Mr. Shannon Becker, President
Aqua of North Carolina, Inc.
202 MacKenan Court
Cary, N.C. 27511
NORTH CAROLINA
Environmental Quality
August 28, 2019
Subject: Compliance Evaluation Inspection
Country Valley Collection System
Permit No. WQCSD0399
Catawba County
Dear Mr. Becker:
1. Mr. Michael Meilinger and Mr. Tony Parker of the Mooresville Regional Office of the NC
Division of Water Resources (DWR or the Division) conducted a compliance evaluation
inspection (CEI) of the subject wastewater collection system (WWCS) on August 27, 2019.
The assistance provided by Mr. Charles Welch during the inspection was greatly
appreciated. A copy of the inspection report is attached for your records and inspection
findings are summarized below.
Site/System Review
2. The following system components were inspected:
a. We inspected seven manholes and one right of way. The right of way was clear of
debris and obstructions. Refer to the inspection report in reference to potential
issues to the manhole behind the shopping center and I&I.
3. As you are aware, owners of permitted collection systems must comply with their permit
and all rules listed under NC Administrative Code 15A NCAC 02T .0400, et seq. The
system status is outlined below:
a. 15A NCAC 02T .0403(a)(1): Requires that the system be effectively maintained
and operated at all times to prevent discharge to land or surface waters and any
contravention of ground or surface water standards.
Observations: The system has had no reportable spills.
Compliance Status: Compliant
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NORTH CAROLINA �
oewro.e�� a 704,663.1699
b. 15A NCAC 02T .0403(a)(2): Requires that a map of the wastewater collection
system be developed and actively maintained.
Observations: A general map was provided during the inspection. The map needs
to be updated to show the newly added line.
Compliance Status: Compliant
15A NCAC 02T .0403(a)(5): Requires that the permittee or its representative
inspect high -priority sewers (HPS - as defined in 15A NCAC 02T .0402(2)) at least
once every six months and document the inspections.
Observations: The system has no High Priority line or aerial crossing.
Compliance Status: NA
d. 15A NCAC 02T .0403(a)(6): Requires that the permittee or its representative
conduct a general observation of the entire wastewater collection system at least
once per year.
Observations: The systems lines were jetted every year and the reports for the
footage jetted were kept at the wastewater plant.
Compliance Status: Compliant.
15A NCAC 02T .0403(a)(7): Requires that overflows and bypasses from the
system be reported to the Division's Mooresville Regional Office in accordance
with 15A NCAC 02B .0506(a), and that public notice must be provided as required
by G.S. 143-215.1C.
Observations: The system has not had any reportable spills. The NC regulations
and statutes, which cover the reporting requirements for SSOs, are found in NC
Administrative Code 15A NCAC 02B .0506(a) and NC General Statute 143-
215.1 C, respectively. You may access the NC regulations online at the NC Office
of Administrative Hearings (OAH) website at: http://www.oah.state.nc.us/rules/
and the NC General Statutes online at the NC General Assembly's website at:
hqp://www.ncga.state.nc.us/ ag scripts/Statutes/StatutesTOC.pl. You may wish to
review them to ensure you are fully familiar with all requirements.
When reporting SSOs to DWQ, you must call the Mooresville Regional Office
(MRO) at 704-663-1699 during normal business hours. If outside normal business
hours, you must report the spill to the NC Division of Emergency Management at
1-800-858-0368. Please note that all reportable SSOs must be reported within 24
hours of the occurrence, or first knowledge, of the SSO. Please also note that voice
mail or faxed messages are not considered as the initial verbal report. You must
talk to and report the spill to a live person.
Compliance Status: Compliant
f. 15A NCAC 02T .0403(a)(8): Requires that a grease control program be developed
and implemented as follows:
1. For privately owned collection systems, the Grease Control Program shall
include at least bi-annual distribution of grease education materials by the
owner or representative.
Observations: Educational information is available on their Website and mail outs
are conducted 2/year from the corporate office in Pa.
Compliance Status: Compliant
g. 15A NCAC 02T .0403(a)(10): Requires that documentation be kept for all
activities you undertake to comply with the requirements of 15A NCAC 02T .0403,
subparagraphs (a)(1) through (a)(9), for a minimum of three years, with the
exception of the map, which shall be maintained for the life of the system. Also any
new additions, subdivisions or phased development needs to be incorporated as
well.
Observations: Records and a system map were available.
Compliance Status: Compliant
The inspection report should be self-explanatory; however, if you have any questions
regarding the inspection report or this letter please contact Michael Meilinger or me at 704-
663-1699.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Mooresville Regional Office
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Attachments:
BIMS Inspection Report
CC: MRO
Central Files/PERCS Unit (e-copy)
Permit: WQCSD0399
SOC:
County: Catawba
Region: Mooresville
Compliance Inspection Report
Effective: 11/15/10 Expiration: Owner: Aqua North Carolina Inc
Effective: Expiration: Facility: Country Valley Collection System
Contact Person: Joseph R Pearce
Directions to Facility:
System Classifications:
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Title: Director of Operations
Certification:
Related Permits:
NCO058742 Aqua North Carolina Inc - Country Valley WWTP
Inspection Date: 08/27/2019 Entry Time: 12:30PM
Primary Inspector: Michael J Meilinger
Secondary Inspector(s):
Phone: 919-653-6964
Phone:
Exit Time: 01:30PM
Phone: 910-796-7336
Tony Parker
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: Compliant Not Compliant
Question Areas:
Miscellaneous Questions General Grease Control
Spills/Response Plan Inspections Lines
Manholes
(See attachment summary)
DocuSigned by:
8/28/2019
A14CC681AF27425...
Page 1 of 5
Permit: WQCSD0399 Owner - Facility: Aqua North Carolina Inc
Inspection Date: 08/27/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
We recommend that you smoke test the system to check for I&I, while on the inspection, the plant opertor said that during
heavy rain events there is higher flows. While inspecting the manhole behind the shopping center we noticed there was extra
flow coming from under the pipe. Also update the site map for manholes to include the new line.
Page 2 of 5
Permit: WQCSD0399 Owner - Facility: Aqua North Carolina Inc
Inspection Date: 08/27/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General
# Is this system a satellite system?
# If Yes, what is system name or permit number?
Is there a overall sewer system map?
Does the map include:
Yes No NA NE
❑■❑❑
■❑❑❑
Pipe sizes
❑
❑ ❑
Pipe materials (PVC, DIP, etc)
❑
❑ ❑
Pipe location
❑ ❑ ❑
# Flow direction
❑ ❑ ❑
# Approximate pipe age
❑ ❑ ❑
# Pump station ID, location and capacity
❑
❑ ❑
# Force main air release valve location & type
❑
❑ ❑
# Location of satellite connections
❑
❑ ❑
Are system maintenance records maintained?
0
❑ ❑ ❑
Comment: Lines were jetted every year, March 2019 1198' flushed, 5 manholes checked. August 2018 840'
flushed, 5 manholes checked. October 2017 693' flushed and 5 manholes checked.
Grease Control
Yes No NA NE
Is grease/sewer education program documented with req'd customer distribution?
0
❑ ❑ ❑
# Are other types of education tools used like websites, booths, special meetings, etc?
❑ ❑ ❑
If Yes, what are they? (This can reduce mailing to annual.)
Able to search on the Aqua website, for protecting your sewer from fats, grease and oil.
For public systems, is there a Grease Control Program via an ordinance/agreement?
❑
❑ ❑
If Yes, does it require grease control devices at applicable locations?
❑
❑ ❑
Is the Grease Control Program enforced via periodic inspections/records review?
❑
❑ ❑
Is action taken against violators?
❑
❑ ❑
Comment:
Spills and Response Action Plan
Yes No NA NE
# Is system free of known points of bypass?
❑ ❑ ❑
If No, describe type of bypass and location
# Have there been any sewer spills in the past 3 years?
❑
❑ ❑
If Yes, were they reported to the Division if meeting the reportable criteria?
❑
❑ ❑
If applicable, is there documentation of press releases and public notices issued?
❑
❑ ❑
Are all spills or sewer related issues/complaints documented?
❑
❑ ❑
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
❑
❑ ❑
# If Yes, is there a corrective action plan?
❑
❑ 0 ❑
Page 3 of 5
Permit: WQCSD0399 Owner - Facility: Aqua North Carolina Inc
Inspection Date: 08/27/2019 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
Is a Spill Response Action Plan available?
0
❑ ❑ ❑
Is a Spill Response Action Plan available for all personnel?
0
❑ ❑ ❑
Does the plan include:
# 24-hour contact numbers
❑ ❑ ❑
# Response time
❑ ❑ ❑
# Equipment list and spare parts inventory
❑ ❑ ❑
# Access to cleaning equipment
❑ ❑ ❑
# Access to construction crews, contractors, and/or engineers
❑ ❑ ❑
# Source of emergency funds
❑ ❑ ❑
# Site sanitation and cleanup materials
❑ ❑ ❑
# Post-overflow/spill assessment
❑ ❑ ❑
Comment: No SSO's have been reported for this system
Inspections
Yes No NA NE
Are adequate maintenance records maintained?
❑ ❑ ❑
Are pump stations being inspected at the required frequency?
❑
❑ ❑
Is at least one complete functionality test conducted weekly per pump station?
❑
❑ ❑
Is there a system or plan in place to observe the entire system annually?
❑
❑ ❑
Is the annual inspection documented?
❑
❑ ❑
# Does the system have any high -priority lines/locations?
❑
❑ ❑
Are inspections of HPL documented at least every 6 months?
❑
❑ ❑
Are new lines being added to the HPL list when found or created?
❑
❑ ❑
Comment:
Lines/Right-of-Ways/Aerial Lines Yes No NA NE
Please list the Lines/Right of Ways/Aerial Lines Inspected:
Inspectors walked the right of way behind the houses to check the manhole that was accessable.
Are right-of-ways and easements maintained for the full width for access? ❑ ❑ ❑
If No, give details on temporary access:
Is maintenance documented? ❑ ❑ ❑
Were all areas/lines inspected free of issues? 0 ❑ ❑ ❑
Comment:
Manholes Yes No NA NE
Please list the Manholes Inspected:
7 Manholes inspected, the manhole behind the shopping center seemed to have a small infiltration from
underneath the influent pipe.
Are manholes accessible? ❑ ❑ ❑
# Are manhole covers/vents above grade? ❑ ❑ ❑
Are manholes free of visible signs of overflow? ❑ ❑ ❑
Page 4 of 5
Permit: WQCSD0399 Owner - Facility: Aqua North Carolina Inc
Inspection Date: 08/27/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Are manholes free of sinkholes and depressions?
Are manhole covers present?
# Are manholes properly seated?
# Are manholes in good condition?
# Are inverts in good condition?
Is flow unrestricted in manholes?
Are manholes free of excessive amounts of grease?
Are manholes free of excessive roots?
Are manholes free of excessive sand?
Are manhole vents screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
Comment: Update site map to include the new manhole lines.
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑❑■❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑■❑❑
❑■❑❑
■❑❑❑