HomeMy WebLinkAboutMO-9475_40916_G_NORR_20190620_Notice of Regulatory RequirementsROY COOPER
Governor
MICHAEL S. REGAN
Secretary
MICHAEL SCOTT
Director
Ganapati, Inc.
Attn: Alkpeshkumar Patel
2500 South Main Street
Kannapolis, NC 28081
Dear Mr. Patel:
NORTH CAROLINA
Environmental Quality
June 20, 2019
Re: Notice of Regulatory Requirements
15A NCAC 2N .0603
Investigation and Confirmation of a Suspected
Release from an Underground Storage Tank
MKDK Food Mart
2500 South Main Street, Kannapolis
Cabarrus County
Facility ID#: 00-0-0000007646
Incident Number: 40916
Risk Classification: Unknown
The submitted analytical data received by the Mooresville Regional Office of the UST Section,
Division of Waste Management, on June 18, 2019 from samples collected from soil samples indicates that
a release or discharge from a petroleum underground storage tank (UST) system may have occurred at the
above -referenced location. Records indicate that you are the owner or operator of this UST system.
Therefore, you must immediately investigate and confirm the suspected release pursuant to Title 15A
NCAC 2N .0603.
To achieve compliance with this rule, you must conduct a tank tightness test for each UST in
accordance with federal regulation 40 CFR 280.43(c) (as incorporated by Title 15A NCAC 2N .0504) and
a line tightness test for each piping system associated with a UST in accordance with 40 CFR 280.44(b) (as
incorporated by Title 15A NCAC 2N .0505). Conduct a site check in accordance with 40 CFR 280.52(b)
(as incorporated by Title 15A NCAC 2N .0603) in accordance with the most recent version of the
Guidelines for Site Checks, Tank Closure, and Initial Response and Abatement Action for UST Releases,
North Carolina Department of Environmental Quality I Division of Waste Management
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.663.1699
which is available on the internet at https://deq.nc.gov/about/divisions/waste-management/ust/,guidance-
documents.
The results of the tank tightness test(s) and line tightness test(s) must be received by this office
within 7 days of receipt of this notice. The results of the site check must be received by this office within
30 days of receipt of this notice. If a release or discharge is confirmed, a Licensed Geologist or a
Professional Engineer, certified by the State of North Carolina, is required to prepare and certify all reports
submitted to the Department of Environmental Quality in accordance with Title 15A NCAC 2L .0103(e)
and 2L .0111(b).
Failure to comply in the manner and time specified may result in the assessment of civil
penalties and/or the use of other enforcement mechanisms.
If you have any questions regarding the actions that must be taken or the rules mentioned in this
letter, please contact me by email at Trudy.Beverlygncdenr.gov or by phone at (704) 235-2182.
Sincerely,
jw,
Trudy Beverly, L.G.
Hydrogeologist
Mooresville Regional Office
UST Section, Division of Waste Management, NCDEQ
cc: David Troutman, Cabarrus County Health Department (via email)
Corey Buchanan, Geological Resources, Inc. (via email)
D F.
North Carolina Department of Environmental Quality I Division of Waste Management
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.663.1699
Beverly, Trudy
From: Beverly, Trudy
Sent: Friday, June 21, 2019 8:23 AM
To: Corey Buchanan
Subject: RE: [External] Re: MKDK Food Mart - Incident #40916 — Notice of Regulatory
Requirements
Good Morning Corey,
This site will likely receive a LSA request Notice of Regulatory Requirements letter once the Site Check report has
been submitted for review.
Trudy
DE
Department of Elivironmental Quality
ltudgr Bmwllr, L.G.
-101 40. Dr=%M=UMMqP�
K
usift im mma imb l offm
(7" 235,2112 (OR*
-hr
Email correspondence to and from this address is subject to the
North Carolina Public Pecords Law and may be disclosed to third parties.
From: Corey Buchanan[mailto:cnb@geologicalresourcesinc.com]
Sent: Thursday, June 20, 2019 3:11 PM
To: Beverly, Trudy <trudy.beverly@ncdenr.gov>
Subject: [External] Re: MKDK Food Mart - Incident #40916 — Notice of Regulatory Requirements
External email. Do not click links or open attachments unless you verify. Send all suspicious email as an
Fechment to report.spam@nc.gov
Hello Trudy,
I hope your week has been going good, I saw your email that this is in your area.
The site check is already completed following the request by the inspector, and the soil samples lab data
confirmed a release has occurred. Native soils were encountered and collected below the failed components so
no wells were required in this case, surprisingly. The site check report should be complete sometime in next
couple days.
The norr request was for the Isa scope of work. I told the client that would be the next step but he wanted to
hear it and be directed by deq.
Sent from my Whone
On Jun 20, 2019, at 3:01 PM, Beverly, Trudy <trudy.beverly@ncdenr.gov> wrote:
Please see the attached Notice of Regulatory Requirements letter for MKDK Food Mart located
at 2500 South Main Street, Kannapolis, Cabarrus County, NC (Incident #40916).
Trudy
<image005.png>
Office Mailing Address:
610 East Center Avenue, Suite 301
Mooresville, NC 28115
Branch's Underground Storage Tanks Website Address: https:Hdeq.nc.gov/about/divisions/waste-
management/ust
Branch's Above Ground Storage Tanks Website Address: https://deq.nc.gov/about/divisions/waste-
mana eement/ust/ast-nro gram
INTERACTIVE MAPS WITH DWM SITES AND PERMITTED FACILITIES:
hiips:Hdeq.nc.gov/about/divisions/waste-management/waste-management-rules-data/waste-mana e
ig s=maps
File Review Procedures:
https:Hdeq.nc.aov/about/divisions/waste-management/ust/file-review-procedures#mooresville-re ig onal-
office
ONLINE ACCESS TO UST SECTION DOCUMENTS (Laserfiche):
https://edocs.deq.nc.gov/WasteManagement/Search.aspx
Document Submittal & UST File Names for Laserfiche Policies:
https://files.nc. gov/ncdeq/Waste%2OMana,gement/DWM/UST/Corrective%2OAction/Electronic%2ODocum
ent%20Submittal%2OMemo%2OUpdate.pdf
https:Hfiles.nc. gov/ncdeq/Waste%20Mana,gement/DWM/UST/Corrective%2OAction/UST%20file%20nam
es%20f6r1/o20Laserfiche. docx
<MO-9475_40916_G NORR 20190620 Notice of Regulatory Requirements.pdf>