HomeMy WebLinkAboutMO-7444_36096_CA_UST-61_20200125_24-Hour Release and UST Leak Reporting Form Auto Diesel Transition SumpUST-61
24-Hour Release and UST Leak Reporting Form.
For Releases This form should be completed and submitted to the UST Section's regional office following a known or suspected release from
an underground storage tank (UST) system. This form is required to be submitted within 24 hours of discovery of a known or
in NC suspected release
(DWM USE ONLY)
Suspected Contamination? (Y/N) N
Facility ID Number 0000011084
Incident # Risk (H,I,L,U)
Confirmed GW Contamination? (Y/N) N
Date Leak Discovered 1/24/20
Received On Received By
Confirmed Soil Contamination ?(Y/N) N
Comm/Non-Commercial? Comm
Reported by (circle one): Phone, Fax or Report
Samples Taken?(Y/N) N
Reg/Non-regulated? Reg
Region
Free Product? (Y/N) Y If Yes, State Greatest
Thickness inch or 2 in Sump
INCIDENT DESCRIPTION
Incident Name: Pilot Travel Center #56
Address: 2825 Lane Street
County: Cabarrus
Regional Office (circle one): Asheville, Mooresville, Fayetteville,
City/Town: Kannapolis
Zip Code: 28081
Raleigh, Washington, Wilmington, Winston-Salem
Latitude (decimal degrees): 35 29 53.20 N Longitude (decimal degrees) : 80 33 39.54 W
Obtained by:
❑GPS
Briefly describe suspected or confirmed release: (including but not limited to: nature of release, date of release, amount
of release, amount of free product present and recovery efforts, initial responses conducted, impacts to receptors)
❑Topographic map
Diesel and water observed in auto diesel transition sump. Once liquids removed observed leak in piping. Piping isolated
to stop leak and repairs scheduled for afternoon o ere was no evidence ot product eaving sump.
Hydrostatic test of sump and line testing will be conducted at conclusion of piping repair.
QGIS Address matching
❑Other
❑Unknown
Describe location:
Reason for service call to locate issue was slow flow on diesel pumps. During service call loss of pressure was detected
on auto diesel line. US Tank brought in to locate leak. Leak in transition sump found during pressure testing.
HOW RELEASE WAS DISCOVERED (Release code)
(Check one)
QRelease Detection Equipment or Methods ❑Visual/Odor ❑Groundwater Contamination
❑During UST Closure/Removal ❑Water in Tank ❑Surface Water Contamination
❑Property Transfer ❑Water Supply Well Contamination ❑Other (specify)
SOURCE OF CONTAMINATION
Source of Release Cause of Release Type of Release Product Type Released
(Check primary source) (Check primary cause) (Check one) (Check primary product type released)
❑ Tank ❑ Spill 0 Petroleum 0 Gasoline/ Diesel/ ❑ Diesel/Veg. Oil
Q Piping ❑ Overfill ❑ Non -Petroleum Kerosene Blend
Heating Oil ❑ Vegetable Oil 100%
❑❑ Dispenser Corrosion Both
❑❑
❑ Other Petroleum ❑ E10 — E20
❑ Submersible Turbine Pump Q Physical/Mechanical
Location Products
❑ (Check one) Metals Delivery Problem Damage ❑ E21 — E84
❑
❑ Install Problem ❑ E85 — E99
❑ Spill Bucket ❑ Other Inorganics o
❑ Other ❑Facilit Y [:]Ethanol 100 /o
❑ Other ❑ Other Organics
❑ Unknown ❑Residence ❑ E01 — E09
❑ Unknown
❑Other
Definitions presented on reverse
Definitions presented on reverse
Ownership
1. Municipal 2. Military 3. Unknown 4. Private 5. Federal 6. County 7. State
Operation Type
1. Public Service 2. Agricultural 3. Residential 4. Education/Relig. 5. Industrial 6. Commercial 7. Mining
UST Form 61 (02/19) Page 1 of 2
IMPACT ON DRINKING WATER SUPPLIES
Water Supply Wells Affected? 1. Yes 2. No 3. Unknown
Number of Water Supply Wells Affected
Water Supply Wells Contaminated: (Include Users Names, Addresses and Phone Numbers. Attach additional sheet
if necessary)
1.
2.
3.
UST SYSTEM OWNER
UST Owner/Company
Pilot Travel Centers, LLC
Point of Contact
Address
Keith Carlton, Environmental Project Manager
5508 Lonas Road
City
State
Zip Code
Telephone Number
Knoxville
TN
37909
864-474-3106
UST SYSTEM OPERATOR
UST Operator/Company
Address
Pilot Travel Centers, LLC
5508 Lonas Road
City
State
Zip Code
Telephone Number
Knoxville
TN
37909
864-474-3106
LANDOWNER AT LOCATION OF UST INCIDENT
Landowner
Address
Pilot Travel Centers, LLC
5508 Lonas Road
City
State
Zip Code
Telephone Number
Knoxville
TN
37909
864-474-3106
Draw Sketch of Area (showing two major road intersections) or Attach Map
See attached site map
Person Reporting Incident R. Wagner
Company Apex Companies, LLC (on behalf of Pilot)
Telephone Number 540-563-4920
Title Sr. Program Manager
Address 7724 Garland Circle, Roanoke, VA 24019
Date 1/25/20
UST Form 61 (02/19)
Page 2 of 2
Definitions of Sources
Tank: means the tank that stores the product and is part of the underground storage tank system
Piping: means the piping and connectors running from the tank or submersible turbine pump to the dispenser or other end -use equipment (Vent, vapor recovery, or fill
lines are excluded.)
Dispenser: includes the dispenser and the equipment used to connect the dispenser to the piping (e.g., a release from a suction pump or from components located above
the shear valve)
Submersible Turbine Pump (STP) Area includes the submersible turbine pump head (typically located in the tank sump), the line leak detector, and the piping that
connects the submersible turbine pump to the tank
Delivery Problem: identifies releases that occurred during product delivery to the tank. (Typical causes associated with this source are spills and overfills.)
Other: serves as the option to use when the release source is known but does not fit into one of the preceding categories (e.g., for releases from vent lines, vapor
recovery lines, and fill lines)
Unknown: identifies releases for which the source has not been determined
Definitions of Causes
Spill: use this cause when a spill occurs (e.g., when the delivery hose is disconnected from the tank fill pipe or when the nozzle is removed from the dispenser)
Overfill: use when an overfill occurs (e.g., overfills may occur from the fill pipe at the tank or when the nozzle fails to shut off at the dispenser)
Physical or Mechanical Damage: use for all types of physical or mechanical damage, except corrosion (e.g., puncture of tank or piping, loose fittings, broken
components, and components that have changed dimension)
Corrosion: use when a metal tank, piping, or other component has a release due to corrosion (e.g., for steel, corrosion takes the form of rust)
Installation Problem: use when the problem is determined to have occurred specifically because the UST system was not installed properly
Other: use this option when the cause is known but does not fit into one of the preceding categories (e.g., putting regulated substances into monitoring wells)
Unknown: use when the cause has not been determined
UST Legend
B-10,000-gallon Gasoline
C - 15,000-gallon Gasoline
A- 4,000-gallon Auto Diesel
D - 20,000-gallon Diesel
E - 20,000-gallons Diesel
DR.: DRY DATE: Oct. 2019
CK.: CLC CAP
APPD.: RSW Implementation
SCALE: 1 = 6T
APEX PROJ. NO.: 768490.030
Incident #3609E
www.apexcos.com
Al,
APEX
7724 Garland Circle
Roanoke, VA24019
Phone:540-563-4920
Site Plan
Pilot Station #56
2825 Lane Street
Kannapolis, North Carolina
FIGURE No. 2
A
,,i,, s'�; :Y
{X' � ,s�
� -t
/�
i� a \
'- .+ ••
q, - - i
�' �'• �.. � ''3�
:� L . t
+�• � ,, ���,,�
. ti — .
^'s.
t� �
r
i
i
s
r
I•:.r i
At
•E-f.
lot •, 1C°.fv�t.r.`'1S+'.0
t ( q e4 �P r
Al
ry NO
10
At
sti
ait 0
7T
w
ANN-
•
i
UST-6F/23B Triennial UST Containment Sump / UDC Integrity Testing D_EQ
Page 1 (Full height hydrostatic or vacuum test)
➢ If any periodic test fails, a suspected release report must be submitted on a UST-17A form, UST Suspected Release 24 Hour Notice. The suspected
release must be investigated, in accordance with 15A NCAC 2N .0603, and defective equipment repaired or replaced in accordance with 15A NCAC
2N .0404/.0900. Results of the investigation must be submitted on a UST-17B form, UST Suspected Release 7 Day Notice.
➢ Containment sumps installed on or after 11/1/2007 that are not monitored continuously for releases using vacuum, pressure, or hydrostatic interstitial
monitoring methods and all other containment sumps installed prior to 11/1/2007 that are used for interstitial monitoring shall be tightness tested at
installation and every three (3) years thereafter in accordance with the manufacturer's written guidelines, PEI/RP100 "Recommended Practices for
Installation of Underground Liquid Storage Systems" and/or PEI/RP1200 "Recommended Practices for the Testing and Verification of Spill, Overfill,
Leak Detection and Secondary Containment Equipment at UST Facilities."
➢ If a UDC / containment sump fails a periodic tightness test, the sump must be replaced or repaired by the manufacturer, or the manufacturer's
authorized representative in accordance with the manufacturer's specifications, or in accordance with a code of practice developed by a nationally
recognized association.
UST FACILITY
Owner / Operator Name
Facility Name
Facility ID#:
PILOT TRAVEL CENTERS, LLC
PILOT TRAVEL CENTERS 056
00-0-0000011084
Facility Street Address
Facility City
County
2825 LANE STREET
KANNAPOLIS
Cabarrus
TESTING CONTRACTOR INFORMATION
Company Name
Phone
E-mail Address
JONES & FRANK
704-393-8542
MSTODDARD@JONES-FRANK.COM
I certify, under penalty of law, that the testing data provided on this form documents the UST system equipment was tested in accordance with the
manufacturer's guidelines and the applicable national industry stan rds listed in 15A N9fC 2N .0406 and/or 15A NCAC 2N .0900.
MICHAEL STODDARD
IA4"_4
Signature of person4Wnducting test
� 01/25/2020
Print Name of person conducting test
Test Date
Identify UDC/sump (By
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
Dispenser No. or Tank Number,
Tank Size, Stored Product, e.g.
®Tank
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
#1 10k Regular STP, Disp 112,
#: #2 20K
#:
#:
#:
#:
#:
etc.)
PIPING SUMP
Transition sumps should be listed above as "TS-XX" (with XX= sump ID#)
® FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
Sump Material
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
M Hydrostatic
❑ Hydrostatic
❑ Hydrostatic
❑ Hydrostatic
❑ Hydrostatic
❑ Hydrostatic
Test Type
❑ Vacuum
❑ Vacuum
❑ Vacuum
❑ Vacuum
❑ Vacuum
❑ Vacuum
Indicate units for all measurements
Liquid and debris removed from
M Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
sump?
Visual inspection (No cracks,
loose parts or separation of the
M Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
containment sum
Sump Depth in inches
24 INCHES
Height from sump bottom to top
of highest penetration or sump
12 INCHES
sidewall seam in inches
Wait time between applying
15 MINUTES
vacuum/water and start of test
Begin i End Test Time
15:00 i 16:00
i
i
i
i
i
(minimum test time: 1 hour)
Begin i End values (inches)
21 IN i 21 IN
i
i
i
i
i
Pass/Fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of 1/8 inch or more fails the test; Vacuum: No change in vacuum
Test Result
® Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
Testing following product line leak found inside containment sump. Sump passed hydrostatic tests.
Date next Containment Sump/UDC integrity test due (required every 3 years)
01/25/2020
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY, DIVISION OF WASTE MANAGEMENT, UST SECTION 3/2019
1646 MAIL SERVICE CENTER, RALEIGH, NC 27699-1646 PHONE (919) 707-8171 FAX (919) 715-1117 http://www.wastenglnc.org
UST-6F/23B Triennial UST Containment Sump / UDC Integrity Testing
Q�
MD.
Page 2 Low Liquid Level Test)
Containment sumps installed on or after 11/1/2007 that are not monitored continuously for releases using vacuum, pressure, or hydrostatic interstitial
monitoring methods and all other containment sumps installed prior to 11/1/2007 that are used for interstitial monitoring can be tightness tested every
three (3) years in accordance with the NCDEQ Low Level Hydrostatic Integrity Test Procedures which can be found on the UST section website at
https:Hdeq.nc.gov/about/divisions/waste-management/ust/forms. This method cannot be used for the installation testing of containment sumps.
➢ If any periodic test fails, a suspected release report must be submitted on a UST-17A form, UST Suspected Release 24 Hour Notice. The suspected
release must be investigated, in accordance with 15A NCAC 2N .0603, and defective equipment repaired or replaced in accordance with 15A NCAC
2N .0404/.0900. Results of the investigation must be submitted on a UST-17B form, UST Suspected Release 7 Day Notice.
➢ If a UDC / containment sump fails a periodic tightness test, the sump must be replaced or repaired by the manufacturer, or the manufacturer's
authorized representative in accordance with the manufacturer's specifications, or in accordance with a code of practice developed by a nationally
recognized association.
➢ Attach all setup reports (e.g. Veeder-Root: Output Relay Setup, Incon: Main console setup) for the sensor alarms positive shut -down to this form. If
the dispenser has a standalone sensor to shut -down the dispenser then annotate on the test form in the comments section.
UST FACILITY
Owner / Operator Name
Facility Name
Facility ID#:
Facility Street Address
Facility City
County
TESTING CONTRACTOR INFORMATION
Company Name
Phone
E-mail Address
I certify, under penalty of law, that the testing data provided on this form documents the UST system equipment was tested in accordance with the
manufacturer's guidelines, the applicable national industry standards listed in 15A NCAC 2N .0406 and/or 15A NCAC 2N .0900, or another method
approved by NC DEQ.
Print Name of person conducting test
Signature of person conducting test
Test Date
Identify UDC/sump (By
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
Dispenser No. or Tank Number,
Tank Size, Stored Product; e.g.
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
#1 10k Regular STP, Disp 112,
#:
#:
#:
#:
#:
#:
etc.
Transition sumps should be listed above as "TS-XX" (with XX= sump ID#)
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
Sump Material
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
Indicate units for all measurements
Liquid and debris removed from
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
sump?
Is sensor 2" or less from lowest
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
portion of sump bottom?
Visual inspection (No cracks,
loose parts or separation of the
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
containment sump)
Did sensor alarm when tested?
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
If sensor alarms, did the STP
and/or dispenser shut-off?
Note for dispenser sensors all
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
product types in the dispenser
must be disabled.
Level above bottom of sump
where sensor alarms. (inches)
Wait time between applying
water and start of test
Begin i End Test Time
i
i
i
i
i
i
(minimum test time: 1 hour)
Begin i End values (inches)
i
i
i
i
i
i
Pass/Fail criteria: Any No or Fail in the above, the sump fails the test . Hydrostatic: Water level drop of 1/8 inch or more fails the test.
Test Result
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests)
Date next Containment Sump/UDC integrity test due (required every 3 years)
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY, DIVISION OF WASTE MANAGEMENT, UST SECTION 3/2019
1646 MAIL SERVICE CENTER, RALEIGH, NC 27699-1646 PHONE (919) 707-8171 FAX (919) 715-1117 http://www.wasteagtnc.org
UST-6F/23B Triennial UST Containment Sump / UDC Integrity Testing
Page 3 (Dri-sUMpTM Test)
Containment sumps installed on or after 11/1/2007 that are not monitored continuously for releases using vacuum, pressure, or hydrostatic interstitial
monitoring methods and all other containment sumps installed prior to 11/1/2007 that are used for interstitial monitoring can be tightness tested every
three (3) years in accordance with the Dri-sumpTM testing method.
➢ If any periodic test fails, a suspected release report must be submitted on a UST-17A form, UST Suspected Release 24 Hour Notice. The suspected
release must be investigated, in accordance with 15A NCAC 2N .0603, and defective equipment repaired or replaced in accordance with 15A NCAC 2N
.0404/.0900. Results of the investigation must be submitted on a UST-17B form, UST Suspected Release 7 Day Notice.
➢ If a UDC / containment sump fails a periodic tightness test, the sump must be replaced or repaired by the manufacturer, or the manufacturer's
authorized representative in accordance with the manufacturer's specifications, or in accordance with a code of practice developed by a nationally
recognized association.
UST FACILITY
Owner / Operator Name
Facility Name
Facility ID#:
Facility Street Address
Facility City
County
TESTING CONTRACTOR INFORMATION
Company Name
Phone
E-mail Address
I certify, under penalty of law, that the testing data provided on this form documents the UST system equipment was tested in accordance with the
manufacturer's guidelines, the applicable national industry standards listed in 15A NCAC 2N .0406 and/or 15A NCAC 2N .0900, or another method
approved by NC DEQ.
Print Name of person conducting test
Signature of person conducting test
Test Date
Tester Certification #:
Equipment Certification #:
Tester Certification Expiration:
Equipment Certification Expiration:
Identify UDC/sump (By
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
Dispenser No. or Tank Number,
Tank Size, Stored Product; e.g.
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
#1 10k Regular STP, Disp 112,
#:
#:
#:
etc.
Transition sumps should be listed above as "TS-XX" (with XX= sump ID#)
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
Sump Material
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
Construction
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
Liquid and debris removed from
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
sump?
Visual inspection (No cracks,
loose parts, open penetrations
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
or separation of the
containment sum
Is groundwater above bottom of
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
sump?
seconds mm WC
seconds mm WC
seconds mm WC
seconds j mm WC
seconds mm WC
seconds mm WC
VST #1 Communication
VST #2 Communication (if
applicable)
VST communication test should be i 2.3 mm WC in 5-10 seconds. Attach a map of the VST locations for each sump to the results.
Test length in seconds
DW Primary wall or SW
Laser Verification
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
(DW Primary wall or SW)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
Test length in seconds
(Secondary wall, if DW
Laser Verification
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
❑ Dot (Pass)
(Secondary wall, if DW)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
❑ Line (Fail)
Pass/Fail criteria: Must pass visual inspection. Laser result must be a laser -dot (pass). If the first test fails, then conduct a second test entering results in
another column. Test is not valid if liquid or debris was not removed from sump.
Final Test Result
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests)
Date next Containment Sump/UDC integrity test due (required every 3 years)
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY, DIVISION OF WASTE MANAGEMENT, UST SECTION 3/2019
1646 MAIL SERVICE CENTER, RALEIGH, NC 27699-1646 PHONE (919) 707-8171 FAX (919) 715-1117 http://www.wasteagtnc.orq
UST-6F/23B Triennial UST Containment Sump / UDC Integrity Testing
Page 4 (DPleak° Test)
Containment sumps installed on or after 11/1/2007 that are not monitored continuously for releases using vacuum, pressure, or hydrostatic interstitial
monitoring methods and all other containment sumps installed prior to 11/1/2007 that are used for interstitial monitoring can be tightness tested every
three (3) years in accordance with the DPleak° sump testing method.
➢ If any periodic test fails, a suspected release report must be submitted on a UST-17A form, UST Suspected Release 24 Hour Notice. The suspected
release must be investigated, in accordance with 15A NCAC 2N .0603, and defective equipment repaired or replaced in accordance with 15A NCAC 2N
.0404/.0900. Results of the investigation must be submitted on a UST-17B form, UST Suspected Release 7 Day Notice.
➢ If a UDC / containment sump fails a periodic tightness test, the sump must be replaced or repaired by the manufacturer, or the manufacturer's
authorized representative in accordance with the manufacturer's specifications, or in accordance with a code of practice developed by a nationally
recognized association.
UST FACILITY
Owner / Operator Name
Facility Name
Facility ID#:
Facility Street Address
Facility City
County
TESTING CONTRACTOR INFORMATION
Company Name
Phone
E-mail Address
I certify, under penalty of law, that the testing data provided on this form documents the UST system equipment was tested in accordance with the
manufacturer's guidelines, the applicable national industry standards listed in 15A NCAC 2N .0406 and/or 15A NCAC 2N .0900, or another method
approved by NC DEQ.
Print Name of person conducting test
Signature of person conducting test
Test Date
Tester Certification #:
Identify UDC/sump (By
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
❑Dispenser
Dispenser No. or Tank Number,
Tank Size, Stored Product; e.g.
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
❑Tank
#1 10k Regular STP, Disp 112,
#:
#:
#:
#:
#:
#:
etc.
Transition sumps should be listed above as "TS-XX" with XX= sump ID#
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
❑ FRP
Sump Material
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
❑ Plastic
Construction
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
❑ SW ❑ DW
Liquid and debris removed from
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
sump?
Visual inspection (No cracks,
loose parts, open penetrations
El Pass El Fail
El Pass El Fail
El Pass El Fail
El Pass El Fail
El Pass El Fail
El Pass El Fail
or separation of the
containment sum
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
North/Rear
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
East/Right
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
South/Front
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
West/Left
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Floor
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Electrical/Pen #1
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
STP/Turbine/Pen#2
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Pen #3 /
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Pen #4 /
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
❑ N/A
Pass/Fail criteria: Must pass visual inspection. Test is not valid if liquid or debris was not removed from sump. No areas of sump that fail.
LDT test report with addendums attached I ❑ Yes ❑ No
Final Test Result I ❑ Pass ❑ Fail I ❑ Pass ❑ Fail I ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail
Comments — (include information on repairs made priorto testing, and recommended follow-up forfailed tests)
Date next Containment Sump/UDC integrity test due (required every 3 ears
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY, DIVISION OF WASTE MANAGEMENT, UST SECTION 3/2019
1646 MAIL SERVICE CENTER, RALEIGH, NC 27699-1646 PHONE (919) 707-8171 FAX (919) 715-1117 htto://www.wastengtnc.org
Beverly, Trudy
From: Beverly, Trudy
Sent: Monday, January 27, 2020 9:28 AM
To: Robert Wagner
Subject: RE: [External] RE: Pilot 56 Kannapolis Release Reporting
Great.
Thanks for the update,
Trudy
� Qi�- Trudy Beverly, L.G.
Hydrogeologist, Division of Waste Management
North Carolina Department of Environmental Quality
UST Section, Mooresville Regional Office
704.235.2182 (Office)
Trudy. B everlykncdenn gov
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
Office Mailing Address:
610 East Center Avenue, Suite 301
Mooresville, NC 28115
Branch's Underground Storage Tanks Website Address: hops://deq.nc.gov/about/divisions/waste-manaaement/ust
Branch's Above Ground Storage Tanks Website Address: ht!ps:Hdeg.nc.gov/about/divisions/waste-management/ust/ast-proeram
INTERACTIVE MAPS WITH DWM SITES AND PERMITTED FACILITIES:
httns://deo.nc. eov/about/divisions/waste-management/waste-management-rules-data/waste-management-eis-mans
File Review Procedures:
https://deq.nc. gov/about/divisions/waste-management/ust/file-review-procedures#mooresville-regional-office
ONLINE ACCESS TO UST SECTION DOCUMENTS (Laserfiche):
hops: //deg.nc. gov/about/divisions/waste-management/laserfiche
Document Submittal & UST File Names for Laserfiche Policies:
https:Hfiles.nc. gov/ncdeg/Waste%20Management/D WM/UST/Corrective%2OAction/Electronic%2ODocument%2OSubmittal%2OMemo%2OUpdate.pdf
https:Hfiles.nc. gov/ncdeq/\Vaste%2OManagement/D WM/UST/Corrective%2OAction/UST%20file%20names%20for%2OLaserfiche.docx
From: Robert Wagner [mailto:RWagner@apexcos.com]
Sent: Monday, January 27, 2020 8:33 AM
To: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Subject: [External] RE: Pilot 56 Kannapolis Release Reporting
External email. Do not click links or open attachments unless you verify. Send all suspicious email as an
attachment to report.spam@nc.Eov
Trudy all repairs have been made and the line is scheduled for testing today.
Attached is the passing hydro test form.
Also attached a picture of the fitting that busted in sump as well as a pic of the repaired line.
Robert Wagner
Sr Program Manager
7724 Garland Cir
Roanoke, VA 24019
O)140-563-4920 x4451 M) 140-798-1494
APEX
ED Add me to your contact list!
am Wu1
ENR Top 30 All -Environmental Firm Im CIE
We've moved! Our new address is 7724 Garland Cir, Roanoke, VA 24019. Please update your contact
list. Thanks.
Privacy Notice: This message and any attachment(s) hereto are intended solely for the individual(s) listed in the masthead. This message may contain
information that is privileged or otherwise protected from disclosure. Any review, dissemination or use of this message or its contents by persons other
than the addressee(s) is strictly prohibited and may be unlawful. If you have received this message in error, please notify the sender by return e-mail and
delete the message from your system. Thank you.
From: Robert Wagner
Sent: Saturday, January 25, 2020 1:39 PM
To: 'Beverly, Trudy' <trudy.beverly@ncdenr.gov>
Cc: Keith Carlton <Keith.Carlton@ pilottravelcenters.com>
Subject: Pilot 56 Kannapolis Release Reporting
Trudy
Pilot has had a release of diesel fuel into a transition sump for the auto diesel.
The release has been stopped and repairs are being made today.
Once repairs are complete the sump with be hydrostatically tested and the line will be tested to ensure a good
fix.
We do not believe that any product left the sump at this time.
Please let us know if you have any questions regarding the attached.
Thanks,
Robert
Robert Wagner
Sr Program Manager
7724 Garland Cir
Roanoke, VA 24019
0)140-563-4920 x4451 M) 140-798-1494
APEXa
Add me to your contact list!
IPMEGUMM Wrk afe
ENR Top 30 All -Environmental Firm om CIE
We've moved! Our new address is 7724 Garland Cir, Roanoke, VA 24019. Please update your contact
list. Thanks.
Privacy Notice: This message and any attachment(s) hereto are intended solely for the individual(s) listed in the masthead. This message may contain
information that is privileged or otherwise protected from disclosure. Any review, dissemination or use of this message or its contents by persons other
than the addressee(s) is strictly prohibited and may be unlawful. If you have received this message in error, please notify the sender by return e-mail and
delete the message from your system. Thank you.