HomeMy WebLinkAbout0601_AveryCounty_MSWLF_LFG_FID1087750_20180216
March 6, 2018
Ms. Jaclynne Drummond
NCDENR DWM Solid Waste Section
2090 U.S. 70 Highway
Swannanoa, North Carolina 28778-8211
RE: Operations, Monitoring, and Maintenance Report –February 2018
Avery County Closed MSW Landfill
Spruce Pine, North Carolina
Dear Ms. Drummond:
Smith Gardner, Inc. (S+G) is pleased to present this report regarding the operation and
maintenance (O&M) of the Avery County Closed MSW Landfill (Permit No. 06-01) Landfill Gas
Collection and Control System (LFGCCS). Monitoring of the on- and off-site landfill gas
probes was also performed. Mr. Frank Terry with S+G performed the site visit on February
16, 2018. Site visit details are provided below.
LFG EXTRACTION WELL MONITORING PROGRAM
Monthly monitoring of the LFGCCS will continue and shall include the following items:
CH4, O2, CO2, and pressure monitoring at each extraction well head;
CH4, O2, CO2, and pressure monitoring at the flare station; and
Adjustment of the LFGCCS to balance recovery and ensure safe system operation.
The County will maintain this LFGCCS and will continue to evaluate the effectiveness of
increased LFG recovery from the waste mass in alleviating off-site LFG migration. Results
from monthly monitoring events will be reported in accordance with the approved LFG
Monitoring Plan.
LFG EXTRACTION WELL MONITORING ACTIVITIES
Mr. Terry performed the flare station and well field monitoring on February 16, 2018. Initial
measurements indicated there was approximately 36 inches of available vacuum at the
vacuum blower inlet, resulting in approximately 35 inches of available vacuum at each of the
LFG wells across the well field. The results from this event are summarized below.
Recommended actions are underlined. Well field data and flare station data are provided in
the attached Table 1.
Ms. Drummond
March 6, 2018
Page 2 of 3
LFG Extraction Well Field
W-1 through W-10: S+G performed methane (CH4), oxygen (O2), carbon dioxide
(CO2), and pressure monitoring. No wellhead valves adjustments were required
during this sampling event.
Orifice Plates: S+G continues to evaluate orifice plate sizes at wells W-5, W-7,
W-9, and W-10 during each site visit. LFG flow potential at these locations
continues to remain stable, the correct orifice plate sizes are currently installed
and no further changes were made.
Flare Station
Condensate Tank: The condensate tank was drained during this site visit. S+G
will continue to monitor the liquid level of the condensate tank.
Filter Tank: The filter tank was drained during this site visit. S+G will continue to
monitor the liquid level of the filter tank.
Flare operation: Due to low methane concentration of approximately 15%
measured at the flare, no active combustion was observed. The spark ignition
system was operational; however, flame ignition continues to be unsuccessful.
The flare vacuum was found to be in normal operating condition at approximately
38”wc. S+G will continue to adjust the system to optimize gas flow and quality.
LFG MONITORING WELL (PERIMETER) MONITORING PROGRAM
Mr. Terry performed monitoring of the perimeter LFG monitoring network during this event.
Monitoring Wells P-1, P-7, and P-13 exhibited CH4 concentration readings of 4.5%, 3.8%, and
4.9% respectively which do not exceed the LEL of 5%. Monitoring Well P-3 had a CH4
concentration of 7.7%. Results of this monitoring event are included in Attachment 1.
Attachment 2 provides a CH4 concentration graph over time for monitoring wells that have
historically had methane present. The current well network will continue to be monitored
and data will be reported to NCDEQ and the County.
Ms. Drummond
March 6, 2018
Page 3 of 3
CONCLUSIONS
The CH4 concentration at P-3 has increased from the January 2018 monitoring event and
exceeds the regulatory LEL threshold of 5%, likely due to rain saturated cover soil prior to
the day of the monitoring event. P-3 will be remonitored next month and evaluated for
potential adjustments if necessary. The vacuum laterals at P-1 and P-3 were drained as part
of the routine monthly maintenance. We will continue to monitor the CH4 concentrations at
the site monthly.
The next routine monitoring event is scheduled for March 2018. If you have any questions, or
require additional information, please contact us at your earliest convenience at
919-828-0577 or by e-mail (address below).
Sincerely,
SMITH GARDNER, INC.
Frank Terry Madeline German, P.G.
Project Manager, ext. 142 Project Geologist ext. 222
frank@smithgardnerinc.com madeline@smithgardnerinc.com
Attachments
cc: Eric Foster – Avery County
Kris Riddle – NCDEQ
file
H:\Projects\Avery County (NC)\Avery-15-1 (LFG Sys Ops)\2018 LFG Monitoring\2 Feb 2018\Avery Co MSW LFG Monitoring Rpt February 2018.docx
This page intentionally left blank.
Attachment 1
This page intentionally left blank.
TABLE
This page intentionally left blank.
DATE:
BY:FAT
Date/Time CH4 CO2 O2 Balance Init. Temperature Init. Static
Pressure
Adj. Static
Pressure
Adj. Diff.
Pressure*Init. Flow Adj. Flow System
Pressure
mm/dd/yyyy %%%%deg F in H2O in H2O in H2O Scfm Scfm in H2O
AVERY-W1 2/16/2018 9:06 26.6 14.0 10.6 48.8 62 -36.8 -36.8 0.0 4.5 0.0 -36.8
AVERY-W2 2/16/2018 9:26 51.7 27.5 0.5 20.3 58 -35.1 -35.4 0.0 0.0 0.0 -35.8
AVERY-W3 2/16/2018 9:17 63.3 30.6 0.4 5.7 60 -35.4 -35.4 0.0 1.9 0.6 -35.1
AVERY-W4 2/16/2018 9:20 34.6 14.9 7.9 42.6 61 -35.4 -35.1 0.0 3.9 8.3 -35.1
AVERY-W5 2/16/2018 9:34 34.9 27.0 0.1 38.0 61 -34.8 -34.8 33.4 17.6 17.6 -34.8
AVERY-W6 2/16/2018 9:37 18.4 23.2 2.5 55.9 64 -6.5 -6.5 0.0 3.9 3.9 -34.8
AVERY-W7 2/16/2018 9:30 8.4 11.6 10.1 69.9 62 -13.0 -13.1 2.7 1.3 1.3 -35.1
AVERY-W8 2/16/2018 9:42 57.1 35.6 0.0 7.3 66 -34.9 -34.9 0.0 0.0 8.6 -35.1
AVERY-W9 2/16/2018 9:08 16.8 11.7 12.4 59.1 56 -34.3 -34.4 0.0 0.2 0.1 -34.0
AVERY-W10 2/16/2018 9:15 63.6 34.2 0.2 2.0 62 -35.0 NR NR 0.2 NR NR
Av-Flare 2/16/2018 10:09 18.7 14.7 10.0 56.6 NR 1.3 1.2 2.4 32.0 32.0 0.0
Av-Flare 2/16/2018 10:10 18.7 14.7 10.2 56.4 NR -36.5 NR NR NR NR -36.5
NR= not recorded
Landfill Gas Collection and Control System Monitoring
February 2018
*The differential pressure measurement should be positive. A negative differential pressure may indicate no gas flow. Negative differential
pressure can be the result of dirt or water obstructing the pitot tube perforations. Overpulling by adjacent extraction wells may also result in
negative pressure being displayed.
February 19, 2018
Avery County Closed MSW Landfill
TABLE 1
Device ID
This page intentionally left blank.
NC Division of Waste Management - Solid Waste Section
Landfill Gas Monitoring Data Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and
examination by any person upon request (NC General Statute 132-6).
Facility Name: ______________________________________________ Permit Number: ____________________________
Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________
Name and Position of Sample Collector: _________________________________________
Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________
Date and Time of Field Calibration: _____________________
Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________
Pump Rate of Gas Meter: _____________
Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________
Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test
must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane
by volume = % LEL/20
If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same
information as contained on this form.
Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that
there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
__________________________________ ________________________
SIGNATURE TITLE
NC Division of Waste Management - Solid Waste Section
Landfill Gas Monitoring Data Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and
examination by any person upon request (NC General Statute 132-6).
Facility Name: ______________________________________________ Permit Number: ____________________________
Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________
Name and Position of Sample Collector: _________________________________________
Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________
Date and Time of Field Calibration: _____________________
Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________
Pump Rate of Gas Meter: _____________
Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________
Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test
must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane
by volume = % LEL/20
If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same
information as contained on this form.
Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that
there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
__________________________________ ________________________
SIGNATURE TITLE
NC Division of Waste Management - Solid Waste Section
Landfill Gas Monitoring Data Form
Notice: This form and any information attached to it are "Public Records" as defined in NC General Statute 132-1. As such, these documents are available for inspection and
examination by any person upon request (NC General Statute 132-6).
Facility Name: ______________________________________________ Permit Number: ____________________________
Date of Sampling: ___________________ NC Landfill Rule (.0500 or .1600): _____________________________________
Name and Position of Sample Collector: _________________________________________
Type and Serial Number of Gas Meter: _______________________________ Calibration Date of Gas Meter: ___________
Date and Time of Field Calibration: _____________________
Type of Field Calibration Gas (15/15 or 35/50): ____________ Expiration Date of Field Calibration Gas Canister: ________
Pump Rate of Gas Meter: _____________
Ambient Air Temperature: __________ Barometric Pressure: ______________ General Weather Conditions: _____________
Instructions: Under “Location or LFG Well” identify the monitoring wells or describe the location for other tests (e.g., inside buildings). A drawing showing the location of test
must be attached. Report methane readings in both % LEL and % methane by volume. A reading in percent methane by volume can be converted to % LEL as follows: % methane
by volume = % LEL/20
If your facility has more gas monitoring locations than there is room on this form, please attach additional sheets listing the same
information as contained on this form.
Certification To the best of my knowledge, the information reported and statements made on this data submittal and attachments are true and correct. I am aware that
there are significant penalties for making any false statement, representation, or certification including the possibility of a fine and imprisonment.
__________________________________ ________________________
SIGNATURE TITLE
Attachment 2
This page intentionally left blank.
By:FAT
Date:2/19/2018
Avery County MSW Landfill
Landfill Gas Monitoring Well Network
Methane Concentrations Between May 2011 and February 2018
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
May-11Jun-11Jul-11Aug-11Sep-11Oct-11Nov-11Dec-11Jan-12Feb-12Mar-12Apr-12May-12Jun-12Jul-12Aug-12Sep-12Oct-12Nov-12Dec-12Jan-13Feb-13Mar-13Apr-13May-13Jun-13Jul-13Aug-13Sep-13Oct-13Nov-13Dec-13Jan-14Feb-14Mar-14Apr-14May-14Jun-14Jul-14Aug-14Sep-14Oct-14Nov-14Dec-14Jan-15Feb-15Mar-15Apr-15May-15Jun-15Jul-15Aug-15Sep-15Oct-15Nov-15Dec-15Jan-16Feb-16Mar-16Apr-16May-16Jun-16Jul-16Aug-16Sep-16Oct-16Nov-16Dec-16Jan-17Feb-17Mar-17Apr-17May-17Jun-17Jul-17Aug-17Sep-17Oct-17Nov-17Dec-17Jan-18Feb-18P1
P3
P7
P11
P12
P13
Well
% CH4 by
Volume
Installation of W9 and W10 (April 30, 2013) Installation of W9/P3
Connection
(September 11, 2014
Installation of P7/W8 and P1/W10 Connection (September 3, 2015)
This page intentionally left blank.
FIGURE
This page intentionally left blank.
0200'400'1234564G:\CAD\Avery County\Avery 13-6\sheets\AVERY-B0216.dwg - 12/3/2013 11:03 AM
This Page Intentionally Left Blank