Loading...
HomeMy WebLinkAboutWQCSD0420_Compliance Evaluation Inspection_20190816Comoliance Insoection Resort Permit: WQCSD0420 Effective: 03/01/00 Expiration: Owner: Town of Taylortown SOC: Effective: Expiration: Facility: Taylortown Collection System County: Moore Region: Fayetteville Contact Person: Ulysses Barrett Title: Phone: Directions to Facility: System Classifications: Primary ORC: Certification: Phone: Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 08/14/2019 Entry Time: 10:30AM Exit Time: 12:30PM Primary Inspector: Chad Turlington DocuSigned by: �C1 E Phone: 910-433-3300 Ext.720 Secondary Inspector(s): 97813D247D_ Trent Allen [DOCUSIgnedby: ,�tAk a—UtA Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling 5189C2D3DD5C42B... Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: ❑ Compliant Not Compliant Question Areas: Miscellaneous Questions General Grease Control Spills/Response Plan Inspections Lines Pump Stations (See attachment summary) Page 1 of 6 Permit: WQCSD0420 Owner - Facility: Town of Taylortown Inspection Date: 08/14/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: A copy of the spill response plan and map of the system were available for review. Inspector was told that grease education materials were being distributed, but no documentation of the distribution was available. Permittee shall begin keeping documentation of bi-annual distribution of grease education materials. No documentation of any maintenance, cleaining, pump station visitation or emergency generator testing was avaible. Please ensure that documentation of all activities related to the operation of this collection system are documented. The right of ways observed during the inspection appeared accesible, but there was considerable vegetation and small trees begining to grow up on the ROW. Documentation of ROW clearing was not available. Please begin keeping written documentation of ROW clearing. 24-hour notification signs were present at both pump stations, but pump station identifier information was not on the sign. Permittee shall provide pump station identifier signage at both pump stations. This issue was documented on a previous Collection Sytem inspection report from 9/7/2016, but has not been corrected as of the date of this inspection. The audible and visual alarms at the Main St. pump station were not functional at the time of this inspection. Corrective actions shall be immediately undertaken. Grease accumulation and debris being removed from the wet wells at both pump stations and being stored in household trash cans at the stations. Some of the trash cans were split open allowing the contents to spill out. Some of the cans had no lids and were allowing rain water to enter and then overflow out onto the ground. Another method for pump station debris removal cleaning should be developed that does not involve storage of the removed material in the current manner. Trash cans of debris present at the pump stations shall be removed and disposed of properly. This issue was also noted in the previous inspection report, but has not been corrected. Page 2 of 6 Permit: WQCSD0420 Owner - Facility: Town of Taylortown Inspection Date: 08/14/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine General Yes No NA NE # Is this system a satellite system? ❑ ❑ 0 ❑ # If Yes, what is system name or permit number? Is there a overall sewer system map? ❑ ❑ ❑ Does the map include: Pipe sizes ❑ ❑ ❑ Pipe materials (PVC, DIP, etc) ❑ ❑ ❑ Pipe location ❑ ❑ ❑ # Flow direction ❑ ❑ ❑ # Approximate pipe age ❑ ❑ ❑ # Pump station ID, location and capacity ❑ ❑ ❑ # Force main air release valve location & type ❑ ❑ ❑ # Location of satellite connections ❑ ❑ ❑ Are system maintenance records maintained? ❑ 0 ❑ ❑ Comment: Records of system maintenance were not available. All maintenance activities should be documented. Grease Control Yes No NA NE Is grease/sewer education program documented with req'd customer distribution? ❑ ❑ ❑ # Are other types of education tools used like websites, booths, special meetings, etc? ❑ ❑ ❑ If Yes, what are they? (This can reduce mailing to annual.) Documentation of the required grease education materials distribution should be maintained. For public systems, is there a Grease Control Program via an ordinance/agreement? ❑ ❑ ❑ If Yes, does it require grease control devices at applicable locations? ❑ ❑ ❑ Is the Grease Control Program enforced via periodic inspections/records review? ❑ ❑ ❑ Is action taken against violators? ❑ ❑ ❑ Comment: Documentation of grease trap inspections should be kept Spills and Response Action Plan Yes No NA NE # Is system free of known points of bypass? ❑ ❑ ❑ If No, describe type of bypass and location # Have there been any sewer spills in the past 3 years? ❑ ❑ ❑ If Yes, were they reported to the Division if meeting the reportable criteria? ❑ ❑ ❑ If applicable, is there documentation of press releases and public notices issued? ❑ ❑ ❑ Are all spills or sewer related issues/complaints documented? ❑ ❑ ❑ # Are there repeated overflows/problems (2 or more in 12 months) at same location? ❑ ❑ ❑ # If Yes, is there a corrective action plan? ❑ ❑ ❑ Page 3 of 6 Permit: WQCSD0420 Owner - Facility: Town of Taylortown Inspection Date: 08/14/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Is a Spill Response Action Plan available? 0 ❑ ❑ ❑ Is a Spill Response Action Plan available for all personnel? 0 ❑ ❑ ❑ Does the plan include: # 24-hour contact numbers ❑ ❑ ❑ # Response time ❑ ❑ ❑ # Equipment list and spare parts inventory ❑ ❑ ❑ # Access to cleaning equipment ❑ ❑ ❑ # Access to construction crews, contractors, and/or engineers ❑ ❑ ❑ # Source of emergency funds ❑ ❑ ❑ # Site sanitation and cleanup materials ❑ ❑ ❑ # Post-overflow/spill assessment ❑ ❑ ❑ Comment: Inspections Yes No NA NE Are adequate maintenance records maintained? ❑ ❑ ❑ Are pump stations being inspected at the required frequency? ❑ ❑ ❑ Is at least one complete functionality test conducted weekly per pump station? ❑ ❑ ❑ Is there a system or plan in place to observe the entire system annually? ❑ ❑ ❑ Is the annual inspection documented? ❑ 0 ❑ ❑ # Does the system have any high -priority lines/locations? ❑ ❑ ❑ Are inspections of HPL documented at least every 6 months? ❑ ❑ ❑ Are new lines being added to the HPL list when found or created? ❑ ❑ 0 ❑ Comment: Written documentation of maintenace was not available. Please be reminded that documentation of any and all maintenace activites is required. No documentation of pump stations was available. Inspector was told during inspection that pump stations were visited 6 days per week. Non -telemetry pump stations shall be visted 7 days per week, 365 days per year. Documentation of inspection of high priority lines should be kept. Lines/Right-of-Ways/Aerial Lines Yes No NA NE Please list the Lines/Right of Ways/Aerial Lines Inspected: Are right-of-ways and easements maintained for the full width for access? ❑ ❑ ❑ If No, give details on temporary access: Is maintenance documented? ❑ ❑ ❑ Were all areas/lines inspected free of issues? 0 ❑ ❑ ❑ Comment: ROW's observed during inspection appeared to be accessible, but were begining to grow up with Vegetation. Documentation of ROW clearing shall be maintained. Pump Stations Please list the Pump Stations Inspected: Main St, Lincoln St. Yes No NA NE Page 4 of 6 Permit: WQCSD0420 Owner - Facility: Town of Taylortown Inspection Date: 08/14/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine # Number of duplex or larger pump stations in system 2 # Number of vacuum stations in system # Number of simplex pump stations in system # Number of simplex pump stations in system serving more than one building How many pump/vacuum stations have: # A two-way "auto polling" communication system (SCADA) installed? 0 # A simple one-way telemetry/communication system (auto -dialer) installed? 0 For pump stations inspected: Are they secure with restricted access? 0 ❑ ❑ ❑ Were they free of by-pass structures/pipes? 0 ❑ ❑ ❑ Were wet wells free of excessive grease/debris? 0 ❑ ❑ ❑ # Do they all have telemetry installed? ❑ ❑ 0 ❑ Is the telemetry system functional? ❑ ❑ 0 ❑ Is a 24-hour notification sign posted ? 0 ❑ ❑ ❑ Does the sign include: Owner Name? 0 ❑ ❑ ❑ Pump station identifier? ❑ 0 ❑ ❑ # Address? ❑ 0 ❑ ❑ Instructions for notification? 0 ❑ ❑ ❑ 24-hour emergency contact numbers? 0 ❑ ❑ ❑ Are audio and visual alarms present? 0 ❑ ❑ ❑ Are audio and visual alarms operable? ❑ 0 ❑ ❑ # Is there a backup generator or bypass pump connected? ❑ ❑ 0 ❑ If tested during inspection, did it function properly? ❑ ❑ ❑ Is the back-up system tested at least bi-annually under normal operating conditions? ❑ ❑ ❑ # Does it have a dedicated connection for a portable generator? 0 ❑ ❑ ❑ # Is the owner relying on portable units in the event of a power outage? 0 ❑ ❑ ❑ # If Yes, is there a distribution plan? 0 ❑ ❑ ❑ If Yes, what resources (Units/StaffNehicles/etc) are included in Plan? # Does Permittee have the approved percentage of replacement simplex pumps? ❑ ❑ 0 ❑ Is recordkeeping of pump station inspection and maintenance program adequate? ❑ 0 ❑ ❑ Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? ❑ 0 ❑ ❑ Inspecting and exercising all valves? ❑ 0 ❑ ❑ Inspecting and lubricating pumps and other equipment? ❑ 0 ❑ ❑ Inspecting alarms, telemetry and auxiliary equipment? ❑ 0 ❑ ❑ Page 5 of 6 Permit: WQCSD0420 Owner - Facility: Town of Taylortown Inspection Date: 08/14/2019 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Comment: 24 hour emergency notification sign was posted but there is no pump station identifier present on the sign. This issue was noted in previous inspection reports and has not been corrected. Pump station identifier sign shall be posted. Audible and visual alarms at the Main St. pump station were not functional. Repairs to the alarms shall be made immediately. Documentation of pump station visitation, inspection and maintenance were not available. Permitte shall immediately begin keeping required documentation. Page 6 of 6