HomeMy WebLinkAbout1202_Burke_East_MSWLF_Feb2020LFG_FID1389776_20200214Data - Email CD (data loaded: Yes / No ) Doc/Event #:
'NC DE►vR " Environmental Monitoring
Division of Waste Management - Solid Waste Reporting Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are
available for inspection and examination by any person upon request (NC General Statute 132-6).
Instructions:
Prepare one form for each individually monitored unit.
• Please type or print legibly.
Attach a notification table with values that attain or exceed NC 2L groundwater standards or NC 2B surface water standards. The notification
must include a preliminary analysis of the cause and significance of each value. (e.g. naturally occurring, off -site source, pre-existing
condition, etc.).
Attach a notification table of any groundwater or surface water values that equal or exceed the reporting limits.
Attach a notification table of any methane gas values that attain or exceed explosive gas levels. This includes any structures on or nearby the
facility (NCAC 138 .1629 (4)(a)(i).
Send the original signed and sealed form, any tables, and Electronic Data Deliverable to: Compliance Unit, NCDENR-DWM, Solid Waste
Section, 1646 Mail Service Center, Raleigh, NC 27699-1646.
Solid Waste Monitoring Data Submittal Information
Name of entity submitting data (laboratory, consultant, facility owner):
LaBella Associates (Joyce Engineering)
Contact for questions about data formatting. Include data preparees name, telephone number and E-mail address:
Name: Natalia S. Soto Rodriquez Phone: (336) 790-2197
E-mail: nsotorodriquez(o)labellapc.com
NC Landfill Rule: Actual sampling dates (e.g.,
Facility name: Facility Address: Facility Permit # (.0500 or .1600) October 20-24, 2006)
East Burke 8855 Rhodhiss Rd,
MSWLF Morganton, NC 12-02 .0500 February 7, 2020
Environmental Status: (Check all that apply)
❑ Initial/Background Monitoring Detection Monitoring Assessment Monitoring Corrective Action
of data submitted: (Check all that apply)
Groundwater monitoring data from monitoring wells OX
Groundwater monitoring data from private water supply wells
Leachate monitoring data El
water monitoring data
Methane gas monitoring data
Corrective action data (specify)
Other(specify)
Notification attached?
E
No. No groundwater or surface water standards were exceeded.
Yes, a notification of values exceeding a groundwater or surface water standard is attached. It includes a list of groundwater and surface water
monitoring points, dates, analytical values, NC 2L groundwater standard, NC 2B surface water standard or NC Solid Waste GWPS and
preliminary analysis of the cause and significance of any concentration.
❑X Yes, a notification of values exceeding an explosive methane gas limit is attached. It includes the methane monitoring points, dates, sample
values and explosive methane gas limits.
Certification
To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct.
Furthermore, I have attached complete notification of any sampling values meeting or exceeding groundwater standards or explosive gas
levels, and a preliminary analysis of the cause and significance of concentrations exceeding groundwater standards. 1 am aware that there
are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
G. Van Ness Burbach, Ph.D., P.G. Technical Consultant (336) 323-0092
(Print)
2211 W. Meadowview Rd., Ste. 101 Greensboro, NC 27407
Facility Representative Address
C-0782
NC PE Firm License Number (if applicable effective May 1, 2009)
Revised 6/2009
(Area Code) Telephone Number
Affix NC Licensed/ Professional Geologist Seal
GCARp��9�g�
SEAL
1349 =
:G9 �FOLOG�'� �Qv
SS 6��.••`•
LaBella
Powered by oartnershiD.
February 14, 2020
Mr. Miles Champion
Burke County
General Services Director/County Engineer
P.O. Box 1486
Morganton, NC 28680
RE: Burke County, East Burke Landfill,
Permit Number 12-02
Landfill Gas Monitoring Report - First Quarter of 2020
Project No. 2912621, Phase 04
Dear Miles,
LaBella Associates (LaBella) is submitting the attached methane monitoring report for the East
Burke Landfill, Permit Number 12-02. The 2020 first quarter landfill gas monitoring event was
performed on February 7, 2020. During this event, LaBella monitored seven gas probes (GP-1,
GP-1B, GP-2, GP-3, GP-4, GP-5, and GP-6). The approximate locations of the gas probes are depicted
in Drawing 1. The monitoring data for the gas probes and buildings are summarized in the attached
Landfill Gas Monitoring Data Log.
Methane was detected above the lower explosive limit (LEL) in gas probes GP-1, GP-3, and GP-4. No
methane was detected in any of the other probes. These detections and exceedances are consistent
with previous results and are summarized in Table 1 and Table 2, respectively.
We have included an EMRF and will forward a copy of this report to Jaclynne Drummond with the
NCDEQ Solid Waste Section. This report should be added to the facility's records. The next quarterly
monitoring event is scheduled for the second quarter of 2020. If we can provide any additional
information, please do not hesitate to call me at (336) 323-0092.
Respectfully submitted,
LaBella Associates
Van Burback, PhD, PG
Sr. Technical Consultant
Attachments Environmental Monitoring Reporting Form (EMRF)
Tables 1 & 2
Landfill Gas Monitoring Log
Site Map with Monitoring Locations
cc: Jaclynne Drummond, NCDEQ
2211 W. Meadowview Road #1o1 i Greensboro. NC 27407 p (336) 323-0092
www.LabeLLapc.com
Notes:
Burke Co. - East Burke Landfill
Permit # 12-02
Date: 2/07/2020
Table 1: Methane Detections - Feb. 7, 2020
LFG
CH4
CH4
Probe
(%Vol.)
(%LEL)
GP-1
30.0
600
G P-3
18.9
378
GP-4
34.6
692
Table 2: Methane Exceedances - Feb. 7, 2020
LFG
CH4
CH4
Probe
(%Vol.)
(%LEL)
GP-1
30.0
600
G P-3
18.9
378
GP-4
34.6
692
CH4 = Methane
%Vol. = Concentration in pecent-by-volume.
%LEL = Concentration as a percent of the LEL.
LEL = Lower Explosive Limit = 5% Vol. for Methane.
Burke Co., East Burke Landfill
Permit # 12-02 Labella Associates
NC Division of Waste Management - Solid Waste Section
Landfill Gas Monitoring Data Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are
available far inspection and examination by anyperson upon request (NC General Statute 132-6).
Facility Name: B u rke C o . - East Burke
Permit Number: 1 2 —0 2
Sampling Date: 02/07/2020 NC Landfill Rule (.0500 or.1600):
.0500
Sample Collector Name &Position:
D. Knagge (Env. Field Tech.) / N. Soto Rodriguez (Env. Field Tech.)
Gas Meter Type & Serial Number: GEM 5000 (S.N. 650549)
Field Calibration Date & Time:
02/07/2020 @ 1215
Gas Meter Calibration Date: 10/03/2019
Field Calibration Gas Type (15115 or 35/50): [35/50] / [4% 02]Field Calibration Gas Canister Expiration Date:
Gas Meter Pump Rate:
300 mL/min
Ambient Air Temperature: 40 s Barometric Pressure (in. or mm Hg): 28.47 Weather Conditions: Sun n
Instructions: Under "Location or LFG Well", list monitoring well # or describe monitoring location (e.g., inside field office).
Attach a test location map or drawing. Report methane readings as both % LEL and % CH4 by volume.
Convert % CH4 (by volume) to % LEL as follows: % methane (by volume)/20 = % LEL.
*Hydrogen Sulfide (H2S) gas monitoring may be required for Construction & Demolition Landfills (CDLFs). See
individual permit conditions and/or Facility LFG monitoring plan.
Location or
LFG Well ID
S ample
Tube
Purge
Time of
Day
Time
Pumped
(sec)
Initial
% LEL
Stabilized
/o LEL
% CH4
(volume)
% 02
(volume)
% CO2
(volume)
% H2S*
(volume)
NOTES
GP-1 B
Y
1309
60
0
0
0
20.9
0.4
-
Pressure: -0.11
GP-1
Y
1312
60
1 0
600
30.0
5.5
1 24.6
-
Pressure: -1.83
GP-2
Y
1304
60
0
0
0
11.4
3.6
-
Pressure: -1.66
GP-3
Y
1259
60
0
378
18.9
13.2
15.2
-
Pressure: -1.41
GP-4
Y
1322
60
0
692
34.6
8.1
23.2
-
Pressure: -1.57
GP-5
Y
1326
60
0
0
0
19.0
2.3
-
Pressure: -0.07
GP-6
Y
1330
60
0
0
0
15.8
4.4
-
Pressure: -0.09
NOTE: If needed, attach additional data forms to include additional LFG monitoring data locations far the facility.
ACTION LEVELS: Methane: >1.25% by volume (inside structures) AND >5% by volume (at facility boundary)
Hydrogen Sulfide: >1% by volume (inside structures) AND >4% by volume (at facility boundary)
Certification
To the best of my knowledge, the information reported and statements made on this data submittal and attachments
are true and correct. I am aware that there are significant penalties for making any false statement, representation,
or certification including the possibility of a fine and imprisonment.
-11af Qla AA* � ,olv-� Environmental Field Technician
SIGNATURE UTITLE
Revised — March 6, 2017
1
i
. d:9• s7,g7ir
�.,'_tr: 'flY4 .::i :.� y+ ! ._y.d♦ 7^J. '� Z'F i9e � b� }V � As� -.
5: C�9 ,[j +y ♦ ti�� s; pia ad:.,§+ e� a �i,�,3 �
+ tt� a. +.�+< ' Ye+4� ' ►+, L� ''.. 7�r: '� *w��` gF`ce t' l�-. "' th}��•.�'Y���`'�4'°• *�,d
�t�+q
Ark— I
y
!",� '` fF k'S'.'
b !
'2+'F '4. '44Y '�V F ?;�! f �KQ' 1Y6 «' A►T R -
4}+t. a
vk
4 M
�
�� .U,,�1({.� � i ���(y' ,, y R♦�'_� .4 f t"` 'R' t4%.
1 4s *� �" P'� "'�*'��Yt h.� A.Sr� � N� +�y ��� � i 1'�F � �.: } •�1� "_T�
-
}�r`,y.t.
,� ��6 kr a �: �>tir ;� + xi+X {+•ksi'�R y s,�}} + �� ��rt� �� ,����W �4 ':«�. � �. 1> ,��.
r �. �' _ �. ��&1` �, v ' ,fit,,, � s� }�!' • '� `'�iY�SF 'x � �l' 'i �� �Q
p .
_.�."i �� , i 'tTrs °�..*!a,*�. �ML�kIN�ils�• . tr,. t.'A.}"� si. - S�i�� �., }, '� y�,�"�,ti`ir�+�'' � fix-41cf'���j�,. ..tom � �?, . ,$
y
-_Y
A �. tiF � ado .��", � t �+�: ��•t F k�'- �� "� � h� ' 't �' '` ' >`,�
t $-k_ t..z .tv t+t s��!b` :.i" r:"i< .* .' j�'m'ic .#,bad,..►�AW�. A
wyam,
♦ `IF q� v� � �� w
'tor t r � -10
+ t �kb ���, 4� '• ��t,y,!"d4 tf`_ i. OEM^+. _ "�,j�� �� +� '`
n15 A w r. 1.4�`
" GP-1 MW-z
GAS VENTS INSTALLED AMW-1
SEPTEMBER 2019 GV 5 •
a
Gv-4 sW z FIELD DETERMINED)
�� ED OF, ST
G P-2 7 -- w s
�a u
i
0
GV-
W-1
GP-3 A
F
%0�y/ 0 �v 2 / e�
SS
IR �
O e, rm
q
MNS GV
GP 4
GP-6
GP-5:
�f
w