DENR USE ONLY ❑Paper Report ❑Electronic Data - Email CD (data loaded: Yes / No Doc/Event #:
NC DENR I IEnvironmental Monitoring
Division of Waste Management - Solid Waste Reporting Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are
available for inspection and examination by any person upon request (NC General Statute 132-6).
Instructions:
Prepare one form for each individually monitored unit.
Please type or print legibly.
Attach a notification table with values that attain or exceed NC 2L groundwater standards or NC 2B surface water standards. The notification
must include a preliminary analysis of the cause and significance of each value. (e.g. naturally occurring, off -site source, pre-existing
condition, etc.).
Attach a notification table of any groundwater or surface water values that equal or exceed the reporting limits.
Attach a notification table of any methane gas values that attain or exceed explosive gas levels. This includes any structures on or nearby the
facility (NCAC 13B .1629 (4)(a)(i).
Send the original signed and sealed form, any tables, and Electronic Data Deliverable to: Compliance Unit, NCDENR-DWM, Solid Waste
Section, 1646 Mail Service Center, Raleigh, NC 27699-1646.
Solid Waste Monitoring Data Submittal Information
Name of entity submitting data (laboratory, consultant, facility owner):
Smith Gardner, Inc.
Contact for questions about data formatting. Include data preparer's name, telephone number and E-mail address:
Name: Joan A. Smvth. PG Phone: (919) 828 - 0577 x221
E-mail: Joan@smithgardnerinc.com
NC Landfill Rule: Actual sampling dates (e.g.,
Facility name: Facility Address: Facility Permit # (.0500 or .1600) October 20-24, 2006)
High Point Riverdale Closed MSW Riverdale Drive, High Point, NC 41-01 .0500 September 16, 2020
Landfill
Environmental Status: (Check all that apply)
Initial/Background Monitoring 0 Detection Monitoring Assessment Monitoring Corrective Action
of data submitted: (Check all that apply)
Groundwater monitoring data from monitoring wells 0
Groundwater monitoring data from private water supply wells El
Leachate monitoring data El
water monitoring data
Methane gas monitoring data
Corrective action data (specify)
Other(specify)
Notification attached?
e No. No groundwater or surface water standards were exceeded.
Yes, a notification of values exceeding a groundwater or surface water standard is attached. It includes a list of groundwater and surface water
monitoring points, dates, analytical values, NC 2L groundwater standard, NC 2B surface water standard or NC Solid Waste GWPS and
preliminary analysis of the cause and significance of any concentration.
FXI Yes, a notification of values exceeding an explosive methane gas limit is attached. It includes the methane monitoring points, dates, sample
values and explosive methane gas limits.
Certification
To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct.
Furthermore, I have attached complete notification of any sampling values meeting or exceeding groundwater standards or explosive gas
levels, and a preliminary analysis of the cause and significance of concentrations exceeding groundwater standards. I am aware that there
are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
Joan A. Smyth, PG Senior Hydrogeologist (919) 828 - 0577 x221
Name (Print) Title (Area Code) Telephone Number
L, 9/29/2020 Affix NC Licensed/ Professional Geologist Seal
Date
14 N. Boylan Ave, Raleigh, NC 27603
Facility Representative Address
F-1370
NC PE Firm License Number (if applicable effective May 1, 2009)
Revised 6/2009
C AR
aUEA
ozo
` A.
ltNUB
DocuSign Envelope ID: 5F918BFC-F78B-4922-8D58-CFDAFDOBF4AD
This page intentionally left blank.
DocuSign Envelope ID: 5F918BFC-F78B-4922-8D58-CFDAFDOBF4AD
NC Division of Waste Management - Solid Waste Section
Landfill Gas Monitoring Data Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and
examination by any person upon request (NC General Statute 132-6).
Facility Name: �gfig�h��C��lv�rl�l��f�14�1 Permit Number: 41-A1_01
Date of Sampling: 9/16/2020 NC Landfill Rule (.0500 or .1600): .0509500
Name and Position of Sample Collector: Michael J. Liebl - Staff Environmental Technician
Type and Serial Number of Gas Meter: GEM 5000
Date and Time of Field Calibration: 9/16/2020 0953
Calibration Date of Gas Meter: 1/2020
Type of Field Calibration Gas (15115 or 35/50): 15/15 Expiration Date of Field Calibration Gas Canister: 12/2020
Pump Rate of Gas Meter: 0.5 LPM
Ambient Air Temperature: 72 F Barometric Pressure: 29.32 in Hg General Weather Conditions: Sunny/Clear
Instructions: Under "Location or LFG Well" identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test
must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane
by volume = % LEL/20
LocaEDn or
LFG V4 a ID
Sample Tube
Purge
Time
Time
Pumped (s)
Initial
%LEL
Stabilized
°•oLEL
%CFI4
by
Volume
%02
%1202
Notes
H2 S ppm
1-1
>60s
1103
>60s
10
10
0.5
18.1
1.3
2
LFG 3
>60s
1057
>60s
0
0
0.0
11.3
7.4
2
LFG 4
>60s
1111
>60s
0
0
0.0
17.9
2.7
2
LFG 5
>60s
1125
>60s
0
0
0.0
13.5
4.1
2
LFG 6
>60s
1120
>60s
92
92
4.6
8.8
17.7
2
LFG 7
>60s
1204
>60s
950
950
47.5
3.7
19.6
3
7-1
>60s
1212
>60s
304
304
15.2
4.2
18.4
1
7-2
>60s
1208
>60s
2
2
0.1
19.3
1.1
1
7-3
>60s
1201
>60s
2
2
0.1
17.8
6.9
0
74
_
-
-
-
_
_
- Inaccessible
LFG 8
-
-
-
-
-
-
- Inaccessible
LFG 8A
>60s
1155
>60s
1156
1156
57.8
1.1
28.1
3
LFG 8B
>60s
1156
>60s
488
488
24.4
11.3
16.5
3
8-1
>60s
1153
>60s
1146
1146
57.3
0.6
35.2
3
8-2
>60s
1151
>60s
1064
1064
53.2
0.2
40.1
3
8-3
>60s
1149
>60s
994
994
49.7
0.2
40.2
2
8-4
>60s
1137
>60s
988
988
49.4
0.6
37.0
2
8-5
>60s
1142
>60s
304
304
15.2
4.0
21.7
3
LFG 9
>60s
1140
>60s
822
822
41.1
3.3
29.7
3
9-1
>60s
1145
>60s
796
796
39.8
2.2
37.5
2
LFG 10
-
-
-
-
-
-
- Inaccessible
Old Maint Bldg
>60s
1128
>60s
0
0
0.0
20.1
0.1
3
Electrical Shop
>60s
1130
>60s
0
0
0.0
20.0
0.1
2
If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same
information as contained on this form.
Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that
there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
Staff Environmental Technician
SIGNATURE
TITLE
DocuSign Envelope ID: 5F918BFC-F78B-4922-8D58-CFDAFDOBF4AD
This page intentionally left blank.
DocuSign Envelope ID: 5F918BFC-F78B-4922-8D58-CFDAFDOBF4AD
f
+� •!
y LFG 5
LFG-3
��9f$r ' LFG-4
+ 5
O LFG Probes
300 150 0 300
Feet
LFG-6
f ,
=-. 'rI`" rj;j�
At'
�." V
# .
7-3 7-4 LFG-8 g_1 8-3 °
8B
7.1 LFG-7 7-2 8A�•
LFG-9
LFG-10
0
cn
Z
O
J
U
In
O
za
Z
Q
Z
w
�
O
m
J
a
o
a
o
O
a
p�
=
tU
Z
>
0
O
O
Q
O
L
Z
C
V
2
O
LL
LIA
J
r