BEINSTALLED AT THE OUTLET TO PROVIDE POWER TO THE DIFFERENTIAL PRESSURE SENSOR.3. THE ALARM SYSTEM SHALL CONSIST OF VISUAL AND/OR AUDIBLE SIGNALS TO NOTIFY OCCUPANTSIF VACUUM LEVELS INDICATE THE ACTIVE FAN OR BLOWER IS NOT OPERATING.4. ALARMS SHALL BE SET TO BE ACTIVATED WHEN VACUUM LEVELS IN THE RISER PIPE DROP BELOW0.25 INCHES OF WATER COLUMN, OR OTHERWISE APPROVED BY THE DESIGN ENGINEER.5. LOW-VACUUM LEVEL ALARMS SHOULD BE READILY VISIBLE TO BUILDING STAFF.6. A LABEL SHALL BE AFFIXED NEAR THE VACUUM ALARMS WITH "VAPOR MITIGATION SYSTEM -CONTACT MAINTENANCE IF ALARM IS ACTIVATED". OTHER SIMILAR LANGUAGE MAY BE USED FORTHE LABELS PER APPROVAL OF THE ENGINEER.1.THE INTENT OF THIS WORK IS TO MINIMIZE THE LEAKAGE OF VAPOR BETWEEN THE VOIDSPACE AND THE INDOOR AIR SPACE OF THE BUILDING.2.ALL FLOOR SLAB PENETRATIONS INCLUDING BUT NOT LIMITED TO EXPANSION JOINTS,CONTROL JOINTS, CONSTRUCTION JOINTS, ISOLATION JOINTS, OPEN CRACKS IN THECUPOLEX® FLOOR SLAB, PLUMBING AND ELECTRICAL CONDUITS, VENTING SYSTEM PIPES,ETC. SHALL BE SEALED USING URETHANE CAULK ACCORDING TO THE MANUFACTURER'SRECOMMENDATIONS. A LOW-VOC URETHANE CAULK SHALL BE USED THAT CONTAINS NOPCE OR TCE.3.THE ANNULUS OF ALL UTILITIES, PIPES, AND OTHER CONDUITS THAT PENETRATE THECUPOLEX® FLOOR SLAB SHALL BE SEALED WITH A URETHANE CAULK ACCORDING TOMANUFACTURER'S RECOMMENDATIONS AND IN A MANNER MEETING APPLICABLE FIRECODES. A LOW-VOC URETHANE CAULK SHALL BE USED THAT CONTAINS NO PCE OR TCE.4.ALL OPENINGS IN THE CUPOLEX® FLOOR SLAB, SUCH AS OPENINGS CREATED BY PLUMBINGBOX OUTS FOR BATHROOM FIXTURES, SHALL BE SEALED USING SUITABLE EXPANDING FOAMSEALANTS OR URETHANE CAULK. LOW-VOC FOAM SEALANTS AND URETHANE CAULK SHALLBE USED THAT CONTAIN NO PCE OR TCE.5.URETHANE CAULK OR SEALANT SHALL COMPLY WITH FEDERAL SPECIFICATION TT-5-00230C(E.G.PECORA CORPORATION'S DYNATROL1-Xl.OR TREMCO'S VULKEM 116)AND FIRE CODES AS APPLICABLE.6.ALL THE ABOVE SEALANT APPLICATIONS WILL BE MADE AT THE FINISHED CONCRETEFLOOR SURFACE.1. AIR TRANSFER PIPES SHALL BE INSTALLED AT INTERVALS THROUGH EXITING WALLS, EXISTINGVOIDS, OR THICKENED SLAB AREAS TO CONNECT THE VOID SPACES OF THE CUPOLEX FLOOR ONEITHER SIDE OF THE WALLS OR THICKENED SLABS. TRANSFER PIPES SHALL BE INSTALLED, ASNEEDED, TO CONNECT ALL VOID SPACES. TRANSFER PIPES SHALL BE INSTALLED TO CONNECTISOLATED AREAS OF THE VOID SPACE TO OTHER AREAS AND, AS NEEDED, TO ALLOW MOREEFFICIENT MOVEMENT OF AIR BETWEEN AREAS OF THE FLOOR.2. AIR TRANSFER PIPES SHALL BE PROVIDED AT INTERIOR WALLS, FOOTINGS, GRADE BEAMS,THICKENED SLABS, OR OTHER OBSTRUCTIONS TO SUB-SLAB AIR MOVEMENT AS SHOWN ON THEDETAILS ON DRAWING VM-2.3. AIR TRANSFER PIPES SHALL BE MADE OF 2-INCH DIAMETER SCHEDULE 40 PVC OR OTHERSUITABLE PIPE MATERIAL SPECIFIED BY THE STRUCTURAL ENGINEER.4. ALL AIR TRANSFER PIPE LOCATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER PRIORTO INSTALLATION TO ENSURE THAT THE INTEGRITY OF THE FOOTING/BEAM OR OTHER STRUCTURESIS NOT IMPACTED.5. IF A SECTION OF CUPOLEX FLOORING IS CUT OR REMOVED, IT MUST BE REPAIRED WITHHORIZONTAL AIR TRANSFER PIPES PLACED THROUGH THE REPAIR ITSELF, AS SHOWN ON THEDETAILS ON SHEET VM-2, TO CONNECT THE VOID SPACES ON EITHER SIDE OF THE REPAIR TOPREVENT THE ISOLATION OF ANY VOID SPACES.4. A VARMINT GUARD SHALL BE INSTALLED ON THE TOP OF THE RISER PIPE AS SPECIFIED ON SHEETVM-2.CONDITIONS:1. DRAWINGS AND DESIGNS ARE BASED ON DRAWINGS AND DESIGNS PROVIDED BY PONTAROLO ENGINEERING INC.AND ARE BEING USED WITH THEIR CONSENT.2. ANY SUBSTITUTION OF MATERIAL IS STRICTLY PROHIBITED AND DOES NOT COMPLY WITH THE DESIGN PROVIDED.3. THE DOCUMENTS DEFINE THE EXTENT AND SCOPE OF THE WORK BUT DO NOT DELEGATE FUNCTIONS OR WORKTO ANY SPECIFIC TRADE.4. THESE DRAWINGS INDICATE PERFORMANCE AND GENERAL ARRANGEMENT OF WORK. THEY ARE DIAGRAMICEXCEPT WHERE SPECIFIC DETAILS ARE GIVEN. THEY MUST BE READ IN CONJUNCTION WITH OTHER DESIGNCONSULTANT'S, ARCHITECTURAL, SITE SERVICES, STRUCTURAL, ELECTRICAL, MECHANICAL, LANDSCAPING AND ALLOTHER DIVISION DRAWINGS.5. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. DO NOT SCALE THESE DRAWINGS.6. THE GENERAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS BEFORE PROCEEDING WITH THE WORK.ANY DISCREPANCIES SHALL BE REPORTED TO THE DESIGNER IMMEDIATELY.5. A LABEL SHALL BE AFFIXED NEAR THE ELETRIC FAN WITH "VAPOR MITIGATION SYSTEM - CONTACTMAINTENANCE IF FAN IS NOT OPERATING". OTHER SIMILAR LANGUAGE MAY BE USED FOR THELABELS PER APPROVAL OF THE ENGINEER.CAMP NORTH END 201 CAMP RD AND 701 KESWICK AVE BROWNFIELDS PROJECT #20050-16-060 CHARLOTTE, NORTH CAROLINANOTE:1.REFER TO SHEET VM-1 FOR VIMS VENTING LAYOUT AND SHEET VM-2 FOR VIMSVENTING DETAILS.07/13/20S:\AAA-Master Projects\ATCO LLC - ATC\ATL-001 - Rite Aid\Task-009 Brownfields\VIMS Design\Figures\VIMP_VENT DRAWINGS.dwg, 7/16/2020 3:19:45 PM, DWG To PDF.pc3 Attachment C Cupolex® Specification Sheets and Structural Slab Design Sheets CUPOLEX-WINDI® creates a ventilated floor in new or remodeled building without affecting the structure of the building. The adoption of CUPOLEX- WINDI® allows you to save on waterproof sheathing and guarantees a constant seal against dampness. CUPOLEX-WINDI® may also be easily attached to walls to obtain an air space capable of ventilating and eliminating mold and installed to create ventilated flat or pitched roofs. Concrete is poured over the modular forms to create floating or structural grade supported slabs, partially supported or fully supported slabs on beam, piles or deep foundations. The unique concrete geometry Cupolex creates, forms an under slab void that can be passively or mechanically vented to remove moisture and soil gases, protecting buildings against the ingress of harmful soil gasses. Applications  Radon & Soil Gas (VI) Mitigation  Basement subfloors  Post tensioned reinforced Concrete Slabs  Concrete Slab on Grade or basement slabs  Replacing Gravel Drainage Layers  Replacing Vapor Barriers & Liners  Building Green With LEED  Technical/Electrical Sub Floors  Acoustical Floors  Ventilating flat or pitched roofs  Green Roofs  Solution to provide a drainage layer on terraces and balconies. Installation CUPOLEX WINDI® provides Excellent Flexibility in Working with new construction or remodeled building layouts. The main characteristics of the forming system are speed and simplicity; the following points should be adhered to:  On average two laborers set 110 m2/hr (1200 sf/hr)  Layout complies with a grid system  Can be installed on any resting surface - soil, gravel, mud slab, etc.  Each CUPOLEX® Form has an installation arrow  Forms are Installed by starting from left to right and top to bottom  Ensure that the feet connection pins are correctly inserted into their connection holes  Pouring and finishing of the concrete slab in the conventional manner TECHNICAL DATA SHEET CUPOLEX - WINDI H.5cm (1.97”) CWTDS.H5 – CUPOLEX-WINDI ADVANTAGES  Arrives on site packaged and ready to be installed  Quick and simple to install with basic hand tools  Can be easily adapted to site variations  Minimizes concrete wastage  made out of 100% non-toxic recyclable material which can contributes to GREEN or LEED certified building  One pallet of CUPOLEX replaces 7.5 trucks of gravel or fill  Minimizes construction traffic damage  Manufactured to ISO 9001:2000 high quality standards  A full range of accessories and field support ensures secure construction ADVANTAGES  Arrives on site packaged and ready to be installed  Quick and simple to install with basic hand tools  Can be easily adapted to site variations  Minimizes concrete wastage  made out of 100% non-toxic recyclable material which can contributes to GREEN or LEED certified building  One pallet of CUPOLEX replaces 7.5 trucks of gravel or fill  Minimizes construction traffic damage  Manufactured to ISO 9001:2000 high quality standards  A full range of accessories and field support ensures secure construction Advantages  Arrives on site packaged and ready to be installed  Quick and simple to install with basic hand tools  Can be easily adapted to site variations  Minimizes concrete wastage  Made out of 100% non-toxic recyclable material which contributes to LEED certified building  One pallet of CUPOLEX replaces 7.5 trucks of gravel or fill  Minimizes construction traffic damage  Manufactured to ISO 9001:2000 high quality standards  A full range of accessories and field support ensures secure construction CWTDS.WINDI H5 - CUPOLEX V1 01/16 CUPOLEX.CA CWTDS. CUPOLEX - WINDI H5 TECHNICAL DATA SHEET Product Data Made from 100% recycled Polypropylene (PP) plastic, the CUPOLEX-WINDI® forms provide the maximum performance and guarantees superior characteristics of stability and resistance in its structure to allow operations that are completed directly above the plastic CUPOLEX-WINDI® elements before and during the placement of the concrete. CUPOLEX-WINDI® Forms are molded in a variety of depths to deal with different levels of Vapor emission and for different depths of fill requirements. CWTDS.WINDI H5 - CUPOLEX V1 01/16 CUPOLEX.CA Storage & Handling  All products are delivered on heat treated wood pallets with polythene wrapping  Handle CUPOLEX-WINDI® with safety gloves and safety glasses  Avoid impact  Avoid tipping CUPOLEX-WINDI® pallets  See specific instructions for installing product in temperatures below 0°C or above 35°C.  CUPOLEX-WINDI® waste can be completely recycled. Issued 01/16 Consistent with manufacturer Pontarolo Engineering’s policy of continued research and development, we reserve the right to modify or update the information contained in this or any other material published by Pontarolo Engineering®. The onus remains on the user of CUPOLEX® to obtain the most recent information available. Because Pontarolo Engineering® has no control over the installation, workmanship, accessory materials or conditions of application, no responsibility or expressed or implied warranty, either as to merchantability or fitness for a particular purpose, is made as to the performance or results of an installation using CUPOLEX® Forms, except that the physical characteristics of CUPOLEX® Forms shall meet or exceed the specifications published by Pontarolo Engineering®. Cupolex®, Beton Stop®, Pontex®, Cupolex Windi®, Cupolex Rialto®, Cupolex Building Systems®, and any other marks, drawing or symbols identifying products and/or services of Cupolex Building Systems are trademarks of Pontarolo Engineering Inc. Concrete Consumption: 0.008m3/m2 (0.0010cy/sf) Form depth: 5cm (2”) Plan Dimension: 56cm x 56cm (22” x 22”) Clear Void Equivalent: 4cm (1.57”) Packaging CUPOLEX-WINDI® is packaged on heat treated wood pallets wrapped with cellophane and certified for international shipping. Pallet Dimension: 1.2m x 1.2m x h 2.0m (4’ X 4’ X h 6.5’) No. Of Units per Pallet: 480 Area per Pallet: 150m2 (1,614sf) Weight per Unit: 1.05kg (2.31Lbs) Total Weight per Pallet: 504kg (1,111Lbs) Material Made from 100% recycled Polypropylene (PP) plastic. The forms provide the maximum performance and guarantees superior characteristics of stability and resistance in its structure to allow operations that are completed directly above the plastic CUPOLEX- WINDI ® elements before and during the placement of the concrete. Attachment D Vapor Intrusion Mitigation System Product Specification Sheets Radon Fan—AMG Legend The AMG Legend is a medium wattage fan suitable for very large building footprints with porous or semi-porous sub-slab soils. All AMG Radon fans are UL Listed for Residential, Commercial AND Industrial Use. All AMG Radon Fans are backed by a 5-year full replacement warranty. All AMG Radon Fans have attractive dove-gray, dough molded glass fiber, non-yellowing UV-resistant casings. All AMG Radon Fans have exceptionally reliable and quiet German-made EBM motors. CLOUD BASED MONITORING HOW LONG BEFORE YOU KNOW SOMETHING IS WRONG? COUNTLESS INDUSTRIES DEPEND ON SENSAPHONE FOR THE MOST COMPREHENSIVE REMOTE MONITORING SOLUTIONS AVAILABLE. WHEN YOU NEED TO BE ABSOLUTELY SURE A REMOTE SITE IS STABLE, SECURE, AND MONITORED AROUND THE CLOCK, THERE’S NO SUBSTITUTE FOR CERTAINTY. ClOUd-Based MOnitOring... COnvenient weB-Based ManageMent • Supervised internet connection assures the sentinel is online and monitoring at all times • Manage an unlimited number of devices from one account • Monitor up to 12 external sensors or equipment status • Receive an e-mail, phone call, or text message when an alarm is detected • Real time status updates available • Included battery backup • Cellular coverage available from at&t and verizon MONITORING & ALERTING LIT-1035 © SENSAPHONE 3/2016SENSAPHONE® 901 TRYENS ROAD ASTON, PA 19014 PH: 877-838-0125 F: 610-558-0222 WWW.SENSAPHONE.COM/Sentinel Distributed By: in tHe ClOUd The Sentinel system stores all sensor readings in the cloud, which provides unlimited information storage. Multiple devices can be managed from one account using intuitive web-based management tools. Enhanced data logging capabilities allow users to print, graph or export accurate historical records. The Sentinel system also can produce event reports and deliver them daily via e-mail, as well as generate an audit trail of all user data activities, edits or deletions. The device is Ethernet based, but it is available with a cellular option for locations that do not have Internet access. envirOnMental MOnitOring FOr tHe MOBile age The cloud-based Sentinel allows you to monitor remote facilities and environments and check critical conditions of your sensitive commodities with the same degree of certainty you’ve come to expect from Sensaphone. It takes the burden out of managing your system by giving you access to your readings from anywhere using a simple, powerful web-based interface and mobile app. If there’s a disruption, you’ll be the rst to know. Alerts can be sent straight to your mobile device—keeping you updated and giving you peace-of-mind wherever you are. Mobile app available for android and iphone Powered by america’s largest cellular networksLearn More: www.sensaphone.com/ Sentinel Sentinel ALARM NOTIFICATION METHODS: E-Mail, Text Messages, Voice Phone Calls Programmable alarm escalation levels Comprehensive scheduling per input, profile, and alarm destination Unlimited number of User Profiles Multiple contact types per user INPUTS: 12 Universal Inputs • Normally Open / Normally Closed Dry Contact • 2.8K / 10K Thermistor • 4-20mA Current Loop • Pulse Count • 12 Bit Resolution TEMPERATURE SENSING RANGE: -109° to 168°F | -85° to 76°C RELAY OUTPUT: Programmable. Rated for 1A 30VAC/ 1A 30VDC DATA LOGGING: Unlimited samples securely stored on the Sentinel servers Programmable sampling interval - 1 min to 24 hrs User programmable channel selection COMMUNICATION PORTS: Ethernet 10/100Base–T STANDARDS: FCC Part 15 – Class A Compliant BATTERY BACKUP: 4.8V 2000mAHr NiMh Battery pack (included) Provides 8 hours of backup LOCAL INDICATORS: 12 Alarm Status LEDs • Power LED • Online LED • Standby LED • Ethernet link and Activity LEDs POWER REQUIREMENTS: Comes with 12VDC plug-in power supply. (International power options available). ENVIRONMENTAL: Operating Humidity: 0-90% RH, non–condensing Operating Temperature: 32° to 122°F | 0° to 50°C PHYSICAL: In metal enclosure: 5.5 x 5.5 x 1.5” | 140 x 140 x 38mm 1 lb. | .45kg With Weatherproof Enclosure: 12.17 x 10.25 x 3.5” | 309 x 260 x 89mm 3.7 lb. | 1.67 kg ENCLOSURE: Durable powder coated metal housing suitable for wall or panel installation or weatherproof NEMA 4X rated fiberglass enclosure. Technical Specifi cations 901 Tryens Road • Aston, PA 19014 • PH: 877-373-2700 • F: 610-558-0222 • www.sensaphone.com MADE INUSA Family owned and made in the USA since 1985 901 Tryens Road Aston, PA 19301 Phone: 877-373-2700 Web: sensaphone.com TECH SPECS All specifi cations subject to change without notice Product Name Part Number 4-20mA Di erential Pressure Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-0302 24VDC Power Supply for 4-20mA Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FGD-0070 Media Compatibility Dry air or inert gas Input Power 2-wire, loop-powered 4 to 20 mA Mode Unidirectional or bidirectional, switch selectable Pressure Ranges Uni Directional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable Bi Directional: ±0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable Dimensions 3.3” x 4.5” x 2.2” | 84mm x 114mm x 55mm Sensor Series 4-20mA Series Notes Requires a 24VDC power supply (FGD-0070) Measure static or di erential pressure A universal design monitors differential or static pressures in commercial buildings, these sensors offer exceptional job-site fl exibility. Excellent tolerance to overpressure & vibration reduces fi eld failures. High accuracy digital sensor maintains calibration and reduces callbacks. The sensors monitor positive and negative pressure for application versatility and the LCD is ideal for set-up, troubleshooting and measuring. 4-20mA Type Di erential Pressure Sensor4-20mASeries SENSAPHONE® REMOTE MONITORING SOLUTIONS SENSAPHONE DIFFERENTIAL/STATIC PRESSURE SENSOR • FGD-0302 Installation Instructions The Sensaphone Differential/Static Pressure sensor will allow you to monitor pressures with any Sensaphone that will accept a 4-20mA Input signal. The FGD-0302 will require a 24VDC power supply to operate (Part No: FGD-0070) for any Sensaphone that does not provide 24VDC output power. Note on wiring: Use 22AWG shielded wiring for all connections (Sensaphone Part No. FGD-0010) and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as motors. Disconnect the power supply before making any con- nections to prevent electrical shock or equipment damage. Make all connections in accordance with national and local codes. Described below is the correct way to wire your sensor to your Sensaphone. 1. Follow your Sensaphone’s owners manual to configure the input for a 4-20mA sensor. 2. Remove the sensor front cover. 3. Connect the 24VDC Power Supply Positive (+) to the sensor terminal marked PWR. 4. Connect the 24VDC Power Supply Negative (-) to the Sensaphone Zone Negative (-) 5. Connect the Sensaphone Zone Positive (+) to the terminal marked COM. + – SENSAPHONE 4-20mA Power Supply with Battery Backup POWER (4-20mA)OUT (0-10v)COMZERO Volt VOLT OUTPUTmA 5V/10VJP4 MODEBI/UNIJP5 WARNING: Do not apply power to output terminal! Permanent damage will result. RESPONSEFAST/STD UNITSIN W.C./PA JP7 JP8 0 1 2 3 4 5 6 74-20mA | 0-10V | COM | Sensor Terminal Block PWR OUT 1.000ZERO + – + – SENSAPHONE • 901 TRYENS ROAD • ASTON, PA 19014 • PH: 610-558-2700 F: 610-558-0222 • LIT-0186 07122 TM PX SERIES INSTALLATION GUIDE OPERATION This device employs ceramic capacitive sensors and sophisticated temperature compensation circuitry. The sensor achieves its best accuracy after an initial warm-up lowest pressure ranges appear erroneous. Following this initial warm-up period, the LCD DISPLAY: .edam si noitceles nehw ”TES“ egnar setacidni yliratnemom yalpsid Pressure is normally indicated on the display. Units are in inches water column (in. W.C.), Pascals (Pa) or kilopascals (kPa) as indicated on the display. The display shows OVER when the pressure is over range. ZERO: Press and hold the ZERO pushbutton for 2 seconds or provide contact closure on ‘AUX ZERO’ terminal to automatically reset the output and display to zero pressure. To protect the unit from accidental zero, this feature is enabled only when the detected pressure is within about 0.1 in. W.C. (25 Pa) of factory calibration. WIRING & CONFIGURATION Connect the transmitter to the Sensaphone and power supply as indicated below. Set the switch to current (mA) mode. Jumper JP4: select 0-10 V. Jumper JP5: select bidirectional or unidirectional mode. Jumper JP7: select inches W.C. or Pascal scale Jumper JP8: select fast or standard response time. Align the arrow (not the slot) on the rotary switch to the desired full-scale range. LCD models momentarily indicate the selected range. 2-wire, 4-20 mA POWER (4-20mA)OUT (0-10v)COMZERO Volt VOLT OUTPUTmA 5V/10V JP4 MODEBI/UNI JP5 ZERO 1.000WARNING: Do not apply power to output terminal! Permanent damage will result. RESPONSEFAST/STD UNITSIN W.C./PA JP7 JP8 0 1 2 3 4 5 6 7Range Selection Guide Rotary Switch Position Inches W.C.Pascal 0 0.1 25 1 0.25 50 2 0.5 100 3 1 250 4 2.5 0.5 kPa 5 5 1 kPa 6 10 2.5 kPa 7 10 2.5 kPa sensor maintains its specied accuracy and stability. 07122 TM PX SERIES INSTALLATION GUIDE OPERATION This device employs ceramic capacitive sensors and sophisticated temperature compensation circuitry. The sensor achieves its best accuracy after an initial warm-up lowest pressure ranges appear erroneous. Following this initial warm-up period, the LCD DISPLAY: .edam si noitceles nehw ”TES“ egnar setacidni yliratnemom yalpsid Pressure is normally indicated on the display. Units are in inches water column (in. W.C.), Pascals (Pa) or kilopascals (kPa) as indicated on the display. The display shows OVER when the pressure is over range. ZERO: Press and hold the ZERO pushbutton for 2 seconds or provide contact closure on ‘AUX ZERO’ terminal to automatically reset the output and display to zero pressure. To protect the unit from accidental zero, this feature is enabled only when the detected pressure is within about 0.1 in. W.C. (25 Pa) of factory calibration. WIRING & CONFIGURATION Connect the transmitter to the Sensaphone and power supply as indicated below. Set the switch to current (mA) mode. Jumper JP4: select 0-10 V. Jumper JP5: select bidirectional or unidirectional mode. Jumper JP7: select inches W.C. or Pascal scale Jumper JP8: select fast or standard response time. Align the arrow (not the slot) on the rotary switch to the desired full-scale range. LCD models momentarily indicate the selected range. 2-wire, 4-20 mA POWER (4-20mA)OUT (0-10v)COMZERO VoltVOLT OUTPUTmA5V/10V JP4 MODEBI/UNI JP5 ZERO1.000WARNING: Do not apply power to output terminal! Permanent damage will result. RESPONSEFAST/STD UNITSIN W.C./PA JP7 JP8 0 1 2 3 4 5 6 7Range Selection Guide Rotary Switch Position Inches W.C.Pascal 0 0.1 25 1 0.25 50 2 0.5 100 3 1 250 4 2.5 0.5 kPa 5 5 1 kPa 6 10 2.5 kPa 7 10 2.5 kPa sensor maintains its specied accuracy and stability. 07122 TM PX SERIES INSTALLATION GUIDE OPERATION This device employs ceramic capacitive sensors and sophisticated temperature compensation circuitry. The sensor achieves its best accuracy after an initial warm-up lowest pressure ranges appear erroneous. Following this initial warm-up period, the LCD DISPLAY: .edam si noitceles nehw ”TES“ egnar setacidni yliratnemom yalpsid Pressure is normally indicated on the display. Units are in inches water column (in. W.C.), Pascals (Pa) or kilopascals (kPa) as indicated on the display. The display shows OVER when the pressure is over range. ZERO: Press and hold the ZERO pushbutton for 2 seconds or provide contact closure on ‘AUX ZERO’ terminal to automatically reset the output and display to zero pressure. To protect the unit from accidental zero, this feature is enabled only when the detected pressure is within about 0.1 in. W.C. (25 Pa) of factory calibration. WIRING & CONFIGURATION Connect the transmitter to the Sensaphone and power supply as indicated below. Set the switch to current (mA) mode. Jumper JP4: select 0-10 V. Jumper JP5: select bidirectional or unidirectional mode. Jumper JP7: select inches W.C. or Pascal scale Jumper JP8: select fast or standard response time. Align the arrow (not the slot) on the rotary switch to the desired full-scale range. LCD models momentarily indicate the selected range. 2-wire, 4-20 mA POWER (4-20mA)OUT (0-10v)COMZERO VoltVOLT OUTPUTmA5V/10V JP4 MODEBI/UNI JP5 ZERO1.000WARNING: Do not apply power to output terminal! Permanent damage will result. RESPONSEFAST/STD UNITSIN W.C./PA JP7 JP8 0 1 2 3 4 5 6 7Range Selection Guide Rotary Switch Position Inches W.C.Pascal 0 0.1 25 1 0.25 50 2 0.5 100 3 1 250 4 2.5 0.5 kPa 5 5 1 kPa 6 10 2.5 kPa 7 10 2.5 kPa sensor maintains its specied accuracy and stability. INSTALLATION 1. Plan the installation. Panel or duct mount? 2. For duct mount applications, thread the probe into the back of the device housing. Ø 0.15 “ (3.7 mm) Ø 0.38 “ (9.7 mm) Ø 0.15 “ (3.7 mm) Ø 3.3 “ (83 mm) Ø 0.2 “ (5.2 mm) Ø 1.6 “ (40 mm) + + Ø 0.38 “ (9.7 mm) Screw Hole Mounting Z103591-0A Dierential Pressure Transmitter Inch H2O Z103591-0A Dierential Pressure Transmitter Inch H2O 90˚ YES! YES! Tubing for Duct Mount Tubing for Panel Mount Use the front barbLarger diameter tube Smaller diameter tube 4. Mount the transducer (see the screw hole diagram). Position the transducer vertically. 5. Determine the length of pilot tubing needed. Static Pressure Dierential Pressure Panel Installa- tions AIR FLOW FILTER LOW HIGH AIR FLOW Duct Installa- tions AIR FLOW AIR FLOW PRODUCT PART # VaporBlock® Plus™ 20 ................................................................ VBP20 UNDER-SLAB VAPOR / GAS BARRIER Under-Slab Vapor/Gas Retarder © 2018 RAVEN INDUSTRIES INC. All rights reserved. VAPORBLOCK® PLUS™VBP20 PRODUCT DESCRIPTION VaporBlock® Plus™ is a seven-layer co-extruded barrier made using high quality virgin-grade polyethylene and EVOH resins to provide unmatched impact strength as well as superior resistance to gas and moisture transmission. VaporBlock® Plus™ 20 is more than 100 times less permeable than typical high-performance polyethylene vapor retarders against Methane, Radon, and other harmful VOCs. Tested and verified for unsurpassed protection against BTEX, HS, TCE, PCE, methane, radon, other toxic chemicals and odors. VaporBlock® Plus™ 20 multi-layer gas barrier is manufactured with the latest EVOH barrier technology to mitigate hazardous vapor intrusion from damaging indoor air quality, and the safety and health of building occupants. VBP20 is one of the most effective underslab gas barriers in the building industry today far exceeding ASTM E-1745 (Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs) Class A, B and C requirements. Available in a 20 (Class A) mil thicknesses designed to meet the most stringent requirements. VaporBlock® Plus™ 20 is produced within the strict guidelines of our ISO 9001 Certified Management System. PRODUCT USE VaporBlock® Plus™ 20 resists gas and moisture migration into the building envelop when properly installed to provide protection from toxic/harmful chemicals. It can be installed as part of a passive or active control system extending across the entire building including floors, walls and crawl spaces. When installed as a passive system it is recommended to also include a ventilated system with sump(s) that could be converted to an active control system with properly designed ventilation fans. VaporBlock® Plus™ 20 works to protect your flooring and other moisture-sensitive furnishings in the building’s interior from moisture and water vapor migration, greatly reducing condensation, mold and degradation. SIZE & PACKAGING VaporBlock® Plus™ 20 is available in 10’ x 150’ rolls to maximize coverage. All rolls are folded on heavy-duty cores for ease in handling and installation. Other custom sizes with factory welded seams are available based on minimum volume requirements. Installation instructions and ASTM E-1745 classifications accompany each roll. APPLICATIONS Radon Barrier Methane Barrier VOC Barrier Brownfields Barrier Vapor Intrusion Barrier Under-Slab Vapor Retarder Foundation Wall Vapor Retarder VaporBlock® Plus™ is a seven-layer co-extruded barrier made using high quality virgin-grade polyethylene and EVOH resins to provide unmatched impact strength as well as superior resistance to gas and moisture transmission. VaporBlock® Plus™ Placement All instructions on architectural or structural drawings should be reviewed and followed. Detailed installation instructions accompany each roll of VaporBlock® Plus™ and can also be located at www.ravenefd.com. ASTM E-1643 also provides general installation information for vapor retarders. VAPORBLOCK® PLUS™ 20 PROPERTIES TEST METHOD IMPERIAL METRIC AppeArAnce White/Gold Thickness, nominAl 20 mil 0.51 mm WeighT 102 lbs/MSF 498 g/m² clAssificATion ASTM E 1745 CLASS A, B & C ³ Tensile sTrengTh ASTM E 154Section 9(D-882)58 lbf 102 N impAcT resisTAnce ASTM D 1709 2600 g permeAnce (neW mATeriAl) ASTM E 154Section 7ASTM E 96Procedure B 0.0098 Perms grains/(ft²·hr·in·Hg) 0.0064 Perms g/(24hr·m²·mm Hg) permeAnce (AfTer condiTioning) (sAme meAsuremenT As Above permeAnce) ASTM E 154Section 8, E96Section 11, E96Section 12, E96Section 13, E96 0.00790.00790.00970.0113 0.00520.00520.00640.0074 WvTr ASTM E 96Procedure B 0.0040 grains/hr-ft²0.0028 gm/hr-m² benzene permeAnce See Note ⁶1.13 x 10-¹⁰ m²/sec or 3.62 x 10-¹³ m/s Toluene permeAnce See Note ⁶1.57 x 10-¹⁰ m²/sec or 1.46 x 10-¹³ m/s eThylbenzene permeAnce See Note ⁶1.23 x 10-¹⁰ m²/sec or 3.34 x 10-¹⁴ m/s m & p-Xylenes permeAnce See Note ⁶1.17 x 10-¹⁰ m²/sec or 3.81 x 10-¹⁴ m/s o-Xylene permeAnce See Note ⁶1.10 x 10-¹⁰ m²/sec or 3.43 x 10-¹⁴ m/s hydrogen sulfide See Note 9 1.92E-⁰⁹ m/s TrichloroeThylene (Tce) See Note ⁶7.66 x 10-¹¹ m²/sec or 1.05 x 10-¹⁴ m/s perchloroeThylene (pce)See Note ⁶7.22 x 10-¹¹ m²/sec or 1.04 x 10-¹⁴ m/s rAdon diffusion coeffiecienT K124/02/95 < 1.1 x 10-13 m2/s meThAne permeAnce ASTM D 1434 3.68E-¹² m/sGas Transmission Rate (GTR):0.32 mL/m²•day•atm mAXimum sTATic use TemperATure 180° F 82° C minimum sTATic use TemperATure - 70° F - 57° C UNDER-SLAB VAPOR / GAS BARRIER VAPORBLOCK® PLUS™VBP20 © 2018 RAVEN INDUSTRIES INC. All rights reserved. Scan QR Code to download current technical data sheets via the Raven website. Note: To the best of our knowledge, unless otherwise stated, these are typical property values and are intended as guides only, not as specification limits. Chemical resistance, odor transmission, longevity as well as other performance criteria is not implied or given and actual testing must be performed for applicability in specific applications and/or conditions. RAVEN INDUSTRIES MAKES NO WARRANTIES AS TO THE FITNESS FOR A SPECIFIC USE OR MERCHANTABILITY OF PRODUCTS REFERRED TO, no guarantee of satisfactory results from reliance upon contained information or recommendations and disclaims all liability for resulting loss or damage. Limited Warranty available at www.RavenEFD.com 061318 EFD 1125 RAVEN ENGINEERED FILMSP.O. Box 5107 Sioux Falls, SD 57117-5107Ph: +1 (605) 335-0174 • TF: +1 (800) 635-3456 efdsales@ravenind.comwww.ravenefd.com ³ Tests are an average of machine and transverse directions.5 Raven Industries performs seam testing at 20” per minute.6 Aqueous Phase Film Permeance. Permeation of Volatile Organic Compounds through EVOH Thin Film Membranes and Coextruded LLDPE/EVOH/ LLDPE Geomembranes, McWatters and Rowe, Journal of Geotechnical and Geoenvironmental Engineering© ASCE/ September 2015. (Permeation is the Permeation Coefficient adjusted to actual film thickness - calculated at 1 kg/m³.) The study used to determine PCE and TCE is titled: Evaluation of diffusion of PCE & TCE through high performance geomembranes by Di Battista and Rowe, Queens University 8 Feb 2018.9 The study used to determine diffusion coefficients is titled: Hydrogen Sulfide (H₂S) Transport through Simulated Interim Covers with Conventional and Co-Extruded Ethylene-Vinyl Alcohol (EVOH) Geomembranes. INSTALLATION GUIDELINES - With VaporSeal™ Tape VaporSeal™ 4” Tape VaporSeal™ 4” Tape Optional Butyl Seal 2-Sided Tape Gas Barrier Applications Elements of a moisture/gas-resistant floor system. General illustration only.(Note: This example shows multiple options for waterstop placement. VaporSeal™ 4” Tape VaporSeal™ 4” Tape Optional Butyl Seal 2-Sided Tape Gas Barrier Applications Fig. 2: VaporBlock® Plus™ Overlap Joint Sealing Methods Fig. 1: VaporBlock® Plus™ Overlapping Roll-out Method Please Note: Read these instructions thoroughly before installation to ensure proper use of VaporBlock® Plus™. ASTM E 1465, ASTM E 2121 and, ASTM E 1643 also provide valuable information regarding the installation of vapor / gas barriers. When installing this product, contractors shall conform to all applicable local, state and federal regulations and laws pertaining to residential and commercial building construction. • When VaporBlock® Plus™ gas barrier is used as part of an active control system for radon or other gas, a ventilation system will be required. • If designed as a passive system, it is recommended to install a ventilation system that could be converted to an active system if needed. Materials List:VaporBlock® Plus™ Vapor / Gas BarrierVaporSeal™* 4” Seaming TapeVaporSeal™* 12” Seaming/Repair TapeButyl Seal 2-Sided TapeVaporBoot Plus Pipe Boots 12/Box (recommended)VaporBoot Tape (optional)POUR-N-SEAL™ (optional)1” Foam Weather Stripping (optional)Mako® Screed Supports (optional) VAPORBLOCK® PLUS™ PLACEMENT 1.1. Level and tamp or roll granular base as specified. A base for a gas-reduction system may require a 4” to 6” gas permeable layer of clean coarse aggregate as specified by your architectural or structural drawings after installation of the recommended gas collection system. In this situation, a cushion layer consisting of a non-woven geotextile fabric placed directly under VaporBlock® Plus™ will help protect the barrier from damage due to possible sharp coarse aggregate. 1.2. Unroll VaporBlock® Plus™ running the longest dimension parallel with the direction of the pour and pull open all folds to full width. (Fig. 1) 1.3. Lap VaporBlock® Plus™ over the footings and seal with Raven Butyl Seal tape at the footing-wall connection. Prime concrete surfaces, when necessary, and assure they are dry and clean prior to applying Raven Butyl Seal Tape. Apply even and firm pressure with a rubber roller. Overlap joints a minimum of 6” and seal overlap with 4” VaporSeal™ Tape. When used as a gas barrier, overlap joints a minimum of 12” and seal in-between overlap with an optional 2-sided Raven Butyl Seal Tape. Then seal with 4” VaporSeal™ Tape centered on the overlap seam. (Fig. 2) Page 1 of 4 Top original diagram and figure #1 were reprinted with permission by the Portland Cement Association.Reference: Kanare, Howard M., Concrete Floors and Moisture, EB119, Portland Cement Association, Skokie, Illinois, and National Ready Mixed Concrete Association, Silver Spring, Maryland, USA, 2008, 176 pages. 1.4. Seal around all plumbing, conduit, support columns or other penetrations that come through the VaporBlock® Plus™ membrane. 1.4a. Method 1: Pipes four inches or smaller can be sealed with Raven VaporBoot Plus preformed pipe boots. VaporBoot Plus preformed pipe boots are formed in steps for 1”, 2”, 3” and 4” PVC pipe or IPS size and are sold in units of 12 per box (Fig. 3 & 5). Pipe boots may also be fabricated from excess VaporBlock® Plus™ membrane (Fig. 4 & 6) and sealed with VaporBoot Tape or VaporSeal™ Tape (sold separately). 1.4b. Method 2: To fabricate pipe boots from VaporBlock® Plus™ excess material (see Fig. 4 & 6 for A-F): A) Cut a square large enough to overlap 12” in all directions. B) Mark where to cut opening on the center of the square and cut four to eight slices about 3/8” less than the diameter of the pipe. C) Force the square over the pipe leaving the tightly stretched cut area around the bottom of the pipe with approximately a 1/2” of the boot material running vertically up the pipe. (no more than a 1/2” of stretched boot material is recommended) D) Once boot is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in between the two layers. Secure boot down firmly over the membrane taking care not to have any large folds or creases. E) Use VaporBoot Tape or VaporSeal™ Tape to secure the boot to the pipe. VaporBoot Tape (option) – fold tape in half lengthwise, remove half of the release liner and wrap around the pipe allowing 1” extra for overlap sealing. Peel off the second half of the release liner and work the tape outward gradually forming a complete seal. VaporSeal™ Tape (option) - Tape completely around pipe overlapping the VaporBlock® Plus™ square to create a tight seal against the pipe. F) Complete the process by taping over the boot perimeter edge with VaporSeal™ Tape to create a monolithic membrane between the surface of the slab and gas/moisture sources below and at the slab perimeter. (Fig. 4 & 6) Preformed Pipe Boot Square Material Pipe Boot Fig. 3 SINGLE PENETRATION PIPE BOOT INSTALLATION Fig. 5 Fig. 6 1. Cut a square of VaporBlock® Plus™ barrier to extend at least 12” from the pipe in all directions. 2. Cut four to eight slices about 3/8” less than the diameter of the pipe. 5. Use Raven VaporBoot or VaporSeal™ Tape and overlap 1” at the seam. 4. Tape over the boot perimeter edge with VaporSeal™ Tape. 1. Cut out one of the preformed boot steps (1” to 4”). 2. Tape the underside boot perimeter with 2-sided Butyl Seal Tape. 3. Force the boot over pipe and press tape firmly in place. 4. Use VaporSeal™ Tape to secure boot to the pipe. 5. Tape around entire boot edge with VaporSeal™ Tape. VaporBoot Flexible Tapeor VaporSeal™ 4” TapeVaporSeal™ 4” Tape VaporBlock® Plus™Material VaporSeal™ 4” Tape Raven Butyl Seal2-Sided Tape Raven Butyl Seal2-Sided Tape VaporBoot PlusPreformed Boot 12”(minimum) 3. Force over pipe and tape the underside boot perimeter to existing barrier with 2-sided Butyl Seal Tape. Fig. 4 Page 2 of 4 Original figure #4 diagram is reprinted with permission by the Portland Cement Association.Reference: Kanare, Howard M., Concrete Floors and Moisture, EB119, Portland Cement Association, Skokie, Illinois, and National Ready Mixed Concrete Association, Silver Spring, Maryland, USA, 2008, 176 pages.Method 1 Method 2 VaporSeal™4” Tape VaporBoot PlusPerformed Boot Raven Butyl Seal 2-sided Tape Raven Butyl Seal 2-sided Tape 1.5. Sealing side-by-side multiple penetrations (option 1); A) Cut a patch large enough to overlap 12” in all directions (Fig. 7) of penetrations. B) Mark where to cut openings and cut four to eight slices about 3/8” less than the diameter of the penetration for each. C) Force patch material over penetration to achieve a tight fit and form a lip. D) Once patch is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in-between the two layers. (Fig. 8) E) After applying Raven Butyl Seal Tape between the patch and membrane, tape around each of the penetrations and the patch with VaporSeal™ 4” tape. (Fig. 9) For additional protection apply POUR-N-SEAL™ or an acceptable polyurethane elastomeric sealant around the penetrations. (Fig. 10) Fig. 7 Fig. 8 Fig. 9 Fig. 10 MULTIPLE PENETRATION PIPE BOOT INSTALLATION Fig. 6 Cut a patch large enough to overlap 12” in all directions and slide over penetrations (Make openings as tight as possible.) Once the overlay patch is positioned, seal the perimeter to the membrane by applying 2-sided Raven Butyl Seal Tape in-between the two layers. After applying Raven Butyl Seal Tapebetween the patch and membrane, tape around the perimeter of the penetration and the patch with VaporSeal™ 4” Tape. For additional protection apply POUR-N-SEAL™ or an acceptable polyurethane elastomeric sealant around the penetrations. VaporSeal™ 4” Tape VaporSeal™ 4” Tape Page 3 of 4 Option 1 Raven Butyl Seal 2-sided Tape 1.6. POUR-N-SEAL™ method of sealing side-by-side multiple penetrations (option 2); A) Install the vapor barrier as closely as possible to pipe penetrations to minimize the amount of POUR-N-SEAL™ necessary to seal around all penetrations. B) Once barrier is in place, remove soil or other particles with a dry cloth or a fine broom to allow for improved adhesion to the POUR-N-SEAL™ liquid. C) Create a dam around the penetration area approximately 2” away from the pipe or other vertical penetrations by removing the release liner from the back of a 1” weather stripping foam and adhere to the vapor barrier. Form a complete circle to contain the POUR-N-SEAL™ materials (Fig. 11). D) Once mixed, pour contents around the pipe penetrations. If needed, a brush or a flat wooden stick can be used to direct the sealant completely around penetrations creating a complete seal (Fig. 12-13). E) DO NOT leave excess POUR-N-SEAL™ in plastic container for longer than the time it takes to pour sealant. Fig. 12 Fig. 13 Fig. 11 Option 2 VAPORBLOCK® PLUS™ REPAIR INSTRUCTIONS 1.7. Proper installation requires all holes and openings are repaired prior to placing concrete. When patching small holes, simply cut a 12” long piece of 12” wide VaporSeal™ tape. Remove release liner and center over the opening. Apply pressure to create a seal (Fig. 14-15). 1.8. When installing VaporBlock® Plus™ around pipe penetrations, vertical columns, electrical ducts and other obstructions, you will find it necessary to cut it to the nearest outside edge. This cut can be easily sealed with 12” wide VaporSeal™ tape, by simply centering it over the cut, 6” on either side. Once the tape is placed correctly, apply pressure to assure a complete seal (Fig. 16). Reminder Note: All holes or penetrations through the membrane will need to be patched with 12” VaporSeal™ Tape. Fig. 14 Page 4 of 5 Fig. 15 2.1. When installing reinforcing steel and utilities, in addition to the placement of concrete, take precaution to protect VaporBlock® Plus™. Carelessness during installation can damage the most puncture–resistant membrane. Sheets of plywood cushioned with geotextile fabric temporarily placed on VaporBlock® Plus™ provide for additional protection in high traffic areas including concrete buggies. 2.2. Use only brick-type or chair-type reinforcing bar supports to protect VaporBlock® Plus™ from puncture. 2.3. Avoid driving stakes through VaporBlock® Plus™. If this cannot be avoided, each individual hole must be repaired per section 1.7. 2.4. To avoid penetrating VaporBlock® Plus™ when installing screed supports, utilize non-penetrating support, such as the Mako® Screed Support System (Fig. 17). Avoid driving stakes through VaporBlock® Plus™. If this cannot be avoided, each individual hole must be repaired per figures 14-15. 2.5. If a cushion or blotter layer is required in the design between VaporBlock® Plus™ and the slab, additional care should be given if sharp crushed rock is used. Washed rock will provide less chance of damage during placement. Care must be taken to protect blotter layer from precipitation before concrete is placed. VaporBlock® Plus™ Gas & Moisture Barrier can be identified on site as gold/white in color printed in black ink with following logo and classification listing (Fig. 18) Page 5 of 5 VaporBlock® Plus™ Gas & Moisture Barrier Note: To the best of our knowledge, unless otherwise stated, these are typical property values and are intended as guides only, not as specification limits. Chemical resistance, odor transmission, longevity as well as other performance criteria is not implied or given and actual testing must be performed for applicability in specific applications and/or conditions. RAVEN INDUSTRIES MAKES NO WARRANTIES AS TO THE FITNESS FOR A SPECIFIC USE OR MERCHANTABILITY OF PRODUCTS REFERRED TO, no guarantee of satisfactory results from reliance upon contained information or recommendations and disclaims all liability for resulting loss or damage. Limited Warranty available at wwww.RavenEFD.com ENGINEERED FILMSP.O. Box 5107 Sioux Falls, SD 57117-5107Ph: +1 (605) 335-0174 • TF: +1 (800) 635-3456 efdsales@ravenind.comwww.ravenefd.com 020316 EFD 1127 VAPORBLOCK® PLUS™ PROTECTION Fig. 16 Fig. 18 Fig. 17 * Patent Pending © Raven 2016. All Rights Reserved. Attachment E Vapor Pin® Standard Operating Procedures Documents Standard Operating Procedure Installation and Extraction of the Vapor Pin® Updated March 16, 2018 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • www.vaporpin.com Scope: This standard operating procedure describes the installation and extraction of the VAPOR PIN® for use in sub-slab soil-gas sampling. Purpose: The purpose of this procedure is to assure good quality control in field operations and uniformity between field personnel in the use of the VAPOR PIN® for the collection of sub- slab soil-gas samples or pressure readings. Equipment Needed: Assembled VAPOR PIN® [VAPOR PIN® and silicone sleeve(Figure 1)]; Because of sharp edges, gloves are recommended for sleeve installation; Hammer drill; 5/8-inch (16mm) diameter hammer bit (hole must be 5/8-inch (16mm) diameter to ensure seal. It is recommended that you use the drill guide). (Hilti™ TE-YX 5/8" x 22" (400 mm) #00206514 or equivalent); 1½-inch (38mm) diameter hammer bit (Hilti™ TE-YX 1½" x 23" #00293032 or equivalent) for flush mount applications; ¾-inch (19mm) diameter bottle brush; Wet/Dry vacuum with HEPA filter (optional); VAPOR PIN® installation/extraction tool; Dead blow hammer; VAPOR PIN® flush mount cover, if desired; VAPOR PIN® drilling guide, if desired; VAPOR PIN® protective cap; and VOC-free hole patching material (hydraulic cement) and putty knife or trowel for repairing the hole following the extraction of the VAPOR PIN®. Figure 1. Assembled VAPOR PIN® Installation Procedure: 1)Check for buried obstacles (pipes, electrical lines, etc.) prior to proceeding. 2)Set up wet/dry vacuum to collect drill cuttings. 3)If a flush mount installation is required, drill a 1½-inch (38mm) diameter hole at least 1¾-inches (45mm) into the slab. Use of a VAPOR PIN® drilling guide is recommended. 4)Drill a 5/8-inch (16mm) diameter hole through the slab and approximately 1- inch (25mm) into the underlying soil to form a void. Hole must be 5/8-inch (16mm) in diameter to ensure seal. It is recommended that you use the drill guide. Standard Operating Procedure Installation and Removal of the Vapor Pin® Updated March 16, 2018 Page 2 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc. • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • www.vaporpin.com 5)Remove the drill bit, brush the hole with the bottle brush, and remove the loose cuttings with the vacuum. 6)Place the lower end of VAPOR PIN® assembly into the drilled hole. Place the small hole located in the handle of the installation/extraction tool over the vapor pin to protect the barb fitting, and tap the vapor pin into place using a dead blow hammer (Figure 2). Make sure the installation/extraction tool is aligned parallel to the vapor pin to avoid damaging the barb fitting. Figure 2. Installing the VAPOR PIN® During installation, the silicone sleeve will form a slight bulge between the slab and the VAPOR PIN® shoulder. Place the protective cap on VAPOR PIN® to prevent vapor loss prior to sampling (Figure 3). Figure 3. Installed VAPOR PIN® 7)For flush mount installations, cover the vapor pin with a flush mount cover, using either the plastic cover or the optional stainless-steel Secure Cover (Figure 4). Figure 4. Secure Cover Installed 8)Allow 20 minutes or more (consult applicable guidance for your situation) for the sub-slab soil-gas conditions to re- equilibrate prior to sampling. 9)Remove protective cap and connect sample tubing to the barb fitting of the VAPOR PIN®. This connection can be made using a short piece of TygonTM tubing to join the VAPOR PIN® with the Standard Operating Procedure Installation and Removal of the Vapor Pin® Updated March 16, 2018 Page 3 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc. • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • www.vaporpin.com Nylaflow tubing (Figure 5). Put the Nylaflow tubing as close to the VAPOR PIN® as possible to minimize contact between soil gas and TygonTM tubing. Figure 5. VAPOR PIN® sample connection 10)Conduct leak tests in accordance with applicable guidance. If the method of leak testing is not specified, an alternative can be the use of a water dam and vacuum pump, as described in SOP Leak Testing the VAPOR PIN® via Mechanical Means (Figure 6). For flush-mount installations, distilled water can be poured directly into the 1 1/2 inch (38mm) hole. Figure 6. Water dam used for leak detection 11)Collect sub-slab soil gas sample or pressure reading. When finished, replace the protective cap and flush mount cover until the next event. If the sampling is complete, extract the VAPOR PIN®. Extraction Procedure: 1)Remove the protective cap, and thread the installation/extraction tool onto the barrel of the VAPOR PIN® (Figure 7). Turn the tool clockwise continuously, don't stop turning, the VAPOR PIN® will feed into the bottom of the installation/extraction tool and will extract from the hole like a wine cork, DO NOT PULL. 2)Fill the void with hydraulic cement and smooth with a trowel or putty knife. Figure 7. Removing the VAPOR PIN® Prior to reuse, remove the silicone sleeve and protective cap and discard. Decontaminate the VAPOR PIN® in a hot water and Alconox® wash, then heat in an oven to a temperature of 265o F (130o C) for 15 to 30 minutes. For both steps, STAINLESS – ½ hour, BRASS 8 minutes Standard Operating Procedure Installation and Removal of the Vapor Pin® Updated March 16, 2018 Page 4 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc. • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • www.vaporpin.com 3)Replacement parts and supplies are available online. Standard Operating Procedure Use of the VAPOR PIN® Drilling Guide and Secure Cover Updated March 16, 2018 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc. • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • www.vaporpin.com Scope: This standard operating procedure (SOP) describes the methodology to use the VAPOR PIN® Drilling Guide and Secure Cover to install and secure a VAPOR PIN® in a flush mount configuration. Purpose: The purpose of this SOP is to detail the methodology for installing a VAPOR PIN® and Secure Cover in a flush mount configuration. The flush mount configuration reduces the risk of damage to the VAPOR PIN® by foot and vehicular traffic, keeps dust and debris from falling into the flush mount hole, and reduces the opportunity for tampering. This SOP is an optional process performed in conjunction with the SOP entitled “Installation and Extraction of the VAPOR PIN®”. However, portions of this SOP should be performed prior to installing the VAPOR PIN®. Equipment Needed: VAPOR PIN® Secure Cover (Figure 1); VAPOR PIN® Drilling Guide (Figure 2); Hammer drill; 1½-inch diameter hammer bit (Hilti™ TE- YX 1½" x 23" #00293032 or equivalent); 5/8-inch diameter hammer bit (Hilti™ TE- YX 5/8" x 22" #00226514 or equivalent); assembled VAPOR PIN®; #14 spanner wrench; Wet/Dry vacuum with HEPA filter (optional); and personal protective equipment (PPE). Figure 1. VAPOR PIN® Secure Cover Figure 2. VAPOR PIN® Drilling Guide Installation Procedure: 1)Check for buried obstacles (pipes, electrical lines, etc.) prior to proceeding. 2)Set up wet/dry vacuum to collect drill cuttings. 3)While wearing PPE, drill a 1½-inch diameter hole into the concrete slab to a depth of approximately 1 3/4 inches. Pre-marking the desired depth on the drill Standard Operating Procedure Installation and Removal of the Vapor Pin® Updated March 16, 2018 Page 2 VAPOR PIN® protected under US Patent # 8,220,347 B2, US 9,291,531 B2 and other patents pending Vapor Pin Enterprises, Inc. • 7750 Corporate Blvd., Plain City, Ohio 43064 • (614) 504-6915 • VaporPin.CoxColvin.com bit with tape will assist in this process. 4)Remove cuttings from the hole and place the Drilling Guide in the hole with the conical end down (Figure 3). The hole is sufficiently deep if the flange of the Drilling Guide lies flush with the surface of the slab. Deepen the hole as necessary, but avoid drilling more than 2 inches into the slab, as the threads on the Secure Cover may not engage properly with the threads on the VAPOR PIN®. Figure 3. Testing Depth with the Drilling Guide 5)When the 1½-inch diameter hole is drilled to the proper depth, replace the drill bit with a 5/8-inch diameter bit, insert the bit through the Drilling Guide (Figure 4), and drill through the slab. The Drilling Guide will help to center the hole for the VAPOR PIN®, and keep the hole perpendicular to the slab. 6)Remove the bit and drilling guide, clean the hole, and install the VAPOR PIN® in accordance with the SOP “Installation and Extraction of the VAPOR PIN®. Figure 4. Using the Drilling Guide 7)Screw the Secure Cover onto the VAPOR PIN® and tighten using a #14 spanner wrench by rotating it clockwise (Figure 5). Rotate the cover counter clockwise to remove it for subsequent access. Figure 5. Tightening the Secured Cover Limitations: On slabs less than 3 inches thick, it may be difficult to obtain a good seal in a flush mount configuration with the VAPOR PIN.®