HomeMy WebLinkAboutMO-9475_40916_CA_SCH_20190705_Tank Tightness TestsTest Date 71512019
SLABS
TOTAL TANK VOL.
8,000
PRODUCT VOL.
4858
ULLAGE VOL.
3142
PRODUCT TYPE
REGULAR
Permit #
7646
TANK #
2
56.0 x 0.026 =
INCHES OF PRODUCT WEIGHT OF PRODUCT
0.0 x .036 =
INCHES OF WATER IN TANK
Line 1 + Line 2 = Total Positive Head Pressure In Tank =
1.0 x .036 =
INCHES OF WATER OUTSIDE TANK
Total Head Pressure Minus Outside Water Pressure
Always add .5 PSI +
NOTE: If Line 6 is Less Than .5 PSI Line 7 Shall be .5 PSI
TEST PRESSURE
Time
Pressure
Baseline Background:
3:55 PM
0.0
Blower Started:
3:57 PM
0.0
Test Pressure Reached:
4:00 PM
1.920
Blower Turned Off:
4:01 PM
2.014
Test Began:
4:02 PM
2.007
Test Ended:
4:04 PM
2.002
Added:
Cal # 1 Cal #2
Average:
Avg. Cal.
Began:
Ended:
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
City/State/Zip KANNAPOLIS, NC, 28081
Location Contact
Location Phone
By: TANK STICK
Where: MONITORING WELL BY TANK PAD
In -Tank Microphone
Acoustic Signal Processor
Pressure Sensor
Water Sensor Display
Water Sensor Probe
=.05 #VALUE! x 60 = #VALUE!
"A" Factor Min. Time of Test
I Height
43
Product
in Tank
Water
Tank
1.456
0.000
1.456
0.036
1.420
1.920
1.920
Serial Number
PSI (1)
PSI (2)
PSI (3)
PSI (4)
+/-PSI (5)
PSI (6)
+/-PSI (7)
ibration Due Date
M1806019
08/2019
E1836004
10/2019
40742714
07/2019
D1704261
07/2019
Din
F96B ttom to
Grade
u"
Ground
Water
1.0000
Test Date 71512019
6LABS
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
TOTAL TANK VOL. 8000 City/State/Zip KANNAPOLIS, NC, 28081
PRODUCT VOL. 4858 Location Contact 0
ULLAGE VOL. 3142 Location Phone 0
PRODUCTTYPE REGULAR
Permit # 7646 Depth of Groundwater Determined:
TANK # 2 By: TANK STICK
Where: AONITORING WELL BY TANK PA
THE ACOUSTIC CHARACTERISTIC OF A LEAK REVEALS:
X TIGHT TANK
THIS UNDERGROUND STORAGE TANK PASSES THE CRITERIA SET FORTH BY THE U.S. EPA.
ULLAGE (DRY) PORTION OF LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
BELOW PRODUCT LEVEL (WET) PORTION LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
WATER SENSOR INDICATES:
(CHECK ONLY ONE)
No Water Intrusion
Water Instrusion
Not Applicable X
Operator Inf• •
Print NameChris StricklandCertification #87-2100
Sign Name Expiration Date:06/2021
Testing FirmEnvironmental LaboratoriesTelephone #864-370-0637
Address15 Sulphur Springs Rd MMM
Greenville SC 29617
NEW YORK STATE REQUIREMENT: A DIAGRAM OF THE TANK SYSTEM MUST BE SUBMITTED TO THE STATE WITH THIS REPORT
EQUIPMENT SERIAL NUMBERS AND CALIBRATION EXPIRATION DATES:
Serial Number Calibration Expiration Date
IN -TANK MICROPHONE
ACOUSTIC SIGNAL PROCESSOR
PRESSURE SENSOR 40742714
WATER SENSOR DISPLAY D
WATER SENSOR PROBE 0 0' • •
Test Date 71512019
SLABS
TOTAL TANK VOL.
8,000
PRODUCT VOL.
1477
ULLAGE VOL.
6523
PRODUCT TYPE
PREMIUM
Permit #
7646
TANK #
3
23.0 x 0.026 =
INCHES OF PRODUCT WEIGHT OF PRODUCT
0.0 x .036 =
INCHES OF WATER IN TANK
Line 1 + Line 2 = Total Positive Head Pressure In Tank =
1.0 x .036 =
INCHES OF WATER OUTSIDE TANK
Total Head Pressure Minus Outside Water Pressure
Always add .5 PSI +
NOTE: If Line 6 is Less Than .5 PSI Line 7 Shall be .5 PSI
TEST PRESSURE
Time
Pressure
Baseline Background:
4:05 PM
0.0
Blower Started:
4:07 PM
0.0
Test Pressure Reached:
4:11 PM
1.062
Blower Turned Off:
4:12 PM
1.115
Test Began:
4:13 PM
1.112
Test Ended:
4:15 PM
1.107
Added:
Cal # 1 Cal #2
Average:
Avg. Cal.
Began:
Ended:
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
City/State/Zip KANNAPOLIS, NC, 28081
Location Contact
Location Phone
By: TANK STICK
Where: MONITORING WELL BY TANK PAD
In -Tank Microphone
Acoustic Signal Processor
Pressure Sensor
Water Sensor Display
Water Sensor Probe
=.05 #VALUE! x 60 = #VALUE!
"A" Factor Min. Time of Test
I Height
1 44
Product
in Tank
Water
Tank
0.598
0.000
0.598
0.036
0.562
1.062
1.062
Serial Number
PSI (1)
PSI (2)
PSI (3)
PSI (4)
+/-PSI (5)
PSI (6)
+/-PSI (7)
ibration Due Date
M1806019
08/2019
E1836004
10/2019
40742714
07/2019
D1704261
07/2019
Din
F96B ttom to
Grade
u"
Ground
Water
1.0000
Test Date 71512019
6LABS
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
TOTAL TANK VOL. 8000 City/State/Zip KANNAPOLIS, NC, 28081
PRODUCT VOL. 1477 Location Contact 0
ULLAGE VOL. 6523 Location Phone 0
PRODUCT TYPE PREMIUM
Permit # 7646 Depth of Groundwater Determined:
TANK # 3 By: TANK STICK
Where: AONITORING WELL BY TANK PA
THE ACOUSTIC CHARACTERISTIC OF A LEAK REVEALS:
X TIGHT TANK
THIS UNDERGROUND STORAGE TANK PASSES THE CRITERIA SET FORTH BY THE U.S. EPA.
ULLAGE (DRY) PORTION OF LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
BELOW PRODUCT LEVEL (WET) PORTION LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
WATER SENSOR INDICATES:
(CHECK ONLY ONE)
No Water Intrusion
Water Instrusion
Not Applicable X
Operator Inf• •
Print NameChris StricklandCertification #87-2100
Sign Name Expiration Date:06/2021
Testing FirmEnvironmental LaboratoriesTelephone #864-370-0637
Address15 Sulphur Springs Rd MMM
Greenville SC 29617
NEW YORK STATE REQUIREMENT: A DIAGRAM OF THE TANK SYSTEM MUST BE SUBMITTED TO THE STATE WITH THIS REPORT
EQUIPMENT SERIAL NUMBERS AND CALIBRATION EXPIRATION DATES:
Serial Number Calibration Expiration Date
IN -TANK MICROPHONE
ACOUSTIC SIGNAL PROCESSOR
PRESSURE SENSOR 40742714
WATER SENSOR DISPLAY D
WATER SENSOR PROBE 0 0' • •
Test Date 71512019
SLABS
TOTAL TANK VOL.
8,000
PRODUCT VOL.
1568
ULLAGE VOL.
6432
PRODUCTTYPE
KEROSENE
Permit #
7646
TANK #
1
24.0 x 0.029 =
INCHES OF PRODUCT WEIGHT OF PRODUCT
0.0 x .036 =
INCHES OF WATER IN TANK
Line 1 + Line 2 = Total Positive Head Pressure In Tank =
1.0 x .036 =
INCHES OF WATER OUTSIDE TANK
Total Head Pressure Minus Outside Water Pressure
Always add .5 PSI +
NOTE: If Line 6 is Less Than .5 PSI Line 7 Shall be .5 PSI
TEST PRESSURE
Time
Pressure
Baseline Background:
3:30 PM
0.0
Blower Started:
3:32 PM
0.0
Test Pressure Reached:
3:44 PM
1.160
Blower Turned Off:
3:46 PM
1.200
Test Began:
3:47 PM
1.196
Test Ended:
3:49 PM
1.193
Added:
Cal #1 Cal #2
Average:
Avg. Cal.
Began:
Ended:
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
City/State/Zip KANNAPOLIS, NC, 28081
Location Contact
Location Phone
By: TANK STICK
Where: MONITORING WELL BY TANK PAD
In -Tank Microphone
Acoustic Signal Processor
Pressure Sensor
Water Sensor Display
Water Sensor Probe
=.05 #VALUE! x 60 = #VALUE!
"A" Factor Min. Time of Test
I Height
43
Product
in Tank
Water
Tank
0.696
0.000
0.696
0.036
0.660
1.160
1.160
..
Serial Number
PSI (1)
PSI (2)
PSI (3)
PSI (4)
+/-PSI (5)
PSI (6)
+/-PSI (7)
ibration Due Date
M1806019
08/2019
E1836004
10/2019
40742714
07/2019
D1704261
07/2019
Din
F96B ttom to
Grade
u"
Ground
Water
1.0000
Test Date 71512019
6LABS
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
TOTAL TANK VOL. 8000 City/State/Zip KANNAPOLIS, NC, 28081
PRODUCT VOL. 1568 Location Contact 0
ULLAGE VOL. 6432 Location Phone 0
PRODUCTTYPE KEROSENE
Permit # 7646 Depth of Groundwater Determined:
TANK # 1 By: TANK STICK
Where: AONITORING WELL BY TANK PA
THE ACOUSTIC CHARACTERISTIC OF A LEAK REVEALS:
X TIGHT TANK
THIS UNDERGROUND STORAGE TANK PASSES THE CRITERIA SET FORTH BY THE U.S. EPA.
ULLAGE (DRY) PORTION OF LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
BELOW PRODUCT LEVEL (WET) PORTION LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
WATER SENSOR INDICATES:
(CHECK ONLY ONE)
No Water Intrusion
Water Instrusion
Not Applicable X
Operator Inf• •
Print NameChris StricklandCertification #87-2100
Sign Name Expiration Date:06/2021
Testing FirmEnvironmental LaboratoriesTelephone #864-370-0637
Address15 Sulphur Springs Rd MMM
Greenville SC 29617
NEW YORK STATE REQUIREMENT: A DIAGRAM OF THE TANK SYSTEM MUST BE SUBMITTED TO THE STATE WITH THIS REPORT
EQUIPMENT SERIAL NUMBERS AND CALIBRATION EXPIRATION DATES:
Serial Number Calibration Expiration Date
IN -TANK MICROPHONE
ACOUSTIC SIGNAL PROCESSOR
PRESSURE SENSOR 40742714
WATER SENSOR DISPLAY D
WATER SENSOR PROBE 0 0' • •
Test Date 71512019
SLABS
TOTAL TANK VOL.
8,000
PRODUCT VOL.
1211
ULLAGE VOL.
6789
PRODUCT TYPE
DIESEL
Permit #
7646
TANK #
4
20.0 x 0.031 =
INCHES OF PRODUCT WEIGHT OF PRODUCT
0.0 x .036 =
INCHES OF WATER IN TANK
Line 1 + Line 2 = Total Positive Head Pressure In Tank =
1.0 x .036 =
INCHES OF WATER OUTSIDE TANK
Total Head Pressure Minus Outside Water Pressure
Always add .5 PSI +
NOTE: If Line 6 is Less Than .5 PSI Line 7 Shall be .5 PSI
TEST PRESSURE
Time
Pressure
Baseline Background:
4:17 PM
0.0
Blower Started:
4:19 PM
0.0
Test Pressure Reached:
4:21 PM
1.084
Blower Turned Off:
4:23 PM
1.112
Test Began:
4:24 PM
1.110
Test Ended:
4:26 PM
1.107
Added:
Cal # 1 Cal #2
Average:
Avg. Cal.
Began:
Ended:
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
City/State/Zip KANNAPOLIS, NC, 28081
Location Contact
Location Phone
By: TANK STICK
Where: MONITORING WELL BY TANK PAD
In -Tank Microphone
Acoustic Signal Processor
Pressure Sensor
Water Sensor Display
Water Sensor Probe
=.05 #VALUE! x 60 = #VALUE!
"A" Factor Min. Time of Test
I Height
1 46
Product
in Tank
Water
Tank
0.620
0.000
0.620
0.036
0.584
1.084
1.084
..
Serial Number
PSI (1)
PSI (2)
PSI (3)
PSI (4)
+/-PSI (5)
PSI (6)
+/-PSI (7)
ibration Due Date
M1806019
08/2019
E1836004
10/2019
40742714
07/2019
D1704261
07/2019
Din
F96B ttom to
Grade
u"
Ground
Water
1.0000
Test Date 71512019
6LABS
Location MKDK FOOD MART
Address 2500 SOUTH MAIN STREET
TOTAL TANK VOL. 8000 City/State/Zip KANNAPOLIS, NC, 28081
PRODUCT VOL. 1211 Location Contact 0
ULLAGE VOL. 6789 Location Phone 0
PRODUCT TYPE DIESEL
Permit # 7646 Depth of Groundwater Determined:
TANK # 4 By: TANK STICK
Where: AONITORING WELL BY TANK PA
THE ACOUSTIC CHARACTERISTIC OF A LEAK REVEALS:
X TIGHT TANK
THIS UNDERGROUND STORAGE TANK PASSES THE CRITERIA SET FORTH BY THE U.S. EPA.
ULLAGE (DRY) PORTION OF LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
BELOW PRODUCT LEVEL (WET) PORTION LEAK
THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA.
WATER SENSOR INDICATES:
(CHECK ONLY ONE)
No Water Intrusion
Water Instrusion
Not Applicable X
Operator Inf• •
Print NameChris StricklandCertification #87-2100
Sign Name Expiration Date:06/2021
Testing FirmEnvironmental LaboratoriesTelephone #864-370-0637
Address15 Sulphur Springs Rd MMM
Greenville SC 29617
NEW YORK STATE REQUIREMENT: A DIAGRAM OF THE TANK SYSTEM MUST BE SUBMITTED TO THE STATE WITH THIS REPORT
EQUIPMENT SERIAL NUMBERS AND CALIBRATION EXPIRATION DATES:
Serial Number Calibration Expiration Date
IN -TANK MICROPHONE
ACOUSTIC SIGNAL PROCESSOR
PRESSURE SENSOR 40742714
WATER SENSOR DISPLAY D
WATER SENSOR PROBE 0 0' • •
Beverly, Trudy
From: Beverly, Trudy
Sent: Wednesday, July 17, 2019 10:31 AM
To: Rick Laroche
Subject: RE: [External] MKDK Food Mart H Permit 07646
Hey Rick,
Please add a note with the paper copies stating that you emailed me the pdf copies on 7/17/2019.
Thanks,
Trudy
From: Rick Laroche [mailto:Rick@elabsinc.net]
Sent: Wednesday, July 17, 2019 10:01 AM
To: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Subject: RE: [External] MKDK Food Mart // Permit 07646
External email. Do not click links or open attachments unless you verify. Send all suspicious email as an
rtachment to report.spam@nc.gov
Trudy,
Thank you for responding. Our office does not have the capability to copy our results onto a CD. Will our
printed test results be sufficient?
Best Regards,
Rick LaRoche
864-370-0637 ext 1
rick@elabsinc.net
From: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Sent: Wednesday, July 17, 2019 9:33 AM
To: Rick Laroche <Rick@elabsinc.net>
Subject: RE: [External] MKDK Food Mart // Permit 07646
The UST section requires paper and electronic copies (pdf on cd) to be mailed to our office.
Office Mailing Address:
610 East Center Avenue, Suite 301
Mooresville, NC 28115
Trudy
From: Rick Laroche [mailto:Rick@elabsinc.net
Sent: Wednesday, July 17, 2019 9:28 AM
1
To: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Subject: RE: [External] MKDK Food Mart // Permit 07646
��report.spam@nc.gov
rnal email. Do not click links or open attachments unless you verify. Send all suspicious email as an
Good morning. This link does not make sense to me. Please summarize/ specify what your requirements are so
that I may submit our results to your office. Thank you!
Best Regards,
Rick LaRoche
864-370-0637 ext 1
rick@elabsinc.net
From: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Sent: Wednesday, July 17, 2019 9:18 AM
To: Rick Laroche <Rick@elabsinc.net>
Cc: mkdkfoodmart@yahoo.com
Subject: RE: [External] MKDK Food Mart // Permit 07646
Please see the following policies for document submittal to the UST Section.
Document Submittal & UST File Names for Laserfiche Policies:
https://files.nc.gov/ncdeq/Waste%20Management/DW M/UST/Corrective%2OAction/Electronic%2ODocument%2OSubmitta
l%20Memo%20Update.pdf
hlt 2s:Hfiles.nc.gov/ncdeq/Waste%20Management/DWM/UST/Corrective%2OAction/UST%20file%20names%20for%2OLas
erfiche.docx
Trudy
DEI QNORTH CAROLINA
Deparhnwd of Environmental Quality
Tr L.G.
Larsedn, momudil: Rqomd am=
(7" 23S,21i2 (O
Ttudyra hithdwa+
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
Office Mailing Address:
610 East Center Avenue, Suite 301
Mooresville, NC 28115
Branch's Underground Storage Tanks Website Address: hlWs:Hdeq.nc.gov/about/divisions/waste-management/ust
Branch's Above Ground Storage Tanks Website Address: hm2s://deq.nc.,gov/about/divisions/waste-management/ust/ast-
program
INTERACTIVE MAPS WITH DWM SITES AND PERMITTED FACILITIES:
hlt2s:Hdeq.nc.gov/about/divisions/waste-mana,gement/waste-management-rules-data/waste-manor eg ment- ig's-maps
2
File Review Procedures:
https://deq.nc. gov/about/divisions/waste-management/ust/file-review-procedures#mooresville-regional-office
ONLINE ACCESS TO UST SECTION DOCUMENTS (Laserfiche):
hllps://edocs.deq.nc.gov/\VasteManagement/Search.aspx
Document Submittal & UST File Names for Laserfiche Policies:
hops://files.nc. gov/ncdeq/Waste%20Management/DWM/UST/Corrective%20Action/Electronic%20Document%20Submittal
%20Memo%20Update.pdf
hiips:Hfiles.nc. gov/ncdeq/Waste%20Management/DWM/UST/Corrective%20Action/UST%20file%20names%20for%20Las
erfiche.docx
From: Rick Laroche [mailto:Rick@elabsinc.net]
Sent: Wednesday, July 17, 2019 9:16 AM
To: Beverly, Trudy <trudy.beverly@ncdenr.Pov>
Cc: mkdkfoodmart@vahoo.com
Subject: [External] MKDK Food Mart H Permit 07646
ernal email. Do not click links or open attachments unless you verify. Send all suspicious email as an
attachment to report.spam@nc.gov
Please view the attached tank tightness test results conducted by Elabs at MKDK Food Mart, permit 07646, in
Kannapolis, NC.
Best Regards,
Rick LaRoche
864-370-0637 ext 1
rick@elabsinc.net
Beverly, Trudy
From: Beverly, Trudy
Sent: Wednesday, July 17, 2019 8:09 AM
To: Susan@elabsinc.net; mkdkfoodmart@yahoo.com
Cc: Corey Buchanan
Subject: RE: [External] Service notification from El-abs for MKDK Food Mart
Mr. Patel and Ms. Marlowe,
Please see the following policies for document submittal to the UST Section.
Document Submittal & UST File Names for Laserfiche Policies:
httns:Hfiles.nc. izov/ncdea/Waste%2OManaizement/DWM/UST/Corrective%2OAction/Electronic%2ODocument%2OSubmittal
%20Memo%20Update.pdf
httns:Hfiles.nc. izov/ncdea/Waste%2OManaQement/DWM/UST/Corrective%2OAction/UST%20file%20names%20for%2OLas
erfiche.docx
Trudy
DE
N2RTR�AR LIANA
Oepe�A l"rita3 0um ft
rrudy Bwely, L.O.
RAfowfiff Wd
NO& C
QMft
L''ST Sedio4 mantle Rz&nd Office
r-W 211-3193 FL )
Email correspondences to arxJ from this address is subject to the
North Carolina Public records Law and may be disclosed to third parties.
Office Mailing Address:
610 East Center Avenue, Suite 301
Mooresville, NC 28115
Branch's Underground Storage Tanks Website Address: https:Hdeq.nc.gov/about/divisions/waste-management/ust
Branch's Above Ground Storage Tanks Website Address: hLtps:Hdeq.nc.gov/about/divisions/waste-mana,gement/ust/ast-
rp o,gram
INTERACTIVE MAPS WITH DWM SITES AND PERMITTED FACILITIES:
https://deq.nc.gov/about/divisions/waste-management/waste-management-rules-data/waste-mana eg ment- ig s maps
File Review Procedures:
https:Hdeq.nc. gov/about/divisions/waste-management/ust/file-review-procedures#mooresville-regional-office
ONLINE ACCESS TO UST SECTION DOCUMENTS (Laserfiche):
hltps:Hedocs.deq.nc.gov/\VasteManagement/Search.asp
Document Submittal & UST File Names for Laserfiche Policies:
httDs:Hfiles.nc. aov/ncdea/Waste%20Mana2ement/DWM/UST/Corrective%2OAction/Electronic%2ODocument°/`2OSubmittal
%20Memo%20Update.pdf
httDs:Hfiles.nc. eov/ncdea/Waste%2OManaeement/DWM/UST/Corrective%2OAction/UST%20file%20names%20for%2OLas
erfiche.docx
From: Susan Marlowe [mailto:Susan@elabsinc.net]
Sent: Tuesday, July 16, 2019 4:38 PM
To: mkdkfoodmart@yahoo.com; Beverly, Trudy <trudy.beverly@ncdenr.gov>
Subject: [External] Service notification from ELabs for MKDK Food Mart
L�:i:B►:i1F E
attachment
I. Do not click links or open
mpnc
Dear Alpesh:I apologize for the delay in processing your report. As you are aware all of the systems
tested well and PASSED. NCDEQ cannot accept a verbal confirmation. The technician produced the
report on an expired template which does not reflect his current certification. It is company policy that
no one may alter the original author's notations. This technician's schedule has been cancelled for
tomorrow 7-17 as he has been summoned to the office to correct the report. You should receive it
tomorrow and it will be copied to: trudy.beverly(&ncdenr.gov. I am very sorry for this delay.
Thank You, Susan
ELabs
(864)370-0637
15 Sulphur Springs Rd
Greenville, SC 29617
§ or
LABS
15 Sulphur Springs Rd
Greenville, SC 29617
1-864-370-0637
Martin@elabsinc.net
DATE
07/05/2019
TIME
DURATION
1h
TECH(S)
Chris
JOB#
21945742
PO#
PAYMENT
Direct Bill, Cash On Delivery
CUSTOMER SERVICE LOCATION
MKDK Food Mart MKDK Food Mart
2500 South Main St
2500 South Main St Kannapolis NC 28081
Kannapolis NC 28081
J
JOB DETAILS TTT on 4 Tanks @8K each ** High Priority**
REG/ PRE/ DSL/ Kero Please copy trudy.beverly@ncdenr.gov
NOTES FOR
TECHS
COMPLETION
NOTES
Description
Single Tank Test
Multiple Tank Tests
Travel & Truck
Travel & Truck
SUB -TOTAL: TIME & LABOR: EXPENSES:
$1,050.00 $0.00 $0.00
Qty Rate Total
0.00 $300.00 $0.00
4.00 $250.00 $1,000.00
1.00 $50.00 $50.00
PMTS/DEPS: TOTAL DUE:
$0.00 $1, 050.00
CUSTOMER MESSAGE PRE -WORK SIGNATURE POST -WORK SIGNATURE